SECTION 08 14 00 Interior Wood Doors

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 11

02-01-16

SECTION 08 14 00
INTERIOR WOOD DOORS

SPEC WRITER NOTE:


1. Delete text between // ______ // not
applicable to project. Edit remaining text
to suit project.
2. See VA Standard Details for door types
and designations.
3. See VA Physical Security Design Manual
for security requirements.

PART 1 - GENERAL

1.1.1.1 SUMMARY
A. Section Includes:
1. Interior flush wood doors // transparent // painted // finish.

SPEC WRITER NOTE: Retain special


application flush wood doors required for
project.

a. Fire rated doors.


b. Smoke rated doors.
c. Acoustical doors.
d. Dutch doors.
2. Interior stile and rail wood doors // transparent // painted //
finish.

1.1.1.2 RELATED REQUIREMENTS

SPEC WRITER NOTE: Update and retain


references only when specified elsewhere
in this section.

A. Paints and Coatings and Composite Wood and Agrifiber VOC Limits: Section
01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
B. Door Hardware including hardware location (height): Section 08 71 00,
DOOR HARDWARE.
C. Installation of Doors and Hardware: // Section 08 11 13, HOLLOW METAL
DOORS AND FRAMES // Section 08 71 00, DOOR HARDWARE //.
D. Door Finish: Section 09 06 00, SCHEDULE FOR FINISHES.

1.1.1.3 APPLICABLE PUBLICATIONS


A. Comply with references to extent specified in this section.
B. American National Standards Institute/Window and Door Manufacturers
Association (ANSI/WDMA):

08 14 00 - 1
02-01-16

1. I.S. 1A-13 - Architectural Wood Flush Doors.


2. I.S. 6A-13 - Interior Architectural Stile and Rails Doors.
C. ASTM International (ASTM):
1. E90-09 - Laboratory Measurements of Airborne Sound Transmission Loss
of Building Partitions and Elements.
D. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
2. 252-12 - Fire Tests of Door Assemblies.
E. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
F. Window and Door Manufacturers Association (WDMA):
1. TM 7-14 - Cycle-Slam Test.
2. TM 8-14 - Hinge Loading Test.
3. TM 10-14 - Screw Holding Capacity.

1.1.1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND
SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
2. Include details of // glazing // louvers //.
3. Indicate project specific requirements not included in
Manufacturer's Literature and Data submittal.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. // Fire rated doors showing conformance with NFPA 80 //.

SPEC WRITER NOTE: Paragraph D., delete


subparagraph No. 1 on projects not
involving large numbers of wood doors.
Delete subparagraph No. 2 on projects
where no transparent door finishes are
required. Samples are not required for
projects involving 10 wood doors or less.

D. Samples:
1. Corner section of flush veneered door 300 mm (12 inches) square,
showing details of construction, labeled to show grade and type
number and conformance to specified standard.
2. Veneer sample 200 mm by 275 mm (8 inch by 11 inch) showing specified
wood species sanded to receive a transparent finish. Factory finish
veneer sample where the prefinished option is accepted.

08 14 00 - 2
02-01-16

E. Sustainable Construction Submittals:

SPEC WRITER NOTE: Retain sustainable


construction submittals appropriate to
product.

1. Low Pollutant-Emitting Materials:


a. Show volatile organic compound types and quantities.
F. Test Reports: Indicate // each product complies // products comply //
with specifications.
1. Screw Holding Capacity Test.
2. Cycle-Slam Test.
3. Hinge-Loading Test.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.

1.1.1.5 QUALITY ASSURANCE


A. Manufacturer Qualifications:
1. Regularly and presently manufactures specified products.
2. Manufactures specified products with satisfactory service on five
similar installations for minimum five years.

1.1.1.6 DELIVERY

SPEC WRITER NOTE: Packaging is required to


be reinstalled on doors after
installation. See Part 3 Article
PROTECTION.

A. Deliver products in manufacturer's original sealed packaging.


1. Minimum 0.15 mm (6 mil) polyethylene bags or cardboard packaging to
remain unbroken during delivery and storage.
B. Mark packaging, legibly. Indicate manufacturer's name or brand,
type, // color, // and manufacture date.
1. Identify door opening corresponding to Door Schedule.
C. Before installation, return or dispose of products within distorted,
damaged, or opened packaging.

1.1.1.7 STORAGE AND HANDLING


A. Store products indoors in dry, weathertight // conditioned // facility.
1. Store doors according to ANSI/WDMA I.S. 1A.
B. Protect products from damage during handling and construction
operations.

08 14 00 - 3
02-01-16

1.1.1.8 FIELD CONDITIONS


A. Environment:
1. Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum
48 hours before installation.
2. Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to
80 degrees F) continuously, beginning 48 hours before installation.
3. Install products when building is permanently enclosed and when wet
construction is completed, dried, and cured.
a. Comply with door manufacturer's instructions for relative
humidity.

1.1.1.9 WARRANTY

SPEC WRITER NOTE: Always retain


construction warranty. FAR includes
Contractor's one year labor and material
warranty.

A. Construction Warranty: FAR clause 52.246-21, "Warranty of Construction."

SPEC WRITER NOTE: Specify extended


manufacturer's warranties for materials
only.

B. Manufacturer's Warranty: Warrant interior factory finished // flush //


stile and rail // wood doors against material and manufacturing defects.

SPEC WRITER NOTE: Specify customarily


available warranty period for specified
products.

1. Warranty Period: Lifetime of original installation.

08 14 00 - 4
02-01-16

SPEC WRITER NOTES:


1. Use 44 mm (1-3/4 inch) thick doors for
medical facilities, nursing homes and
domiciliary buildings.
2. Use 35 mm (1-3/8 inch) thick doors for
office buildings, unless facility requests
44 mm (1-3/4 inch) thick doors or doors
are fire rated.
3. If 35 mm (1-3/8 inch) doors are
specified, ensure that they are
coordinated with frame details on the
Drawings.

PART 2 - PRODUCTS

2.1.1.1 PRODUCTS - GENERAL


A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Provide each product from one manufacturer.
C. Sustainable Construction Requirements:

SPEC WRITER NOTE:


1. Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS includes
comprehensive product list setting VOC
limits for low-emitting materials.
2. Retain subparagraphs applicable to
products specified in this section.

1. Low Pollutant-Emitting Materials: Comply with VOC limits specified


in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the
following products:
a. Paints and coatings.
b. Composite wood and agrifiber.

2.1.1.2 FLUSH WOOD DOORS


A. General:
1. ANSI/WDMA I.S. 1A, Extra Heavy Duty.
2. Adhesive: Type II.
3. Core: Structural composite lumber, except when mineral core is
required for fire rating.
4. Thickness: // 35 mm (1-3/8 inch) // 44 mm (1-3/4 inches) // unless
otherwise shown or specified.

08 14 00 - 5
02-01-16

SPEC WRITER NOTE: For face veneer other


than those specified below see
ANSI/WDMA I.S. 1A, Section A-8, Flush Door
Face Veneer Characteristics, regarding
AA and A grade door faces. See Section
A-3, Appearance of Individual Veneer
Leaves; Section A-4, Matching Between
Individual Veneer Leaves; Section A-5,
Assembly of Spliced Veneer Leaves on Door
Face; and Section A-6, Appearance of Doors
in Pairs or Sets. For highest quality
paint finish, specify only medium density
overlay faces.

B. Faces:
1. ANSI/WDMA I.S. 1A.
2. One species throughout project unless scheduled or otherwise shown.
3. Transparent Finished Faces: // Premium Grade. rotary cut, // white
maple // white birch // red oak // white oak // ______ //.
a. // A Grade // AA Grade // face veneer.

SPEC WRITER NOTE: Specify lay up of veneer


leaves. For rotary cut veneers, no
matching within each door face is
possible. Premium grade requires center
balance book matching. Consider specifying
slip matched veneers and running matched
faces if a cut other than rotary is
selected.

b. Match face veneers for doors for uniform effect of color and
grain at joints.
c. Door Edges: Same species as door face veneer, except maple is
acceptable for stile face veneer on birch doors.
d. In existing buildings, where doors are required to have
transparent finish, use wood species, grade, and assembly of
face veneers to match adjacent existing doors.
4. Painted Finishes: Custom Grade, mill option close grained hardwood,
premium or medium density overlay.
5. Factory sand doors for finishing.
C. Wood For Stops, Louvers, Muntins and Moldings For Flush Doors Required
to Have Transparent Finish:
1. Solid wood of same species as face veneer, except maple is
acceptable on birch doors.
2. Glazing:

08 14 00 - 6
02-01-16

a. On non-fire-rated doors, use applied wood stops nailed tightly


on room side and attached on opposite side with flathead,
countersunk wood screws, spaced approximately 125 mm (5 inches)
on center.
3. Wood Louvers:
a. Door manufacturer's standard product, fabricated of solid wood
sections.
b. Wood Slats: minimum 5 mm (3/16 inch) thick.
c. Stiles routed out to receive slats.
d. Secure louvers in prepared cutouts with wood stops.
D. Stiles and Rails:
1. Composite material having screw withdrawal force greater than
minimum performance level value when tested according to WDMA TM 10.
2. Provide adequate blocking for bottom of doors having mechanically
operated door bottom seal meeting or exceeding performance duty
level per WDMA TM 10 for horizontal door edge screw holding.
3. Rabbeted transom meeting rail edges match face veneers of
doors. // Bottom rail of transom panel match face veneer on
non-rabbeted meeting rail edge. //

SPEC WRITER NOTE: Do not use 60 minute


doors and 20 minute doors. Solid core
door, 44 mm (1-3/4 inches) gives 20 minute
performance. Coordinate fire door rating
with wall or barrier assembly rating.

E. Fire-Rated Wood Doors:


1. Fire Resistance Rating:
a. B Label: 1-1/2 hours.
b. C Label: 3/4 hour.
2. Labels:
a. Comply with NFPA 252, UL 10C, and labeled by qualified testing
and inspection agency showing fire resistance rating.
b. Metal labels with raised or incised markings.
3. Performance Criteria for Stiles of Doors Utilizing Standard Mortise
Leaf Hinges:
a. Hinge Loading: WDMA TM 8. Average of 10 test samples for Extra
Heavy Duty doors.

08 14 00 - 7
02-01-16

b. Direct Screw Withdrawal: WDMA TM 10 for Extra Heavy Duty doors.


Average of 10 test samples using a steel, fully threaded #12
wood screw.
c. Cycle-Slam: 1,000,000 cycles with no loose hinge screws or other
visible signs of failure when tested according to WDMA TM 7.
4. Hardware Reinforcement:
a. Provide // fire // smoke // rated doors with hardware
reinforcement blocking.
b. Size of lock blocks as required to secure hardware specified.
c. Top, Bottom and Intermediate Rail Blocks: Minimum 125 mm
(5 inches) by full core width.
d. Reinforcement blocking in compliance with labeling requirements.
e. Mineral material similar to core is not acceptable.
5. Other Core Components: Manufacturer's standard as allowed by
labeling requirements.
6. Glazed Vision Panel Frame: Steel approved for use in labeled doors.

SPEC WRITER NOTE: Astragals are not always


required for fire rated doors. With an
astragal, there will be an active and an
inactive leaf. If both have exit devices,
the inactive leaf will not open.

7. Astragal: Steel type for pairs of doors.


F. Smoke Barrier Doors:
1. Glazed Vision Panel Frame: Steel approved for use in labeled doors.

SPEC WRITER NOTE: Astragals are not


required for smoke rated doors.

2. Astragal: Steel type for pairs of doors, including double egress


doors.

SPEC WRITER NOTE: Standard flush doors


with applied seals can achieve STC 35. If
greater STC is required, a tested door,
frame, and hardware assembly must be
specified.

G. Sound Rated Doors:


1. Fabricated as specified for flush wood doors with additional
construction requirements to comply with specified sound
transmission class (STC).

08 14 00 - 8
02-01-16

2. STC Rating of door assembly in place when tested according to


ASTM E90 by independent acoustical testing laboratory
minimum // 35 // ______ //.
3. Accessories:
a. Frame Gaskets and Automatic Door Bottom Seal: As specified in
Section 08 71 00, DOOR HARDWARE.
H. Dutch Doors:
1. Consist of two sections, each fabricated as specified for flush
doors.
2. Construct shelf as detailed, from clear hardwood stock of same
species as face veneer of door.
3. Place shelf on top of lower section of door and support as shown
with a pair of wood or wrought steel brackets.
4. Prime steel brackets for finish painting.

2.1.1.3 STILE AND RAIL WOOD DOORS


A. Doors: ANSI/WDMA I.S. 6A; Grade // Premium, // Custom, // size and
design shown on drawings.
B. Species: Ponderosa pine.
C. Door Panels:
1. Grain of face of panels parallel with longest dimensions of panel.
2. Flat panels: Veneered composite core, minimum 16 mm (5/8 inch)
thick.
3. Raised panels: Unless otherwise shown, thickness of raised panels
minimum the following:

SPEC WRITER NOTE: Fire-rated stile and


rail doors are only available 44 mm
(1-3/4 inch) thick.

a. For 35 mm (1-3/8 inch) and 44 mm (1-3/4 inch) thick doors: 28 mm


(1-1/8 inch) thick.
4. Where armor plate is required for paneled doors, provide panels with
plywood fillers, glued in place, and finished.
D. Stops and Molds:
1. Solid sticking both sides, same material as stiles and rails, coped
joints.
2. Glazed Vision Panel Frame: Applied wood stops nailed on interior
side of door.
E. Louvers: Size as shown.

08 14 00 - 9
02-01-16

2.1.1.4 FABRICATION
A. Factory machine interior wood doors to receive hardware, bevels,
undercuts, cutouts, accessories and fitting for frame.
1. Factory fit fire rated doors according to NFPA 80.
B. Rout doors for hardware using templates and location heights specified
in Section 08 71 00, DOOR HARDWARE.
C. Factory fit doors to frame, bevel lock edge of doors 3 mm (1/8 inch) for
each 50 mm (2 inches) of door thickness // undercut where shown //.
D. Clearances between Doors and Frames and Floors:
1. Fire Rated Doors: Comply with NFPA 80.
a. Doors with Automatic Bottom Seal: Maximum clearance 10 mm
(3/8 inch) at threshold.
b. Other Door Bottoms: Maximum 3 mm (1/8 inch) clearance at the
jambs, heads, and meeting stiles, and a 19 mm (3/4 inch)
clearance at bottom, except as otherwise specified.
2. Door Jambs, Heads, and Meeting Stiles: Maximum 3 mm (1/8 inch).
E. Provide cutouts for // glazed // and louver // openings.
F. Finish surfaces, including both faces, top and bottom and edges of the
doors smooth to touch.
G. Identify each door on top edge.
1. Mark with stamp, brand or other indelible mark, giving
manufacturer’s name, door’s trade name, construction of door, date
of manufacture and quality.
2. Mark door or provide separate certification including name of
inspection organization.
3. Identify door manufacturing standard, including glue type.
4. Identify veneer and quality certification.
5. Identification of preservative treatment for stile and rail doors.

SPEC WRITER NOTE: If there are more than


10 doors at any project, factory apply
transparent finish.

2.1.1.5 FINISHES
A. Field Finished Doors: Seal top and bottom edges of doors with two coats
of catalyzed polyurethane or water resistant sealer.
B. Factory Transparent Finish:
1. Factory finish // flush // stile and rail // wood doors.
a. ANSI/WDMA I.S. 1A Section F-3 Finish System Descriptions for
System 5, Conversion Varnish or System 7, Catalyzed Vinyl.

08 14 00 - 10
02-01-16

b. Use stain when required to produce finish specified in Section


09 06 00, SCHEDULE FOR FINISHES.

PART 3 - EXECUTION

3.1.1.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Verify door frames are properly anchored.
2. Verify door frames are plumb, square, in plane, and within
tolerances for door installation.
B. Protect existing construction and completed work from damage.
C. Install astragal on active leaf of pair of smoke doors and one leaf of
double egress smoke doors.

3.1.1.2 INSTALLATION
A. Install products according to manufacturer's instructions // and
approved submittal drawings //.
1. Install fire rated doors according to NFPA 80.
2. When manufacturer's instructions deviate from specifications, submit
proposed resolution for Contracting Officer's Representative
consideration.

3.1.1.3 PROTECTION
A. After installation, place shipping container over door and tape in
place.
1. Do not apply tape to door faces and edges.
B. Provide protective covering over exposed hardware in addition to
covering door.
C. Maintain covering in good condition until removal is directed by
Contracting Officer's Representative.

- - E N D - -