COLDPOINT

Complaint Frequency LOCATION Problem/Findings Description Action Taken Remarks

UNIT 1502, UNIT 2205, UNIT 1201,


UNIT 1403, UNUT 2605, UNIT 2103, PRIORITY SCHEDULE DUE TO FIRE STATUS ON FDAS
UNIT 2219, UNIT 2308, UNIT 2511, CONDUCT CHECKING OF LIST OF FAULT AND FIRE PANEL
25-Sep-17 FAULTS STATUS ON FDAS AS NEEDED UNIT 3001, UNIT 2906, UNIT 822, FAULTS AND FIRE DISPLAY ON FDAS PANEL
DISPLAY ON FDAS PANEL UNIT PH08
UNIT 2416, AUX. RM 12/F, AUX. RM
24/F, FUNCTION RM G/F, PMO B1,
EE RM 24/F, EE RM G/F, EE 23/F

CONDUCT PREVENTIVE MAINTENANCE FOR FDAS


EE RM, AUX. RM FROM ROOF DECK DEFECTIVE TOUCH SCREEN FOR FDAS PANEL AT 28TH FLR DEVICES ON GOING PREVENTIVE MAINTENANCE
26-Sep-17 NONE AS NEEDED TO 21ST FLR, UNIT PH08 AND DUE TO HALF DISPLAY ON TOUCH SCREEN ELIMINANTE TRIGGER ALARM AT PH08 AND MANUAL DEFECTIVE TOUCH SCREEN SUBJECT FOR REPLACEMENT
MACHINE ROOM ROOF DECK
CALL POINT 14/F

EE ROOM & AUX. ROOM 10TH TO CONDUCT PREVENTIVE MAINTENANCE FOR FDAS ON GOING PREVENTIVE MAINTENANCE
27-Sep-17 NONE AS NEEDED DEFECTIVE SMOKE DETECTOR AT AUX. RM 12/F
20TH FLOOR DEVICES DEFECTIVE DETECTOR SUBJECT FOR REPLACEMENT

GROUND FLR TO 10TH FLR, ON GOING PREVENTIVE MAINTENANCE


CONDUCT PREVENTIVE MAINTENANCE FOR FDAS
28-Sep-17 NONE AS NEEDED FUNCTION RM, STUDY RM AND DEFECTIVE LINE RESISTOR END OF LINE RESISTOR AT FUNCTION RM GROUND FLR
DEVICES
LOBBY AREA SUBJECTED FOR REPLACEMENT
PMO, WATER STATION, MAIL RM,
CONDUCT PREVENTIVE MAINTENANCE FOR FDAS ON GOING PREVENTIVE MAINTENANCE
29-Sep-17 NONE AS NEEDED CONVINIENCE STORE, PARKING AREA ALL DETECTOR AT PMO HAVE NO 24 VDC SUPPLY
DEVICES DETECTOR AT PMO SUBJECT FOR TROUBLE SHOOT
IN BASEMENT 1
ON GOING PREVENTIVE MAINTENACE
CONDUCT PREVENTIVE MAINTENANCE FOR FDAS DEFECTIVE HEAT DETECTOR AT BASEMENT 2 AREA
30-Sep-17 NONE AS NEEDED BASEMENT 2 PARKING AREA DEFECTIVE HEAT DETECTOR (CONVENTIONAL)
DEVICES FRONT OF PARKING SLOT 236 G 237 (1PC)
SUBJECT FOR REPLACEMENT
DEFECTIVE HEAT DETECTOR @ PARKING -30
NO DETECTOR HEAD @ CHECK STATUS OF PANEL & CONDUCT PREVENTIVE
2-Oct-17 NONE AS NEEDED BASEMENT 3 ON GOING PREVENTIVE MAINTENACE
PARKING - 55 MAINTENACE OF FDAS DEVICE
NO HEAT DETECTOR HEAD AND BASE @ PARKING -61

DEFECTIVE SMOKE DETECTOR @ UNIT 2612


2 BEDROOM SMOKE DETECTOR CONVENTIONAL
CONTINOUS ALARM @ CONTROL 1 LIVING ROOM SMOKE DETECTOR CONVENTIONAL CONDUCT PREVENTIVE MAINTENANCE AND
3-Oct-17 AS NEEDED UNIT 2612, PH08. AND BASEMENT 3 ALL DEFECTIVE DETECTOR SUBJECT FOR REPLACEMENT
PANEL 1 KITCHEN (PH08) HEAT DETECTOR TROUBLESHOOTING
1 BASEMENT 3 (PARKING 30) HEAT DETECTOR
ALL DEFECTIVE

UNIT 3102, UNIT 3104, UNIT 3107,


4-Oct-17 NONE AS NEEDED UNIT 3115, UNIT 3116, PH13, PH14, DEFECTIVE SMOKE DETECTOR @ MASTER BEDROOM CONDUCT PREVENTIVE MAINTENANCE OF FDAS DEFECTIVE SMOKE DETECTOR SUBJECT FOR
DEVICES @ 31ST FLOOR REPLACEMENT
PH16, PH09, PH01
UNIT 3005, UNIT 3007, UNIT 3008,
UNIT 3005, UNIT 3004, UNIT 3001,
CONDUCT PREVENTIVE MAINTENACE OF FDAS AT
5-Oct-17 NONE AS NEEDED UNIT 3015, UNIT 3013, UNIT 3012, NONE 31ST AND 30TH FLOOR ON GOING PREVENTIVE MAINTENACE
UNIT 3114, UNIT 3113, UNIT 3103
AND UNIT 3009

UNIT 2906, UNIT 3216, UNIT 1605,


UNIT 1117, UNIT 2905, UNIT 2904,
6-Oct-17 NONE AS NEEDED UNIT 2903, UNIT 2902, UNIT 2901, UNIT 2906 NO SMOKE DETECTOR AND BASE INSTALLED @ CONDUCT PREVENTIVE MAINTENANCE OF FDAS ON GOING PREVENTIVE MAINTENANCE
UNIT 2909, UNIT 2911, UNIT 2914, BEDROOM DEVICES @ 32ND, 29TH, 28TH, 16TH, 11TH/FLOOR
UNIT 2915, UNIT 2809, UNIT 2810,
UNIT 2804

UNIT 2806, UNIT 2514, UNIT 2511,


UNIT 2506, UNIT 2507, UNIT 2516, DEFECTIVE MIU ( MAIN INSTRUMENT UNIT ) @ UNIT 2514 CONDUCT PREVENTIVE MAINTENANCE OF FDAS
7-Oct-17 NONE AS NEEDED UNIT 2515, UNIT 2512, UNIT 2803, ALL DETECTOR ARE COVERED BY CEILING NEED FOR ON GOING PREVENTIVE MAINTENANCE
DEVICES @ 28TH, 27TH, 28TH/FLR
UNIT 2813, UNIT 2710, UNIT 2712, RELOCATION @ UNIT 2813
UNIT 2711, UNIT 2715, UNIT 2707

UNIT 2120, UNIT 1918, UNIT 1920,


UNIT 1917, UNIT 1013, UNIT 1915, CONDUCT PREVENTIVE MAINTENANCE OF FDAS
9-Oct-17 NONE AS NEEDED NONE ON GOING PREVENTIVE MAINTENACE
UNIT 1916, UNIT 1919, UNIT 1904, DEVICES @ 21ST, 19TH, 26TH/FLR
UNIT 2608
UNIT 2410, UNIT 2409, UNIT 2609,
UNIT 2411, UNIT 2402, UNIT 2613,
10-Oct-17 NONE AS NEEDED UNIT 2614, UNIT 2615, UNIT 2601, UNIT 2409 HEAT DETECTOR WAS ALREADY DEFECTIVE CONDUCT PREVENTIVE MAINTENANCE OF FDAS ON GOING PREVENTIVE MAINTENANCE
DEVICES @ 24TH, 26TH FLOOR DEFECTIVE DETECTOR NEED FOR REPLACEMENT
UNIT 2602, UNIT 2412, UNIT 2413,
UNIT 2415

UNIT 2307, DEFECTIVE SMOKE DETECTOR @ LOBBY RM


UNIT 2313, DEFECTIVE SMOKE DETECTOR @ BEDROOM
UNIT 3203, UNIT 2307, UNIT 2404, BATTERY DEFECTIVE OF PANEL 1,2,3 (12V, 12AH ZDF) FOR CONDUCT PREVENTIVE MAINTENANCE OF FDAS ON GOING PREVENTIVE MAINTENANCE
11-Oct-17 NONE AS NEEDED UNIT 2316, UNIT 3201, UNIT 3202,
UNIT 3204, UNIT 3206 DF6020 (6PCS) DEVICES @ 32TH, 23TH, 24TH/FLOOR AND PANEL DEFECTIVE BATTERY SUBJECT FOR REPLACEMENT
BATTERY DEFECTIVE OF PANEL 4 ( 12V 7AH FOR CF1200)
(2PCS)

UNIT 2213, UNIT 2219, UNIT 2220,


UNIT 2201, UNIT 2203, UNIT 2217,
UNIT 2210, 2204, UNIT 2206, UNIT
12-Oct-17 NONE AS NEEDED 2109, UNIT 2112, UNIT 2113, UNIT DEFECTIVE SMOKE DETECTOR @ UNIT 2002 MASTER CONDUCT PREVENTIVE MAINTENACE OF FDAS ON GOING PREVENTIVE MAINTENACE
BEDROOM DEVICES @ 22TH, 21TH, 20TH/FLOOR
2119, UNIT 2102, UNIT 2105, UNIT
2019, UNIT 2004, UNIT 2001, UNIT
2002

UNIT 3213, UNIT 3214, UNIT 3215,


13-Oct-17 NONE AS NEEDED UNIT 3212, UNIT 2406, UNIT 2405, NONE CONDUCT PREVENTIVE MAINTENANCE OF FDAS ON GOING PREVENTIVE MAINTENACE
UNIT 2308, UNIT 2213, DEVICES @ 32TH, 23TH

UNIT 1908, UNIT 1812, UNIT 1811,


UNIT 1816, UNIT 1818, UNIT 1807,
14-Oct-17 NONE AS NEEDED UNIT 1810, UNIT 1804, UNIT 11718, 1 HEAT DETECTOR WAS ALREADY DEFECTIVE @ UNIT 1816 CONDUCT PREVENTIVE MAINTENACE OF FDAS ON GOING PREVENTIVE MAINTENACE
UNIT 1720, UNIT 1701, 1702, UNIT DEVICES @ 19TH, 18TH, 17TH, 25TH/FLOOR HEAT DETECTOR SUBJECT TO BE REPLACE
1703, UNIT 2505, UNIT 1503, UNIT
1507

16-Oct-17 NONE AS NEEDED UNIT 109, UNIT 103, UNIT 102, UNIT NONE CONDUCT PREVENTIVE MAINTENANCE OF FDAS ON GOING PREVENTIVE MAINTENACE
101, UNIT 105, UNIT 1508 DEVICES @ 15TH TO GROUND FLOOR
UNIT 1407, UNIT 1505, UNIT 1510,
UNIT 1506, UNIT 1415, UNIT 1416,
UNIT 1417, UNIT 1418, UNIT 1419, CONDUCT PREVENTIVE MAINTENACE OF FDAS
17-Oct-17 NONE AS NEEDED NONE ON GOING PREVENTIVE MAINTENACE
UNIT 1420, UNIT 1401, UNIT 1606, DEVICES @ 14TH, 15TH, 16TH/FLOOR
UNIT 1606, UNIT 1404, UNIT 1410,
UNIT 1408

UNIT 1501, UNIT 1520, 1519, UNIT


18-Oct-17 NONE AS NEEDED 1209, UNIT 1208, UNIT 1207, UNIT NONE CONDUCT PREVENTIVE MAINTENACE OF FDAS ON GOING PREVENTIVE MAINTENANCE
DEVICES @ 15TH, 12TH FLOOR
1222, UNIT 1221, UNIT 1213
UNIT 1003, UNIT 1007, UNIT 1008, CONDUCT PREVENTIVE MAINTENANCE OF FDAS
19-Oct-17 NONE AS NEEDED UNIT 1017, UNIT 1020, UNIT 912 NONE DEVICES @ 10TH AND 9TH/FLR ON GOING PREVENTIVE MAINTENACE

UNIT 913, UNIT 902, UNIT 903, UNIT CONDUCT PREVENTIVE MAINTENANCE OF FDAS
20-Oct-17 NONE AS NEEDED NONE ON GOING PREVENTIVE MAINTENACE
904, UNIT 921, UNIT 901 DEVICES @ 9TH FLOOR
DEFECTIVE END OF LINE SMOKE DETECTOR @ FUNCTION
SMOKE DETECTOR AND HEAT ROOM LOBBY AREA CONDUCT PREVENTIVE MAINTENACE & TROUBLE
21-Oct-17 AS NEEDED GROUND FLOOR, BASEMENT 2 & 3 ON GOING PREVENTIVE MAINTENACE
DETECTOR DEFECTIVE END OF LINE OF HEAT DETECTOR @ B2 & B3 SHOOTING OF FDAS @ GF/B2 & B3

UNIT 722, UNIT 719, UNIT 718, UNIT CONDUCT PREVENTIVE MAINTENACE & TROUBLE
23-Oct-17 NONE AS NEEDED 716, UNIT 712, UNIT 710 NONE SHOOTING OF FDAS @ 7TH ON GOING PREVENTIVE MAINTENACE

UNIT 706, UNIT 702, UNIT 701, UNIT


822, UNIT 817, UNIT 817, UNIT 816, CONDUCT PREVENTIVE MAINTENACE & TROUBLE
24-Oct-17 NONE AS NEEDED NONE ON GOING PREVENTIVE MAINTENACE
UNIT 815, UNIT 814, UNIT 812, UNIT SHOOTING OF FDAS @ 7TH, 8TH FLOOR
810
UNIT 511, UNIT 504, UNIT 505, UNIT CONDUCT PREVENTIVE MAINTENACE & TROUBLE
25-Oct-17 NONE AS NEEDED NONE ON GOING PREVENTIVE MAINTENACE
503, UNIT 501, UNIT 502, UNIT 607 SHOOTING OF FDAS @ 5TH, 6TH FLOOR

26-Oct-17 NONE AS NEEDED UNIT 620, UNIT 601, UNIT 603, UNIT BEDROOM 1 SMOKE DETECTOR WAS ALREADY DEFECTIVE @ CONDUCT PREVENTIVE MAINTENACE & TROUBLE ON GOING PREVENTIVE MAINTENACE
610, UNIT 609, UNIT 606, UNIT 506 UNIT 506 SHOOTING OF FDAS @ 5TH, 6TH FLOOR
UNIT 512, UNIT 515, UNIT 517, UNIT
SMOKE DETECTOR @ MASTER BEDROOM WAS ALREADY CONDUCT PREVENTIVE MAINTENACE & TROUBLE ON GOING PREVENTIVE MAINTENACE
27-Oct-17 NONE AS NEEDED 412, UNIT 402, UNIT 422, UNIT 403, DEFECTIVE @ UNIT 403 SHOOTING OF FDAS @ 5TH, 4TH, 3RD FLOOR SMOKE DETECTOR NEED FOR REPLACEMENT
UNIT 411, UNIT 410, UNIT 306
BASEMENT 1, PMO 1 HEAT DETECTOR DEFECTIVE CONDUCT PREVENTIVE MAINTENANCE &
28-Oct-17 NONE AS NEEDED UNIT 307, UNIT 312, UNIT 317, UNIT BASEMENT 2, END OF LINE RESISTOR TROUBLESHOOTING OF FDAS DEVICES @ ON GOING PREVENTIVE MAINTENACE
322, UNIT 301
BASEMENT 3, END OF LINE RESISTOR 3RD/B1/B2/B3

8-Nov-17 NONE AS NEEDED UNIT 2002-130, 1502-130, 2205-0, FAULTS STATUS CONDUCT CHECK-UP OF PANELS FOR PRIORITY UNIT NONE
1201-0, TO CHECK DUE TO FAULTS STATUS
MCIM-C MODULE STILL "O" UNIT 21, UNIT 22, 27TH FLOOR CONDUCT CHECK-UP OF WATER FLOW SWITCH @
10-Nov-17 AS NEEDED DEFECTIVE MCIM-C MODULE 3 MCIM - C MODULE FOR REPLACEMENT
ANALOGUE COMMON AREA 21ST, 22ND, 27TH COMMON AREA
UNIT PH 11, UNIT 3203, UNIT 3111,
UNIT 3010, UNIT 3011, UNIT 2808, DEFECTIVE SMOKE DETECTOR @ UNIT 2702, UNIT 3010, CONDUCTING PREVENTIVE MAINTENANCE OF SMOKE
17-Nov-17 NONE AS NEEDED SMOKE DETECTOR SUBJECT FOR REPLACEMENT
UNIT 2801, UNIT 2702, UNIT 2716, UNIT 3202 DETECTOR FDAS SYSTEM
UNIT 2716, UNIT 2603, UNIT 2604
CONDUCT PREVENTIVE MAINTENANCE OF FDAS @
21-Nov-17 NONE AS NEEDED UNIT 2501, UNIT 2314, UNIT 2101 NONE NONE
UNIT 2501, UNIT 2314, UNIT 2101
UNIT 2010, UNIT 2020, UNIT 2012,
UNIT 2015, UNIT 1907, UNIT 1905,
23-Nov-17 NONE AS NEEDED DEFECTIVE HEAT DETECTOR @ UNIT 1705 CONDUCT PREVENTIVE MAINTENANCE OF FDAS HEAT DETECTOR SUBJECT FOR REPLACEMENT
UNIT 1901, UNIT 1820, UNIT 1716,
UNIT 1704, UNIT 1710, UNIT 1705

COMMON AREA @ 9TH FLOOR CONDUCT CHECK - UP OF PANEL, 1 FAULTS &


24-Nov-17 NONE AS NEEDED UNIT 1608, UNIT 1618, UNIT 1620, CALL POINT FAULT STATUS @ 9TH FLOOR PREVENTIVE MAINTENANCE STATUS OK
CHECK MCIMC MODULE FOR WATER FLOW &
UNIT 1615
TAMPER SWITCH
UNIT 1514, UNIT 1578, UNIT 1412, CONDUCT PREVENTIVE MAINTENACE OF FDAS @
28-Nov-17 NONE AS NEEDED UNIT 1414, UNIT 1416, UNIT 1405, NONE UNIT 1514, UNIT 1578, UNIT 1412, UNIT 1414, UNIT STATUS OK
UNIT 1202, UNIT 1211, UNIT 1216 1416, UNIT 1405, UNIT 1202, UNIT 1211, UNIT 1216
UNIT 1121, UNIT 1120, UNIT 1012,
UNIT 1015, UNIT 1001, UNIT 1005, CONDUCT PREVENTIVE MAINTENANCE OF FDAS @
29-Nov-17 NONE AS NEEDED UNIT 918, UNIT 920, UNIT 914, UNIT DEFECTIVE HEAT DETECTOR @ UNIT 717 STATUS OK
UNIT
707, UNIT 709, UNIT 711, UNIT 720,
UNIT 717
CONDUCT PREVENTIVE MAINTENANCE OF FDAS @
UNIT 401, UNIT 520, UNIT 519, UNIT
4-Dec-17 FIRE STATUS AT 2304 AS NEEDED END OF LINE RESISTOR IS SHORTED UNIT 401, UNIT 520, UNIT 519, UNIT 518, UNIT 509, END OF LINE NEED TO BE REPLACE
518, UNIT 509, UNIT 618, UNIT 612 UNIT 618, UNIT 612
CONDUCT CHECK - UP OF MCIM MODULE "O"
INSTALL SMOKE @ PH16 - 1, 2612 - 3
6-Dec-17 NONE AS NEEDED 15TH, 22ND, 23RD FLOOR STATUS OF MODULE READING "O" ANALOGUE MODULE ANALOG "O" ANALOGUE FOR REPLACEMENT
INSTALL HEAT @ 2409 - 1, BASEMENT 3 @ FRONT
SLOT # 30 -1, PMO - 1

LIST OF DEFECTIVE END OF LINE (EOL) RESISTOR


717,1403,1705,2304,2703,2017,2605,2612,703,604,2409,
2802,PH08,3203,3010,3208,3107,822,3209,2511,1006,2103,
2219, PARKING 3A-B3,4-B2, NEAR PUMP RM. B3
6TH, 7TH, 8TH, 10TH, 12TH, 14TH, MAIN INSTRUMENT UNIT (MIU)
REPLACED DEFECTIVE SMOKE DETECTOR
15TH, 17TH, 20TH, 21ST, 23RD, 1201,2416,2514 UNITS
7-Dec-17 NONE AS NEEDED 24TH, 25TH, 26TH, 27TH, 28TH, MICRO SINGLE CHANNEL INPUTS UNITS (MCIM) MODULE CONDUCT CHECK - UP OF FDAS MAIN INSTRUMENT UNIT FOR REPLACEMENT
30TH, 31ST, 32ND, PENTHOUSE, B3, WATER & TAMPER FLOW SWITCH INSTALL SMOKE DETECTOR @ 2002 END OF LINE RESISTOR FOR REPLACEMENT
MCIM FOR REPLACEMENT
B2 15TH, 21ST, 22ND, 27TH FLOOR
SMOKE DETECTOR
12TH FLOOR AUX. RM
22ND FLOOR EE RM
6TH FLOOR EE RM

UNIT 2307, UNIT 2313, UNIT PH08, INSTALLATION OF HEAD OF HEAT AND SMOKE
11-Dec-17 NONE AS NEEDED UNIT 3010, UNIT 2702, UNIT 1705 DEFECTIVE SMOKE AND HEAT DETECTOR DETECTOR STATUS OK

INSTALLATION OF SMOKE DETECTOR & HEAT


DETECTOR HEADS ONLY
UNIT 1201, UNIT 2711, AND 28TH PREVENTIVE MAINTENANCE @ UNIT 2711 BEDROOM REPLACED LCD PANEL, EOL, SMOKE AND HEAT DETECTOR
14-Dec-17 DETECTOR ALARM AND LCD FAILURE AS NEEDED FLOOR DEFECTIVE LCD, DETECTOR ALARM AND DEFECTIVE EOL AREA DUE TO DETECTOR ALARM HEADS
REPLACE LCD PANEL 3 @ 28TH FLOOR

15-Dec-17 DEFECTIVE DEVICE AS NEEDED UNIT 2416 DEFECTIVE MIU MODULE INSTALL OF MIU MODULE DUE TO DEFECTIVE DEVICE CONTINUE INSTALL