Division 23 - Heating, Ventilating, and Air-Conditioning (Hvac) Section 230529 - Hangers and Supports For Hvac Piping and Equipment
Division 23 - Heating, Ventilating, and Air-Conditioning (Hvac) Section 230529 - Hangers and Supports For Hvac Piping and Equipment
Division 23 - Heating, Ventilating, and Air-Conditioning (Hvac) Section 230529 - Hangers and Supports For Hvac Piping and Equipment
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
2 SUMMARY
A. Section Includes:
B. Related Sections:
1. Section 055000 "Metal Fabrications" for structural-steel shapes and plates for
trapeze hangers for pipe and equipment supports.
2. Section 230548.13 "Vibration Controls for HVAC" for vibration isolation
devices.
3. Section 233113 "Metal Ducts" for duct hangers and supports.
3 DEFINITIONS
A. MSS: Manufacturers Standardization Society of The Valve and Fittings Industry Inc.
4 PERFORMANCE REQUIREMENTS
A. Delegated Design: Design trapeze pipe hangers and equipment supports, including
comprehensive engineering analysis by a qualified professional engineer, using
performance requirements and design criteria indicated.
B. Structural Performance: Hangers and supports for HVAC piping and equipment shall
withstand the effects of gravity loads and stresses within limits and under conditions
indicated according to ASCE/SEI 7.
1. Design supports for multiple pipes, including pipe stands, capable of supporting
combined weight of supported systems, system contents, and test water.
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 1
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
5 ACTION SUBMITTALS
B. Shop Drawings: Show fabrication and installation details and include calculations for
the following; include Product Data for components:
6 QUALITY ASSURANCE
PART 2 - PRODUCTS
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 3
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
B. Insulation-Insert Material for Cold Piping: minimum compressive strength and vapor
barrier.
C. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference
of pipe.
D. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.
E. Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below
ambient air temperature.
5 FASTENER SYSTEMS
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 4
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
1. Provide mechanical anchors that meet ACI 318 Appendix D requirements for
cracked concrete and have a current approved ICC Evaluation Service Report.
6 PIPE STANDS
B. Compact Pipe Stand: One-piece plastic unit with integral-rod roller, pipe clamps, or
V-shaped cradle to support pipe, for roof installation without membrane penetration.
C. Low-Type, Single-Pipe Stand: One-piece plastic base unit with plastic roller, for roof
installation without membrane penetration.
a. Approved Equal.
a. Approved Equal.
7 EQUIPMENT SUPPORTS
A. See Roof Plans or Schedules for rail height and dimensions - if no dimensions given,
height is 24" high or as required for proper installation and wide enough to support
equipment feet and/or vibration isolation devices. (see Vibration Control specification
section).
C. Install per manufacturer's instructions including flashing & counterflashing for a water
tight installation - including patching of roof. Attach equipment to rail and rail to
support structure.
A. See Roof Plans or Schedules for curb height and dimensions - if no dimensions given,
height is 24" high or as required for proper installation and enough length/width to
accommodate the duct or ducts including their insulation going through the curb to
penetrate the roof.
B. Curb shall have a minimum of 2" of insulation including the top of the curb. The top
of the curb insulation shall be installed on the interior side.
C. Install per manufacturer's instructions including flashing & counterflashing for a water
tight installation - including patching of roof. Attach duct to curb and curb to support
structure.
A. See Roof Plans or Schedules for curb height and dimensions - if no dimensions given,
height is 24" high or as required for proper installation and enough length/width to
accommodate the pipe or pipes including their insulation going through the curb to
penetrate the roof.
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 6
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
B. Piping shall exit curb near the top and through the side of the curb. Piping exit shall
be made water tight.
C. Curb shall have a minimum of 2" of insulation including the top of the curb. The top
of the curb insulation shall be installed on the interior side.
D. Install per manufacturer's instructions including flashing & counterflashing for a water
tight installation - including patching of roof. Attach duct to curb and curb to support
structure.
11 MISCELLANEOUS MATERIALS
A. Structural Steel: ASTM A 36/A 36M, carbon-steel plates, shapes, and bars; black and
galvanized.
PART 3 - EXECUTION
A. Provide and install hangers / supports per manufacturer's instructions, applicable year
of International Mechanical Code and Construction Documents for a complete hanger /
support system.
B. Metal Pipe-Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install
hangers, supports, clamps, and attachments as required to properly support piping from
the building structure.
C. Metal Trapeze Pipe-Hanger Installation: Comply with MSS SP-69 and MSS SP-89.
Arrange for grouping of parallel runs of horizontal piping, and support together on
field-fabricated trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe
size or install intermediate supports for smaller diameter pipes as specified for
individual pipe hangers.
2. Field fabricate from ASTM A 36/A 36M, carbon-steel shapes selected for loads
being supported. Weld steel according to AWS D1.1/D1.1M.
E. Metal Framing System Installation: Arrange for grouping of parallel runs of piping,
and support together on field-assembled metal framing systems.
F. Fiberglass Strut System Installation: Arrange for grouping of parallel runs of piping,
and support together on field-assembled fiberglass struts.
J. Install hangers and supports complete with necessary attachments, inserts, bolts, rods,
nuts, washers, and other accessories.
L. Install hangers and supports to allow controlled thermal and seismic movement of
piping systems, to permit freedom of movement between pipe anchors, and to facilitate
action of expansion joints, expansion loops, expansion bends, and similar units.
M. Install lateral bracing with pipe hangers and supports to prevent swaying.
N. Install building attachments within concrete slabs or attach to structural steel. Install
additional attachments at concentrated loads, including valves, flanges, and strainers,
NPS 2- and larger and at changes in direction of piping. Install concrete inserts before
concrete is placed; fasten inserts to forms and install reinforcing bars through openings
at top of inserts.
O. Load Distribution: Install hangers and supports so that piping live and dead loads and
stresses from movement will not be transmitted to connected equipment.
P. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not
exceed maximum pipe deflections allowed by ASME B31.9 for building services
piping.
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 8
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
Q. Insulated Piping:
2. Install MSS SP-58, Type 39, protection saddles if insulation without vapor
barrier is indicated. Fill interior voids with insulation that matches adjoining
insulation.
3. Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier.
Shields shall span an arc of 180 degrees.
a. NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick.
b. NPS 4: 12 inches long and 0.06 inchthick.
c. NPS 5 and NPS 6: 18 inches long and 0.06 inch thick.
d. NPS 8 to NPS 14: 24 inches long and 0.075 inch thick.
e. NPS 16 to NPS 24: 24 inches long and 0.105 inch thick.
2 EQUIPMENT SUPPORTS
B. Grouting: Place grout under supports for equipment and make bearing surface
smooth.
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 9
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
3 METAL FABRICATIONS
A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and
equipment supports.
B. Fit exposed connections together to form hairline joints. Field weld connections that
cannot be shop welded because of shipping size limitations.
C. Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc
welding; appearance and quality of welds; and methods used in correcting welding
work; and with the following:
1. Use materials and methods that minimize distortion and develop strength and
corrosion resistance of base metals.
2. Obtain fusion without undercut or overlap.
3. Remove welding flux immediately.
4. Finish welds at exposed connections so no roughness shows after finishing and
so contours of welded surfaces match adjacent contours.
4 ADJUSTING
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.
5 PAINTING
A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas
immediately after erecting hangers and supports. Use same materials as used for shop
painting. Comply with SSPC-PA 1 requirements for touching up field-painted
surfaces.
1. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0
mils.
B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
A. Specific hanger and support requirements are in Sections specifying piping systems and
equipment.
B. Comply with MSS SP-69 for pipe-hanger selections and applications that are not
specified in piping system Sections.
C. Use hangers and supports with galvanized metallic coatings for piping and equipment
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 10
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
E. Use carbon-steel pipe hangers and supports, metal trapeze pipe hangers and metal
framing systems and attachments for general service applications.
F. Use copper-plated pipe hangers and copper or stainless-steel attachments for copper
piping and tubing.
16. Adjustable Pipe Saddle Supports (MSS Type 38): For stanchion-type support
for pipes NPS 2-1/2 to NPS 36 if vertical adjustment is required, with steel-pipe
base stanchion support and cast-iron floor flange.
17. Single-Pipe Rolls (MSS Type 41): For suspension of pipes NPS 1 to NPS 30,
from two rods if longitudinal movement caused by expansion and contraction
might occur.
18. Adjustable Roller Hangers (MSS Type 43): For suspension of pipes NPS 2-1/2
to NPS 24, from single rod if horizontal movement caused by expansion and
contraction might occur.
19. Complete Pipe Rolls (MSS Type 44): For support of pipes NPS 2 to NPS 42 if
longitudinal movement caused by expansion and contraction might occur but
vertical adjustment is not necessary.
20. Pipe Roll and Plate Units (MSS Type 45): For support of pipes NPS 2 to NPS
24 if small horizontal movement caused by expansion and contraction might
occur and vertical adjustment is not necessary.
21. Adjustable Pipe Roll and Base Units (MSS Type 46): For support of pipes NPS
2 to NPS 30 if vertical and lateral adjustment during installation might be
required in addition to expansion and contraction.
1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS
3/4 to NPS 24.
2. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers
NPS 3/4 to NPS 24 if longer ends are required for riser clamps.
1. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy
loads.
2. Steel Clevises (MSS Type 14): For 120 to 450 deg F piping installations.
3. Swivel Turnbuckles (MSS Type 15): For use with MSS Type 11, split pipe
rings.
4. Malleable-Iron Sockets (MSS Type 16): For attaching hanger rods to various
types of building attachments.
5. Steel Weldless Eye Nuts (MSS Type 17): For 120 to 450 deg F piping
installations.
1. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to
suspend pipe hangers from concrete ceiling.
2. Top-Beam C-Clamps (MSS Type 19): For use under roof installations with
bar-joist construction, to attach to top flange of structural shape.
3. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange
of beams, channels, or angles.
4. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 12
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
of beams.
5. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if
loads are considerable and rod sizes are large.
6. C-Clamps (MSS Type 23): For structural shapes.
7. Top-Beam Clamps (MSS Type 25): For top of beams if hanger rod is required
tangent to flange edge.
8. Side-Beam Clamps (MSS Type 27): For bottom of steel I-beams.
9. Steel-Beam Clamps with Eye Nuts (MSS Type 28): For attaching to bottom of
steel I-beams for heavy loads.
10. Linked-Steel Clamps with Eye Nuts (MSS Type 29): For attaching to bottom of
steel I-beams for heavy loads, with link extensions.
11. Malleable-Beam Clamps with Extension Pieces (MSS Type 30): For attaching
to structural steel.
12. Welded-Steel Brackets: For support of pipes from below or for suspending from
above by using clip and rod. Use one of the following for indicated loads:
13. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams.
14. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is
required.
15. Horizontal Travelers (MSS Type 58): For supporting piping systems subject to
linear horizontal movement where headroom is limited.
M. Saddles and Shields: Unless otherwise indicated and except as specified in piping
system Sections, install the following types:
N. Spring Hangers and Supports: Unless otherwise indicated and except as specified in
piping system Sections, install the following types:
O. Comply with MSS SP-69 for trapeze pipe-hanger selections and applications that are
not specified in piping system Sections.
P. Comply with MFMA-103 for metal framing system selections and applications that are
not specified in piping system Sections.
CHILLED WATER PLANT #1 HANGERS AND SUPPORTS FOR HVAC PIPING AND
SSHE - 401-BL-1099 EQUIPMENT
Addendum #3 - 230529 - 14