615 Series ANSI: Engineering Manual
615 Series ANSI: Engineering Manual
615 Series ANSI: Engineering Manual
The software or hardware described in this document is furnished under a license and may
be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/mediumvoltage
www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties. All
persons responsible for applying the equipment addressed in this manual must satisfy
themselves that each intended application is suitable and acceptable, including that any
applicable safety or other operational requirements are complied with. In particular, any
risks in applications where a system failure and/or product failure would create a risk for
harm to property or persons (including but not limited to personal injuries or death) shall
be the sole responsibility of the person or entity applying the equipment, and those so
responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This product has been designed to be connected and communicate data and information
via a network interface which should be connected to a secure network. It is the sole
responsibility of the person or entity responsible for network administration to ensure a
secure connection to the network and to take the necessary measures (such as, but not
limited to, installation of firewalls, application of authentication measures, encryption of
data, installation of anti virus programs, etc.) to protect the product and the network, its
system and interface included, against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information. ABB is not liable for
any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall ABB
be responsible or liable for any loss or damage resulting from the use of this manual or the
application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on
the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use
within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is
the result of tests conducted by ABB in accordance with the product standards EN 50263
and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and
EN 60255-27 for the low voltage directive. The product is designed in accordance with the
international standards of the IEC 60255 series and ANSI C37.90. This product complies
with the UL 508 certification.
Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.
When the plug-in unit has been detached from the case, do not touch the
inside of the case. The relay case internals may contain high voltage
potential and touching these may cause personal injury.
Table of contents
Section 1 Introduction............................................................................5
This manual.............................................................................................. 5
Intended audience.................................................................................... 5
Product documentation.............................................................................6
Product documentation set..................................................................6
Document revision history................................................................... 6
Related documentation........................................................................7
Symbols and conventions.........................................................................7
Symbols...............................................................................................7
Document conventions........................................................................ 7
Functions, codes and symbols............................................................ 8
Section 1 Introduction
The engineering manual contains instructions on how to engineer the protection relays
using the different tools in PCM600. The manual provides instructions on how to set up
a PCM600 project and insert relays to the project structure. The manual also recommends
a sequence for engineering of protection and control functions, LHMI functions as well as
communication engineering for IEC 61850 and other supported protocols.
This manual addresses system and project engineers involved in the engineering process
of a project, and installation and commissioning personnel, who use technical data during
engineering, installation and commissioning, and in normal service.
The system engineer must have a thorough knowledge of the application, protection and
control equipment and the configured functional logic in the relays. The installation and
commissioning personnel must have a basic knowledge of handling electronic equipment.
Maintenance
Engineering
Planning &
Installation
Operation
Quick start guide purchase
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual
Communication protocol manual
IEC 61850 engineering guide
Point list manual
Cyber security deployment guideline
GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V2 EN
Figure 1: The intended use of documents during the product life cycle
1.4.1 Symbols
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project
or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. Therefore, comply
fully with all warning and caution notices.
• Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push
button icons.
PCM600 is used for various tasks in the protection relay engineering process.
• Communication management
• IEC 61850 station communication engineering is done with a separate tool, for
example, CCT600 or IET600. PCM600 interacts with CCT600 or IET600 by
importing and exporting SCL files.
• Configuring the GOOSE receiving data connections to the protection relay's
application configuration function blocks by using the Application
Configuration tool and the Signal Matrix tool.
• Configuring protocol data mapping for Modbus or DNP3 with the
Communication Management tool.
• Configuring the sampled values (process bus) between the devices using the
Application Configuration tool and IEC 61850 Configuration tool.
• Record management
• Service management
• Monitoring the selected signals of a protection relay for commissioning or
service purposes by using the Signal Monitoring tool and Event Viewer tool
(including audit trail).
GUID-AEEFCDDD-591F-4555-A6D5-78FC69BF623F V3 EN
There are also additional functions for managing projects and organizing user rights.
Once the engineering of the protection relay is finished, the results must be written to the
protection relay.
The connection between the physical IED and PCM600 is established via an Ethernet link
on the front or rear port on the protection relay.
The monitoring and control system for electrical substations contains a number of devices
for various purposes.
Station bus
Station
Communication
IEC08000101.vsd
GUID-414609A0-5B40-453F-83D4-4551B2894023 V1 EN
The monitoring and control system can be divided into three main parts.
A plant structure is used to identify each device in its location within the substation
organization. The plant structure is a logical image of the substation and the bays within
the substation. The organization structure for the devices may differ from the structure of
the primary equipment in the substation.
In PCM600 it is possible to set up a hierarchical structure of five levels for the device
identification.
• Project
• Substation = name of the substation
• Voltage level = identifies to which grid type or part the device belongs in the
substation
• Bay = bay within the voltage level
• IED = the selection of the IED that is used in the bay; it is possible to insert several
IEDs within a bay, for example, one control device and two protection relays
The product series covers protection relays developed for the protection of medium
voltage applications. Every product has predefined application-specific software called
standard configuration that contains protection, control, supervision and measurement
function blocks and default logical connections; for more information, see the application
manuals. The product also includes the standard configuration specific default single-line
diagram.
The content of the standard configuration depends on the intended functional application.
The standard configurations also have selectable software options, which are selected
when ordering the protection relay. Some of the software options are related to the
protection relay hardware.
The standard configurations can be used as is, but they can also be modified by using the
PCM600. The standard configuration itself can be modified or extended by using the
Application Configuration tool, the Signal Matrix tool and the communication
configuration tools. The single-line diagram can also be modified with Graphical Display
Editor.
Some of the standard configurations offers very wide functionality in means of number of
different functions available as part of the product configuration. It is possible to use all
of the offered functions at the same time.
However, if unused function blocks are removed from the configuration with the
Application Configuration, more resources in the protection relay can be used for other
purposes.
2.3 Workflow
Start
End
GUID-400C23DB-E4D5-4DA6-86DB-07BC898E102A V1 EN
It is possible to follow a different sequence based on the information available at the time
when the project is started. This means that several iterations may be needed to complete
the project.
LHMI engineering
• The LEDs are configured with Application Configuration.
• The LED behavior is defined with Parameter Setting.
• The HMI Event Filtering tool can be used to configure event visibility on the LHMI
event list.
Protection and Control IED Manager PCM600 offers all the necessary functionality to
work throughout all stages of the protection relay life cycle.
• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis
The whole substation configuration can be controlled and different tasks and functions
can be performed with the individual tool components. PCM600 can operate with many
different topologies, depending on the customer needs.
PCM600 is used to conduct complete engineering and configuration activities needed for
the bay level protection relays.
Connectivity Packages are separate software packages that provide type and version
information to PCM600. Further Connectivity Packages assist the tool with
communications.
PCM600 uses IEC 61850 over Ethernet to communicate with bay devices. This
communication allows PCM600 to configure and monitor the devices. In addition to IEC
61850 the devices have optional communications protocols and hardware to connect to
station engineering tools. PCM600 provides the ability to export the configuration of the
devices or an entire substation in a standard file format which enables station engineering
in separate IEC 61850 System Configuration tools.
A PC with PCM600 can be connected to any 615 series protection relay within a station
by using the Ethernet connection. The connection can also be used for service and
maintenance purposes. In addition, the connection is used to handle digital fault records
from the protection relays.
The modern-day protection relays are designed using the concept of the IEC 61850
standard. This is primarily in regards to how functions within the protection relay are
modelled and how the protection relay is represented in the substation. See the IEC 61850
parameter list for the list of logical nodes available in the protection relay and observe how
they follow the structure and rules as defined in part 7 of the standard.
The engineering of the used communication protocols is a separate task and an addition to
the engineering of protection and control functions.
PCM600 can be used for different purposes throughout the protection relay life cycle. A
set of special tools is available for different applications.
• Relay engineering
• Communication engineering
• Record management
• Device monitoring and diagnostic
Symbol standard and naming style can be set in PCM600 by selecting Tools/Options/
System Settings. For further information regarding the system settings, see PCM600
online help.
GUID-B21ECBDD-2478-42B5-A292-C816120E5B58 V2 EN
A connectivity package is a software component that consists of executable code and data
which enables system tools to communicate with a protection relay. Connectivity
packages are used to create configuration structures in PCM600. The latest PCM600 and
connectivity packages are backward compatible with older protection relay versions.
A connectivity package includes all the data which is used to describe the protection relay.
For example, it contains a list of the existing parameters, data format used, units, setting
range, access rights and visibility of the parameters. In addition, it contains code which
allows software packages that use the connectivity package to properly communicate with
the protection relay. It also supports localization of text even when it is read from the
protection relay in a standard format such as COMTRADE.
Update Manager is a tool that helps in defining the right connectivity package versions for
different system products and tools. Update Manager is included with the products that
use connectivity packages.
1. Close PCM600.
2. Run the ABB IED Connectivity Package RE_6xx Ver. n.msi installer.
(n = version number)
3. To install the connectivity package, follow the steps in the connectivity package
installation wizard.
GUID-7A72A86C-7F41-4342-AAF3-CF34E8279B4E V3 EN
2. Select Get Connectivity Packages from the menu on the left column.
3. Select all the required connectivity packages.
4. Click Download and Install.
The status bar shows the installation status.
GUID-CD8A9C2A-0CF0-451F-A820-82482C646EB3 V1 EN
1. Select Manage Connectivity Packages from the menu on the left column to access
the installed connectivity packages.
2. Browse the tree structure to find the correct product.
3. Select the connectivity package version from the drop-down list beside the product
name.
GUID-B3D2C177-2737-425F-B4E4-22F4D4326343-ANSI V2 EN
PCM600 recognizes the installed connectivity packages during start-up, and the
corresponding IED types are available in PCM600 when starting a new project.
The 2.0, 4.0, 4.2 and 5.0 FP1 ANSI protection relay versions can be in the
same PCM600 project only if the project was created with ANSI 4.2
connectivity package.
A typical project in PCM600 contains a plant structure including one or several IED
objects, where each IED object contains the engineering data created or modified using
the different PCM600 tools.
Several projects can be created and managed by PCM600, but only one project can be
active at a time.
Regardless the protocol used in installation for each project, the IEC 61850 version must
be selected when adding the first IED to plant structure. After the initial selection, all IEDs
in plant structure use the selected version, either Edition 1 or Edition 2. In case the IEC
61850 is not used for station bus, the default version can be applied. By default, the IEC
61850 version of PCM600 is Edition 1. The protection relay's IEC 61850 version is by
default Edition 2.
The extension of the exported project file is .pcmp. The files are only used for exporting
and importing projects between PCM600s.
Both a physical IED and an IED object in PCM600 have a technical key. The technical key
in the protection relay and PCM600 must be the same, otherwise it is not possible to
download a configuration.
Each IED in a PCM600 project must have a unique technical key. Therefore, it is not
possible to set the same technical key for several IEDs in the same PCM600 project.
The protection relay is delivered with a factory default technical key. The
validation of the technical keys between PCM600 and the protection relay
does not occur if the protection relay contains the factory default technical
key.
The technical key must be the same for the communication between the protection relay
and PCM600. The technical key can be read from the protection relay and updated to
PCM600, or the PCM600 technical key can be written to the protection relay.
Alternatively, a user-defined technical key can be defined.
When writing a configuration to the protection relay, PCM600 checks for a mismatch
between the IED object and the physical IED technical key.
GUID-EF8A07F6-C6D1-4AA8-BDAD-A5F29F33389A V1 EN
Ensure that the IED object in PCM600 has the same IP address as the
physical IED that is intended to be connected through the technical key
concept.
Change the technical key for an IED object in the Object Properties
dialog box in PCM600.
• Technical key is used in engineering drawings and for signal identifications. This is
contained in the attribute name as an identification of each object. If the value is used
as a reference to an object, it is contained in an attribute name starting with a string
denoting the reference target object type and ending with the string Name. The
technical key is used within SCL for referencing to other objects. The name is a
relative identification within a hierarchy of objects. The maximum characters
allowed for a technical key is 28 for IEC 61850 Edition 1 and 60 for Edition 2 projects.
• User-oriented textual designation is contained in the desc attribute. Attributes are not
allowed to contain carriage return, line feed, tab, greater than, less than, double quotes
or ampersand characters. The semantics of desc must also be relative within an object
hierarchy. The maximum length is 100.
PCM600 takes care of these two possibilities. The two possible signal designations are
available per object in the Object Properties for all the hierarchical levels beginning with
the station as the highest level.
The technical key is automatically generated based on the rules and type specifications of
IEC 61346 and the extended definitions assigned for substations by a technical committee.
The technical key is shown in the Object Properties dialog box under SCL Technical Key
or Technical Key.
• The station is predefined by “AA1" where 1 is the index. To get the real station name
that is used, it is possible to rename the SCL Technical Key for the station as the name
used by the project. To minimize the word length, a short form should be used,
because this name is used also in the transmitted messages to identify the events, for
example.
• The voltage level. In the example it is 20 kV and J1 is selected from the list below SCL
Technical Key in the Object Properties dialog box.
• The bay and the IED are appended with the coding defined in the IEC 61346 standard
and the substation definition lists. In the example, the Bay SCL Technical Key part is
Q01 and IED is A1.
The user-oriented textual designation is visible in the Plant structure view for each object.
It is the name given by default or changed by using the Rename function.
GUID-81D555F9-0F22-4112-BF6D-48F2A3376612-ANSI V1 EN
The created technical key for the full path name of the IED would be: AA1J1Q01A1.
1. In the Plant Structure view, right-click the IED and select Set Technical Key in
IED.
GUID-EE8F635B-1895-4117-A756-F80FA9027037-ANSI V1 EN
Figure 11: PCM600: Setting the technical key on the IED level
GUID-96ECAC44-6A11-4C1F-B50C-3E8A80051950 V1 EN
2. Click OK.
The technical key is read from the IED and the Set Technical Key dialog box opens.
GUID-177E6088-50E3-4A18-83E6-9777AEACB3C1 V1 EN
3. In Set Technical Key dialog box, select the technical key to be used. There are three
alternatives.
• Use the existing technical key in the IED
• Use the existing technical key defined for the IED object in PCM600
• Set a user-defined technical key, which changes the technical key for both the
physical IED and IED object in PCM600
4. Click OK to confirm the selection.
The communication between the protection relay and PCM600 is independent of the used
communication protocol within the substation or to the NCC.
All communication is done over Ethernet using either IEC 61850 or FTP/FTPS protocol.
Each protection relay has an Ethernet interface connector on the front and optionally on
the rear side as well. The Ethernet connector can be used for communication with
PCM600.
When an Ethernet-based station protocol is used, the same Ethernet port and IP address
can be used for PCM600 communication.
Two basic variants have to be considered for the connection between PCM600 and the
protection relay.
• Direct point-to-point link between PCM600 and the protection relay's front port
• Indirect link via station LAN or from remote via network
For successful protection relay engineering and usage, check the workstation firewall
TCP and UDP port configurations, especially for IEC 61850 and FTP. Other protocols are
not used for engineering and/or they are optional.
Table 2: Ports that must be open in the firewall for different protocols
Protocol TCP port
File Transfer Protocol (FTP and FTPS) 20, 21
IEC 61850 102
Web Server HTTP 80
Web server HTTPS 443
Simple Network Time Protocol (SNTP) 123
Modbus TCP 502
DNP TCP 20000
1. Set the IP address for the protection relay's rear port and the corresponding subnet
mask via the LHMI path Configuration/Communication/Ethernet/Rear port.
Table 3: Default IP address for the rear port and the corresponding subnet mask
IP address Subnet mask
192.168.2.10 255.255.255.0
Communication fails if the IP addresses of the front and the rear port
belong to the same subnet.
The firmware update tool is used for patching the IED firmware and for adding or
replacing additional languages to the IED. Update packages are provided by Customer
Support. The update tool can be used either locally or remotely.
It is recommended to take a backup of the IED configuration before starting the update.
This can be done by using the Read from IED function from the IED context menu in
PCM600. The user needs to be authorized before using the tool. User credentials are asked
if the default administrator password has been changed. Administrator or engineer
credentials are needed for authorization.
Remote update
• Communication is recommended to be secured either by setting up a VPN connection
or enabling secure communication in the IED via LHMI (Configuration/
Authorization/Remote Update) while updating remotely.
• Remote update can be enabled in the IED either via the LHMI (Configuration/
Authorization/Security/Remote Update) or by an administrator in the Parameter
Setting tool in PCM600 (IED Configuration/Configuration/Authorization/
Remote Update to be able to update remotely. If the IED is in local control mode,
remote update proceeds only after a confirmation is received from the user.
• Remote update has to be disabled manually after the update, if wanted.
• Remote update only works when the IED is connected from the rear port with a
custom IP address.
GUID-DFB23CF8-9966-4A5E-B322-C9C998B4BA7C V1 EN
3. Select the network interface controller, for example, the PC's integrated Ethernet
communication card or an external Ethernet adapter, connected to the IED and click
OK.
GUID-AF43F861-54EB-4F5E-B745-38994F6A423A V1 EN
4. When updating remotely, wait for 30 seconds for the local user confirmation before
proceeding with the update.
• The local user can cancel the update via the LHMI by pressing during the
30 second window.
• IED use is allowed after the update is completed successfully.
GUID-82BB575B-99D9-4C84-B35E-FB85D8465323 V1 EN
Figure 16: Waiting for local user confirmation with remote update
GUID-31FD0CB0-CFBC-48AB-BF96-D3F9436DBDEE V1 EN
1. Start PCM600.
2. To see the projects that are currently available in the PCM databases, select File/
Open/Manage Project on the menu bar.
The Open/Manage Project window is displayed.
3. Click Projects on my computer.
4. Click New Project.
5. If there are currently projects or object tools open, a confirmation dialog box opens.
• Click Yes to close the open projects. A Create New Project dialog box opens.
GUID-F7D1FC0A-CFD5-4A4C-900C-E1F90DEDF3BF V2 EN
IEC09000375 V2 EN
• Right-click the Plant Structure view, point to New and select Create from
Template.
• Right-click the Plant Structure view, point to New and select General and
select the element either IED Group or Substation.
2. On the View menu, select Object Types.
3. Select the needed elements and drag them into the plant structure.
GUID-E856B2E2-8200-46FC-AA98-878F70C20A96-ANSI V1 EN
Figure 20: The start of a project with IEDs placed but not renamed
4. Rename each level in the structure by the names/identifications used in the grid.
• Right-click the level and select Rename.
• Rename the levels in the Object Properties view.
The context menu or the Object Types view shows the available IEDs that can be inserted,
on the bay level, into the plant structure according to the installed connectivity package.
PCM600 uses two kinds of IED files: .pcmt and .pcmi. Both files include
the complete IED configuration but their usage differs. The .pcmt files are
always accessed through the PCM600 template manager while the .pcmi
files are meant for sharing the IED instances between different PCM600
users enabling quick import/export directly from the plant structure
context menu.
From the plant structure, it is possible to see whether the inserted IED is in the offline or
online mode. A red cross in front of the IED symbol indicates offline mode, a green tick
indicates online mode.
GUID-F9E16EA2-CDE7-4488-8CC5-5B66849C89FC V1 EN
Figure 21: Plant structure showing Bay1 in the online mode and Bay2 in the offline
mode
When the protection relay is already connected to PCM600, PCM600 can read the order
number directly from the relay. It is possible to read the full configuration from the relay
by using the Read from IED function.
1. In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Motor Protection IEDs and select the protection relay type
to be inserted.
Alternatively, drag an IED from the Object Types view to the bay
level.
GUID-AF88B4EA-85AF-43E8-AED7-D6EF9DD25B9C-ANSI V1 EN
2. On the Configuration mode selection page, select Online Configuration and click
Next.
GUID-C326AA0A-27ED-46DF-8B61-7484B8CB41F1-ANSI V1 EN
GUID-F8B3A98A-BD75-4E2D-B279-822A2504F1EE-ANSI V1 EN
4. On the IEC61850 communication protocol page, select the port from the Port list.
• If the rear port is selected, type the correct IP address (of the physical
protection relay to be configured) to the IP address box.
GUID-3FD49387-3726-4483-AD54-7FBC6D441805-ANSI V1 EN
GUID-FAC9B045-7D1C-4996-B038-F2DEEEFAD10A V1 EN
GUID-DAE10A3A-6821-4B06-B33A-670E22FC9834 V5 EN
GUID-DAE10A3A-6821-4B06-B33A-670E22FC9834-ANSI V1 EN
7. On the Configuration selection page, select the configuration type and click Next.
• Select Empty Configuration to create an empty configuration.
• Select Example Configuration to import any existing example
configuration.
Click Browse to select the .pcmi/.pcmt file that has the example configuration.
• Select Standard Configuration to generate a default configuration.
GUID-9DF2D226-E34F-468B-BA0C-5A829948AD86 V1 EN
8. On the Version selection page, select the IEC 61850 version and click Next.
9. The Setup complete page shows the summary of the protection relay's IED type,
version, IP address and the selected order number. Click Finish to confirm the
configuration and conduct the insertion.
GUID-02789F3F-DD47-4CDB-86DE-F9258E01BF50-ANSI V1 EN
10. From the Plant structure view, check that PCM600 has turned online the IED that
was inserted to the bay level.
Working in the offline mode has an advantage compared to online mode in that the
preparation for the configuration can be started even though the protection relay is not
available.
1. In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Feeder IEDs and select the protection relay type to be
inserted.
Alternatively, drag an IED from the Object Types view to the bay
level.
2. On the Configuration mode selection page, select Offline Configuration and click
Next.
Setting up an IED in the offline mode is similar as in the online mode; however, with
the offline mode it is not necessary to type the correct IP address in the
Communication port and IP address dialog box.
GUID-2A8CE4A6-1AA7-4129-A1B5-A739D4BCA4B7 V3 EN
3. On the Order Code selection page, select the correct order codes and click Next.
Ensure that the order code is correct. PCM600 verifies later that the
order code matches with the relay. If the order code digits related to
the configuration, I/O or version do not match with the relay,
PCM600 does not allow writing the configuration to the device. If
other digits in the order code do not match, PCM600 informs about
the mismatch with a dialog.
4. On the Configuration Selection Page, select the configuration type and click
Next.
It is also possible to insert an IED from the template library to create a new IED in the plant
structure. After a template IED has been imported, the IP address, the Caption in IED's
Object Properties and the Technical Key that corresponds to the physical IED have to be
changed.
A template IED can be inserted only when the bay is selected in the plant
structure.
1. In the Plant structure view, select the bay, right-click, point to New and select
Create from template.
The Create New Object from Template dialog box opens.
GUID-176DF09D-AF72-483A-B1FD-519D69345121 V2 EN
GUID-62DCC284-90D6-498A-A79A-25E884C61CC8-ANSI V1 EN
4. Check and verify the template information and click Close to close the dialog box.
The Create New Object from Template dialog box is displayed.
5. Delete, import or create a template by clicking the corresponding button.
• To delete the selected template, click Delete Template.
• To import a template from the selection window, click Import Template.
• To insert the selected IED to the bay, click Create.
It is possible to insert more than one IED from the Create New
Object from Template dialog box. The dialog box remains open
until Close is clicked .
1. In the Plant Structure view, right-click the bay and select Import.
A .pcmi file can be imported only when the bay is selected in the
plant structure.
GUID-187F89B8-CF8B-457B-A6C2-09E3FF34E929-ANSI V1 EN
2. In the Import dialog box, select the .pcmi file to be imported and click Open.
After importing, the IED object is created in the plant structure.
After the .pcmi file has been imported, the IP address, the name and the technical key that
correspond to the physical IED have to be changed.
The IP address and subnet mask of the IED object in PCM600 must match the front and
rear port of the protection relay (physical IED) to which the PC is connected. The IP
address of the protection relay can only be set via the LHMI or Parameter Setting tool in
PCM600. The PC and protection relay need to be on the same subnet.
There are two alternatives to set the IP address of an IED object in PCM600.
• On the first page of the wizard when including a new IED into a project.
• In the IP address box of the IED's Object Properties dialog box.
GUID-0C8D23CA-5BB5-4D36-9B11-245B5465D9E1-ANSI V1 EN
Figure 36: Alternative 1: Setting the IP address on the first wizard page
GUID-B4B71E12-25CB-4B8B-8F9A-90131BD68E4D V3 EN
Figure 37: Alternative 2: Setting the IP address in IED's Object Properties dialog box
Choosing between the two ways depends on when the IP address is set. Typing the IP
address via the IED's Object Properties dialog box is possible at any time while entering
it via the configuration wizard can only be done when adding the IED object.
1. In the Plant Structure view, select the IED to which the IP address is to be entered.
2. On the View menu, select Object Properties.
Object Properties dialog box is opened.
3. Type in the IP address to the IP Address row.
The 615 series connectivity package supports SAB600. A 615 series protection relay is
imported as a 615 series device. It is also possible to import a full PCM600 project
including several 615 series devices to SAB600. In this case, PCM600 project information
is imported to SAB600 using a SCD file.
In PCM600, the front or rear communication port can be selected from the project
structure.
When using the front port, DHCP server functionality must be activated in the computer
network adapter settings to get the IP address from the relay. Alternatively, the computer
network adapter IP address can be set manually to the same subnet range as the front port.
GUID-6B209BB8-F07E-4414-B404-EA33CEB71DB2 V1 EN
• Check that the settings are correct to ensure successful configuration access to the
relay.
• Computer port settings must match relay settings (IP address, subnet mask,
DHCP).
• Any firewall in the computer or in the network must pass required
communication services.
• When using the front port and switching the connection from the computer to
another relay, it takes some time before the computer refreshes the relay's MAC
address for front port IP address automatically. The MAC address can also be
reset manually by clearing the computer ARP table.
GUID-01F6FEB6-B57B-4A56-939B-46750205D914 V2 EN
IEC09000687 V2 EN
Figure 40: Exporting SCD file from PCM600 and importing it to SAB600
GUID-70E8B187-FADA-4657-9BC7-223FDA7374ED V2 EN
Figure 41: Importing the SCD configuration into the SAB600 project
4. In the SCL Import view, click Select File to select the SCD file exported from
PCM600.
GUID-6F47B4AD-B956-4F77-A6A2-DE6F4A71D607 V2 EN
5. Check the default settings in the SCL Import view and change the settings if they
are not suitable.
The default settings in the SCL Import dialog should be correct in most cases.
6. Click Import to import the SCD file.
7. Check the IP address on the IEC 61850 subnetwork and change it if needed.
When the SCD file is directly exported from PCM600, it uses the IP address of the
PCM600 computer, not the COM600S.
The communication towards the protection relays is now ready. For information on how
to finalize the single-line diagram and enable parameter setting through COM600S HMI,
see COM600S documentation.
WHMI is disabled by default, and has to be activated in the protection relay configuration.
As secure communication is enabled by default, the WHMI must be accessed from a Web
browser using the HTTPS protocol.
Disable the Web browser proxy settings or make an exception to the proxy
rules to allow the protection relay's WHMI connection, for example, by
including the relay's IP address in Internet Options/Connections/LAN
Settings/Advanced/Exceptions.
IED user authorization is disabled by default. IED user passwords can be changed in
LHMI, WHMI and using the IED Users tool in PCM600.
Local passwords can be changed only via the LHMI. Remote passwords
can be changed via the LHMI or WHMI or with PCM600.
GUID-FC9D4AB3-C472-4BDB-B64B-DEE4FEACC4FA V1 EN
Figure 43: Changing the password using the IED User Management tool
3. Set the object property values in PCM600 to make the communication between the
IED and PCM600 work, if the remote authentication has been enabled.
Table 4: Object properties to change
Object Properties field Value
Is Authentication Disabled False
Is Password used True
Password Write the correct password
GUID-D0853D4E-D594-454A-9299-997ADF3E0896 V1 EN
When communicating with the protection relay with PCM600 tools and with the
relay authentication enabled, the relay username and password must be given when
prompted. When setting the technical key, the username and password must be given
twice.
GUID-310E1587-D064-4823-9329-12163E0C9306 V1 EN
Audit trails (login, logoff events) can be monitored by using the Event
Viewer tool. By default, the audit trails are not shown in the Event Viewer
tool. To view them, change the default ADMINISTRATOR password by
using the IED Users tool, and log in as ADMINISTRATOR user when
opening the Event Viewer tool.
The IEC 61850 version of a PCM600 project can be identified from the Object Properties
pane of the project.
GUID-0830B8BF-8B2D-4D4F-8DC4-AF19F6EB1F77 V1 EN
To change the IEC 61850 version Edition 1 of an IED to Edition 2, the configuration has
to be written to the IED from a PCM600 project that has the IEC 61850 version Edition
2. A dialog box notifies on the difference of the versions.
GUID-76919861-F55B-489A-B031-A78229ADDDB2 V1 EN
For more information on the function blocks, see the technical manual.
Most function blocks are mapped as logical nodes according to the IEC 61850 standard.
See the IEC 61850 parameter list for more information.
Other function blocks are not mapped as logical nodes; for example, logical gates.
The basic features of Application Configuration tool include the ability to organize a
configuration into several MainApplications as well as providing different application
programming features.
1 2 3 4 5 6 7
8 9 10 11 12 13 14
GUID-74FFF952-C539-422D-BC40-EF4AA5C279FB V2 EN
1 Connection(s)
2 User-defined function block name
3 Function block, selected (red)
4 Function block name
5 Function block, locked
6 Hardware, binary output channel
7 Hardware, programmable LED
8 Hardware, binary input channel
9 Hardware, analog input channel
10 User-defined signal name
11 User-defined input variable
12 Execution order
13 Cycle time
14 Instance number
Function blocks can contain more signals than needed in that application part. Unused
signals can be hidden to get a clear picture.
Signals are located up and down on both sides of the middle position. When there is space
left, some signals may be moved up or down for better visibility and connection routing.
Boolean input and output signals may need to be inverted to fulfil the logic. The
Application Configuration tool supports the adding of inversion logic to a binary signal.
All input signals have a default value that is used when the signals are not connected in the
configuration.
The input signal on glue logic function blocks can only be inverted if a
glue logic function block with lower execution order in the same cycle
time is available. Similar, the output signal can only be inverted if a glue
logic function block with higher execution order in the same cycle time is
available. Up to two input signals and two output signals can be inverted
for glue logic blocks in the same cycle time.
• Execution order
• Cycle time
• Instance number
Each time a new function block is selected, these parameters must be selected from the
lists in the Application Configuration tool. The three parameters are selectable and not
selectable depending on the function block type. The cycle time may be predefined to one
value. The instance number is a counter for the total possible number of function blocks
of that type used within the application configuration.
The Execution Order and Instance Number are a combination that is predefined within a
product. It is possible to select a pair out of the list.
GUID-4129D712-CD43-4729-8FE4-27FFE758D151-ANSI V1 EN
The Cycle Time is automatically set to 2.5 ms (50 Hz) or to 2.083 ms (60 Hz) and it cannot
be modified. Depending on the function block type and the 615 series product, only one
or both possibilities may be available.
Example shows a simple situation where the execution order causes one cycle time delay
if the NOT port is executed in the order determined by the automatic calculation.
GUID-F8162182-FF21-467A-AEB9-23284CB3FABD V1 EN
Figure 50: Feedback loop situation with automatically calculated execution orders
By setting a smaller execution number than in the AND port to where the NOT port is
connected, it is possible to fix the execution order of all functions in a loop so that they are
handled in the same task.
GUID-0C12B88A-0ABE-49DE-9A44-05D213D04922 V1 EN
Figure 51: Feedback loop situation with manually fixed execution order for NOT port
Execution number can be changed by right-clicking the function and selecting Change
CycleTime ExecOrder.
After manually defining the execution number, the function is no longer part of the
automatic execution order calculation. The function can be included back to the automatic
calculation by right-clicking the function and selecting Include FB in calculation.
Connection validation
A connection is only useful or even possible between two signals of the same base
attribute type.
GUID-720C9C93-AB56-4AEB-AF72-7E136E62A87F-ANSI V1 EN
Figure 52: Application Configuration tool: an error message of a signal mismatch for
a connection
GUID-40339889-3049-4C50-BA8F-8C3EB9A54C4D V1 EN
Hardware input channel can be used as often as needed. A hardware binary output channel
is taken from the list of available channels when a new channel is requested. This prevents
using the same hardware binary output channel twice.
Online monitoring can be started by clicking the Work online button in the toolbar. If the
application configurations in the IED and PCM600 are the same, the online monitoring
starts. The online monitoring ends and the tool returns to the configuration mode if the
Work Offline button is clicked.
In some cases when the function block input is directly mapped to the
function block output, the input is internally forced to the correct value
depending of the function block's settings. This kind of function block
design is present in control blocks, setting group handling and tap
changer.
5.1.9 Validation
Validation checks the application configuration for errors based on the rules that govern
the creation of the application at three different times.
• During the logic creation, while making a connection or placing a function block
• On demand by starting the validation
• When writing the application configuration to the protection relay
Warnings do not prevent writing to the protection relay. However, errors must be
corrected before writing the application configuration to the protection relay. The
application configuration can be saved and the Application Configuration tool can be
closed with open errors, but the application configuration cannot be written to the
protection relay.
These problems are listed in the Output view under the Application Configuration tab.
Double-clicking the error or warning row navigates to the MainApplication/Page/Area,
where the problem was identified.
GUID-F33821B8-2643-4092-85DB-9C732A95C77E V1 EN
Calculation results are divided into three different sections which are OK, Warning and
Error. If the calculation result is 105% or more, the configuration is too large for the IED
to handle and PCM600 prevents writing the configuration to the IED. If the configuration
load is more than 100%, PCM600 gives a warning not to add functionality to the
configuration. The configuration is written to the IED if the result is inside or below the
warning range.
Some inaccuracy exists between the calculated load estimate and the actual load of an IED
when considering all parameters. This is why PCM600 does not prevent the writing
immediately when the estimated load exceeds 100%. The IED supervises its performance
continuously and indicates with self-supervision warning code 2 if an actual performance
risk is detected. It is recommended to verify the configuration load also with an actual IED
and actual settings when exceeding the calculation result of 90% or when using GOOSE
on a larger scale.
GUID-21A6BC31-DE9C-42DB-B19B-368B2711A271 V2 EN
Configuration parameters and settings parameters can be changed with LHMI, WHMI or
with the Parameter Setting tool in PCM600.
Some parameters are only visible in the Parameter Setting tool and some
only in LHMI.
All parameters listed and displayed in the parameter list can be sorted into two groups.
• Configuration parameters
• Setting parameters
The parameter import/export functionality is available via the File menu when the
Parameter Setting tool is open.
GUID-4A63FE0D-7846-4387-A5D3-BD7B4F519A76 V2 EN
The Signal Matrix tool is used to make cross-references between the physical I/O signals
and function blocks and for the GOOSE signal input engineering.
Binary
BIO
Inputs
FBs
Analog
RTD FBs
Inputs
GOOSERSV
GOOSE IEC 61850
(input side)
Functions
GOOSERSV
(output side)
FBs
FBs
GUID-50BC48B0-574F-4DD8-9678-67A0954D1C13 V1 EN
A binary input channel can be connected to one or more function block inputs. If a binary
input channel is connected to several different function blocks in the Application
Configuration tool, the connection appears as glue logic in Signal Matrix.
A binary output channel can only be activated from one function block output. If it is
activated from more than one function block output, the glue logic has to be used.
Glue logic means inserting a logical gate (OR and AND blocks) between the binary input
and the function blocks or between the function blocks and the binary output channel. This
can be engineered with the Signal Matrix tool.
Connections made with the Signal Matrix tool are automatically also
shown in the Application Configuration tool.
GUID-D0C99F05-64B1-487F-A713-3C9A495B27AC-ANSI V1 EN
Figure 58: Signal Matrix: a connection between binary input channels to binary input
signals
The Signal Matrix tool has a separate sheet for each possible combination.
• Binary inputs
• Binary outputs
• Analog inputs
• Functions
• GOOSE
Load Profile tool is used for reading load profile records of COMTRADE format from a
protection relay, clearing old records and viewing records via an external COMTRADE
viewer. The default viewer included with PCM600 is Wavewin, but a third party viewer
can be used.
GUID-F8120497-31C8-4F8B-BBE8-D1338CF4E4E6 V1 EN
• To close the Load Profile tool, click the Close button in the tool.
The Load Profile tool runs in the same process as PCM600 but in a separate window.
Multiple instances of the tool can be run at the same time. Any open tool instances are
closed without confirmation when PCM600 is closed.
GUID-4B275369-045F-4407-89A2-44071839699D V1 EN
By default, the Load Profile tool uses the \PCMDataBases\LPR directory as a saving
target directory.
GUID-4B275369-045F-4407-89A2-44071839699D V1 EN
Action Description
Open Select any record and click Open to view the record in Wavewin, provided that this
external software is installed. Additionally, any record row can be double-clicked to view
that record.
Sort To sort the record rows by any column click a column header.
Close Clicking the Close button closes this instance of the tool. Any open instance is finally
closed when the whole PCM600 is closed.
File All the actions are also available on the tool through File drop-down menu.
In the record grid, the name, creation time, modification time and size of each record are
shown. The times and dates shown in the grid are the times when the files have been read
rather than the original date stamps in the device.
GUID-82E7859C-3C2B-43F1-83C3-7AA8087C569C V1 EN
The Fault Record tool is used for reading the fault records from the protection relay and
it is included in the connectivity packages. The tool makes analyzing the fault records
easier by showing them separately in their own user control components. It also includes
save, copy and clear functions where all the fault records are saved or copied in text format
for later viewing or cleared from the protection relay or the tool.
GUID-06441245-E6DA-4C9F-9363-26CE8D521CB2 V1 EN
• To close the Fault Record tool, click the Close button in the tool.
The Fault Record tool runs in the same process as PCM600 but in a separate window.
Multiple instances of the tool can be run at the same time. Any open tool instances are
closed without confirmation when PCM600 is closed.
The Fault Record tool is a connectivity package tool. The main functionality is divided
into three parts: reading the fault record parameters from the protection relay, displaying
their names, values and units on the user interface and saving them to a text file. It is also
possible to clear all the fault records from both the tool and the protection relay and copy
the fault records either individually or all at once to a word processor.
GUID-6E8576DB-7917-45FE-A54A-877A9892E83C V1 EN
IED Compare is used to compare the IED configuration of two same type of IEDs. It
generates a text report which lists the differences in the IED configuration. IED Compare
provides an option to compare an IED configuration stored in PCM600, IED or .pcmi file.
IED Compare can compare certain types of IED configurations and parameters.
• Application configuration
• Display configuration
• GOOSE receive configuration
• Parameters
GUID-DF0FE82F-7465-4D01-BB32-A591EF3115B9 V1 EN
Each configuration group can be expanded or collapsed by clicking the plus (+) or minus
(-) button next to it in the result grid.
GUID-54429A22-126B-4256-94DF-37F921A833AD V1 EN
All of the relay’s logical nodes are set with Test mode. Test mode is selected through one
common parameter via the HMI path Tests/IED test. By default, Test mode can only be
set locally through LHMI. Test mode is also available via IEC 61850 communication
(LD0.LLN0.Mod).
Table 8: Test mode
Test mode Description Protection BEH_BLK
Normal mode Normal operation FALSE
IED blocked Protection working as in “Normal mode” but ACT TRUE
configuration can be used to block physical outputs
to process. Control function commands blocked.
IED test Protection working as in “Normal mode” but FALSE
protection functions are working in parallel with test
parameters.
IED test and blocked Protection working as in “Normal mode” but TRUE
protection functions are working in parallel with test
parameters. ACT configuration can be used to block
physical outputs to process. Control function
commands blocked.
The mode of all logical nodes located under CTRL logical device are set with Control
mode. Control mode is selected via the HMI or PCM600 path Configuration/Control/
General. By default, Control mode can only be set locally through LHMI.Control mode
inherits its value from Test mode but Control mode ”On”, “Blocked” and “Off” can also
be independently set. Control mode is also available via IEC 61850 communication
(CTRL.LLN0.Mod).
Table 9: Control mode
Control mode Description Control BEH_BLK
On Normal operation FALSE
Blocked Control function commands blocked TRUE
Off Control functions disabled FALSE
According to IEC 61850, the physical outputs to process should be blocked when device
is set to blocked or test blocked mode. The usage depends heavily on the actual ACT
configuration. In the protection blocking example the main trip from TRPPTRC1 is
blocked, and in the control blocking example the CBXCBR1 is blocked. Both comply to
the IEC 61850. In real applications some of PTRC’s might also be used for signalling
purposes (GOOSE) and blocking and interlocking via IO.
Protection
BI_SG_2 SG_LOGIC_SEL
BI_SG_3 SG_1_ACT
BI_SG_4 SG_2_ACT
BI_SG_5 SG_3_ACT
BI_SG_6 SG_4_ACT
SG_5_ACT
SG_6_ACT
BEH_TEST
BEH_BLK
TRPPTRC1
BLOCK TRIP TRPPTRC1_TRIP
OPERATE CL_LKOUT
RST_LKOUT
GUID-CAF67CB2-774E-4122-A235-D07F8768B202 V1 EN
Figure 67: Master trip TRPPTRC blocked using Protection function block BEH_BLK
output
NOT AND
CBXCBR1 IN OUT B1 O CBXCBR1_EXE_OP
B2
X120_BI3_CB_OPENED POSOPEN SELECTED
X120_BI2_CB_CLOSED POSCLOSE EXE_OP
TRUE ENA_OPEN EXE_CL
CBXCBR1_ENA_CLOSE ENA_CLOSE OP_REQ
FALSE BLK_OPEN CL_REQ CBXCBR1_OPENPOS
BLK_CLOSE OPENPOS
CBXCBR1_AU_OPEN AU_OPEN CLOSEPOS AND
CBXCBR1_AU_CLOSE AU_CLOSE OKPOS NOT
TRIP OPEN_ENAD B1 O CBXCBR1_EXE_CL
SYNC_OK CLOSE_ENAD IN OUT B2
SYNC_ITL_BYP
GUID-190D6D90-44B9-42B4-8505-7497F1AAA2E2 V1 EN
Figure 68: Circuit breaker control CBXCBR1 blocked using Protection function
block BEH_BLK output
A single-line diagram of the protection relay can be designed by using the Graphical
Display Editor tool of PCM600. The single-line diagram is modelled according to the IEC
61850 standard in the Graphical Display Editor.
GUID-8843160D-28CC-46D5-8045-445FAAB335B9-ANSI V1 EN
The Graphical Display Editor has a stationary symbol library window on the left side of
the view. The window is empty when no page exists for the protection relay. A default
single-line diagram presentation is displayed if standard configurations are used.
Additional single-line diagram HMI display pages can be added or removed with the Add
Display Page or Remove Display Page commands in the Graphical Display Editor menu.
• The protection relay supports one bay with up to ten single-line diagram HMI pages.
• Measurements and the single-line diagram can be displayed on the page in any
possible order and placement.
• All symbol objects, for example apparatus and measurement, on the HMI page must
be linked to the correct function block in the application configuration to present the
correct process values.
The Symbol Library view contains panes that include drawing symbols or elements for
creating a single-line diagram, measurements and texts onto a page. Panes can be opened
by clicking the name bar of the selected element.
The library shows the symbols either in the ANSI standard or IEC standard. The standard
is selected from the list located on top of the window.
When changing to another library standard, Graphical Display Editor changes the
symbols according to the selected new standard and redraws the single-line diagram in the
window.
To change the symbol format used in the protection relay, select Main
menu/Configuration/HMI/SLD symbol format and choose IEC or
ANSI.
To become familiar with the available symbols, select the different panes
and their symbols.
In-feeder
Out-feeder
Current transformer
Voltage transformer
Ground symbol
Motor
Generator
Fuse
Grounding transformer
Petersen coil
The raster on the page changes from symbol presentation to text presentation when a text
object is selected and vice versa.
The text can be presented in UniCode characters (6 x 12 pixels). The total size of the
presented white area (page) represents the visible part of the LHMI display without the
header line.
The description text for an apparatus object can be placed in all four directions around the
symbol. The description is part of the apparatus object. It is possible to place the symbols
without the assistance of Snap to Grid and manually change the position coordinates.
The display switches when text is selected in a display of 22 x 9 (columns x rows). One
display box holds one character. A text element must be placed in the position of the
display.
The name and the unit of a measurement or text symbol can be changed by
double-clicking the symbol or via the Object Properties view.
Selecting and toggling Show Texts using the IED fonts can be used to preview the single-
line diagram to see how it is presented in the real HMI display.
GUID-4D3D2FE7-B26C-4177-BE09-CE3CEBAF71B8 V1 EN
2. Edit the text in the Name field in the Object Properties view, or alternatively
double-click the text to edit it.
GUID-04FCDF78-2E81-417A-8F2E-035AAD3A976D V1 EN
2. Right-click the select button symbol, point to Select Input Signal and select the
input signal from the list.
GUID-E252A3F2-D93F-42E0-8129-8D19EA161AFA V1 EN
GUID-4606198B-521D-4804-BBC8-8E041E144026 V1 EN
2. In the Objects Properties view, edit the name, unit and the number of decimals.
Unit text specifies the default text used for the measurement's unit. If the Unit text
is empty in the Graphical Display Editor, no unit is shown. If the Unit text is not
empty, the unit in the protection relay is updated dynamically based on the signal it
is connected to. The Scale factor parameter is not used.
1. Add at least two Busbar Junction elements from the Symbol Library to the display
page.
2. Select the Busbar Junction and use the rotate command from the toolbar to ensure
that the busbar ends to the margin.
3. Add links between the busbar junctions.
2
1
GUID-A58439A5-575C-4EED-A5A9-77FDECAA9D21 V2 EN
Figure 74: Graphical Display Editor: drawing a busbar and placing busbar
junctions
1 Busbar junction
2 Rotate command
4. Add a link between one busbar junction point and the corresponding symbol or
junction point.
1. Prepare the body of the single-line diagram by locating symbols to the wanted
positions on the display.
2. Drag the apparatus or transformer symbols into a raster box.
3. Drag the connection symbols into a raster box.
4. Place the junction points.
Do not connect two symbols directly to each other. Instead, add a junction between
them.
5. Use the X and Y coordinates in the Object Properties window to adjust the
placement of symbols in the single-line diagram.
GUID-BB90E914-7B02-4D1E-A385-FB6D6305869C-ANSI V1 EN
Figure 75: Graphical Display Editor: adding single-line diagram symbols into a
display page
After the apparatus symbols are placed, lines can be drawn to create links.
GUID-795A6797-D4D9-4705-A496-C3FBD771C211-ANSI V1 EN
Once the symbols are placed on the HMI page, they must be linked to the corresponding
function block in the application configuration, which protects or controls the object that
the symbol on the HMI page represents.
• Application Configuration tool for programming the application function block for
the apparatus and measurements
• Parameter Setting tool for adapting the settings and configuration parameters of the
application function block
• Graphical Display Editor for establishing the link to update the selected data attribute
in the HMI of the application function block
The needed information is delivered with switch controller (of type CSWI) for an
apparatus and all the configured function blocks with measurements (of type MMXU) for
the measurements
GUID-28A8463E-7A11-47FA-938F-17436CBFB0BD-ANSI V1 EN
The ordering number in the selection window of the process objects corresponds to
the number given in the Parameter Setting tool tree and to the application function
block in the Application Configuration tool.
Only the apparatus and measurements that are configured in the application
configuration program are displayed.
GUID-1DB1A930-A312-4B55-8F68-3D8327A873FB V1 EN
Figure 78: Graphical Display Editor: object properties view for text insertion
GUID-F21E4F43-442D-4868-BAA3-EBA903E9C62E-ANSI V1 EN
The single-line diagram templates enable the reuse of the single-line diagram created in
the Graphical Display Editor tool. The single-line diagram can be exported as a template
and the same template can be imported to another IED. The file extension of the single-line
diagram template file is .psld.
1. On the menu bar, point to Graphical Display Editor and select Import Display
Pages from Template or on the File menu, point to Display Editor Template and
click Import.
The Import GDE Template window appears with two sections, List of Templates
and Display Pages Preview.
2. Click Browse to select the template files.
The templates available in the folder appear in the List of Templates section.
3. Select a template file to preview the display pages available in the template file.
4. Once the display pages are selected, click Import to import the display page.
HMI Event Filtering is a tool that helps in configuring visibility of events shown on the
LHMI and WHMI of the IED. This tool does not modify the actual events on the protocol
level, it only modifies the event visibility on the LHMI and WHMI.
The event tree view is used to modify the visibility of the events shown on the LHMI and
WHMI. Events in the tree view are structured in the same way as functions in the PCM600
plant structure.
GUID-21867F5D-E9C4-45E3-95D4-F16F2BEF16CF V1 EN
• When the check box is cleared, the event is not visible on either LHMI or
WHMI.
• When the check box is selected, the event is visible on both LHMI and WHMI.
The HMI visibility can also be modified for multiple events by selecting the check box of
the parent node in the event tree view.
Some events in the event tree are read-only and cannot be modified. The read-only events
appear dimmed in the user interface.
GUID-F84AA328-8EE2-4793-B2B9-94776233C3EF V1 EN
To engineer the IEC 61850 protocol interface for the protection relay, the following
additional manuals or knowledge of their contents is required.
• Knowledge of the IEC 61850 engineering process as described in the IEC 61850
standard
• The technical manual describes the function blocks defined as logical nodes
• The IEC 61850 engineering guide
• The IEC 61850 conformance documents for the protection relay to be engineered
• The IEC 61850 parameter list
Table 11: Function blocks and IEC 61850 Edition 1 and Edition 2 Logical Nodes
Function IEC 61850 Logical device Logical nodes in Logical nodes in
Ver.5.0 FP1 Ver.4.2 or older
Protection
Protection LLN0 Protection LD0 LLN0 LLN0
LPHD LPHD
LINF IHMI
LDEV GSAL
Three-phase non-directional overcurrent protection, low PHLPTOC LD0 PHLPTOC PHLPTOC
stage
Three-phase non-directional overcurrent protection, high PHHPTOC LD0 PHHPTOC PHHPTOC
stage
Three-phase non-directional overcurrent protection, PHIPTOC LD0 PHIPTOC PHIPTOC
instantaneous stage
Three-phase directional overcurrent protection, low stage DPHLPDOC LD0 DPHLPTOC DPHLPTOC
DPHLRDIR DPHLRDIR
Table continues on next page
FBs SMV
SMV interface
FBs
GOOSE
SMV Receive
Receive
Monitoring
FB SMV
SMVSENDER Send
FBs
FBs GOOSE
GOOSE interf.
GOOSE
GOOSE
Receive Receive
LN Receive
LN
GOOSE
GOOSE
Send GOOSE
Communication handler
Send Send
only
part
Commands
FB
AFL
FBs LN
with part
Event
monitoring
handler
and
commands
FB
AFL
Event
queue
LN
part
GUID-8283BA4D-A196-4637-83F3-89C1D122732B V1 EN
IEC 61850 provides a method for identifying all signals that belong to a function. These
signals are identified through the logical nodes representing the functions. All signal
information for commands and monitoring are available in logical nodes.
The IEC 61850 protocol supports a method to directly exchange data between two or more
devices (IEDs). This method is described in the IEC 61850-7-2 clause 15.
The concept is based on sending a multicast over the Ethernet. Whoever needs the
information, detects the telegram by its source address, reads the telegram and handles it.
The telegrams are multicast sent and not acknowledged by the receiver.
Receive
Receive
Receive
Receive
Receive
Send
Send
Send
Data-set Data-set Data-set
LN LN LN
LN LN
LN
LN LN LN
LN
LN LN LN LN LN
When a GOOSE message is to be sent, it is defined by configuring the data set with the
defined trigger option and GoCB. This engineering process is done in a station
configuration tool, for example, IEC 61850 Configuration tool or IET600. The task
involves configuring lists with the signal, value and quality (data attributes or data objects)
that belong to the GOOSE message data set.
In the opposite direction, the standard only defines the IED as a receiver of a GOOSE
message. How the GOOSE input signals are handled must be defined in the device's
application configuration. The SCL data generated by the IEC 61850 Configuration tool
or IET600 (or any other station configuration tool) contains the GOOSE data sets as input
data. The input data must be connected to a GOOSE receive function blocks in the Signal
Matrix tool.
The concept in the IED is such that the IEC 61850 data for each function instance is
available in the data model, even when the function is not used in the application. This
means that it is not necessary to handle any instance information for the functions
regarding IEC 61850.
The IEC 61850 standard defines how information is communicated in a substation. The
information communication can be divided into different parts.
When exporting an SCL file from PCM600, the tool builds a default substation structure
and creates default data sets and control blocks for vertical communication between the
substation client and IEDs. For more information, see the IEC 61850 standards.
In the following example, it is assumed that PCM600 and IET600 are used as the system
configuration tools. Another option is to use the IEC 61850 Configuration tool inside
PCM600. In that case the SCL file export and import operations (steps 1 and 3) are not
needed.
1. SCL files are exported from PCM600. In this case, a SCD file. It is also possible to
export other SCL file types.
2. Horizontal and vertical communication is configured using the station configuration
tool, for example, IEC 61850 Configuration tool or IET600.
3. SCL files are imported to a PCM600 project. In this case, it is the updated SCD file.
CCT600 (2)
è create project
è import SCD file
SCD file è configure data sets SCD file
è configure Report CBs
è configure GOOSE CBs
è export SCD file
IEC08000413.vsd
GUID-7F3E5CB6-E662-4951-B619-D5F87B206F09 V1 EN
Figure 84: IEC 61850: Signal engineering procedure flow when a complete station
is exported as a SCD file
IEC08000415-ANSI V1 EN
GUID-632A916F-B7FE-4EF4-B29A-6A2A5B9FBC4D V1 EN
5. Change the SCL file version by clicking the Advanced button, if required by the
receiving configuration tool.
GUID-FD84C31F-93F5-4F2A-BC40-646CE604F8D7 V1 EN
IEC08000416.vsd
GUID-41A96291-035E-475D-8B3D-2AF21C0EBE4D V1 EN
4. Click Save.
The SCL Export Options dialog box opens.
5. Select the export options.
GUID-F58BB3D3-745B-4997-8CBD-023244CD840B V1 EN
6. Change the SCL file version by clicking the Advanced button, if required by the
receiving configuration tool.
GUID-DA9E7D95-2EA6-4861-9D40-4A2CDFA33F58 V1 EN
7. Click Export.
Data sets meant for vertical reporting can only contain data on
the data object level, not on the data attribute level.
The data set for GOOSE can contain signals on the data
attribute or data object level. Data object level GOOSE entries
can only be received of the following CDC types: SPS, SPC,
ACD, ACT, DPS, DPC, INC, INS, ENC and ENS.
3.3. Configure additional Report Control Blocks when needed for each data set
used for vertical communication.
3.4. Link the IED clients to the Report Control Blocks.
One data can be included in the GOOSE data set only once.
4.2. Define the client IEDs for each GOOSE control block.
4.3. Link the IEDs to the GOOSE control block that is to receive the GOOSE
control block.
5. Export the updated SCD file. [1]
All data sets, Report Control Blocks and GOOSE control blocks
must be located in LLN0.
To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
1. On the Tools menu, select Options and click IEC 61850 Configuration.
2. Clear the option IED 61850 configuration engineering mode enabled and click
OK.
GUID-3C811FF5-97F7-4703-81EE-A0C4AC30C8D0 V1 EN
If the IED 61850 configuration engineering mode is enabled, SCD files cannot be
imported and an error message is shown.
GUID-68D1D489-27AC-4729-A887-DCE496CB48E0 V1 EN
To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
GUID-ADF60975-2AD7-47CF-AD26-37094ACEA4F0 V1 EN
4. In the SCL Import Options dialog box, select how to handle the file during the
import.
• Click Don't import IEDs of unknown type to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
• Click Replace unknown if it is known that the file includes additional IEDs
that are needed. The IED of type “Generic IEC 61850 IED” is used to integrate
these kinds of IEDs into the plant structure, for example.
• Click Ignore PCM Object Type to update the IED object(s) in PCM600 from
the IED type(s) in the SCD file, whether or not the IED type(s) in the SCD file
matches the IED object(s) in PCM600. This option can be used, for example,
when third party IEDs are included in the system and the SCD file sends
GOOSE messages to ABB IEDs included in the project.
• Click Ignore Substation Section to not import the SSD file part of the SCD
file.
5. Click Import when the file definition has been completed.
A progress view displays the importing procedure.
6. Make connections from the sending IEDs to the receiving function blocks with the
Signal Matrix tool.
Make connections between the signals that the server is sending and the function
blocks on the receiver's side.
7. Write the configuration to the IED.
In the Plant Structure view, select the IED, right-click and select Write to IED.
IEC09000616-ANSI V1 EN
GUID-ADF60975-2AD7-47CF-AD26-37094ACEA4F0 V1 EN
• Don't import protects the existing IEDs in case the SCD file does not match
the original configuration in PCM600.
• Replace unknown can be used when it is known that the file includes
additional IEDs that are needed. The IED of type “Generic IEC 61850 IED” is
used to integrate these kinds of IEDs into, for example, the plant structure.
• Ignore PCM Object Type updates the IED object(s) in PCM600 from the
IED type(s) in the SCD file, discarding whether or not the IED type(s) in the
SCD file matches the IED object(s) in PM600.
• Ignore Substation Section does not import the SSD file part of the SCD file.
4. Click Import when the definition has been completed.
A progress view displays the importing procedure.
It is possible to make a configuration change in one IED, without affecting the horizontal
communication (GOOSE or IEC 61850-9-2 LE) engineering between IEDs. For example,
when the Application Configuration tool configuration is changed, but no changes are
done to the instantiation or deletion of functions that represent a logical node.
GUID-EEB7D9BD-5D8C-4A18-9A94-848B2821658D V2 EN
Figure 96: Updating the communication configuration in the IED with the
configuration made in PCM600
Section 8 Glossary
www.abb.com/mediumvoltage
www.abb.com/substationautomation
1MAC108982-MB E