Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Circuit Breaker Analyzer and Microohmmeter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

CBA 1000

Circuit Breaker Analyzer


and Microohmmeter
CBA 1000
2

Circuit Breaker Analyzer and Microohmmeter

• Circuit Breaker timing test set • Large graphical high brightness sunlight display

• Built-in 200 A microOhmmeter • Analysis and result evaluation directly on the


display
• 16 timing channels

• Up to 4 trip/close coils control • Internal memory for up to 250 test results and 64
pre-defined test plans
• Motion and speed analyzer
• Cross trigger for the synchronization of up to
• Static and dynamic contact resistance 4 cba 1000
measurement
• Circuit Breaker test with both ends connected to
• Suitable for ehv, hv and mv circuit breakers
ground (BSG option)
• Stand alone functionality - no pc connection
• TDMS software for test results analysis and
is required
reporting

Application Main contact inputs


CBA 1000 is a unique tool for the complete test of all circuit . Number of contact inputs: 6 Main contacts
breakers. It is a powerful timing and motion analyzer test set (2 break per phase) plus 6 Resistor contacts
with built-in 200 A pure DC current microOhmmeter for static and (2 break per phase)
dynamic contact resistance tests.
CBA 1000 measures CB operation times according with . Resistor contact ranges: from 20 Ohm to 10 kOhm
international standards: Open (O), Close (C), Open-Close (O-C), . Contact test voltage: 24 V. Main contact test
Close-Open (C-O), Open-Close-Open (O-C-O). It is also possible to current: 50 mA
set up customized operation sequences. In this way is possible . Each input group is isolated with respect to the others
to get the circuit breaker spread. In the same time you can
measuring the coils currents.
CBA 1000 is a stand alone unit with a large graphical display. The unit
Event inputs
is supplied with TDMS analysis software. TDMS performs test results . Number of auxiliary event inputs: 4, divided in 2
analysis and creates test reports; it allows also to pre-define test plans. groups of 2 each
TDMS is also a powerful Test and Data Management software, compatible . Capability of testing dry (24 V) or wet contacts (20
with all ISA Test Sets.
to 300 V). Test current: 2 mA
All CBA 1000 circuits have been designed to ensure safe and reliable
operations in the noisy environment of HV / MV substations and
power plants. Sample rates
20 kHz - 10 kHz - 5 kHz - 2 kHz - 1 kHz - 500 Hz - 200 Hz - 100 Hz,
Characteristics 50 Hz, 20 Hz user selectable.
Coil operation
Timing accuracy
. Number of circuits: 2 (1 Open and 1 Close coils);
optional 4 (3 Open and 1 Close coils) 50 µs ± 0.025% of the time reading at 20 kHz.
. Type of driver: electronic; it ensures superior
timing control Maximum record length
. Driver characteristic: 300 V DC max; 30 A DC max 1000 s.
. Operating time accuracy: 0.025% of delay ± 50 µs
. Measurement of the coil current: one per channel;
the waveform is displayed on the dedicated
channels
. Coil current ranges: 2.5; 10; 25 A full scale, user
selectable CBA 1000 test
. In case of 4 coils option, it is possible to select the result display
single or multiple phase opening
. Coil current measurement accuracy: 0.5% of the
reading ± 0.1% of the selected range
. Outputs are isolated between them
Circuit Breaker Analyzer and Microohmmeter
3

Analog inputs Display


. Number of analog inputs: 4 (6 Optional) Large graphical high brightness sunlight display (viewing area 122
. 2 (4 optional) dedicated to Open and Close coil currents x 92 mm). Test results are displayed graphically and in table for-
. 1 dedicated to Dynamic and Static Resistance mat. Zoom functions and cursors for test data analysis are directly
Measurement. Input voltage range: ± 5 V available on the CBA 1000 display.
. 1 dedicated to travel, velocity, station battery votage, etc. Input
voltage range: ± 5 V.; ± 50 V; ± 500 V, user selectable
Interfaces to PC
. Analog inputs are isolated with respect to all other circuits 2 available interfaces: USB and RS232.
. Analog input measurement resolution: 16 bit
Memory size
Programmable sequences 128 Mbytes (approx. 250 results).
The user can select the following Open and Close sequences: Open;
Close; Open-Close; Close-Open; Open-Close-Open.
TDMS software
TDMS is a powerful software package, providing data management
Static and Dynamic resistance for commissioning and maintenance testing activities.
measurement (Option) Circuit breaker data and test results are saved in the TDMS
. DC Test current: 200 A, 100 A, 20 A database for historical results analysis.
. Resistance measurement ranges 200 µOhm; 1 mOhm; 10 mOhm;
100 mOhm, user selectable
. Resolution: 1µOhm
. Resistance measurement accuracy: 1% of the reading
± 0.2% of the range.

Microhmmeter display TDMS software has the following main features.


. Full control of CBA 1000 functions from PC
Minimum trip Voltage test (Option)
. Download of test plans
The minimum trip voltage test allows to verify the minimum trip
. Download of test results
voltage threshold and the voltage drop-off delays.
. Test plans and test results can be viewed, edited in the missing
. Two options: 250 V Max and 70 V Max
descriptions, saved, printed, exported. Possibility of viewing,
. Maximum current: 4 A (250 V); 10 A (70 V)
overlaying and gluing more results, for an easy test result comparison
. Maximum voltage adjustement: up to 50% of V Max
. Possibility to pre-set test plans and to upload them into the test set
. Two cursors select measurement points and intervals
Internal or external Printer (Option)
. Zoom in and out feature
. Optional internal thermal printer 58 mm wide
. Enhanced measurement features for movement
. Optional external thermal printer: Seiko DPV-414, 112 mm wide
speed acceleration control.
Test set control ISA software updating policy allows all users to update their software
. The control is local, via graphical display, keypad and pushbutton from the ISA web site www.isatest.com, at no additional cost.
for menu selection: no PC control is necessary
. It is available the local interface in several languages: English,
Spanish, French, Italian, Turkish.
CBA 1000
4

Built-in 200 A Static / Dynamic resistance


module
With 10 m long test cables, cross section 25 sq.mm, terminated
with high current clamps.
Minimum trip Voltage test

Internal thermal printer


CBA 1000 has an (optional) built-in thermal printer, 58 mm wide.

CBA Heavy duty transport case with wheels


CBA plastic soft bag
Test Result Analysis Linear transducer
. Linear transducer: TLH 150 - 150 mm length (IP40).
Other characteristics
. Linear transducer: LWG 150 - 150 mm length.
CBA 1000 can operate both from mains (AC or DC) and from an . Linear transducer: TLH 225 - 225 mm length (IP40).
internal rechargeable battery:
. Linear transducer: LWG 225 - 225 mm length.
. Mains supply: . Linear transducer: TLH 300 - 300 mm length (IP40).
- From 85 to 265 V AC; 50-60 Hz . Linear transducer: TLH 500 - 500 mm length (IP40).
- From 100 to 350 V DC . Linear transducer: LWG 500 - 500 mm length.
. Internal battery. Battery type: NiMh . Linear transducer: LWG 750 - 750 mm length.
. Case: aluminium, with hinged removable cover and handle
. Dimensions: 400(W) * 300(D) *240(H) mm
Pressure transducer: PA-21 Y 40 BAR.
Weight: 10 kg basic unit; 11 kg with Microhmmeter module Rotary transducer: IP 6501 - 355° rotation angle.
Universal transducer mounting kit
Standard Accessories for TLH, LWG and IP travel transducers.
The following accessories are supplied with the unit: Hall effect clip-on transformer
. Mains cable it allows measuring the DC current of motors and of the auxiliary supply.
. User’s manual for hardware and software
. Serial cable
. Grounding cable
. USB cable Applicable Standard
. Spare fuses The test set conforms to the EEC directives regarding
. Software TDMS Electromagnetic Compatibility and Low Voltage instruments.
. Electromagnetic Compatibility: Directive 2004/108/
Optional Accessories EC (CE conform).Applicable standard: EN 61326:2006.
The following options are available upon request: . Low Voltage Directive: Directive 2006/95/EC (CE conform)
. Applicable standards, for a class I instrument, pollution degree 2,
Basic unit test cable kit Installation category II: CEI EN 61010-1. In particular:
The set includes:
. Inputs/outputs protection: IP 2X - CEI EN 60529.
. N. 3 Cables for connection to Main contacts
. N. 2 Cables for connection to Auxiliary contacts . Operating temperature: -10°C to 55 °C; storage: -20°C to 70 °C
. N. 1 Cable for connection to Breaker Coils . Relative humidity: 10 - 95% without condensing
. N. 1 Cable for Low Voltage Measurement
. N. 1 Kit of adaptors and N. 1 adaptor 15 cm long
. N. 1 Cable for connection to Trasducers
. N. 1 Kit of auxiliary cables and a kit of crocodile clamps
. Transport Plastic bag
. Standard cable length 10m; optional cables 18m long.

Additional 2 Open driving coils module


This module increases to 3 the number of Open Coils.
Circuit Breaker Analyzer and Microohmmeter
5

Ordering Information

CODE MODULE
10166 CBA 1000 basic unit supplied with
10015 TDMS - Test & Data Management Software

Optional Accessories

CODE MODULE
15166 CBA1000 Test Cables Kit with transport case
43166 Additional 2 Open Coils Module*
23166 200 A Static / Dynamic Resistance Module
(with test cables 10 m terminated with
clamps)*
33166 Internal Thermal Printer*; **
14102 External Thermal Printer 4.5”
18166 Heavy Duty Plastic Transport Case
19166 Plastics soft bag
34166 MTC - Minimum Trip Coil test module*; **
11166 TLH 150 Linear Transducer 150 mm
12166 TLH 225 Linear Transducer 225 mm
36166 TLH 300 Linear Transducer 300 mm
13166 TLH 500 Linear Transducer 500 mm
14166 Rotary Transducer: IP 6501 – 355° rotation
angle
26166 LWG 150 Linear Transducer 150 mm
27166 LWG 225 Linear Transducer 225 mm
28166 LWG 500 Linear Transducer 500 mm
42166 LWG 750 Linear Transducer 750 mm
13169 Pressure Transducer PA-21 Y 40 BAR
29166 Hall effect clip-on transformer
16166 Universal Analogic Transducer mounting kit
44166 Flexible Coupling Shaft

Options with * must be specified at order.


Options with ** are exclusive each other: code 33166 Internal
thermal printer cannot be ordered together with code 34166
Minimum Trip Voltage Test Module
CBA 1000
6

CBA 1000 - Transport case CBA 1000 - Soft bag

Transducer case Mounting kit TLH linear transducer

LWG linear transducer Rotary transducer Hall effect clamp


Circuit Breaker Analyzer and Microohmmeter
7

CBA 1000 - Example of test cable kit


www.altanova-group.com
DS CBA1000 EN - REV. 07/2020

TECHIMP - ALTANOVA GROUP ISA - ALTANOVA GROUP IntelliSAW - ALTANOVA GROUP


Via Toscana 11, Via Prati Bassi 22, 100 Burtt Rd
40069 Zola Predosa (Bo) - ITALY 21020 Taino (Va) - ITALY Andover, MA 01810 (USA)
Phone +39 051 199 86 050 Phone +39 0331 95 60 81 Phone +1 978-409-1534
Email sales@altanova-group.com Email isa@altanova-group.com Email contact@intellisaw.com

The product and the information contained herein may be changed at any time without prior notification. This document nor any parts thereof may not be reproduced or transmitted in any form
either electronically or mechanically, including photocopying and recording, without the express written consent of Techimp - Altanova Group Srl and ISA - Altanova Group Srl.

You might also like