DCA2007SS 07 Page
DCA2007SS 07 Page
DCA2007SS 07 Page
[Include the following with High Performance Concrete (HPC) Latex Modified Concrete
(LMC) work.]
This Subsection specifies the requirements for the preparation, testing and evaluation of
Portland Cement Concrete specimens. Final quality acceptance testing shall be in
accordance with Section 905. In order that the Engineer can maintain a record of the
strength gain of all concrete placed, the Engineer will make standard test specimens: 6"
x 12" concrete test cylinders for compressive strength, 4” x 8” cylinders for AASHTO
T277 and 6” x 6” x 3” molds for AASHTO T259/T260 permeability testing, and beams
for flexural strength testing. The Contractor shall provide the concrete and molds for the
test specimens, shall be responsible for the handling and protection of the specimens on
the job site and shall arrange for delivery of the specimens to the designated Testing
Laboratory between 24 and 48 hours after casting.
Delete the last paragraph in its entirety and replace with the following:
The final surfaces of Latex Modified Concrete (LMC) overlays, Silica Fume Concrete
overlays and High Performance Concrete (HPC) shall be finished in accordance with
Subsection 401.17 (F) (3) unless specified otherwise in the contract documents.
401.18 CURING.
(D) General.
Delete the first paragraph in its entirety and replace with the following:
All new bridge deck and overlay concrete shall be wet cured. No curing
compound will be permitted.
NOTE FOR THE DESIGNER: Designers shall consider the following when High
Performance Concrete (HPC) is placed under staged construction with live load:
Where feasible, lane closures adjacent to the HPC placement should be scheduled for the
duration of the HPC placement and curing until early age strength is attained.
Lane closures should be 12 hours minimum plus duration of the HPC pour. If this time
frame is not available, permit HPC pours a maximum of 4 hours prior to installation of
lane closings based on initial set time of HPC.
The submission and durations required for the mix designs and verification testing
requirements shall be accounted for in the Contract Schedule.
Variable Message signs should be used to direct trucks away from lanes adjacent to where
HPC is being placed.
Use State Police to check for overweight vehicles and enforce via fines. Consider placing
portable load sensors on bridge during design phase to confirm presence of overweight
vehicles.
434.01 DESCRIPTION.
This work shall consist of the construction of portland cement concrete deck slabs with the
use of High Performance Concrete (HPC). HPC is defined as concrete that meets special
performance and uniformity requirements that cannot always be obtained by using
conventional ingredients, normal mixing procedures and typical curing practices.
Construction shall be as specified in Section 401 except as modified herein.
This work shall also consist of furnishing and installing methacrylate crack sealer for the
sealing of cold joints as shown on the Plans.
434.02 MATERIALS.
Materials shall conform to the following Sections and Subsections:
The ratio of coarse aggregate to fine aggregate shall be a minimum of 1.5 with a total coarse
aggregate content not lower than 1800 lbs.
Proportions of pozzolanic materials shall be such that silica fume will replace a maximum of
5% of portland cement by weight and fly ash a maximum of 20% of the portland cement.
Silica Fume. Prior to submitting a mix design, a sample of the silica fume admixture
shall be submitted to the Authority’s testing laboratory and tested for conformity against
the requirements of the latest AASHTO M 307 or ASTM C 1240 standard and shall be
accompanied by a copy of the manufacturer’s recommendations. Silica fume admixture
shall be approved by the Engineer prior to its use on the Contract. Only one brand of
silica fume admixture shall be used for the entire duration of the Contract. Silica fume
admixture may be supplied either in dry or in slurry form. If the slurry form is used, it
shall be homogeneous and agitated to prevent separation. The Contractor shall submit a
procedure for the introduction of the silica fume into the mix for the Engineer’s approval.
Fly Ash. Fly ash for HPC shall conform to ASTM C 618, Class F except that the loss on
ignition shall not be more than 2.5 percent. Fly ash used to control alkali-silica reactivity
shall be Class F and shall contain not more than 1.5 percent available alkali in accordance
with ASTM C 618, Table 1A. Before each source of fly ash is approved, certified results
of tests conducted by a testing agency shall be submitted to and verified by the Engineer.
Accompanying the certification shall be a statement from the supplier listing the source
and type of coal, the methods used to burn, collect, and store the fly ash, and the quality
control measures employed. Fly ash, Class C will not be permitted for use.
Conformance to the requirements for loss on ignition and fineness shall be determined by
the supplier for each truck load of fly ash delivered to the mixing site. The test values
determined shall be included on the delivery ticket. The Engineer may require that the fly
ash not be used until the Authority has performed tests for loss on ignition and fineness.
Mix Design Verification. In the development of the HPC mix design, the following
performance requirements, in accordance with the indicated test method, shall be
achieved. The verification mix shall be produced in the batching plant using those
materials and equipment to be used for production. A minimum of 8 cubic yards shall be
produced for each of the two (2) required mix designs for verification of the HPC. The
Authority’s testing laboratory shall cast samples from each of the two concrete batches.
A report to document these results shall be provided to the Engineer. The Contractor
shall obtain the results of these standard tests from an AASHTO accredited testing
agency, that is approved for the portland cement concrete testing methods specified in the
below table. The Contractor shall submit a list of their testing laboratory’s
accreditations.
The mix design verification testing shall be accomplished by the Contractor at no cost to
the Authority.
The Authority’s testing laboratory’s lab results will govern the acceptance of the mix
design.
NOTE FOR THE DESIGNER: The Early Age Concrete strength performance
characteristic shall be utilized for bridge decks built under staged construction with live
load, with the Authority’s approval.
Note: For the Scaling Resistance performance testing, as prescribed in the Standard Test Method,
specimens shall be moist cured for 14 days and then air cured for 14 days.
The plan shall also include the procedures for reducing the atmospheric
evaporation rate below 0.75 kilograms per square meter per hour by fog misting,
wind shields or other methods.
The measurements for air temperature, relative humidity and wind speed shall be
taken at the location of the concrete placement. Concrete temperatures shall be
taken from the sample used for slump and air content tests. These measurements
and calculations shall be performed at least once per hour, beginning with the
initial concrete placement and whenever, in the opinion of the Engineer, changes
in the atmospheric condition merit such. The Contractor shall supply all the
instruments necessary to take these measurements, subject to approval by the
Engineer, including two (2) battery operated psychrometers, two (2) concrete
thermometers and two (2) wind gauges. These instruments shall become the
property of the Contractor after final Acceptance. All instruments shall be
certified by an independent laboratory that has been approved by the Engineer.
The instruments shall be certified to be in good working order and as having been
calibrated within the two months immediately prior to use. No separate payment
will be made for providing these instruments.
Placement shall not begin, or shall be discontinued, in the event of rain. The
Contractor shall provide a sufficient number of approved covers and take adequate
precautions to protect freshly-placed concrete from rain. The Engineer may order
the replacement of any material damaged by rain.
2. The Contractor is advised that curing of the HPC shall be performed in accordance
with the provisions of Subsection 401.18. Furthermore, wet burlap, for the curing
of the deck slab concrete, shall be placed within ten (10) minutes after the concrete
is struck off.
If it is anticipated that the ten (10) minute limitation will not be met, the concrete
placement operation shall be stopped. A cold joint shall be formed and the
Contractor shall submit a revised plan of operation for review and approval by the
Engineer before resumption of the HPC placement.
The curing by wet burlap shall be for a minimum period of fourteen (14) calendar
days.
b. To demonstrate that the Contractor can place, finish and cure the HPC, a
trial HPC placement of a minimum of 6 cubic yards of the HPC shall be
placed at the project site at a location that is acceptable to the Engineer.
A 9.25-inch thick and minimum 15-foot wide slab, cast into structurally-
supported stay-in-place forms, shall be constructed to simulate the
placement of the HPC bridge deck.
d. The Contractor shall have ACI grade certified personnel on-site, one of
whom is experienced with HPC and shall be responsible for all quality
control measures related to curing and placing the HPC. The
Contractor’s designee for all HPC quality control measures shall be a
single point of contact.
Chloride Permeability **
56 days (coulombs) AASHTO T 277, ASTM
C 1202 1,100 maximum
90 day ponding AASHTO T 259/T 260 0.65 maximum. Total integral
chloride to 1.6 in depth.
56 days Free Shrinkage ASTM C 157 450 microstrains maximum
3. For quality acceptance limits, testing, sampling and pay adjustments see
Subsections 905.21, 905.22 and 905.23.
NOTE FOR THE DESIGNER: The use of admixtures on bridge decks built under staged
construction with live load shall be evaluated on a project by project basis. Designers shall
consult with the Authority and consider the following minimum requirements:
4. Retarder admixtures shall not be permitted when bridge decks are poured under
staged construction with live load.
434.07 PAYMENT.
Payment will be made under:
No separate payment will be made for the saw cut finish on HPC deck, but all the cost for
this work shall be included in the unit price bid for the bid item Concrete in Deck, HPC.
No separate payment will be made for the crack sealer, but all the cost thereof shall be
included in the unit price bid for the bid item Concrete in Deck, HPC.
DIVISION 900 – MATERIALS
[Include the following with High Performance Concrete (HPC) and Latex Modified
Concrete (LMC) work.]
Fine aggregate for concrete decks shall contain a maximum of 0.06 percent chloride
content.
[Include the following with High Performance Concrete (HPC) and Latex Modified
Concrete (LMC) work.]
[Include the following with High Performance Concrete (HPC) and Latex Modified
Concrete (LMC) work.]
Subsections 905.21, 905.22 and 905.23 are applicable to Latex Modified Concrete
(LMC) and High Performance Concrete (HPC) with the following noted
modifications.
[Include the following with High Performance Concrete (HPC) and Latex Modified
Concrete (LMC) work.]
(3) Permeability.
(a) AASHTO T277 – The Upper Quality Limit (UQL) shall be
2,000 Coulomb resistivity for LMC overlays and 1,100
Coulomb for HPC.
Total integral
Charge chloride to 1.6 in.
Chloride passed depth after 90 day
permeability (coulombs) Type of Concrete ponding test
High > 4000 High water-cement ratio, > 1.3
conventional (> 0.6) PCC*
Moderate 2000-4000 Moderate water-cement ratio, 0.8 to 1.3
conventional (0.4 to 0.5) PCC*
Low 1000-2000 Low water-cement ratio, 0.55 to 0.8
conventional (< 0.4) PCC*
including LMC
Very Low 100-1000 Latex-modified concrete Internally 0.35 to 0.55
sealed concrete
Negligible < 100 Polymer impregnated concrete < 0.35
Polymer concrete
* Portland cement concrete.
[Include the following with High Performance Concrete (HPC) and Latex Modified
Concrete (LMC) work.]
(6) The number of Sublots shown in the table, including the requirements in
Notes (1) thru (4), may be modified by the Engineer.
B) REFERENCES.
(1) American Association of State Highway and Transportation Officials
(AASHTO) Standard Specifications for Highway Bridges.
Add the following:
[Include the following with High Performance Concrete (HPC) and Latex Modified
Concrete (LMC) work.]