Steam Turbine Oil System Operation Shutdown Diagram

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Steam Turbine Oil System

Operation Shutdown Diagram

(01) + CRITERIA FOR STANDSTILL CHECK


+ CASING TEMPERATURE < 100 °C MAA50 CT053A
BEFORE THE TURBINE GEAR IS STOPPED, SHAFTS AND MAA50 CT054A
AND CASING MUST COQL DOWN TO 100 °C TO
PREVENT SHAFT DISTORTION DURING STANDSTILL
PERIOD FOLLOWING TURNING GEAR OPERATION.
THE TURNING GEAR MUST BE STOPPED IF ABOVE
TEMPERATURES ARE REACHED, EXCEPT IN CASES
WHERE EXTENDED TURNING GEAR OPERATION IS
REQUIRED e.g. IF THE TURBINE IS TO BE STARTED
IN SHORT TIME.

(02) + CRITERIA FOR BEGIN OF SHUT DOWN CHECK


IF THE FOLLOWING CRITERIA ARE FULFILLED
THE SYSTEM WILL BE SHUT DOWN FROM
TURNING GEAR OPERATION.
+ SUBLOOP CONTROL TURNING GEAR ON
AND
+ SUBLOOP CONTROL OF AUXILIARY OIL PUMPS ON
AND
+ SUBLOOP CONTROL OF EMERGENCY OIL PUMPS ON
AND
+ AVXILIARY OIL PUMP ON MAV22 A Pool
OR MAV23 A Pool
+ WAITING TIME FOR COOLING DOWN (K4) EXPIRED
+ SUBLOOP CONTROL OF JACKING OIL PUMPS ON
AND
+ JACKING OIL PUMP ON MAV31 A Pool
OR MAV32 A Pool

(03) + FGA (OIL SUPPLY STANDSTILL)


FOR OPERATION OF PUSH BUTTONS REFER
TO MANUAL FOR FGA.
OR
+ TURNING GEAR MANUALLY OPERATED SHUTDOWN

(04) + SUBLOOP CONTROL TURNING GEAR SWITCH OFF


AND
+ TURNING GEAR OIL VALVE CLOSE MAV51 AAOO1
+ SUBLOOP CONTROL TURNING GEAR OFF
AND
+ TURNING GEAR OIL VALVE CLOSED MAV51 AAOO1
OR WITH FGA (OIL SUPPLY)
(04/S) *+ SUBLOOP CONTROL TURNING GEAR OFF MAV51AAO12

(05) + WAIT
THE WAITING TIME IS EXPIRED WHEN THE
SHAFT COMES TO A COMPLETE STOP.
+ SHAFT STAND STILL

BHEL Hardwar 6.2-0340-01/1


06) + SUBLOOP CONTROL OF AUXILIARY OIL PUMPS SWITCH OFF
AND
+ SUBLOOP CONTROL OF EMERGENCY OIL PUMPS SWITCH OFF
AND
+ AUXILIARY OIL PUMP SWITCH OFF MAV22 A Pool
OR MAV23 A Pool
+ SUBLOOP CONTROL OF AUXILIARY OIL PUMPS OFF
AND
+ SUBLOOP CONTROL OF EMERGENCY OIL PUMPS OFF
AND
+ AUXILIARY OIL. PUMP OFF MAV22 A Pool
AND MAV23 A Pool
AND
+ EMERGENCY OIL PUMPS OFF MAV24 A Pool
OR WITH FGA (OIL SUPPLY)
(06/S) *+ SUBLOOP CONTROL OF AUXILIARY OIL PUMPS OFF
AND
*+ SUBLOOP CONTROL OF EMERGENCY OIL PUMPS OFF
AND
*+ AUXILIARY OIL PUMP OFF MAV22 A Pool
AND MAV23 A Pool
AND
*+ EMERCJENCY OIL PUMP OFF MAV24 A Pool

(07) + WAIT
WAIT FOR SHUTDOWN OF JACKING OIL PUMP UNTIL
THE RELATIVE EXPANSIONS ARE REDUCED AND NO
FURTHER MAJOR AXIAL SHIFTING OF THE JOURNALS
IN THE BEARINGS IS EXPECTED.

(08) + SUBLOOP CONTROL OF JACKING OIL PUMP SWITCH OFF


AND
+ JACKING OIL PUMP SWITCH OFF MAV31 A Pool
OR MAV32 A Pool
+ SUBLOOP CONTROL OF JACKING OIL PUMP OFF
AND
+ JACKING OIL PUMP OFF MAV31 A Pool
OR WITH FGA (OIL SUPPLY) AND MAV32 A Pool
(08/S) *+ SUBLOOP CONTROL OF JACKING OIL PUMP OFF
AND
*+ JACKING OIL PUMP OFF MAV31 A Pool
AND MAV32 A Pool

BHEL, Hardwar 6.2-0340-01/2