AE4-1135 R18 Cooling Requirements For Copelametic and Copeland Discus Compressors AE4-1135 R19 August 2012
AE4-1135 R18 Cooling Requirements For Copelametic and Copeland Discus Compressors AE4-1135 R19 August 2012
AE4-1135 R18 Cooling Requirements For Copelametic and Copeland Discus Compressors AE4-1135 R19 August 2012
Introduction
In response to customer inquires, both domestic and
international, Emerson Climate Technologies has
reviewed our application requirements for oil coolers and POE must be handled carefully and the proper
head fans applied on Copeland Discus™ compressors protective equipment (gloves, eye protection, etc.)
in the R-404A/R-507 low temperature applications. must be used when handling POE lubricant. POE
Product engineering has done extensive testing of must not come into contact with any surface or
various parameters, including unloading as well as fully material that might be harmed by POE, including
loaded. The results were the basis for the application without limitation, certain polymers (e.g. PVC/
envelope shown in Figure 1. CPVC and polycarbonate).
The latest testing has shown that as long as the Water-Cooled Compressors
suction return gas is maintained below 65°F, Discus™ Some smaller Copelametic compressors are wrapped
compressors can be operated down to -25°F evaporating with water coils for application on water-cooled
on R-404A/R-507 without the requirement of a head fan condensing units. If water is circulated through the coil
or oil coolers. Additionally, head fans can be eliminated wrapped around the compressor, adequate cooling will
at even lower evaporating temperatures if return gas be provided.
temperatures can be maintained at the lower values.
Emerson Climate Technologies application engineering Refrigerant-Cooled Compressors (Non Discus)
will approve these applications upon receipt of acceptable Refrigerant suction cooled compressors are adequately
test data. cooled by the refrigerant at evaporating temperatures
above 0°F. If operated at evaporating temperatures
NOTE: If you remove the oil cooler, you must install the below 0°F, auxiliary cooling is required.
by-pass loop to maintain proper oil flow.
At evaporating temperatures below 0°F, the compressor
The cooling requirements for all other Copelametic can be cooled adequately by the condenser
motor-compressors and refrigerants are clearly defined fan discharge. Fan cycling for head pressure control is
below. Any deviation from these recommendations can not acceptable unless auxiliary cooling is provided. Fan
result in failure of the compressor. cycling for head pressure control for medium and high
temperature applications is acceptable.
Air-Cooled Compressors
As the name implies, air-cooled compressors Vertical cooling fans are recommended for
are totally dependent on heat transfer to the air to compressors 3 H.P. in size and larger when auxiliary
maintain proper temperatures. cooling is required. A standard fan assembly developing
1000 CFM airflow is available, with interchangeable
Air-cooled compressors require constant airflow across brackets to fit different model compressors.
the compressor for proper cooling. Merely drawing
air through a compartment over the compressor is not Compressors designed for an oil cooler, (6RL, 6RT,
adequate - direct impingement on the compressor from 4RL) must be applied with an oil cooler and a vertical
the fan discharge is necessary. cooling fan.
Table 2
Vertical Cooling Fan Space Requirement
Compressor Add to Compressor
Model Height, Inches
L 8
N 8
M 8.5
9 8.5
4 9.5
4D*X,4D*N 2
7.3
6 10.25
6D*X,6D*N2 9.5
2
Overall Height is measured from the
mounting point to the top of the Fan Guard
Table 3
Horizontal Fan Assemblies
(To blow on compressor side)
130 53.9
120 48.4
110 42.9
100 37.4
Head Fan No Head Fan
90 Required Except & No Oil 31.9
by A.E. Cooler Required
80 Approval (°65F Max R.G.) 26.4
70 20.9
60 15.4
50 9.9
40 4.4
30 -1.1
20 -6.6
-50 -45 -40 -35 -30 -25 -20 -15 -10 -5 0 5 10
Figure 1
Discus™ Head Fan Requirements
R-404A, R-507
Table 4
Nomenclature Scheme to Identify Copeland Discus™
Compressor Models without Oil Coolers
4DA3F47Kx-TSK/TSE SAME
4DL3F63Kx-TSK/FSD/TSE 4DH3F63Kx-TSK/FSD/TSE
4DT3F76Kx-TSK/FSD/TSE 4DJ3F76Kx-TSK/FSD/TSE
6DL3F93Kx-TSK/FSD/TSE 6DH3F93Kx-TSK/FSD/TSE
6DC3F93Kx-TSK/FSD/TSE 6DK3F93Kx-TSK/FSD/TSE
6DD3F93Kx-TSK/FSD/TSE 6DP3F93Kx-TSK/FSD/TSE
6DT3F11Mx-TSK/FSD/TSE/ESX 6DJ3F11Mx-TSK/FSD/TSE/ESX
6DE3F11Mx-TSK/FSD/TSE 6DR3F11Mx-TSK/FSD/TSE
6DF3F11Mx-TSK/FSD/TSE 6DS3F11Mx-TSK/FSD/TSE
Note: Discus III models are not offered with oil coolers.
The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"),
as applicable, reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the
selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser
or end user.