NRC Generic Fundamentals Examination Question Bank - PWR February 2016
NRC Generic Fundamentals Examination Question Bank - PWR February 2016
NRC Generic Fundamentals Examination Question Bank - PWR February 2016
February 2016
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P6 (B1806)
Density input is normally used in steam flow instruments to convert __________ into __________.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P305 (B2906)
If the steam pressure input to a density-compensated steam flow instrument fails high, the associated
flow rate indication will...
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P406 (B1606)
The density compensating input to a steam flow instrument is used to convert volumetric flow rate
to…
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P705 (B708)
A steam flow measuring instrument uses density compensation and square root compensation to
convert the differential pressure across a flow element to flow rate in lbm/hr.
The purpose of square root compensation in this flow measuring instrument is to convert __________
to __________.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P1212
If the steam pressure input to a density-compensated steam flow instrument fails low, the indicated
flow rate will...
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P3605 (B3608)
A steam flow measuring instrument uses density compensation and square root extraction to convert
the differential pressure across the flow element to flow rate in lbm/hr.
The purpose of density compensation in this flow measuring instrument is to convert __________ to
__________.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P4603 (B4604)
A main steam flow rate differential pressure detector was properly calibrated to produce a main steam
flow rate indication of 500,000 lbm/hr with the following initial input conditions:
Assume that the detector and associated circuitry do not have steam density compensation. Also
assume that the main steam quality and volumetric flow rate do not change.
The current main steam flow rate indication is __________ 500,000 lbm/hr; and the current main
steam flow rate is __________ 500,000 lbm/hr.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P4703 (B4704)
A nuclear power plant is initially operating with the following main steam parameter values:
Assume 100 percent quality saturated steam and that main steam volumetric flow rate is the same
before and after the pressure change.
Which one of the following is the approximate mass flow rate of main steam after the pressure
change?
A. 528,000 lbm/hr
B. 500,000 lbm/hr
C. 472,000 lbm/hr
D. 444,000 lbm/hr
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P6103 (B6104)
For water flowing through a venturi, there is a proportional relationship between flow rate and
differential pressure. For steam flowing through a venturi, the relationship must be modified to
account for changes in __________ as the steam flows through the venturi.
A. velocity
B. enthalpy
C. internal energy
D. specific volume
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.02 [2.7/2.9]
QID: P6403
A nuclear power plant is operating at 100 percent power with constant steam generator water levels.
Only main feedwater is entering the steam generators and only main steam is leaving the steam
generators. Both the main feedwater mass flow rate and the main steam mass flow rate instruments
use venturi flow sensing elements.
For the above conditions, the indication that most accurately reflects the mass flow rate through a
steam generator will typically be the mass flow rate indication for...
A. main feedwater, because condensation can adversely affect the characteristics of a steam flow
venturi.
B. main feedwater, because steam generator pressure changes affect the specific volume of steam
more than water.
C. main steam, because the enthalpy of high quality steam flowing through a venturi is constant,
unlike the enthalpy of water.
D. main steam, because a given mass flow rate of steam through a venturi develops a larger pressure
change than the same mass flow rate of water.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.03 [2.7/2.9]
QID: P206
The most probable cause for fluctuating indication from a liquid flow rate differential pressure
detector is...
D. the valve on the high pressure sensing line being partially closed.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.03 [2.7/2.9]
QID: P905
A properly calibrated differential pressure-type water flow detector is located several feet below a
horizontal pipe containing the detector's sensing element. The detector was removed for inspection
and then reconnected to the sensing element with its low-pressure sensing line filled with air and its
high-pressure sensing line filled with water.
When the water system is operating, indicated flow rate will be...
A. zero.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P8 (B607)
How will flow rate indication be affected if the equalizing valve for the associated differential pressure
detector is fully opened?
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P307 (B307)
A differential pressure flow detector is connected to a calibrated orifice in a cooling water system.
Which one of the following will cause indicated volumetric flow rate to be lower than actual
volumetric flow rate?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P706 (B707)
Flow rate is being measured using a differential pressure flow detector and a calibrated orifice. If
actual flow rate remains constant, which one of the following will cause indicated flow rate to be
higher than actual flow rate?
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P1007 (B1907)
Refer to the drawing of a pipe elbow used for flow measurement in a cooling water system (see figure
below).
If instrument line A develops a leak, indicated flow rate will __________ due to a __________
measured D/P.
A. increase; larger
B. increase; smaller
C. decrease; larger
D. decrease; smaller
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P1205 (B1506)
If the orifice in a differential pressure (D/P) flow sensor erodes such that the orifice opening becomes
larger, indicated flow rate will __________ due to a __________ D/P across the orifice. (Assume
actual flow rate remains the same.)
A. increase; larger
B. increase; smaller
C. decrease; larger
D. decrease; smaller
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P1608 (B1608)
Refer to the drawing of a horizontal pipe elbow (top view) in an operating water system (see figure
below).
Three separate differential pressure flow detectors are connected to taps A, B, C, and D as follows:
Detector Taps
X A and D
Y B and D
Z C and D
Assuming zero head loss in this section of pipe, how will the detectors be affected if tap D ruptures?
C. Two detectors will fail low and one will fail high.
D. Two detectors will fail high and one will fail low.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P2107 (B2209)
Refer to the drawing of a pipe elbow used for flow measurement in a cooling water system (see figure
below).
If instrument line B develops a leak, indicated flow rate will __________ due to a __________
measured D/P.
A. increase; larger
B. increase; smaller
C. decrease; larger
D. decrease; smaller
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P2305 (B2310)
An orifice is being used in an operating cooling water system to measure flow rate. Which one of the
following will cause the differential pressure sensed across the orifice to decrease?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P2307 (B2307)
Refer to the drawing of a horizontal pipe elbow (top view) in an operating water system (see figure
below). Three separate bellows differential pressure flow detectors are connected to taps A, B, C, and
D as follows:
Detector Taps
X A and D
Y B and D
Z C and D
Assume that water is incompressible and there is no head loss in this section of pipe. How will the
detectors be affected if system flow rate remains the same while system pressure increases from 1000
psig to 1200 psig?
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P2807 (B1007)
Refer to the drawing of a pipe elbow (top view) in an operating water system (see figure below).
At which one of the following locations is the highest pressure sensed? (Assume a constant pipe
diameter and zero head loss in this section of pipe.)
A. Point A
B. Point B
C. Point C
D. Point D
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.04 [2.7/2.7]
QID: P2905 (B3108)
Refer to the drawing of a horizontal pipe elbow (top view) in an operating water system (see figure
below).
Three separate bellows-type differential pressure flow detectors are connected to taps A, B, C, and D
as follows:
Detector Taps
X A and D
Y B and D
Z C and D
Assuming zero head loss in this section of pipe, how will the detectors be affected if tap B experiences
a significant leak? (Assume water system pressure does not change.)
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P9
Flow detectors (such as an orifice, flow nozzle, and venturi tube) measure flow rate using the principle
that the flow rate of a liquid is...
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P308 (B305)
A cooling water system is operating at steady-state conditions indicating 900 gpm with 60 psid across
the flow transmitter venturi. If cooling water flow rate is increased to 1,800 gpm, differential
pressure across the flow transmitter venturi will be approximately...
A. 85 psid.
B. 120 psid.
C. 175 psid.
D. 240 psid.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P607 (B608)
The flow rate of water passing through a venturi can be determined by measuring the...
D. rotation rate of a paddle wheel-type device installed in the throat of the venturi.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P707 (B706)
A cooling water system is operating at a steady-state flow rate of 700 gpm with 60 psid across the flow
transmitter venturi. If cooling water flow rate is increased to 1,000 gpm, differential pressure across
the flow transmitter venturi will be...
A. 85.7 psid.
B. 122.4 psid.
C. 171.4 psid.
D. 244.8 psid.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P807 (B807)
Refer to the drawing of a venturi flow element (see figure below) with direction of water flow
indicated by the arrow.
Where should the high pressure tap of a differential pressure flow detector be connected?
A. Point A
B. Point B
C. Point C
D. Point D
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P907 (B1905)
A differential pressure (D/P) detector is being used with a venturi to measure main steam flow rate.
With a steam flow rate of 5 x 106 lbm/hr, the measured D/P is 40 psid.
If steam flow changes such that the current D/P is 30 psid, what is the approximate current steam flow
rate? (Assume that main steam pressure at the inlet of the venturi remains constant.)
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P908 (B2106)
Which one of the following flow measuring elements produces the largest unrecoverable head loss
when used in an operating fluid system?
A. Venturi
B. Flow nozzle
C. Pipe elbow
D. Orifice
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1106 B3306)
Refer to the drawing of a venturi flow element in an operating cooling water system (see figure
below).
A. Point A
B. Point B
C. Point C
D. Point D
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1308 (B907)
Refer to the drawing of a venturi flow element in an operating cooling water system (see figure
below).
A differential pressure detector measuring flow rate through the venturi will produce the highest flow
rate indication if its high-pressure tap is connected at point _____; and its low-pressure tap is
connected at point _____.
A. A; B
B. A; D
C. B; C
D. B; D
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1407
A cooling water system is operating at a steady-state flow rate of 500 gpm with 60 psid across the
associated venturi flow element. If cooling water flow rate increases to 1,000 gpm, the differential
pressure sensed by the venturi flow element will be approximately...
A. 85 psid.
B. 120 psid.
C. 240 psid.
D. 480 psid.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1606 (B407)
Refer to the drawing in which water is flowing through a convergent-divergent venturi (see figure
below). The pipe diameters at P1 and P2 are equal.
Compared to the conditions at the inlet of the venturi (P1), the pressure at the outlet of the venturi (P2)
has __________; and water velocity at the outlet of the venturi has __________. (Assume "real"
conditions.)
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1808
Water is flowing through a venturi flow element. At the throat of the venturi, the __________ water
pressure and the __________ water velocity occurs.
A. highest; highest
B. lowest; lowest
C. lowest; highest
D. highest; lowest
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1873 (B1773)
Water is flowing through each of the following devices. Which one of the devices will produce an
outlet pressure that is greater than the inlet pressure?
A. Convergent nozzle
B. Divergent nozzle
C. Orifice
D. Flow restrictor
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P1906 (B1408)
Refer to the drawing of a pipe elbow (top view) in an operating water system (see figure below).
At which one of the following pairs of connection points will the greatest differential pressure be
sensed? (Assume a constant pipe diameter and zero head loss in this section of pipe.)
A. Points A and B
B. Points B and C
C. Points C and D
D. Points D and A
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P2306 (B2306)
A venturi is being used to measure the flow rate in a cooling water system. As the water flows from
the throat to the discharge of the venturi, water pressure will __________; and volumetric flow rate
will __________.
B. increase; increase
D. decrease; decrease
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P2406 (B2206)
A cooling water system is operating at a steady-state flow rate of 700 gpm with 60 psid across the
associated venturi flow element. If cooling water flow rate increases to 900 gpm, the differential
pressure sensed by the venturi flow element will be approximately...
A. 68 psid.
B. 77 psid.
C. 99 psid.
D. 127 psid.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P2505 (B2506)
A main steam flow rate measuring instrument uses a steam pressure input to produce main steam mass
flow rate indication. Assuming steam volumetric flow rate does not change, a steam pressure
decrease will cause indicated steam mass flow rate to...
C. remain the same, because steam pressure does not affect the mass flow rate of steam.
D. remain the same, because the steam pressure input compensates for changes in steam pressure.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P2507 (B2508)
A differential pressure detector is being used with an orifice plate to measure water flow rate through a
pipe. When the flow detector was last calibrated, the following parameters were observed:
Significant erosion of the orifice has occurred since the calibration such that actual flow rate through
the orifice has increased to 120 gpm while the upstream and downstream pressures have changed to
110 psig and 106 psig respectively.
A. 44 gpm
B. 67 gpm
C. 81 gpm
D. 120 gpm
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P2606
A cooling water system is operating at steady-state conditions at 900 gpm with 64 psid across the flow
transmitter venturi. Cooling water flow rate changes such that venturi differential pressure decreases
to 36 psid.
A. 506 gpm
B. 576 gpm
C. 675 gpm
D. 745 gpm
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P2808 (B2806)
A differential pressure detector is being used with an orifice plate to measure water flow rate through a
pipe. When the flow detector was last calibrated, the following parameters were observed:
Significant erosion of the orifice hole has occurred since the last calibration, such that actual flow rate
through the orifice has increased to 120 gpm while the upstream and downstream pressures have
changed to 124 psig and 109 psig respectively.
A. 44 gpm
B. 67 gpm
C. 100 gpm
D. 120 gpm
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P3207 (B3206)
A cooling water system uses a horizontal venturi with a differential pressure flow detector to provide
flow rate indication. Water enters and leaves the venturi at 70°F, 120 psig, and 20 ft/sec. Water
velocity at the throat of the venturi is 45 ft/sec. Assume water is incompressible and the venturi
experiences no unrecoverable head loss.
What is the approximate pressure of the water at the throat of the venturi?
A. 109 psig
B. 98 psig
C. 86 psig
D. 71 psig
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P3306 (B2010)
A cooling water system is operating at steady-state conditions. A calibrated system flow meter
indicates 600 gpm with 50 psid across the flow element.
If cooling water flow rate increases to 900 gpm, the differential pressure sensed by the flow element
will be approximately...
A. 63 psid.
B. 75 psid.
C. 97 psid.
D. 112 psid.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P3706 (B3706)
The following is the current calibration data for an orifice plate that is being used for water flow rate
measurement:
During a surveillance, the following pressures are observed across the orifice plate:
What is the approximate water flow rate through the orifice plate?
A. 47 gpm
B. 57 gpm
C. 68 gpm
D. 78 gpm
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P3807 (B3807)
The manometer is filled with water and installed across an orifice in a ventilation duct to determine the
rate of air flow. The manometer is currently indicating a water level difference of 16 inches at an air
flow rate of 300 ft3/min.
Which one of the following will be the approximate rate of air flow when the manometer indicates a
water level difference of 4 inches?
A. 75 ft3/min.
B. 125 ft3/min.
C. 150 ft3/min.
D. 175 ft3/min.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P4003 (B4005)
A differential pressure detector is being used with an orifice plate to measure water flow rate through a
pipe. When the flow instrument was last calibrated, the following parameters were observed:
Since the calibration, debris has collected in the orifice such that the actual flow rate through the
orifice has decreased to 80 gpm while the upstream and downstream pressures have changed to 135
psig and 110 psig, respectively.
What is the approximate flow rate that is currently indicated by the flow instrument?
A. 125 gpm
B. 133 gpm
C. 156 gpm
D. 167 gpm
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P4604 (B4605)
The manometer is filled with water and installed across an orifice in a ventilation duct to determine the
rate of air flow. The manometer is currently indicating a water level difference of 8 inches at an air
flow rate of 300 cubic feet per minute (ft3/min).
Which one of the following will be the approximate air flow rate when the manometer indicates a
water level difference of 4 inches?
A. 75 ft3/min
B. 150 ft3/min
C. 188 ft3/min
D. 212 ft3/min
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P4804 (B4804)
A cooling water system uses a horizontal venturi with a differential pressure flow detector to provide
flow rate indication. Water enters and leaves the venturi at 70°F, 100 psig, and 24 ft/sec. Water
velocity at the throat of the venturi is 50 ft/sec. Assume water is incompressible and the venturi
experiences no unrecoverable head loss.
What is the approximate pressure of the water at the throat of the venturi?
A. 98 psig
B. 94 psig
C. 87 psig
D. 74 psig
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P6803 (B6804)
Refer to the drawing of a frictionless venturi flow element (see figure below). Subcooled water is
flowing through the venturi with the following initial conditions:
Flow rate increases to 1,000 gpm, which results in a tap A pressure of 68 psia. What is the new
pressure at tap B?
A. 60 psia
B. 52 psia
C. 44 psia
D. 32 psia
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P7632 (B7632)
Refer to the drawing of a frictionless venturi flow element (see figure below). Subcooled water is
flowing through the venturi with the following initial conditions:
When flow rate is increased to 750 gpm, the pressure at tap A increases to 68 psia. What is the new
pressure at tap B?
A. 66 psia
B. 62 psia
C. 59 psia
D. 52 psia
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.05 [2.6/2.8]
QID: P7681 (B7681)
Refer to the drawing of a frictionless venturi flow element (see figure below). Subcooled water is
flowing through the venturi with the following initial conditions:
When flow rate is increased to 900 gpm, the pressure at tap A increases to 62 psia. What is the new
pressure at tap B?
A. 46 psia
B. 49 psia
C. 55 psia
D. 60 psia
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P208 (B909)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The associated level instrument was calibrated with the water storage tank at 100°F. If mass in the
tank remains constant and the water temperature increases to 120°F, the indicated level will...
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P411
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below). The pressurizer level instrument was calibrated while the plant was in a cold shutdown
condition.
When the plant is returned to normal operating conditions, pressurizer level will indicate __________
than actual level because a given pressurizer level at normal operating conditions produces a
__________ D/P compared to cold shutdown conditions.
A. higher; smaller
B. higher; larger
C. lower; smaller
D. lower; larger
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P507
Refer to the drawing of a water storage tank with a differential pressure level detector that was recently
calibrated at a tank water temperature of 80°F (see figure below).
If the mass of the water in the tank remains the same while the tank water temperature is raised from
80°F to 150°F, the indicated level will...
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P608
Refer to the drawing of a water storage tank with two tank differential pressure (D/P) level indicators
(see figure below).
Two D/P level indicators are installed on a large water storage tank. Indicator 1 was calibrated at
100°F water temperature and indicator 2 was calibrated at 200°F water temperature.
Assuming both indicators are on scale, which indicator will indicate the higher level?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P808 (B809)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The level detector is being used in a level control system that was calibrated to maintain tank level at
80 percent when the tank water temperature was 100°F. If tank water temperature gradually
increases and stabilizes at 150°F, the level control system will cause actual tank level to...
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P1107 (B1507)
Refer to the drawing of a water storage tank with two tank differential pressure (D/P) level indicators
(see figure below).
Two D/P level indicators are installed on a large water storage tank. Indicator 1 was calibrated at
100°F water temperature and indicator 2 was calibrated at 200°F water temperature.
Assuming both indicators are on scale, which indicator will indicate the lower level?
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P1706 (B1706)
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Two D/P level indicators are installed on a large water storage tank. Indicator No. 1 was calibrated at
200°F water temperature and indicator No. 2 was calibrated at 100°F water temperature.
Assuming both indicators are on scale, which indicator will indicate the lower level?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P1907 (B4205)
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Indicator 1 was calibrated at 120°F and indicator 2 was calibrated at 180°F. If tank water temperature
is currently 150°F, then indicator...
A. 1 will read greater than indicator 2, and greater than actual level.
B. 1 will read greater than indicator 2, and less than actual level.
C. 2 will read greater than indicator 1, and greater than actual level.
D. 2 will read greater than indicator 1, and less than actual level.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P2108 (B2408)
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Indicator 1 was calibrated at 180°F and indicator 2 was calibrated at 120°F. If tank water temperature
is 150°F, then indicator...
A. 1 will read greater than indicator 2, and greater than actual water level.
B. 1 will read greater than indicator 2, and less than actual water level.
C. 2 will read greater than indicator 1, and greater than actual water level.
D. 2 will read greater than indicator 1, and less than actual water level.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P2308 (B2308)
Refer to the drawing of a steam generator differential pressure (D/P) level detection system that was
calibrated at normal operating conditions (see figure below).
A reactor coolant system cooldown has resulted in a decrease in steam generator pressure from 900
psia to 400 psia in one hour. Without density compensation of the level instrumentation, at the end of
the cooldown steam generator level indication would indicate __________ than actual level because
the density of the water in the __________ has changed significantly.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P2509
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below) that was calibrated at the current SG pressure of 400 psia.
A reactor coolant system heatup has resulted in an increase in SG pressure from 400 psia to 900 psia
over 4 hours. The ambient air temperature surrounding the SG has remained constant.
Without density compensation of the level instrumentation, at the end of the heatup SG level
indication would indicate __________ than actual level because the density of the water in the
__________ has changed significantly.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P3208
A reactor is currently shut down with the reactor coolant system at 140°F and 150 psig. Pressurizer
level is being monitored using a differential pressure detector with a wet reference leg. The
pressurizer level instrument was calibrated at normal plant operating conditions.
The pressurizer level instrument currently indicates __________ than actual pressurizer level because,
compared to the calibration conditions, there has been a significant change in the density of the fluid in
the __________.
B. lower; pressurizer
D. higher; pressurizer
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P4104
Refer to the drawing of a pressurizer and differential pressure (D/P) level detection system that was
recently calibrated at normal operating conditions (see figure below). Assume that the associated
pressurizer level instrument does not use density compensation.
With the nuclear power plant shut down at reduced reactor coolant system temperature and pressure,
the pressurizer level instrument will indicate __________ than actual water level because the D/P
currently sensed by the D/P detector is __________ than the D/P for the same pressurizer water level
at normal operating conditions.
A. lower; smaller
B. lower; larger
C. higher; smaller
D. higher; larger
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P4404
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below).
The associated pressurizer level instrument was recently calibrated with the nuclear power plant at
normal operating conditions. Assume that the level instrument does not use density compensation.
If the plant is currently shut down at reduced reactor coolant system temperature and pressure,
pressurizer water level will currently indicate __________ than actual water level because, for a given
pressurizer water level, the D/P sensed by the D/P detector is currently __________.
A. higher; smaller
B. higher; larger
C. lower; smaller
D. lower; larger
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P4504
Refer to the drawing of a differential pressure (D/P) level detection system for a pressurizer at normal
operating temperature and pressure (see figure below).
A nuclear power plant uses several differential pressure detectors like the one below to provide
multiple channels of pressurizer water level indication. A hot channel was calibrated when the
pressurizer was at normal operating temperature. A cold channel was calibrated when the pressurizer
was at 160°F.
How will the level indications on the two channels compare when the pressurizer is at normal
operating temperature?
A. The cold channel will indicate higher than the hot channel, due to the difference in reference leg
water density at the two calibration temperatures.
B. The cold channel will indicate lower than the hot channel, due to the difference in reference leg
water density at the two calibration temperatures.
C. The cold channel will indicate higher than the hot channel, due to the difference in pressurizer
water density at the two calibration temperatures.
D. The cold channel will indicate lower than the hot channel, due to the difference in pressurizer
water density at the two calibration temperatures.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.06 [2.5/2.6]
QID: P6203
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below).
With the pressurizer containing saturated water and steam at 2,250 psia, pressurizer level indication is
20 feet. Assume that reference leg level and temperature do not change. Also, ignore the effect of
steam density changes on level indication.
With no change in actual pressurizer level, what will level indication be at 600 psia (saturated)?
A. 14.9 feet
B. 18.3 feet
C. 22.4 feet
D. 26.8 feet
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P410
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
If the differential pressure detector equalizing valve is opened, level indication will:
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P708 (B2609)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The level detector is being used in a level control system that is calibrated to maintain tank level at 75
percent at the current water temperature of 90°F. If water temperature gradually increases and
stabilizes at 120°F, the level control system will cause actual tank level to...
A. remain at 75 percent.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P910 (B910)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The D/P sensed by the detector varies in the __________ direction as the temperature of the water in
the tank if the __________ of the tank water is constant. (Assume reference leg and tank water
temperatures are initially the same.)
A. same; level
B. inverse; level
C. same; mass
D. inverse; mass
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P1008 (B1909)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The level detector is being used in a level control system that is calibrated to maintain tank level at 75
percent at the current water temperature of 120°F. If water temperature gradually decreases and
stabilizes at 90°F, actual tank level will...
A. remain at 75 percent.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P1807 (B1211)
A cooling water system is cooling a lube oil heat exchanger. Cooling water system surge tank level is
being measured using a differential pressure level detector that has been calibrated at the current water
temperature in the tank. A leak in the heat exchanger results in lube oil collecting in the surge tank.
Assuming that the temperature of the contents in the surge tank does not change, indicated tank level
will be __________ than actual tank level because lube oil is __________ than water.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P2009
Many steam generator water level instruments are designed with a condensing chamber in the
reference leg. The purpose of the condensing chamber is to...
A. maintain a constant water level in the reference leg during normal operations.
B. provide reference leg compensation for the steam generator pressure exerted on the variable leg.
C. prevent reference leg flashing during a rapid depressurization of the steam generator.
D. ensure the reference leg temperature remains close to the temperature of the variable leg.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P3008 (B3010)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
Assume the initial temperature of the reference leg and the water in the tank is 100°F, and that
reference leg temperature does not change.
If the temperature of the water in the tank increases by 20°F, the D/P sensed by the detector will
__________ as long as the water __________ is maintained constant.
A. increase; level
B. decrease; level
C. increase; mass
D. decrease; mass
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P3407 (B3408)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below). Assume that the initial temperature of the reference leg and the water in the tank
are the same, and that reference leg temperature and level do not change.
The level detector is being used in a level control system (not shown) that is calibrated to maintain tank
level at 75 percent at the current tank water temperature (70°F) and pressure (5 psig).
If the tank water temperature remains constant, but the tank pressure is increased by 10 psig, the level
control system will cause actual tank level to...
A. remain at 75 percent.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P5003
The downcomer region of a steam generator contains 40 feet of saturated water at 536°F. A steam
generator water level detector has a pressure tap located at the bottom of the downcomer region.
Approximately how much of the total pressure at the pressure tap is caused by the downcomer water?
A. 0.6 psi
B. 13.0 psi
C. 27.7 psi
D. 156.0 psi
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P5204
Refer to the drawing of a differential pressure (D/P) level detection system (see figure below) for a
pressurizer at normal operating temperature and pressure. The level detector has just been calibrated.
The high pressure side of the detector is connected to the __________; and if the equalizing valve is
opened, the indicated pressurizer level will be __________ than the actual level.
C. pressurizer; lower
D. pressurizer; higher
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P6104 (B6105)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The D/P level detector was just calibrated and returned to operation with the following conditions:
Assume the actual tank water level and the temperature of the water in the tank and reference leg do
not change. Which one of the following will be the new tank level indication if the reference leg
water level decreases to 18 feet?
A. 22 feet
B. 20 feet
C. 18 feet
D. 2 feet
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P6604 (B6606)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The water storage tank is 40 feet tall. The level detection system is calibrated to provide a level
indication of 30 feet when the tank and reference leg levels are equal.
If the tank is completely filled with water, the tank level will indicate...
B. 30 feet.
D. 40 feet.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P6704 (B6705)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
Assume that the initial temperature of the reference leg and the water in the tank is 100°F, and that
reference leg temperature does not change.
If the temperature of the water in the tank increases by 20°F, the D/P sensed by the detector will
__________ if the __________ of the water in the tank is constant.
A. decrease; level
B. decrease; mass
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P7404 (B7404)
Refer to the drawing of a vented water storage tank with a differential pressure (D/P) level detection
system (see figure below). The water in the tank and reference leg is at the same temperature.
The tank level indicator was just calibrated to indicate 0 percent when the tank is empty and 100
percent when the water level reaches the upper tap. The indicator’s display range is 0 percent to 120
percent. The initial water level is as indicated in the figure.
If the tank water level slowly increases and stabilizes just below the top of the tank, the level indication
will increase until…
A. the water level stabilizes, at which time the level indication will stabilize at 100 percent.
B. the water level stabilizes, at which time the level indication will stabilize at a value greater than
100 percent.
C. the water level reaches the upper tap, at which time the level indication will remain at 100 percent
as the water level continues to increase.
D. the water level reaches the upper tap, at which time the level indication will continue to increase as
the water level continues to increase.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.07 [2.5/2.6]
QID: P7602 (B7602)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below). The level detector has just been calibrated.
How will the indicated level be affected if condensation partially fills the normally dry reference leg?
D. Indicated level may be higher or lower than actual level depending on the pressure in the upper
volume of the tank.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P11
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The level instrument has just been calibrated to read actual tank water level. If the reference leg
subsequently experiences high ambient temperature, indicated level will...
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P14 (B510)
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Indicator 1 was calibrated at 200°F and indicator 2 was calibrated at 100°F. If tank water temperature
is 150°F, then...
D. both indicators will be inaccurate, but it is impossible to predict which indicator will read greater.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P609 (B12)
Refer to the drawing of two water storage tanks with four differential pressure (D/P) level detectors
(see figure below).
The tanks are identical with equal water levels and both are pressurized to 20 psig. All detectors were
calibrated at the current water temperature and 70°F external (ambient) temperature.
Which detectors will provide the most accurate level indication following an increase in external
(ambient) temperature from 70°F to 100°F? (Assume tank contents temperatures and external
pressure do not change.)
A. 1 and 3
B. 2 and 4
C. 1 and 4
D. 2 and 3
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P1108 (B1609)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
A calibrated D/P level detector is being used to measure level in a vented tank inside the auxiliary
building. If building pressure increases with no change in temperature, the associated level indication
will...
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P1411
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below).
The pressurizer level instrument was calibrated while the plant was at normal operating conditions.
With the plant in cold shutdown conditions, the pressurizer level D/P instrument will indicate
__________ than actual level because the D/P sensed by the detector at cold shutdown conditions will
be __________ than at normal operating conditions for the same level.
A. lower; greater
B. lower; smaller
C. higher; greater
D. higher; smaller
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P1607 (B1409)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The associated level instrument was calibrated with the water storage tank at 120°F. If the mass in
the tank remains constant and the water temperature decreases to 100°F, the indicated level will...
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P2810 (B2808)
Refer to the drawing of a pressurizer level detection system (see figure below). The differential
pressure (D/P) detector was calibrated while the plant was at normal operating conditions.
With the plant initially at normal operating conditions, a pressurizer steam space leak occurred.
Pressurizer pressure decreased by 300 psia, and the ambient air temperature surrounding the reference
leg increased by 80°F, where these parameters stabilized.
If the actual pressurizer water level is 60 percent, the reduced pressurizer pressure will tend to make
the indicated pressurizer level read __________ than actual level; and the increased reference leg
temperature will tend to make the indicated pressurizer level read __________ than actual level.
A. higher; higher
B. higher; lower
C. lower; higher
D. lower; lower
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.08 [2.8/3.1]
QID: P4004 (B4006)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The level instrument has just been calibrated to indicate actual tank water level. Assume that tank
water temperature and level remain constant. If the reference leg temperature increases by 20°F,
indicated tank water level will...
A. be unpredictable.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P12
The level indication for a wet reference leg differential pressure (D/P) level instrument will fail low as
a result of...
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P209 (B1010)
Refer to the drawing of a steam generator differential pressure (D/P) level detection system (see figure
below).
The D/P detector was calibrated at the current conditions. Which one of the following will cause the
level instrument to indicate lower than actual level? (Assume actual level remains the same.)
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P309 (B308)
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
Tank water level indication will be lower than actual level when reference leg temperature is
__________ than calibration conditions or when there is a break in the __________ leg of the D/P cell.
A. less; reference
B. less; variable
C. greater; reference
D. greater; variable
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P911 (B3508)
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below) that was recently calibrated at normal operating conditions.
With the reactor shut down, SG pressure was inadvertently decreased from 900 psig to 700 psig in 5
minutes due to operator error. SG pressure was stabilized at 700 psig, but during the pressure
decrease a small amount of water in the condensing pot flashed to steam. Assume the reference leg
water remained subcooled, except for the small amount of water that flashed to steam in the
condensing pot.
As a result of the small loss of condensing pot water, SG level will indicate __________ than actual
level; and as the condensing pot refills, indicated level will __________.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P2408 (B1212)
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below).
Which one of the following events will result in a SG level indication that is greater than actual level?
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P2609
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below).
The SG is at normal operating temperature and pressure with accurate level indication. Which one of
the following events will result in a SG level indication that is greater than actual level?
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P2708
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below).
The SG is supplying steam at normal operating temperature and pressure and the level instrumentation
has just been calibrated. Which one of the following events will result in a SG level indication that is
less than actual level?
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P2907
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below).
The SG is at normal operating temperature and pressure with accurate level indication. Which one of
the following events will result in a SG level indication that is lower than actual level?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.09 [2.9/3.0]
QID: P3808
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below).
A reactor is shutdown with the reactor coolant system being maintained at 100 psia. The pressurizer
level detector has just been calibrated. Suddenly a rupture in the condensing pot of the level detector
results in a rapid drop of the condensing pot pressure to atmospheric pressure.
Which one of the following describes the current pressurizer level indication from the detector?
A. Off scale low, because the bulk of the water in the reference leg has flashed to steam.
B. Off scale high, because the bulk of the water in the reference leg has flashed to steam.
C. Off scale low, because the static pressure on the reference leg is much less than the static pressure
in the pressurizer.
D. Off scale high, because the static pressure on the reference leg is much less than the static pressure
in the pressurizer.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.10 [2.3/2.5]
QID: P310
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.10 [2.3/2.5]
QID: P413 (B410)
If the pressure sensed by a bourdon tube increases, the curvature of the detector will __________
because the greater force is being applied to the __________ curve of the detector.
A. increase; outer
B. increase; inner
C. decrease; outer
D. decrease; inner
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.10 [2.3/2.5]
QID: P810
In a diaphragm type pressure detector, pressure is measured using the __________ of the diaphragm.
A. rotational movement
B. axial deflection
C. change in circumference
D. change in diameter
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.10 [2.3/2.5]
QID: P1508 (B1011)
A bourdon tube works on the principle that when the pressure inside the tube decreases, the tube tends
to: (Assume detected pressure remains above atmospheric pressure.)
C. coil, due to the spring action of the metal overcoming the pressure-induced force on the inside of
the tube.
D. straighten, due to the spring action of the metal overcoming the pressure-induced force on the
inside of the tube.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.10 [2.3/2.5]
QID: P2109 (B2109)
A centrifugal pump is taking suction from the bottom of a vented cylindrical storage tank that contains
100,000 gallons of water at 60°F. A pressure gauge at the inlet to the pump indicates 40 psig. Over
the next several days, storage tank temperature increases to 90°F with no change in tank water level
and no change in head loss in the pump suction line.
Which one of the following is the current pressure at the inlet to the pump?
A. 31.2 psig
B. 34.6 psig
C. 37.4 psig
D. 39.8 psig
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P210 (B210)
A simple bellows pressure detector is connected to a cooling water system. The detector is located in
the reactor containment and has its low pressure side vented to the containment atmosphere. Current
system pressure indication is 100 psig.
If a main steam line break raises containment pressure by 40 psig, the system pressure indication will:
(Disregard any temperature effect on the pressure detector.)
A. increase by 40 psig.
C. decrease by 40 psig.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P509 (B1310)
A cooling water system bourdon tube pressure detector is located inside a sealed building and system
pressure currently indicates 50 psig. A building ambient temperature increase of 20°F will cause a
__________ change in indicated system pressure; a building pressure increase of 20 psig will cause a
__________ change in indicated system pressure.
A. significant; significant
B. negligible; significant
C. significant; negligible
D. negligible; negligible
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P611
A bellows pressure transmitter with its low-pressure side vented to containment atmosphere is being
used to measure reactor coolant system (RCS) pressure. A decrease in the associated pressure
indication could be caused by either a containment pressure __________ or an RCS pressure
__________.
A. decrease; decrease
B. increase; increase
C. decrease; increase
D. increase; decrease
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P710 (B711)
Cooling water system pressure is being monitored by a simple diaphragm pressure detector with its
low pressure side vented to the containment. If a main steamline rupture raises containment pressure
by 20 psi, cooling water system pressure indication will: (Disregard any temperature effect on the
detector.)
A. increase by 20 psi.
B. decrease by 20 psi.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P3509 (B2912)
The pressure within a cooling water system is 100 psig, as indicated by a bourdon tube pressure
detector. The cooling water system and the detector are located inside a reactor containment
building. The pressure detector case is vented to the containment building, which is currently at
atmospheric pressure.
If a steam line rupture raises the containment building pressure by 20 psi, the cooling water system
pressure indication will... (Disregard any temperature effect on the detector.)
A. decrease to 80 psig.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P7503 (B7504)
A cooling water system pressure detector uses a bourdon tube as the sensing element. Which one of
the following explains how the indicated system pressure will be affected if a local steam leak raises
the temperature of the bourdon tube by 50°F? (Assume the cooling water system pressure does not
change.)
A. Indicated pressure will decrease because the bourdon tube will become more flexible.
B. Indicated pressure will increase because the bourdon tube will become more flexible.
C. Indicated pressure will decrease because the bourdon tube internal pressure will increase.
D. Indicated pressure will increase because the bourdon tube internal pressure will increase.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.11 [2.7/3.0]
QID: P7642 (B7642)
A cooling water system pressure detector uses a bourdon tube as the sensing element. Which one of
the following explains how the indicated system pressure will be affected if the temperature of the
bourdon tube decreases by 30°F? (Assume the cooling water system pressure does not change.)
A. Indicated pressure will decrease because the bourdon tube will become less flexible.
B. Indicated pressure will increase because the bourdon tube will become less flexible.
C. Indicated pressure will decrease because the bourdon tube internal pressure will decrease.
D. Indicated pressure will increase because the bourdon tube internal pressure will decrease.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.12 [2.8/2.9]
QID: P211 (B212)
A bourdon-tube pressure detector was indicating 50 percent of scale when it was suddenly exposed to
a high pressure transient that caused permanent strain to the bourdon tube. The detector remained
intact and actual pressure was restored to its original value.
During the pressure transient, the affected pressure indication initially went off scale high. After the
original pressure was restored, the indication was...
A. unpredictable.
C. 50 percent of scale.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.12 [2.8/2.9]
QID: P510 (B1610)
Refer to the drawing of a bellows-type differential pressure (D/P) detector (see figure below).
The spring in this detector (shown in a compressed state) has weakened from long-term use. If the
actual D/P is constant, how will indicated D/P respond as the spring weakens?
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.12 [2.8/2.9]
QID: P511
If a bourdon tube pressure detector is over-ranged sufficiently to permanently distort the bourdon tube,
subsequent pressure measurement will be inaccurate because the __________ of the detector tube will
be inaccurate.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.12 [2.8/2.9]
QID: P1011 (B2910)
A properly calibrated 0 to 100 psia diaphragm pressure detector is connected to a pressurized system;
the low pressure side of the detector is vented to the atmosphere. The detector is currently producing
a system pressure indication of 75 psia.
A. 0 psia.
B. 15 psia.
C. 60 psia.
D. 90 psia.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.12 [2.8/2.9]
QID: P2211 (B1908)
A bellows-type pressure detector with its low-pressure side vented to containment atmosphere is being
used to measure reactor vessel pressure. A decrease in the associated pressure indication will be
caused by either a containment pressure __________ or a __________.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P13
A resistance temperature detector operates on the principle that the change in the electrical resistance
of...
A. two dissimilar metals is directly proportional to the temperature change measured at their junction.
B. two dissimilar metals is inversely proportional to the temperature change measured at their
junction.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P212
A resistance temperature detector operates on the principle that the change in the electrical resistance
of a metal is __________ proportional to the change in __________.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P311
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P812
If the reference junction temperature of a thermocouple remains constant, the output voltage of the
thermocouple is __________ proportional to the __________.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P1209 (B1314)
A thermocouple temperature indication is initially 350°F. A small steam leak raises reference (cold)
junction temperature by 20°F, while the measuring junction temperature remains constant. Without
temperature compensation for the reference junction, the new temperature indication will be...
A. 310°F.
B. 330°F.
C. 370°F.
D. 390°F.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P1311
A thermocouple operates on the principle that a measurable voltage will be produced when two...
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P1412 (B2911)
A thermocouple temperature indication is initially 390°F. A small steam leak raises reference (cold)
junction temperature by 20°F, while the measuring junction temperature remains constant. Without
temperature compensation for the reference junction, the new temperature indication will be...
A. 370°F.
B. 390°F.
C. 400°F.
D. 410°F.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P1510 (B309)
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P1710 (B1710)
A thermocouple temperature indication is initially 150°F. A small steam leak raises both the
measuring (hot) junction and reference (cold) junction temperatures by 20°F. Without temperature
compensation for the reference junction, the new temperature indication will be...
A. 130°F.
B. 150°F.
C. 170°F.
D. 190°F.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P2212 (B1510)
Circuit temperature indication is initially 350°F. The reference (cold) junction temperature decreases
by 10°F, while the measuring junction temperature remains constant. Without temperature
compensation for the reference junction, the new temperature indication will be...
A. 340°F.
B. 350°F.
C. 360°F.
D. 370°F.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P2409 (B2412)
What is the purpose of the reference junction panel that is provided with many thermocouple circuits?
A. Ensures that thermocouple output is amplified sufficiently for use by temperature indication
devices.
B. Ensures that temperature changes away from the thermocouple measuring junction do not affect
thermocouple temperature indication.
C. Ensures that electrical noise in the thermocouple extension wires does not affect thermocouple
temperature indication.
D. Ensures that different lengths of thermocouple extension wires do not affect thermocouple
temperature indication.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P2711 (B2712)
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P3011 (B3013)
A thermocouple temperature indication is initially 410°F with the reference (cold) junction at 125°F.
An ambient temperature decrease lowers the reference junction temperature to 110°F, while the
measuring junction temperature remains constant. Without temperature compensation for the
reference junction, the new thermocouple temperature indication will be...
A. 380°F.
B. 395°F.
C. 410°F.
D. 425°F.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P4206 (B4206)
Given that the temperatures at the measuring and reference junctions remain constant, if a ventilation
system malfunction causes the temperature of the temperature indication panel to increase by 10°F,
indicated temperature will...
A. not be affected.
B. increase by 10°F.
C. decrease by 10°F.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P5305 (B5305)
The measuring and reference junctions are located inside the reactor containment building while the
instrument is located in a remote location outside the containment building. Thermocouple
temperature indication is initially 500°F.
An ambient temperature decrease outside the containment building lowers the temperature of the
instrument by 10°F, while the measuring and reference junction temperatures remain constant.
Thermocouple temperature indication at the lower ambient temperature will be...
A. 490°F.
B. 500°F.
C. 510°F.
D. unpredictable.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P5505 (B5507)
Refer to the drawing of a simple chromel-alumel thermocouple circuit (see figure below).
What is the effect on the thermocouple reference junctions if the chromel and alumel extension wires
from the thermocouple connection head to the reference junction panel are replaced with copper
wires?
C. The reference junctions will still be located in the reference junction panel.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P5805 (B5805)
Which one of the following is a characteristic of a resistance temperature detector but not a
thermocouple?
C. Extension leads made from relatively expensive metals or alloys are required for accurate
temperature measurement.
D. Temperature measurement relies on a sensor material property that varies directly with the change
in the measured temperature.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P6004 (B6005)
Refer to the drawing of a simple chromel-alumel thermocouple circuit (see figure below).
What is the effect on the thermocouple reference junctions if the copper extension wires from the
reference junction panel to the temperature instrument are replaced with alumel (top) and chromel
(bottom) extension wires?
B. The reference junctions will still be located in the reference junction panel.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P6305 (B6306)
Refer to the drawing of a simple chromel-alumel thermocouple circuit (see figure below).
The thermocouple, thermocouple connection head, and reference junction panel are located inside a
reactor building (RB) while the temperature instrument is located outside the RB. Thermocouple
temperature indication is initially 440°F.
A steam leak inside the RB increases the temperatures of the thermocouple connection head and
reference junction panel by 40°F, while the temperature at the measuring tip is unchanged. What is
the resulting temperature indication?
A. 400°F
B. 440°F
C. 480°F
D. 520°F
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P6905 (B6905)
A simple two-wire resistance temperature detector (RTD) is being used to measure the temperature of
a water system. Copper extension wires run from the RTD to a temperature instrument 40 feet away.
If the temperature of the extension wires decreases, the electrical resistance of the extension wires will
__________; and the temperature indication will __________ unless temperature compensation is
provided.
A. increase; increase
B. increase; decrease
C. decrease; increase
D. decrease; decrease
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P7405 (B7405)
The measuring junction temperature is currently 300°F while the reference junction temperature is
being held constant at 120°F. The thermocouple circuit is capable of indicating 32°F to 600°F and
has just been calibrated at the current conditions.
If the measuring junction temperature decreases and stabilizes at 90°F, what temperature will be
indicated?
A. 32°F
B. 60°F
C. 90°F
D. 120°F
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.13 [2.6/2.8]
QID: P7612 (B7612)
C. may be less than, greater than, or equal to the measuring junction temperature.
D. may be less than or greater than, but not equal to, the measuring junction temperature.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P213
An open circuit in a thermocouple detector causes the affected temperature indication to fail...
A. high.
B. low.
D. as is.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P312 (B310)
If shorting occurs within a resistance temperature detector, the associated indication will fail...
A. low.
B. high.
C. as is.
D. to midscale.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P414 (B208)
A resistance temperature detector (RTD) is used in a balanced bridge circuit to indicate temperature.
If the RTD develops an open circuit (bridge circuit remains intact), temperature indication will fail...
A. high.
B. low.
C. as is.
D. to midscale.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P2011 (B2009)
Refer to the drawing of a simple thermocouple circuit (see figure below) that is calibrated for a
reference junction temperature of 90°F.
Thermocouple temperature indication is currently 150°F. Indicator range is from 0°F to 2000°F.
If one of the thermocouple extension wires loosens and becomes dislodged from its terminal in the
reference junction panel, which one of the following temperature indications will result?
A. 0°F
B. 60°F
C. 90°F
D. 2000°F
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P6504 (B6506)
Because of a thermocouple temperature display failure, the millivolt output of a thermocouple circuit
is being converted to a temperature value using conversion tables. The tables are based on a
thermocouple reference junction temperature of 32°F. The actual reference junction is located in a
panel that is maintained at 120°F. Room temperature surrounding the panel is 80°F.
What adjustment must be made to the temperature value taken from the conversion tables to calculate
the actual temperature at the measuring tip of the thermocouple?
A. Add 48°F.
B. Subtract 48°F.
C. Add 88°F.
D. Subtract 88°F.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P7103 (B7106)
A resistance temperature detector (RTD) and a thermocouple (TC) are commonly used sensors for
temperature measurement. If a temperature display fails, which of the sensors, if any, has a property
that can be measured manually and converted to a temperature value with the aid of conversion tables.
A. TC only.
B. RTD only.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P7205 (B7206)
Because of a thermocouple temperature display failure, the millivolt output of a thermocouple circuit
is being converted to a temperature value using conversion tables. The tables are based on a
thermocouple reference junction temperature of 32°F. The actual reference junction is located in a
panel that is currently at 80°F.
What adjustment must be made to the temperature value taken from the conversion tables to calculate
the actual temperature at the measuring tip of the thermocouple?
A. Add 48°F.
B. Subtract 48°F.
C. Add 88°F.
D. Subtract 88°F.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.14 [2.8/2.9]
QID: P7652 (B7652)
Because of a thermocouple temperature display failure, the millivolt output of a thermocouple circuit
is being converted to a temperature value using conversion tables. The tables are based on a
thermocouple reference junction temperature of 32EF. The actual reference junction is located in a
panel that is maintained at 96EF. Room temperature surrounding the panel is 72EF.
What adjustment must be made to the temperature value taken from the conversion tables to calculate
the actual temperature at the measuring tip of the thermocouple?
A. Add 64EF.
B. Subtract 64EF.
C. Add 40EF.
D. Subtract 40EF.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.16 [2.3/2.7]
QID: P813 (B812)
What type of sensor is most commonly used to provide remote position indication of a valve that is
normally either fully open or fully closed?
A. Limit switch
B. Reed switch
C. Servo transmitter
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.16 [2.3/2.7]
QID: P1313 (B1712)
Which one of the following devices is commonly used to provide remote indication of valve position
on an analog meter in units of "percent of full open"?
A. Limit switch
B. Reed switch
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.16 [2.3/2.7]
QID: P2611
Refer to the simplified drawing of a control rod position detector (see figure below).
Coils of wire connected to an AC power supply are being used to monitor the position of a control rod
in a reactor. The coils are mounted in a column outside the reactor vessel head such that the steel
control rod drive shaft passes upward through the coils as the control rod is withdrawn. Currently, the
top of a control rod drive shaft is located between coils A and B as shown. The control rod is to be
withdrawn until the top of the control rod drive shaft is located just below coil C.
Compared to the initial coil output currents, after the control rod is withdrawn the output current of
coil A will be __________; and the output current of coil B will be __________.
A. higher; higher
B. higher; lower
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.16 [2.3/2.7]
QID: P2813 (B2811)
Refer to the simplified drawing of a control rod position detector circuit (see figure below).
A magnet on the control rod extension (or drive) shaft sequentially closes individual reed switches
mounted vertically adjacent to the control rod drive housing. A constant +5 DC volts is supplied to
the input of the resistor network at resistor R1.
A control rod is initially fully inserted such that all reed switch contacts are open; then the rod is
withdrawn until reed switch contact S1 is closed. Compared to the initial circuit currents, the current
through resistor R5 after the rod withdrawal will be __________; and the output current of the resistor
network to the amplifier will be __________.
A. lower; higher
B. lower; lower
C. higher; higher
D. higher; lower
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.16 [2.3/2.7]
QID: P2911
Reed switches are being used in an electrical measuring circuit to monitor the position of a control rod
in a reactor. The reed switches are mounted in a column above the reactor vessel such that the control
rod drive shaft passes by the reed switches as the control rod is withdrawn.
Which one of the following describes the action that causes the electrical output of the measuring
circuit to change as the control rod is withdrawn?
A. An AC coil on the control rod drive shaft induces a voltage into each reed switch as the drive shaft
passes by.
B. A metal tab on the control rod drive shaft mechanically closes each reed switch as the drive shaft
passes by.
C. The primary and secondary coils of each reed switch attain maximum magnetic coupling as the
drive shaft passes by.
D. A permanent magnet on the control rod drive shaft attracts the movable contact arm of each reed
switch as the drive shaft passes by.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.17 [3.3/3.5]
QID: P1612
A reactor is shut down at 100 cps in the source range when a loss of coolant accident occurs.
Assuming the source neutron production rate remains constant, how and why will excore source range
detector outputs change as homogeneous core voiding increases from 20 percent to 40 percent?
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.17 [3.3/3.5]
QID: P3112
Assuming that the source neutron flux level remains constant, how and why will source range detector
outputs change as homogeneous core voiding increases from 0 percent to 50 percent?
A. Increase, because the detectors will experience a higher rate of neutron interactions due to the axial
power distribution shifting toward the lower portion of the core.
B. Increase, because the detectors will experience a higher rate of neutron interactions due to
increasing neutron leakage from the core.
C. Decrease, because the detectors will experience a lower rate of neutron interactions due to a
decreasing subcritical multiplication neutron level.
D. Decrease, because the detectors will experience a lower rate of gamma interactions due to
decreasing reactor coolant attenuation.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P15 (B314)
Scintillation detectors convert radiation energy into light by a process known as...
A. gas amplification.
C. luminescence.
D. photoionization.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P16
A BF3 proportional counter is being used to measure neutron level during a reactor startup. Which
one of the following describes the method used to ensure that neutron indication is not affected by
gamma reactions in the detector?
A. Two counters are used: one sensitive to neutron and gamma and the other sensitive to gamma only.
The outputs are electrically opposed to cancel the gamma-induced currents.
B. The BF3 proportional counter measures neutron flux of such high intensity that the gamma signal
is insignificant compared to the neutron signal.
D. In a proportional counter, neutron-induced pulses are significantly larger than gamma pulses.
The detector instrumentation filters out the smaller gamma pulses.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P214 (B213)
Most of the electrons collected in a fission chamber are released as a result of ionizations caused
directly by...
A. fission fragments.
B. fission gammas.
C. fission betas.
D. fissionable materials.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P215
Which one of the following describes the reason for the high sensitivity of a Geiger-Mueller tube
radiation detector?
C. Any incident radiation event causing primary ionization results in ionization of the entire detector
gas volume.
D. Geiger-Mueller tubes are operated at relatively low detector voltages, allowing detection of low
energy radiation.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P314
A gas-filled radiation detector operating in the ion chamber region is exposed to a gamma radiation
field. If the gamma radiation field remains constant while the detector applied voltage is increased
but kept within the ion chamber region, the detector output will…
B. remain the same, because detector output is not affected by a change in voltage in this region.
D. remain the same, because the detector is already producing its maximum output.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P316
Which one of the following materials is typically installed inside an ion chamber detector that is used
for reactor power indication?
A. Polyethylene
B. Boron-10
C. Uranium-238
D. Rhodium-103
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P614
In a gas-filled radiation detector operating in the proportional region, essentially __________ of the
ions caused by incident radiation are collected; and the number of ions collected from secondary
ionizations is __________ the applied voltage.
A. all; independent of
B. none; related to
C. all; related to
D. none; independent of
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1013
Which one of the following features is typically used to enhance thermal neutron detection in a
gas-filled detector?
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1112
B. They can discriminate between gammas of differing energies in the MeV range.
C. They provide an output that is inversely proportional to the applied voltage within the
Geiger-Mueller region.
D. They undergo maximum gas amplification whenever an ion is formed in the tube.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1213
Which one of the following describes why a BF3 proportional counter can be used in the source range
to measure neutron radiation in a radiation field that also contains gamma radiation?
A. Neutrons directly ionize the BF3 gas, producing larger pulses than gammas.
B. Neutrons interacting with the BF3 gas result in the release of alpha particles which produce larger
pulses than gammas.
C. Neutrons are captured by boron-10 and produce additional neutrons that completely ionize the fill
gas in the detector.
D. The gamma radiation field is insignificant when compared to the neutron field.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1314
Which one of the following types of radiation will produce the greatest number of ions while passing
through one centimeter of air? (Assume the same initial kinetic energy for each type of radiation.)
A. Alpha
B. Beta
C. Gamma
D. Neutron
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1513 (B1514)
Which one of the following lists the two types of gas-filled radiation detectors whose outputs will be
least affected by a small variation (±10 volts) in the voltage applied to the detectors? (Assume the
applied voltage remains within normal range.)
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1613 (B913)
C. Small variations in applied voltage will result in large changes in detector output.
D. Any type of radiation that ionizes the detector gas will produce the same magnitude detector output
pulse.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1713 (B1714)
A Geiger-Mueller radiation detector is located in a radiation field consisting of beta, gamma, and fast
neutron radiation. Assuming each type of radiation enters the detector gas chamber and ionizes the
detector gas, which one of the following describes the resulting detector pulse sizes?
A. Beta radiation will produce a larger pulse size than either gamma or fast neutron radiation.
B. Gamma radiation will produce a larger pulse size than either beta or fast neutron radiation.
C. Fast neutron radiation will produce a larger pulse size than either beta or gamma radiation.
D. Beta, gamma, and fast neutron radiation will produce pulse sizes that are equal in magnitude.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1812 (B814)
A gas-filled radiation detector operating in the proportional region is exposed to a constant gamma
radiation field. If the applied voltage is increased but maintained within the proportional region, the
rate of ion collection will...
B. increase, because fewer primary ions are recombining in the detector prior to reaching the
electrodes.
C. stay approximately the same, because the ion chamber is operating at saturated conditions.
D. stay approximately the same, because all of the primary ions were already being collected at the
lower voltage.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1909 (B1113)
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P1910
Just prior to a plant outage, the power range nuclear instruments (using excore detectors) were
calibrated at 50 percent reactor power. During the outage, 25 percent of the fuel assemblies were
shuffled to reduce the power being produced at the center of the core. No fuel assemblies were
replaced.
Immediately after the outage, when the reactor is stabilized at 50 percent, indicated reactor power will
be __________ than actual power because neutron leakage from the core has __________.
A. higher; increased
B. higher; decreased
C. lower; increased
D. lower; decreased
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2013 (B313)
A gas-filled radiation detector operating in the ion chamber is exposed to a constant gamma radiation
field. If the applied voltage is increased but maintained within the ion chamber region, the rate of ion
collection will...
B. stay approximately the same, because all of the primary ions were already being collected at the
lower voltage.
C. increase, because fewer primary ions are recombining in the detector prior to reaching the
electrodes.
D. stay approximately the same, because the ion chamber is operating at saturated conditions.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2014 (B2413)
What is the effect on a gas-filled neutron detector operating in the proportional region if the detector
voltage is increased such that the detector operates closer to the high end of the proportional region?
A. Neutron-induced pulses will become so large that gamma pulse discrimination is no longer
needed, yielding a more accurate neutron count rate.
B. The positive space charge effect will increase and prevent collection of both gamma- and
neutron-induced pulses, yielding a less accurate neutron count rate.
C. A high rate of incident gamma radiation will result in the combination of multiple small
gamma-induced pulses into larger pulses. The larger combined pulses will be counted as
neutron-induced pulses, yielding a less accurate neutron count rate.
D. Detection of any single ionizing event will result in ionizing nearly the entire detector gas volume.
The resulting large pulses will prevent the detector from differentiating between radiation types,
yielding a less accurate neutron count rate.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2313 (B2613)
A gas-filled radiation detector operating in the proportional region is exposed to a constant gamma
radiation field. If the applied voltage is decreased but maintained within the proportional region, the
rate of ion collection will...
A. stay approximately the same, because all primary ions are collected as long as detector voltage
remains in the proportional region.
B. stay approximately the same, because the detector is still operating at saturated conditions.
C. decrease, because a decreased space charge around the positive electrode reduces gas
amplification.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2413 (B2414)
A gas-filled radiation detector operating in the ion chamber region is exposed to a constant gamma
radiation field. If the applied voltage is decreased but maintained within the ion chamber region, the
rate of ion collection will...
A. stay approximately the same, because all of the primary ions continue to be collected and
essentially no secondary ionizations are occurring.
B. stay approximately the same, because detector operation in the ionization chamber region is
characterized by complete ionization of the detector gas.
C. decrease, because fewer primary ionizations are occurring in the detector as detector voltage
decreases.
D. decrease, because fewer secondary ionizations are occurring in the detector as detector voltage
decreases.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2513
A nuclear power plant startup is in progress immediately following a reactor refueling outage. The
external nuclear instrumentation (NI) was calibrated at 50 percent power just prior to the refueling
outage and has not been readjusted.
If actual reactor power level is increased to 50 percent and stabilized, NI power level will indicate
__________ than actual reactor power level because, when compared to pre-outage 50 percent power
level operation, __________.
C. higher; the fission rate in the outer portion of the core has increased
D. lower; the fission rate in the outer portion of the core has decreased
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2613 (B1114)
Which one of the following describes the reason for the high sensitivity of a gas-filled radiation
detector operating in the Geiger-Mueller region?
B. Geiger-Mueller detectors are longer than other types of radiation detectors, resulting in greater
detector surface area.
C. The detector output is inversely proportional to the applied voltage within the Geiger-Mueller
region.
D. High detector voltage allows differentiation between the various radiation types.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2713
During a refueling outage, the fuel assemblies were reconfigured to reduce the radial power peak at the
center of the core while maintaining the same rated thermal power. Excore power range detectors
were calibrated at 50 percent power just prior to the outage.
How will indicated reactor power compare to actual reactor power when the nuclear power plant is
stabilized at 50 percent power following the outage?
A. Indicated reactor power will be higher than actual reactor power due to increased core neutron
leakage.
B. Indicated reactor power will be higher than actual reactor power due to decreased core neutron
leakage.
C. Indicated reactor power will be lower than actual reactor power due to decreased core neutron
leakage.
D. Indicated reactor power will be lower than actual reactor power due to increased core neutron
leakage.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P2913 (B414)
Which one of the following statements describes the operation of a gas-filled radiation detector
operating in the proportional region?
A. The number of ions collected from both primary and secondary ionizations is independent of the
applied voltage.
B. Essentially all of the ions from primary ionizations are collected; the number of ions collected
from secondary ionizations is independent of the applied voltage.
C. The number of ions collected from both primary and secondary ionizations varies directly with the
applied voltage on a logarithmic scale.
D. Essentially all of the ions from primary ionizations are collected; the number of ions collected
from secondary ionizations varies directly with the applied voltage on a logarithmic scale.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P3413
A boron trifluoride (BF3) detector (proportional counter) is normally used to monitor only source
range core neutron level. How will the detector and source range count rate indication be affected if
normal detector high voltage is inadvertently applied during reactor operation in the power range?
A. The BF3 gas will become completely ionized and source range indication will stabilize at a
constant low value.
B. The BF3 gas will become completely ionized and source range indication will stabilize at a
constant high value.
C. The detector electrodes will become exposed to an extremely high neutron flux and cause a false
high reading on the source range indication.
D. The detector electrodes will become exposed to an extremely high gamma flux and cause a false
high reading on the source range indication.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P3906 (B3907)
A beta particle and an alpha particle enter and cause ionization in a gas-filled radiation detector
operating in the Geiger-Mueller region. Which one of the following accurately compares the
amplitude of the detector pulses caused by each type of radiation?
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P4506 (B4507)
A nuclear power plant has been shut down for one month. A portable gas-filled radiation detector is
needed to monitor shutdown reactor core neutron level from a location outside the reactor vessel.
The detector must be able to distinguish between ionizations caused by gamma and neutron radiation.
Which region(s) of the gas-filled detector characteristic curve is/are acceptable for operation of the
detector?
B. Proportional region is acceptable, and Ion Chamber region also may be usable.
C. Ion Chamber region is acceptable, and Geiger-Mueller region also may be usable.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P4806 (B4807)
Quench gases are added to gas-filled radiation detectors that operate in the __________ region; the
quench gases prevent a single ionization event from causing __________ in the detector gas volume.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P4906 (B4907)
Which one of the following contains the pair of radiation detector types that are the most sensitive to
low-energy beta and/or gamma radiation?
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P5206 (B5207)
A beta particle and an alpha particle with equal kinetic energies cause ionization in a gas-filled
radiation detector. The detector is operating in the ion chamber region of the gas ionization curve.
Which one of the following describes the amplitudes of the detector pulses caused by each type of
radiation?
C. The amplitudes of both pulses will be approximately equal for all detector voltages in the ion
chamber region.
D. The amplitudes of both pulses will be approximately equal for all detector voltages in the ion
chamber region, as well as all detector voltages outside the ion chamber region.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P5306 (B5307)
Which one of the following types of radiation detectors is generally not used for measuring a
high-intensity beta and gamma radiation field because of a relatively long detector recovery time, or
dead time, following each ionization event.
A. Geiger-Mueller
B. Ion chamber
C. Proportional
D. Scintillation
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P5606 (B5607)
A proportional detector with pulse height discrimination circuitry is being used in a constant field of
neutron and gamma radiation to provide source range neutron count rate indication. Assume that the
pulse height discrimination setpoint does not change.
If the detector voltage is increased but maintained within the proportional region, count rate indication
will increase because...
A. a single neutron- or gamma-induced ionizing event will result in multiple pulses inside the
detector.
B. the ratio of the number of neutron-induced pulses to gamma-induced pulses inside the detector will
increase.
C. the positive space charge effect will increase and promote the collection of both gamma- and
neutron-induced pulses.
D. all detector pulses will increase in amplitude and previously uncounted gamma pulses will be
added to the total count rate.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P6006 (B6007)
Which one of the following types of radiation detectors uses a gas volume for radiation detection and
will typically produce the weakest output signal if all of the detectors are placed in the same gamma
radiation field?
A. Geiger-Mueller
B. Ion chamber
C. Proportional counter
D. Scintillation
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P6206 (B6206)
Which one of the following types of radiation detectors is typically the least accurate in determining
the dose rate to a human body from an unspecified source of radiation?
A. Geiger-Mueller
B. Ion chamber
C. Proportional counter
D. Scintillation
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P6405 (B6407)
A fission chamber neutron detector is located in a constant neutron radiation field and is initially
operating in the proportional region. If the voltage applied to the detector is changed such that the
detector operates in the ion chamber region, the rate of neutron interactions in the detector will
__________; and the amplitude of each neutron-induced detector pulse will __________.
A. increase; increase
B. decrease; decrease
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P6505 (B6507)
Which one of the following describes the positive space charge effect associated with a gas-filled
radiation detector?
A. Multiple detector pulses result from a single ionization event because positive ions form a cloud
around the negative electrode, which increases the electric field strength, thereby initiating
secondary ionizations.
B. Multiple detector pulses result from a single ionization event because positive ions form a cloud
around the positive electrode, which increases the electric field strength, thereby initiating
secondary ionizations.
C. The pulse amplitude resulting from an ionization event is reduced because positive ions form a
cloud around the negative electrode, which reduces the electric field strength, thereby limiting
secondary ionizations.
D. The pulse amplitude resulting from an ionization event is reduced because positive ions form a
cloud around the positive electrode, which reduces the electric field strength, thereby limiting
secondary ionizations.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P6906 (B6906)
In which usable region(s) of the gas-filled detector ionization curve is the pulse height resulting from
the detection of a 1 MeV beta particle the same as a 5 MeV alpha particle?
A. Geiger-Mueller only.
C. Proportional only.
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7206 (B7207)
Which one of the following personal radiation monitoring devices can be charged with DC voltage to
“zero” the device prior to use?
A. Film badge
B. Alarming dosimeter
C. Thermoluminescent dosimeter
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7505 (B7507)
A Geiger-Mueller detector with a Apancake@ probe (often called a frisker) is being used to monitor
personnel leaving a radiologically controlled area. The probe is equipped with a mica window.
Two individuals have radioactive skin contamination—one individual with only alpha emitters, and
the other with only beta emitters. Both types of radiation are being emitted at the same rate. The
same percentage of each type of radiation enters the probe’s detection chamber and causes ionization.
Which one of the following describes the detector=s count rate response to the alpha and beta
radiation?
C. The count rate will be the same for both types of radiation.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7506
Just prior to a plant outage, the power range nuclear instruments (using excore detectors) were
calibrated at 50 percent reactor power. During the outage, 40 fuel assemblies from the center of the
core were exchanged with 40 higher enriched fuel assemblies from the outer portions of the core. No
other fuel assemblies were affected.
Immediately after the outage, when the reactor is stabilized at 50 percent power, indicated reactor
power will be __________ than actual reactor power because neutron leakage from the core has
__________.
A. lower; decreased
B. lower; increased
C. higher; decreased
D. higher; increased
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7613 (B7613)
A proportional detector with pulse height discrimination circuitry is being used in a constant field of
neutron and gamma radiation to provide source range neutron count rate indication. Assume the
pulse height discrimination value does not change.
If the detector voltage is decreased significantly, but maintained within the proportional region, the
detector count rate indication will __________; and the detector will become __________ susceptible
to the positive space charge effect.
A. decrease; less
B. decrease; more
ANSWER: A.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7662 (B7662)
A gas-filled radiation detector that operates in the Geiger-Mueller region of the gas ionization curve is
being used in a constant radiation field. If the detector=s operating voltage is increased by 50 volts
while remaining in the Geiger-Mueller region, the detector’s count rate indication will __________;
and the ability of the detector to detect gamma radiation will __________.
A. increase; improve
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7672 (B7672)
A proportional detector with pulse height discrimination circuitry is being used in a constant field of
neutron and gamma radiation to provide source range neutron count rate indication. Assume the
pulse height discrimination value does not change.
If the detector voltage is increased significantly, but maintained within the proportional region, the
detector count rate indication will __________; and the detector will become __________ susceptible
to the positive space charge effect.
A. increase; less
B. increase; more
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.18 [2.6/2.8]
QID: P7701 (B7701)
A fission chamber detector is initially operating in the proportional region to measure neutron flux in
the source range. If the voltage applied to the detector is changed such that the detector is operating in
the ion chamber region, the detector will produce __________ pulses; and will experience a
__________ positive space charge effect.
A. larger; larger
B. larger; smaller
C. smaller; larger
D. smaller; smaller
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P216 (B214)
Which one of the following describes a characteristic of a self-reading pocket dosimeter (SRPD)?
D. SRPDs hold their charge indefinitely when removed from a radiation field.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P714 (B714)
Which one of the following types of radiation is the major contributor to the dose indication on a
self-reading pocket dosimeter (SRPD)?
A. Alpha
B. Beta
C. Gamma
D. Neutron
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P5706 (B5707)
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P6806 (B6807)
A nuclear plant worker normally wears a thermoluminescent dosimeter (TLD) or similar device for
measuring radiation exposure. When a self-reading pocket dosimeter (SRPD) is also required, where
will the SRPD be worn and why?
A. Below the waist near the TLD to measure radiation from the same source(s).
B. Below the waist away from the TLD to measure radiation from different sources.
C. Above the waist near the TLD to measure radiation from the same source(s).
D. Above the waist away from the TLD to measure radiation from different sources.
ANSWER: C.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P7633 (B7633)
A Geiger-Mueller detector with a Apancake@ probe (often called a frisker) is being used to monitor
workers leaving a radiologically controlled area for contamination. The probe is equipped with a
mica window. The background detector count rate is 20 cpm.
As one individual’s shoe is scanned, the detector reading increases to 200 cpm. When a sheet of
paper is placed between the probe and the shoe, the detector reading decreases to 60 cpm. Which one
of the following is indicated by the decrease in the detector reading?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P7653 (B7653)
A Geiger Mueller detector with a Apancake@ probe (sometimes called a frisker) is being used to
monitor for skin contamination. During frisking, the probe is more likely to detect contamination if
the probe is held __________ than one-half inch from the skin; and is moved __________ than two
inches per second.
A. farther; faster
B. farther; slower
C. closer; faster
D. closer; slower
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.19 [3.1/3.3]
QID: P7691 (B7691)
A nuclear plant worker normally wears a thermoluminescent dosimeter (TLD) or similar device for
measuring whole body radiation exposure. When a self-reading pocket dosimeter (SRPD) is also
required for whole body monitoring, where will the SRPD be worn and why?
B. Near the TLD to measure radiation affecting the same part of the body.
D. Away from the TLD to measure radiation affecting a different part of the body.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.20 [2.5/2.7]
QID: P1114
Which one of the following describes the ion collection that occurs in a proportional counter, such as a
BF3 detector?
A. A fraction of the ions created by primary ionizations are collected. No secondary ionizations take
place.
B. Virtually all of the ions created by primary ionizations are collected. No secondary ionizations
take place.
C. Virtually all of the ions created by primary ionizations along with a fraction of the ions created by
secondary ionizations are collected.
D. Virtually all of the ions created by primary and secondary ionizations are collected.
ANSWER: D.
TOPIC: 191002
KNOWLEDGE: K1.20 [2.5/2.7]
QID: P1514 (B511)
A. upscale.
B. downscale.
C. as is.
D. to midscale.
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.20 [2.5/2.7]
QID: P3714
During reactor power operation, a reactor coolant sample is taken and analyzed. Which one of the
following lists three radionuclides that are all indicative of a fuel cladding failure if detected in
elevated concentrations in the reactor coolant sample?
ANSWER: B.
TOPIC: 191002
KNOWLEDGE: K1.20 [2.5/2.7]
QID: P6406
During power operation, a reactor coolant sample is taken and analyzed. Which one of the following
lists three nuclides that are all indicative of a possible fuel cladding failure if found to be at elevated
concentrations in the reactor coolant sample?
ANSWER: C.