BS en 50600-2-3-2014
BS en 50600-2-3-2014
BS en 50600-2-3-2014
Information technology —
Data centre facilities and
infrastructures
Part 2-3: Environmental control
BS EN 50600-2-3:2014 BRITISH STANDARD
National foreword
This British Standard is the UK implementation of EN
50600-2-3:2014.
The UK participation in its preparation was entrusted to Technical
Committee TCT/7, Telecommunications - Installation requirements.
A list of organizations represented on this committee can be
obtained on request to its secretary.
This publication does not purport to include all the necessary
provisions of a contract. Users are responsible for its correct
application.
© The British Standards Institution 2014. Published by BSI Standards
Limited 2014
ISBN 978 0 580 81135 7
ICS 35.020; 35.110; 35.160
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 31 October 2014.
Amendments issued since publication
Date Text affected
BS EN 50600-2-3:2014
English Version
This European Standard was approved by CENELEC on 2014-09-01. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
© 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Contents Page
Foreword ........................................................................................................................................................... 4
Introduction ....................................................................................................................................................... 5
1 Scope ....................................................................................................................................................... 7
2 Normative references............................................................................................................................. 7
3 Terms, definitions and abbreviations .................................................................................................. 7
3.1 Terms and definitions ............................................................................................................................... 7
3.2 Abbreviations ............................................................................................................................................ 9
4 Conformance .......................................................................................................................................... 9
5 Environmental control within data centres ......................................................................................... 9
5.1 General ..................................................................................................................................................... 9
5.2 Environmental control of data centre spaces ......................................................................................... 10
6 Availability ............................................................................................................................................ 14
6.1 General ................................................................................................................................................... 14
6.2 Design options by space......................................................................................................................... 14
6.3 Environmental control system capacity planning with respect to expansion .......................................... 18
6.4 Environmental control system capacity planning with respect to resilience ........................................... 18
7 Physical security .................................................................................................................................. 18
7.1 General ................................................................................................................................................... 18
7.2 Access .................................................................................................................................................... 18
8 Energy efficiency enablement ............................................................................................................ 18
8.1 General ................................................................................................................................................... 18
8.2 Measurement of temperature ................................................................................................................. 19
8.3 Measurement of relative humidity ........................................................................................................... 20
8.4 Measurement of air pressure .................................................................................................................. 21
8.5 Coolant flow rates ................................................................................................................................... 21
8.6 Heat removal .......................................................................................................................................... 21
8.7 Outside air............................................................................................................................................... 22
8.8 Provision of alarms ................................................................................................................................. 22
8.9 Measurement requirements by Granularity Level................................................................................... 22
Bibliography .................................................................................................................................................... 27
BS EN 50600-2-3:2014
EN 50600-2-3:2014 –4–
Foreword
This document (EN 50600-2-3:2014) has been prepared by CLC/TC 215 “Electrotechnical aspects of
telecommunication equipment”.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European Commission and
the European Free Trade Association.
BS EN 50600-2-3:2014
–5– EN 50600-2-3:2014
Introduction
The unrestricted access to internet-based information demanded by the information society has led to an
exponential growth of both internet traffic and the volume of stored/retrieved data. Data centres are housing
and supporting the information technology and network telecommunications equipment for data processing,
data storage and data transport. They are required both by network operators (delivering those services to
customer premises) and by enterprises within those customer premises.
Data centres need to provide modular, scalable and flexible facilities and infrastructures to easily
accommodate the rapidly changing requirements of the market. In addition, energy consumption of data
centres has become critical both from an environmental point of view (reduction of carbon footprint) and with
respect to economical considerations (cost of energy) for the data centre operator.
b) security level;
c) physical size;
The needs of data centres also vary in terms of availability of service, the provision of security and the
objectives for energy efficiency. These needs and objectives influence the design of data centres in terms of
building construction, power distribution, environmental control and physical security. Effective management
and operational information is required to monitor achievement of the defined needs and objectives.
This series of European Standards specifies requirements and recommendations to support the various
parties involved in the design, planning, procurement, integration, installation, operation and maintenance of
facilities and infrastructures within data centres. These parties include:
4) installers, maintainers.
At the time of publication of this European Standard, the EN 50600 series will comprise the following
standards:
— EN 50600-1, Information technology — Data centre facilities and infrastructures — Part 1: General
concepts;
— EN 50600-2-1, Information technology — Data centre facilities and infrastructures — Part 2-1: Building
construction;
— EN 50600-2-2, Information technology — Data centre facilities and infrastructures — Part 2-2: Power
distribution;
— EN 50600-2-3, Information technology — Data centre facilities and infrastructures — Part 2-3:
Environmental control;
BS EN 50600-2-3:2014
EN 50600-2-3:2014 –6–
— EN 50600-2-4, Information technology — Data centre facilities and infrastructures — Part 2-4:
Telecommunications cabling infrastructure;
— EN 50600-2-5, Information technology — Data centre facilities and infrastructures — Part 2-5: Security
systems;
— EN 50600-2-6, Information technology — Data centre facilities and infrastructures — Part 2-6:
Management and operational information.
The inter-relationship of the standards within the EN 50600 series is shown in Figure 1.
EN 50600-2-X standards specify requirements and recommendations for particular facilities and
infrastructures to support the relevant classification for “availability”, “physical security” and “energy efficiency
enablement” selected from EN 50600-1.
This European Standard addresses the environmental control facilities and infrastructure within data centres
together with the interfaces for monitoring the performance of those facilities and infrastructures in line with
EN 50600-2-6 (in accordance with the requirements of EN 50600-1).
This series of European Standards does not address the selection of information technology and network
telecommunications equipment, software and associated configuration issues.
BS EN 50600-2-3:2014
–7– EN 50600-2-3:2014
1 Scope
This European Standard addresses environmental control within data centres based upon the criteria and
classifications for “availability”, “security” and “energy efficiency enablement” within EN 50600-1.
This European Standard specifies requirements and recommendations for the following:
a) temperature control,
d) particulate control,
e) vibration,
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 50600-1, Information technology — Data centre facilities and infrastructures — Part 1: General concepts
EN 50600-2-5 1), Information technology — Data centre facilities and infrastructures — Part 2-5: Security
systems
For the purposes of this document, the terms and definitions in EN 50600-1 and the following apply.
3.1.1
adiabatic cooling
adiabatic cooling is a cooling system that is using the evaporative cooling principle to reduce the air
temperature
3.1.2
absolute humidity
quantity of water vapour in a given volume of air, expressed by mass
———————
3.1.3
access floor
system consisting of completely removable and interchangeable floor panels that are supported on
adjustable pedestals connected by stringers to allow the area beneath the floor to be used by building
services
3.1.4
comfort environmental controls
controls which produce an environment which is appropriate for the effective performance of personnel in a
given space
3.1.5
dew point
temperature at which the water vapour in a gas begins to deposit as a liquid or ice, under standardized
conditions
3.1.6
exhaust air temperature
the temperature of the air leaving the data centre building or the temperature of the air leaving the heat load
3.1.7
fresh air cooling
cooling system that uses the external air to cool the data centre either directly or indirectly
3.1.8
heat load
thermal power that is produced
3.1.9
information technology equipment
equipment providing data storage, processing and transport services together with equipment dedicated to
providing direct connection to core and/or access networks
3.1.10
outdoor air temperature
temperature of the air measured outside of the data centre building
3.1.11
relative humidity
ratio, expressed as a percentage, of the vapour pressure of water vapour in moist air to the saturation vapour
pressure with respect to water or ice at the same temperature
3.1.12
return air temperature
temperature of the air re-entering the environmental control system e.g. the air handling unit
3.1.13
supply air temperature
temperature of the air entering the IT equipment
BS EN 50600-2-3:2014
–9– EN 50600-2-3:2014
3.1.14
ventilation
supply of air motion in a space by circulation or by moving air through the space
Note 1 to entry: Ventilation can be produced by any combination of natural or mechanical supply and exhaust.
Note 2 to entry: Such systems may include partial treatment such as heating, relative humidity control, filtering or
purification, and, in some cases, evaporative cooling.
3.2 Abbreviations
For the purposes of this document, the abbreviations given in EN 50600-1 and the following apply.
4 Conformance
a) it shall feature an environmental control solution that meets the requirements of Clauses 4 and 5;
b) it shall feature an approach to physical security in relation to the environmental control solution that
meets the requirements of Clause 6;
c) it shall feature an energy efficiency enablement solution that meets the requirements of the relevant
Granularity Level of Clause 7;
5.1 General
The environmental control system is one of the most important parts of the data centre infrastructure.
Excessive variations of temperature or relative humidity can directly affect the functional capability of the
data centre and its infrastructures.
The functional elements of the environmental control system are divided into primary and secondary
elements.
Primary elements relate to the mechanical generation of temperature controlled fluids. Secondary elements
relate to the distribution of fluids generated by the primary elements. See Table 1 for examples of these
elements.
Some environmental systems combine the function of primary and secondary elements.
BS EN 50600-2-3:2014
EN 50600-2-3:2014 – 10 –
It should be noted that a Class 1 environmental control system does not necessarily contain any of these
elements.
5.1.2 Requirements
The approach taken for the design of the environmental control system shall take into account available
technology, physical security and data centre availability.
The design of the environmental control system and the selection and installation of functional elements shall
take into consideration the effect of vibration on the data centre spaces.
The design of the environmental control system and the selection and installation of functional elements shall
take into consideration the effect of friction and/or obstruction in the pathways for temperature controlled
fluids. Operational controls shall be provided to ensure no degradation of fluid flow due to changes in the
pathways.
During the design phase the requirement for the number of air changes per unit time and air pressure shall
be established.
In all data centre spaces the requirements for filtration shall be considered.
In all spaces where there is a risk of damage to static-sensitive equipment from electro-static discharge the
relative humidity shall be maintained in accordance with the instructions of the supplier of the equipment to
be accommodated. Where no information exists or where the equipment manufacturer is not specified, a
minimum dew point of 5,5 °C shall be maintained.
Where direct fresh air cooling solutions are chosen the requirements analysis and the resulting methodology
of monitoring and control is of prime importance. In these circumstances particular consideration shall be
given to the control of contaminants.
For guidance on the ventilation requirements of activated gaseous suppression systems see EN 50600-2-5.
5.1.3 Recommendations
Opportunities for reductions in energy consumption exist where wider tolerances of temperature and relative
humidity can be tolerated in defined data centre spaces. It is recommended to use cooling units with
integrated vibration decoupling for all rotating parts (e.g. fan, compressor) or low vibration parts. If the
cooling units or other external components with rotating parts are not equipped with integrated vibration
decoupling the whole unit should be decoupled.
No specific requirements.
BS EN 50600-2-3:2014
– 11 – EN 50600-2-3:2014
No specific requirements.
Temperature shall be maintained in accordance with the instructions of the supplier of the equipment to be
accommodated. Where no information exists or where the equipment manufacturer is not specified the
temperature shall be maintained above 0 °C and should be above 10 °C.
Adequate ventilation shall be provided for combustion and for radiator cooling.
Where the manufacturer is not known at the time of design the maximum temperature shall be 35 °C.
Temperature and the presence of particulates (smoke, carbon monoxide and fuel) shall be monitored. See
EN 50600-2-5 for further information regarding monitoring of smoke.
Heater elements in the generator engine may provide sufficient heat for this space, where this is not possible
thermostatically controlled heaters shall be applied.
The fuel storage system shall be protected against continuous sub-zero ambient temperatures to avoid fuel
solidification.
NOTE The availability of generators can be adversely affected by cold (<10 °C) or poor quality fuel and can be
improved through the installation of crankcase heaters.
Temperature shall be maintained in accordance with the instructions of the supplier of the equipment to be
accommodated unless the system has been de-rated for operation at higher ambient temperatures. Where
no information exists or where the equipment manufacturer is not specified the temperature shall be
maintained above 0 °C and should be above 10 °C.
The maximum ambient temperature shall not exceed the maximum temperature specified by the equipment
manufacturer unless the system has been de-rated for operation at higher ambient temperatures. Where the
manufacturer is not known at the time of design the maximum temperature shall be 35 °C.
Filtration against dust shall be provided, if required, in accordance with the instructions of the supplier of the
equipment to be accommodated.
Forced air cooling of the transformer should be considered at the design phase where this would represent
an improvement in transformer efficiency.
Temperature and the presence of smoke particulates shall be monitored. See EN 50600-2-5 for further
information regarding monitoring of smoke.
Temperature shall be maintained in accordance with the instructions of the supplier of the equipment to be
accommodated. Where no information exists or where the equipment manufacturer is not specified the
temperature shall be maintained above 0 °C and should be above 10 °C.
The maximum ambient temperature shall not exceed the maximum temperature specified by the supplier of
the equipment to be accommodated unless the system has been de-rated for operation at higher ambient
temperatures. Where the manufacturer is not known at the time of design the maximum temperature shall be
40 °C.
Temperature controlled air extraction shall be provided, where the facility’s redundancy so requires
ventilation shall be by redundant fans each rated to the maximum load expected. Temperature and relative
humidity shall be monitored.
Temperature and relative humidity shall be maintained in accordance with the instructions of the supplier of
the equipment to be accommodated. Where this is not known in advance temperature shall be maintained
between 10 °C and 30 °C with relative humidity maintained between 20 % and 70 %.
Where the data centre is supported by a single telecommunications space, or by multiple, non-resilient
telecommunications spaces, the space(s) shall have a single path resilient environmental control system (for
examples see 6.2.5.3).
If external to computer room space the requirements of 5.2.7 shall be applied; if contained within the
computer room space then the requirements of 5.2.9 shall be applied.
The computer room space is the most important space from an environmental control perspective.
An analysis examining the balance between tight environmental controls versus high performance energy
saving controls with reference to the type of IT equipment to be accommodated shall be performed by the
owner of the data centre. The results of this analysis shall be compared with the business model for the data
centre.
Environmental controls shall be applied that maintain the following parameters within limits defined by the
requirements of the analysis described above:
a) operating temperature;
b) relative humidity;
c) air quality:
BS EN 50600-2-3:2014
– 13 – EN 50600-2-3:2014
1) particulate content;
2) bacterial content;
3) gaseous contaminants.
The designer of the environmental control system shall assess the impact of the failure of the system on the
data centre infrastructure.
Temperature shall be maintained in accordance with the instructions of the supplier of the equipment to be
accommodated. Where no information exists or where the equipment manufacturer is not specified the
temperature shall be maintained above 0 °C and should be above 10 °C.
The maximum ambient temperature shall not exceed the maximum temperature specified by the supplier of
the equipment to be accommodated unless the system has been de-rated for operation at higher ambient
temperatures. Where the manufacturer is not known at the time of design the maximum temperature shall be
40 °C.
If the mechanical space accommodates electrical equipment then the requirements of 5.2.10 apply.
Basic environmental controls shall be applied (temperature and relative humidity); temperature and relative
humidity shall be monitored.
Temperature shall be maintained in accordance with the instructions of the supplier of the equipment to be
accommodated. Where no information exists or where the UPS equipment is not specified the temperature
shall be maintained between 15 °C and 35 °C (non-condensing); where storage batteries are included in the
UPS space the requirements of 5.2.15.3 shall be applied.
BS EN 50600-2-3:2014
EN 50600-2-3:2014 – 14 –
Air conditioning, rated for the maximum heat output of the UPS system, shall be provided if the external
ambient conditions preclude the use of filtered fresh air.
Closed loop monitoring for temperature and relative humidity shall be provided.
Waste heat should be used to pre-heat standby generator plant of the UPS system where possible.
The environmental controls required for the accommodation of diesel rotary UPS are as stated in 5.2.4.
5.2.15.3 Batteries
Where UPS storage batteries are located away from the UPS equipment that they serve, temperature shall
be controlled in accordance with the manufacturer’s instructions. Where no information exists or where the
UPS equipment is not specified the temperature shall be maintained at (20 ± 2) °C.
Ventilation shall be provided to avoid hydrogen accumulation. Where mechanical extraction is used the fans
shall be redundant and fed from separate secondary power supply points.
6 Availability
6.1 General
The environmental control system shall be designed to support the Availability Class chosen following the
risk assessment undertaken in accordance with the availability classification defined EN 50600-1.
This standard defines four Classes of Environmental Control Systems of increasing availability (Class 2,
Class 3, Class 4 and Enhanced Class 4).
6.2.1 General
All systems in data centres utilize the concept of ‘N’ when planning the load and the redundancy, e.g. N, N+1,
2N or 2(N+1), etc. where N is seldom equal to 1. To maximize the utilization of capital plant, and so minimize
energy standing losses, the designer shall take into account the increased redundancy for running at partial
load when choosing how to specify the configuration of ‘N’.
It should be noted that Class 1 as defined by EN 50600-1 has no meaning within this standard and no
specific requirements exist.
a) Class 2: Single path (no resilience) - a single path system without resilience is suitable where it is
acceptable that a single fault in an element in the path will result in loss of functional capability and
where maintenance requires the load to be shut-down.
b) Class 3: Single path (resilience provided by redundancy of components) - a single path system with
resilience is suitable where it is required that a single fault in the path will not result in loss of
functional capability because sufficient redundant components in each sub-assembly are included
and where routine planned maintenance does not require the load to be shut-down. Major faults may
BS EN 50600-2-3:2014
– 15 – EN 50600-2-3:2014
result in unplanned load shutdown and some maintenance routines may require planned load
shutdown.
d) Enhanced Class 4: Multi-path resilience, concurrent repair/operate, and fault tolerant solution - an
active/active multi-path system is suitable where it is required that no single fault in any path will
result in loss of functional capability and where planned maintenance does not require the load to be
shut-down. A major fault in one path will not result in unplanned load shutdown and no maintenance
routines will require planned load shutdown by use of the other active path. Each path serves to act
as the concurrent maintenance enabler as well as avoiding any recovery of service time (mean
downtime of zero) after a major fault. The designer should aim to have no common-point-of-failure
between the two paths, including segregated routing, physical compartmentalisation and fire-rated
enclosures. Each path does not require N+1 redundancy unless the client specifies that during
maintenance or repair (planned or unplanned) where one path is removed from service the
remaining path has to retain a higher degree of resilience than N. This is most valid when each path
is modular and contains more than three elements. It is assumed in this standard that during system
maintenance or repair, unless specified by the client, a degraded level of resilience is permitted.
The following spaces are not subject to a classification for the design of environmental control systems in
relation to availability:
b) personnel entrances,
c) docking/loading bays,
e) transformer space,
g) telecommunications space(s),
h) electrical space(s),
i) mechanical space(s),
k) office space(s),
If external to computer room space there are no scalable design options for this space. If contained within
the Computer Room space the requirements of 6.2.4 shall be applied.
6.2.4.1 General
The computer room space is the most important space from an environmental control perspective.
An example of a chilled water cooling system would comprise a single (or N) compressor based chiller,
single primary pump and single (or N) air-conditioning modules in the critical space - all being fed from a
single path electrical power system that need not include redundancy.
An example of a fresh-air cooling system with adiabatic cooling would comprise a single (or N) inlet fan,
single (or N) supplementary cooling coil, single (or N) adiabatic cooling spray system and, where required,
powered louvres - all being fed from a single path electrical power system that need not include redundancy.
The supplementary cooling coils would feed N heat rejection systems.
An example of a chilled water cooling system would comprise a redundant (N+1) compressor based chiller
system, redundant (N+1) primary pumps and redundant (N+1) air-conditioning modules in the critical space -
all being fed from a single path electrical power system that includes N+1 redundancy in key components.
Some passive and inherently reliable sub-systems (e.g. the chilled water piping) would not have redundancy
built-in and a failure in such an element would be considered major and would usually result in a loss of
cooling.
An example of a fresh-air cooling system with adiabatic cooling would comprise a redundant array (N+1) of
inlet fans, a redundant array (N+1) of supplementary cooling coils, single (or N) adiabatic cooling spray
system and, where required, powered louvres - all being fed from a single path electrical power system that
includes N+1 redundancy in key components.
Where water is used for humidification or adiabatic cooling then a redundant source, or on-site storage of
sufficient volume to meet the clients’ resilience requirements, shall be included in the design. All pumps and
water treatment plant (where required) shall have N+1 redundancy in key components.
An example of a chilled water cooling system would comprise a redundant (N+1) compressor based chiller
system, dual (N+1) primary pumps and redundant (N+1) air-conditioning modules in the critical space - all
being fed from a single path electrical power system that includes N+1 redundancy in key components but
also has a passive delivery path (with automatic or manual changeover switches). All passive sub-systems
(e.g. the chilled water piping) shall also have in-built path redundancy where a failure in such an element
would usually result in a loss of cooling albeit with a rapid (manual) substitution of the active path with the
passive path.
An example of a fresh-air cooling system with adiabatic cooling would comprise a redundant array (N+1) of
inlet fans, a redundant array (N+1) of supplementary cooling coils, a redundant array (N+1) of adiabatic
cooling spray systems and, where required, powered louvres - all being fed from a single path electrical
power system that includes N+1 redundancy in key components but also has a passive delivery path (with
automatic or manual changeover switches). Heat transfer from the supplementary cooling coils to the
external heat rejection system shall have N+1 redundant topology. If the heat rejection path is common then
a passive path shall be provided.
BS EN 50600-2-3:2014
– 17 – EN 50600-2-3:2014
Where water is used for humidification or adiabatic cooling then a redundant source, or on-site storage of
sufficient volume to meet the clients’ resilience requirements, shall be included in the design. All pumps and
water treatment plant (where required) shall have N+1 redundancy in key components and a passive path for
delivery of water with manual intervention.
The environmental control system shall be designed such that loss of functional capability is limited to 10 min
in any one operating year.
6.2.4.5 Enhanced Class 4: Multi-path resilience, concurrent repair/operate, and fault tolerant
solution
An example of an active/active (2N) chilled water cooling system would comprise two segregated and
entirely separate (N) compressor based chiller systems, each with (N) primary pumps, separate (N) piping
systems and non-redundant (N) air-conditioning modules in the critical space - each system fed from its own
single path electrical power system that may or may not include N+1 redundancy in key components.
An example of a fresh-air cooling system with adiabatic cooling would comprise two cooling systems each
with a non-redundant array (N) of inlet fans, an array (N) of supplementary cooling coils, an array (N) of
adiabatic cooling spray systems and, where required, powered louvres - each system being fed from its own
single path electrical power system that may or may not include N+1 redundancy in key components. Heat
transfer from the supplementary cooling coils to the external heat rejection system need only have N
redundant topology. The heat rejection path shall not be common.
Where water is used for humidification or adiabatic cooling then two separate and redundant sources, or dual
on-site storage of sufficient volume to meet the clients’ resilience requirements, shall be included in the
design. If there is only one primary source of water then dual storage systems shall be included with as much
water capacity as needed to match the on-site autonomy of diesel fuel provision for the emergency electrical
generators. All pumps, piping system and water treatment plant (where required) shall have 2N redundancy,
each system fed by separate power systems.
6.2.5.1 General
The requirements of this clause apply where the UPS equipment is not accommodated in the computer room
space.
The UPS space shall be ventilated/cooled by a single air-conditioning terminal or fresh-air fan that is rated to
supply the cooling capacity equal to the maximum possible power losses in the UPS and not exceed the
peak temperature supported by the chosen UPS, usually in the order of 40°C. A single failure in the cooling
plant exposes the UPS to over-temperature and shut-down/bypass with associated risk to the critical load.
The UPS space shall be ventilated/cooled by an N+1 redundant air-conditioning terminal array or fresh-air
fans that are rated at N to supply the cooling capacity equal to the maximum possible power losses in the
UPS and not exceed the peak temperature supported by the chosen UPS. A single failure in the cooling
plant components shall not expose the UPS to over-temperature and shut-down/bypass with associated risk
to the critical load.
The UPS space shall be ventilated/cooled by two separate air-conditioning terminal array’s or fresh-air fan
arrays that are each rated to supply the cooling capacity equal to the maximum possible power losses in the
BS EN 50600-2-3:2014
EN 50600-2-3:2014 – 18 –
UPS and not exceed the peak temperature required by the chosen UPS. A complete failure in the cooling
plant of one path shall not expose the UPS to over-temperature and shut-down/bypass with associated risk
to the critical load. The two systems shall not share a common power system.
6.2.5.5 Enhanced Class 4: Multi-path resilience, concurrent repair/operate, and fault tolerant
solution
Not applicable.
During the design phase the use of modular solutions providing capacity for the expected load with respect
to time shall be considered.
Where resilience is provided by multiple CRACs consideration shall be given to the number of CRACs and
the fan speed at which each CRAC is operated.
The design of the system shall accommodate a situation where all CRACs run at minimum fan speed. Where
capacity allows consideration shall be given to switching a proportion of CRACs to standby mode, ready to
start up upon failure of a running CRAC.
7 Physical security
7.1 General
Based on the security classification defined following the risk assessment undertaken in accordance with
EN 50600-1, EN 50600-2-3 provides requirements and recommendations (with optional implementations as
required) in relation to the following aspects with the design, planning and installation of the environmental
control facilities and infrastructures.
7.2 Access
All controls and equipment comprising the environmental control system shall be in areas of Protection
Class 3 or above as specified in EN 50600-2-5.
Where pathways are routed in areas of a lower Protection Class they shall be monitored for unauthorized
access. See EN 50600-2-4.
8.1 General
Based on the energy efficiency enablement granularity level defined following the risk assessment
undertaken in accordance with EN 50600-1, this clause provides requirements and recommendations (with
optional implementations as required) in relation to the following aspects with the design, planning and
installation of the environmental control facilities and infrastructures. 8.2 and 8.3 define requirements and
recommendations for measurement by parameter. 8.9 summarizes these requirements by granularity level.
BS EN 50600-2-3:2014
– 19 – EN 50600-2-3:2014
In all cases external temperature shall be measured and monitored. An external temperature sensor should
be used, located away from any building exhausts and from direct sunlight. The output from this sensor shall
be fed into the control system for the data centre. For data centres of Class 2 and above the feedback from
the external temperature sensor shall be automatic.
For Level 2 and above an additional sensor should be employed to provide resilience.
Computer room temperature shall be monitored. In an air-cooled environment air temperature varies by
location. Where liquid-cooled enclosures are used the temperature of the liquid coolant shall be monitored.
Temperature sensors should not be placed in areas of high turbulence and should be so placed as to
establish thermal gradient.
The requirements analysis shall determine which of the following air temperatures shall be measured:
The supply air temperature is the temperature at the intake to the IT equipment.
Level 1:
Supply air temperature shall be measured with a single sensor placed in proximity to the IT equipment.
Where used, cold aisle temperature shall be measured at a single location per aisle.
Level 2:
Cold aisle temperature shall be measured at every five cabinets or racks in every aisle.
Level 3:
Supply air temperature shall be measured by one sensor per equipment cabinet or rack located in
accordance with the cooling method chosen.
Two sensors per equipment cabinet or rack located at the front 1/3 of the way from the top and 1/3 up from
the base are recommended.
BS EN 50600-2-3:2014
EN 50600-2-3:2014 – 20 –
Level 1:
Return air temperature shall be measured with a single sensor placed in proximity to the intake of the cooling
equipment. Where there are multiple systems, e.g. CRAC units, the temperature shall be measured at each
unit.
Where used, hot aisle temperature shall be measured at a single location per aisle.
Level 2:
Return air temperature shall be measured with a single sensor placed in proximity to the intake of the cooling
equipment and a sensor at the rear of one cabinet or rack. Where there are multiple systems, e.g. CRAC
units, the temperature shall be measured at each unit.
Where used, hot aisle temperature shall be measured at every five cabinets or racks in every aisle.
Level 3:
Return air temperature shall be measured with a single sensor placed in proximity to the intake of the cooling
equipment and at one sensor per equipment cabinet or rack located in accordance with the cooling method
chosen.
Two sensors per equipment cabinet or rack located at the rear 1/3 of the way from the top and 1/3 up from
the base are recommended.
The cold aisle temperature is the temperature of the supply air in the cold aisle. This temperature shall be
measured in order to regulate the cold aisle.
The hot aisle temperature is the exhaust temperature in the hot aisle. The temperature can either be
measured directly at each hot aisle or centrally at the air conditioning components.
Level 1:
Where used, hot aisle temperature shall be measured at a single location per aisle.
Level 2:
Where used, hot aisle temperature shall be measured at every five racks in every aisle.
Level 3:
Hot aisle temperature shall be measured at one sensor per equipment rack, located in accordance with the
cooling method chosen. Two sensors per equipment rack, located at the rear 1/3 of the way from the top and
1/3 up from the base are recommended.
In all cases external relative humidity shall be measured and monitored. An external relative humidity sensor
should be used, located away from any building exhausts and from direct sunlight. The relative humidity
sensor should be co-located with the temperature sensor (see 8.2.1). The output from this sensor shall be
BS EN 50600-2-3:2014
– 21 – EN 50600-2-3:2014
fed into the control system for the data centre. For data centres of Class 2 and above the feedback from the
external relative humidity sensor shall be automatic.
For Level 2 and above an additional, combined relative humidity and temperature sensor should be
employed to provide resilience.
Level 1:
Computer room relative humidity shall be measured at the same locations as for supply air temperature.
Level 2:
Computer room relative humidity shall be measured at the same locations as for supply air temperature.
Level 3:
As per Level 2.
It is recommended to install a dew point sensor where relative humidity is measured, or to calculate a dew
point from temperature and relative humidity data.
Where an access floor is installed, the design of the environmental control system shall consider the
requirements for the maintenance of static pressure under the access floor. The requirements for airflow at
all points across the access floor shall be determined.
If one part of the cooling concept is the securing of a constant pressure under the access floor through fan
speed control of the CRAC unit fans, the differential pressure between the room and the access floor shall be
measured. The associated sensors shall be positioned in locations where reasonable values can be obtained
and shall ensure that all areas of the access floor are monitored.
Where the design of the environmental control system relies on the movement of fluids, coolant flow meters
shall be installed.
It is recommended that coolant mass flow is measured in order to use the data for monitoring and thus
improve the operation of the system.
The location of these sensors shall be determined in accordance with the design requirements of the system.
The design of the environmental control system shall determine the requirement to measure or calculate the
heat removed in order to use the data for monitoring and optimization of the cooling units.
Additionally the design shall determine the requirement to quantify total energy use of the cooling system.
BS EN 50600-2-3:2014
EN 50600-2-3:2014 – 22 –
Where outside air is drawn into the data centre space(s) for environmental control purposes, sensors for
temperature and relative humidity shall be placed at the air inlet.
Note that air quality would also be measured at this point in support of contamination protection (see 5.2.9).
Provision of alarms should consist of two upper and two lower set points against any environmental
parameter to provide warning and critical alarms.
Granularity Level
Requirement
Level 1 Level 2 Level 3
Supply Air Temperature Single sensor in Two sensors in proximity One sensor per cabinet
proximity to IT equipment to IT equipment or rack
One sensor per cold One sensor every 5
aisle cabinets or racks in a
cold aisle
Return Air Temperature Single sensor in One sensor in proximity One sensor in proximity
proximity to intake of to intake of cooling to intake of cooling
cooling equipment equipment and a single equipment and a single
sensor at rear of one sensor at rear of each
or
cabinet or rack cabinet or rack
One sensor per hot aisle
or
One sensor every 5
cabinets or racks in a hot
aisle
Relative humidity As supply air As supply air As supply air
temperature temperature temperature
External relative humidity One sensor Two sensors Two sensors
and temperature
Air Pressure As required As required As required
Coolant Flow As required As required As required
Heat Removal As required As required As required
Outside Air As required As required As required
BS EN 50600-2-3:2014
– 23 – EN 50600-2-3:2014
Annex A
(normative)
Recirculation of cooling air inside the cabinet or rack can lead to active equipment overheating. Air will
always take the path of least resistance. To avoid overheating of the active equipment and to increase the
efficiency of the cooling system, blanking panels are required to fill gaps in cabinet or racks where active
equipment has been removed or is not installed. Hot exhaust air from the active equipment would otherwise
circulate through the gap back to the air inlet of the active equipment or cold air will pass through the cabinet
or rack without cooling the active equipment (bypass).
A.2.1 General
If a data centre comprises an access floor system, the cooled air is brought to the cabinet or racks/active
equipment through the access floor and perforated access floor tiles. If the perforated floor tiles are placed
haphazardly, a mixing of different temperature profiles is possible and this leads to very inefficient operation
of cooling equipment.
The height of the access floor has a major influence on the efficiency of the air circulation. Usually the
access floor contains cabling, piping and is designated as the “supply air duct” for the cold air. A certain
obstruction free area is necessary for a proper supply of cold air to any area of the room. The correct sizing
of the access floor height helps to maintain the correct pressure under the floor, to avoid velocity pressure
effects and to maintain a uniform air distribution across the floor plate. That means, if pipe work, cabling or
any other obstructions are placed under the floor, the total height of the access floor shall be increased
accordingly. Also, any fixtures (like beams, pillars, etc.) should be avoided. Table A.1 provides the required
height of unobstructed space under the floor as a “free height of access floor”. Generally, it depends on the
room size, the heat density, the total amount of air and the cooling solution chosen.
In general, perforated floor tiles shall only be placed at positions where cold air is required to cool the IT
equipment. Perforated floor tiles shall not be placed in areas with high air velocity (e.g. close to CRAC units)
to avoid room air being drawn into the access floor due to possible underpressure caused by high air
velocity. The position and the quantity of perforated access floor tiles have to be in line with the design and
the actual/required total air flow.
Example: An access floor tile has a specific characteristic - that means a certain air flow across the tile
3
creates a certain pressure drop. If the total design airflow of the IT equipment is e.g. 50 000 m /h and a
3
perforated floor tile with an air flow of 500 m /h with a pressure drop of 20 Pa is chosen, a total number of
100 perforated floor tiles has to be installed. If the real airflow requirement is lower for whatever reason, e.g.
3
30 000 m /h, it has to be ensured that the chosen access floor tile is operated at its specific characteristic.
That means the total number of perforated tiles has to be reduced to 60. If the original quantity of 100
remains at the reduced airflow, the static pressure under the access floor will also be reduced (according to
perforated tile curve) and this can lead to an uneven air distribution and eventually lack of cooling in some
areas.
The use of perforated floor tiles with dampers has two major advantages:
No replacement of solid tiles in case of a change of IT equipment with different air flow requirements. The
number of perforated floor tiles remains unchanged during the lifetime of a data centre but all of them need
to be adjusted to the required air flow.
It is possible to operate with different adjustments according to the actual needs of the IT equipment and
therefore to vary the amount of air in different areas of the data centre.
A.3.1 General
The computer room is equipped with cabinet or racks placed in pairs of opposing rows with the front of each
row facing each other, called an aisle configuration. The aisles (alleys/passages) are designated as cold
aisle which have floor mounted air distribution grilles to provide cold air in front of the cabinet or rack. The hot
aisle is normally not equipped with floor mounted perforated tiles. This concept helps to reach a certain level
of separation between cold supply air and warm/hot return air. The temperature difference between these
two air flows is increased and the performance (and efficiency) of the cooling equipment is improved.
Unused or unwanted openings in an access floor concept lead to air flow leakages and therefore inefficient
air circulation. On the one hand cooled air can circulate back to the cooling equipment without taking a
sufficient amount of heat from the IT-equipment (short circuit air) and fan power is wasted. On the other hand
a certain overpressure under the access floor is required to realize an even air distribution throughout the
whole computer room and to make sure that each perforated floor tile gets the correct amount of air. This
means that all openings in the access floor have to be closed and/or sealed. Within cabinets openings
should be no larger than necessary and should use gaskets, brushes, or other methods for sealing.
A.3.3.1 General
The object of all of the philosophies mentioned below is the full separation of supply and return air. This
separation leads to a higher temperature difference between hot return and cold supply air, thus increasing
the efficiency of the cooling equipment and therefore the efficiency of the data centre in general.
BS EN 50600-2-3:2014
– 25 – EN 50600-2-3:2014
The cabinet or racks are placed in rows front to front. The cold aisle in between the cabinet or racks will be
covered on the top and at the end of the rows. A full separation between supply and return air is achieved.
Cold air will be either supplied through the access floor or through row cooling units into the contained cold
aisle. Hot return air leaves the cabinet or racks into the room and is then fed back to the cooling equipment.
The room itself will be at a high temperature level.
The cabinet or racks are positioned in rows back to back. The hot aisle between the cabinet or racks will be
covered on the top and the end of the rows. Therefore, a full separation between return and supply air is
achieved. The hot return air out of the hot aisle will be supplied to the cooling equipment either via a duct
system or to integrated cooling units in the cabinet or rack row. Cold supply air then will be supplied into the
room and therefore the room itself will be at low temperature level.
Cold supply air enters the cabinet or rack through the access floor directly to a contained area at the front of
the cabinet or rack. Hot return air leaves the cabinet or rack directly into the room. A full separation between
supply and return is achieved, and the room itself is at a high temperature level.
Cold supply air enters the cabinet or rack through the room. Hot return air leaves the cabinet or rack through
a duct and suspended ceiling back to the cooling unit. A full separation between supply and return is
achieved, and the room itself is at a low temperature level.
Cold supply air enters the cabinet or rack through the access floor directly to a contained area at the front of
the cabinet or rack. Hot return air leaves the cabinet or rack through a duct and a suspended ceiling back to
the cooling equipment. A full separation between supply and return is achieved, and the room itself is at
average temperature level.
A heat exchanger and fans are integrated in the rear door of the cabinet. Hot air from the back of the IT
equipment is cooled as it passes through the door back to the room. A full separation between supply and
return is achieved, the room is at low temperature level.
The cabinet or rack doors are closed and a heat exchanger and fans are integrated in the cabinet or rack,
the whole cooling circuit is completely independent from the room. The cold supply air is brought directly in
front of the active equipment and the hot return air is taken from the back of the cabinet or rack to the heat
exchanger. The room itself is at average temperature level.
BS EN 50600-2-3:2014
EN 50600-2-3:2014 – 26 –
Annex B
(informative)
B.1 General
The control systems are used to regulate and control the building management systems of the data centre.
The control modules are usually incorporated directly into the systems and/or are grouped together in one
place as external regulators. The concept of redundancy shall also take into account the control system.
A fixed default air temperature is set for the control of the exhaust air temperature. The air conditioning
varies the supply air temperature by variably adjusting the flow rate of the cooling agent. The supply air
temperature to the computer room spaces is not constant using this control concept.
A fixed default air temperature is set for the control of the supply air temperature. This technique varies the
flow rate of the supply air. Yet the exhaust air temperature cannot be regulated, which may lead to an
overheating of the IT spaces in some scenarios.
The advantages of each of the above regulation concepts are combined by this concept in order to eliminate
their detrimental effects. The aim is to maintain a stable supply temperature and to keep the exhaust air
temperature as constant as possible. The flow rate of the cooling agent and the flow rate of the air are
adjusted accordingly. In order to prevent the formation of hot spots, the differential pressure between the hot
and cold aisles can be evaluated and included in the control of the airflows.
The relative humidity in the computer room space is always measured in the supply air and is then regulated
to obtain a defined relative humidity value at the IT components.
Control of the proportion of the outside air drawn into the environmental control system for the computer
room space is performed by the air handling system. Sensors provide information related to the temperature,
relative humidity and air quality allowing a use/not use decision to be made. The air exchange rate is
adjusted accordingly.
BS EN 50600-2-3:2014
– 27 – EN 50600-2-3:2014
Bibliography
EN 378-2, Refrigerating systems and heat pumps — Safety and environmental requirements — Part 2:
Design, construction, testing, marking and documentation
EN 779, Particulate air filters for general ventilation — Determination of the filtration performance
EN 15243, Ventilation for buildings — Calculation of room temperatures and of load and energy for buildings
with room conditioning systems
EN 50272-2, Safety requirements for secondary batteries and battery installations — Part 2: Stationary
batteries
EN 50600-2-1, Information technology — Data centre facilities and infrastructures — Part 2-1: Building
construction
EN 50600-2-4 2), Information technology — Data centre facilities and infrastructures — Part 2-4:
Telecommunications cabling infrastructure
EN 50600-2-6 3), Information technology — Data centre facilities and infrastructures — Part 2-6:
Management and operational information
prEN ISO 14644-13), Cleanrooms and associated controlled environments — Part 1: Classification of air
cleanliness by particle concentration (ISO/DIS 14644-1)
prEN ISO 14644-23), Cleanrooms and associated controlled environments — Part 2: Specifications for
monitoring and periodic testing to prove continued compliance with ISO 14644-1 (ISO/DIS 14644-2)
ETS 300 119-1, Environmental Engineering (EE) European telecommunication standard for equipment
practice Part 1: Introduction and terminology
ETS 300 019-1-3, Environmental Engineering (EE) Environmental conditions and environmental tests for
telecommunications equipment Part 1-3: Classification of environmental conditions Stationary use at
weather-protected locations
ETS 300 119-2, Environmental Engineering (EE) European telecommunication standard for equipment
practice Part 2: Engineering requirements for racks and cabinets
ETS 300 119-3, Environmental Engineering (EE) European telecommunication standard for equipment
practice Part 3: Engineering requirements for miscellaneous racks and cabinets
ETS 300 119-4, Environmental Engineering (EE) European telecommunication standard for equipment
practice Part 4: Engineering requirements for subracks in miscellaneous racks and cabinets
ETS 300 119-5, Environmental Engineering (EE) European telecommunication standard for equipment
practice Part 5: Thermal management
IEC 60050-212:2010, International Electrotechnical Vocabulary — Part 212: Electrical insulating solids,
liquids and gases
IEC 60050-705:1995, International Electrotechnical Vocabulary — Part 705: Radio wave propagation
———————
About us Revisions
We bring together business, industry, government, consumers, innovators Our British Standards and other publications are updated by amendment or revision.
and others to shape their combined experience and expertise into standards We continually improve the quality of our products and services to benefit your
-based solutions. business. If you find an inaccuracy or ambiguity within a British Standard or other
The knowledge embodied in our standards has been carefully assembled in BSI publication please inform the Knowledge Centre.
a dependable format and refined through our open consultation process.
Organizations of all sizes and across all sectors choose standards to help Copyright
them achieve their goals. All the data, software and documentation set out in all British Standards and
other BSI publications are the property of and copyrighted by BSI, or some person
Information on standards or entity that owns copyright in the information used (such as the international
We can provide you with the knowledge that your organization needs standardization bodies) and has formally licensed such information to BSI for
to succeed. Find out more about British Standards by visiting our website at commercial publication and use. Except as permitted under the Copyright, Designs
bsigroup.com/standards or contacting our Customer Services team or and Patents Act 1988 no extract may be reproduced, stored in a retrieval system
Knowledge Centre. or transmitted in any form or by any means – electronic, photocopying, recording
or otherwise – without prior written permission from BSI. Details and advice can
Buying standards be obtained from the Copyright & Licensing Department.
You can buy and download PDF versions of BSI publications, including British
and adopted European and international standards, through our website at Useful Contacts:
bsigroup.com/shop, where hard copies can also be purchased. Customer Services
If you need international and foreign standards from other Standards Development Tel: +44 845 086 9001
Organizations, hard copies can be ordered from our Customer Services team. Email (orders): orders@bsigroup.com
Email (enquiries): cservices@bsigroup.com
Subscriptions
Subscriptions
Our range of subscription services are designed to make using standards
Tel: +44 845 086 9001
easier for you. For further information on our subscription products go to
Email: subscriptions@bsigroup.com
bsigroup.com/subscriptions.
With British Standards Online (BSOL) you’ll have instant access to over 55,000 Knowledge Centre
British and adopted European and international standards from your desktop. Tel: +44 20 8996 7004
It’s available 24/7 and is refreshed daily so you’ll always be up to date. Email: knowledgecentre@bsigroup.com
You can keep in touch with standards developments and receive substantial
Copyright & Licensing
discounts on the purchase price of standards, both in single copy and subscription
format, by becoming a BSI Subscribing Member. Tel: +44 20 8996 7070
Email: copyright@bsigroup.com
PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
revised or replaced.
To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email bsmusales@bsigroup.com.