Power Systems Fault Analysis
Power Systems Fault Analysis
Fault Analysis
Objective
Upon completion of this chapter you will be able to:
Represent the entire power system in a single circuit based on pu values.
Determine the sequence components for an unbalanced phasor system.
Determine the fault current for Symmetrical Faults i.e. 3 phase faults.
Determine the sequence currents and fault current for unsymmetrical faults.
Determine the ratings of Circuit Breakers to be employed in the system.
Understand the methods of Neutral Grounding.
Introduction
There can be abnormal conditions in the power system due to flashover of the lines initiated
by a lightning stroke or insulation failure or through accidental faulty operation. Fault
Analysis is done to predict the conditions existing in the system under faulty conditions so
that effective protection system can be designed. Protection system must be able to handle
large currents under faulty operation and isolate the faulty part from the system. Majority of
faults are unsymmetrical in nature that makes the system unbalanced and hence require
special tools for analysis like Symmetrical Components as discussed in this chapter.
By this method we can avoid representing each and every component by its equivalent
circuit. Otherwise, in a practical Power System consisting of 100’s of Transmission Lines, it
would be nearly impossible to read the topology of the Power System.
The equivalent circuit of each and every component used in Power System is given below,
Generator (G)
Generator can be modeled as a constant voltage source behind synchronous impedance
which consists of Armature Resistance and Synchronous Reactance.
Usually, Xs R so we neglect the resistance of generator.
1
Power Systems (Fault Analysis)
Transformer (T)
Magnetizing current & core loss are neglected. So, the shunt elements in equivalent circuit
are not shown.
V2 N2
Transformation ratio, k or
V N1
1
If the entire circuit is referred to primary side then it looks like as shown in first circuit below
or if it is referred to secondary side then it looks like as shown in second circuit below,
3
Power Systems (Fault Analysis)
Transmission line Tx
Usually The Transmission Lines are modeled using Nominal-π Model as shown below,
Synchronous Motor
The model for Synchronous Motor is similar to Synchronous Generator with slight
modifications as shown below,
Static Load
Static Load means Stationery Load which may consist of Resistors and Inductors,
During fault analysis, the static load can be neglected from the circuit whereas the dynamic
load especially Synchronous Motor must be considered in fault analysis.
The equivalent circuit for Single Line Diagram given below,
Power Systems (Fault Analysis)
Here numbers of loops to be solved are more (3) if current is represented in absolute
parameters. This number increases rapidly when we talk about practical power systems
consisting of 100’s of buses. The number of equations are more due to Transformers in the
Power System.
To avoid this we represent Network in PU. For basics of pu system refer Chapter-1.
Transformer in PU
Since, KVA rating on both sides of Transformer is same
V1I1 V2I2
V2 I1
k (Transformation ratio)
V1 I2
Here, ‘1’ subscript represents the primary side of Transformer and ‘2’ subscript represents
secondary side of Transformer.
Base Values
The base MVA on both sides of Transformer is same but voltage and current bases are
different and are not independent on both the sides but are related by Transformation Ratio.
If primary side base voltage is V1 base
Z1 Z2 / k
2
Z01
pu Z1 base
Equivalent Impedance on secondary side is,
Z02 Z1k Z2
2
It can be expressed in pu as,
Z 2 Z1 / k
2
Z 2 Z1 / k
2
Z1 Z 2 / k
2
Z02 pu
k2Z1 base
Z2 base Z1 base
Z02 pu Z01 pu
But Z1 pu Z2 pu
So transformer coupling can be removed
Z01 pu Z02 pu
Z2
Z01 Z1 ; Z02 Z2 Z1k
2
2
k
Z01 Z02 if k 1
The PU values on primary & secondary are so chosen that PU voltage are same &
transformation ratio of Transformer will become unity, so Transformer coupling factor k can
be removed.
Thus, the equivalent circuit for Power System shown in last example is,
Hence, one only one equation needs to be solved. Hence, number of network equation
reduces & analysis of network becomes easy.
Solved Examples
Problem: Draw reactance diagram for the system whose Single Line Diagram is given below,
Gen-1 30MVA, 10.5kV, x’’=1.6Ω
Gen-2 15MVA, 6.6kV, x’’=1.2Ω
Gen-3 25MVA, 6.6kV, x’’=0.56Ω
T1 15MVA, 11/33kV, x=15.2Ω/ph on HT side
T2 15MVA, 33/11kV, x=15.2Ω/ph on HT side
TL 20.5 Ω/ph
LA 40MW, 11kV, 0.9pf lag
LB 40MW, 6.6kV, 0.85 pf lag
30
G2 : 1.2 =0.2975 pu
11
2
30
G3 : 0.56 =0.1388 pu
11
2
Since, Transformer impedance is referred on High Voltage side so we will use Secondary
Base for T1 and primary base for T2 i.e. base values in Transmission Line section of power
system.
30
T1, T2 : 15.2 =0.4187 pu
33
2
Power Systems (Fault Analysis)
30
TL : 20.5 =0.5647 pu
33
2
Based on these values if we interconnect the impedances to form reactance diagram, it looks
like,
Note: We have neglected the static loads as is done for the case of Fault Analysis.
2400
2
100
2pu
G1: 0.2 2
2400
10
2
2400
G2: 0.2 2
100
1pu
2400 20
For Transformers we need to take care to choose both old and new base on same side of
Transformer i.e. either primary or secondary.
2
5000
2
100
T2: 0.1 0.136pu
4800 80
2
Since, Transmission Line Impedance is given in ohms we can directly convert it to pu using
base values as,
100 103
TL : 50 j200 0.054 j0.217pu
9600
2
Symmetrical components
In a balance system, analysis can be done on a single phase basis. The knowledge of voltage
and current in one phase is sufficient to determine the voltages and current in other two
phases. But when the system is unbalanced, the voltages, currents and the phase impedance
are in general unequal. Unbalanced system operation can result due to unsymmetrical fault,
ex. line to line fault, double line to ground or single line to ground. Unbalanced operation
may also result when loads are unbalanced three phase voltages and currents are
transformed into three sets of balanced voltages and currents called symmetrical
components.
If the currents and voltages are related by constant impedances, the system is said to be
linear and the principle of super position applies. The voltage response of the linear system
to the unbalanced currents can be determined by considering the separate responses of the
individual elements to the symmetrical components of the currents. The system elements of
Power Systems (Fault Analysis)
interest are the machines, transformers, transmission lines and loads connected to delta or
star configurations.
Fortesque’s Theorem
In an unbalanced set of phasors the system may be resolved in (n-1) balanced system for
different phase sequence & one zero phase sequence.
This is applicable for only voltage & currents.
Unbalanced Quantities
Va Positive sequence = Va1 , Vb1 , Vc1
Vb Negative sequence = Va2 , Vb2 , Vc2
Vc Zero sequence = Va0 , Vb0 , Vc0
Vc Vc1 Vc2
Vc0
2 0 0
1 1 1120 1240 0
Power Systems (Fault Analysis)
2
Vb1 Va1 , Vc1 Va1 , Vb0 Va0
2
Vb2 Va2 , Vc2 Va2 , Vc0 Va0
For voltages
Va 1 12 1 Va0
V 1
b V a1
1 V
2
V a2
c
V A V
abc 012
a a
Va0 1 1 1 Va
V 1 1 V
2
Va1 b
a2 3 1 2 Vc
For currents
aI012 A 1 Iabc
The sum of three line voltages is always zero & hence zero sequence component of line
voltage is always
1 zero.
V V V V 0
3
ab 0ab bc ca
The sum of line currents in a 3 , 4 wire system is equal to current in neutral wire.
1 1
I I I I I
a0 a b c n
3 3
For 3 , 3 wire system (neutral is not grounded)
Ia0 0 In 0
Power Systems (Fault Analysis)
If the system is unbalanced then both +ve and –ve sequence components will exist. If the
sum of voltage and current is non-zero then there is an existence of zero sequence
components.
T * 1 12 1 1 1 1 1 0 0
A A 1 2 3 0 1 0
2 1
1
1
2
0 0 1
T * T *
S
abc
V012 3I I012 3 V012 I012
a a a a
abc * * *
S 3 V I V I V I
a1 a1 a2 a2 a0 a0
abc
S 3S012
The disadvantage with these symmetrical components is that the transformation matrix A
is not power invariant or is not orthogonal or unitary.
Solved Examples
Phase voltages in kV
Va=0 ; 11 0 11 0
1.325 109.84 kV ; V 1.325109.84 kV
Vb 3
c
3
0 0
Vab Va Vb 0 1.325 109.84 =1.32570.2 p.u.
0 0 0
Vbc Vb Vc 1.325 109.84 1.325109.84 = 2.49 90 p.u.
0 0
Vca Vc Va 1.325109.84 0 = 1.325109.84 p.u.
Line voltages in kV
Va 11 0 11 0
11 0
1.32570.2 kV ; Vbc 2.49 90 kV ; 1.325109.84 kV
b
3 3 Vca= 3
Solution: 0
I0 I1 I2 3 j4 5 53.13 p.u.
abc * * *
S 3 V I V I V I
a1 a1 a2 a2 a0 a0
abc 0 0 0 0
S 3 0.1 553.13 1.2 553.13 0.4 553.13 10.553.13 p.u.
abc 100 0 0
S 10.553.13 MVA 35053.13 MVA /phase
3
Pa 350cos53.13 210MW and Qa 350sin53.13 280 MVAR
Sequence Network
Neutral current,
In Ia Ib Ic
In 3Ia0
Va1 Ia1Z1
Ia2 V
; Ib2 ; Ic2 Zc2
Va2 Vb2
Z Z
2 2 2
Va2 Ia2 Z2
Ia0 V V
; Ib0 Zb0 ; Ic0 Zc0
Va0
Z
0 0 0
In 3Ia0
Vn 3Ia0 Zn
Power Systems (Fault Analysis)
Zn Va0 Ia0 Z 0
3Zn
Ia0 0
Ia Ica Iab
Ib Iab Ibc
Ic Ibc Ica
Power Systems (Fault Analysis)
So, no zero sequence current in line of -winding but zero sequence current can exist in
phase of -winding
Star grounded -winding will provide closed path for zero sequence currents whereas
star ungrounded winding will not provide any closed path for zero sequence currents.
In star grounded network, zero sequence currents can flow in both phase & line.
Kp , of each winding is same
Kd
Va , Vb , are unbalanced terminal voltage
Vc
Inducted emf Ea ,Eb ,Ec are balanced
Power Systems (Fault Analysis)
0
As rotor rotates in a single direction and windings are displaced in space by 120 so the
emf induced are balanced and always positive sequence, there are no negative or zero
sequence induced emf.
Ea1 Eb1 Ec1 Ea
Ef
loaded condition we use Ef
Per phase electrical equivalent circuit
Va1 Ea1 Ia1Z1
Xd2 Xq
2
Z j
Power Systems (Fault Analysis)
Generally,
For salient pole alternator X X => Z Z
d q 2 1
Zero sequence currents flowing in stator windings produce mmfs which are in time phase
0
but space displaced by 120
Sinusoidal space mmf produced by each of the three stator windings at any instant at a
point on the axis of the stator would be zero.
No armature reaction flux effect on main field. So stator is presented with only leakage
reactance
Z0 jXl leakage reactance
Z0 Z2 Z1
Va Ea1 Ia1 Z1
1
3 3
Ia2 Z2
V
Va0 0
positive, negative and zero sequence impedances are same and equal to leakage impedance
of the transformer
ZT1 ZT2 ZT0 jXl
Xl Leakage reactance of the transformer windings.
The positive & negative sequence networks are independent on nature of winding, nature
of grounding used, flow of zero sequence currents.
1.
2.
3.
4.
Power Systems (Fault Analysis)
5.
6.
7.
8.
Or
Power Systems (Fault Analysis)
9.
10.
11.
12.
Power Systems (Fault Analysis)
13.
14.
V Z Z Z s Ic
c m m
Vabc Zabc Iabc (4)
Iabc A I012
Vabc A V012
012
A V Z abc A I012
1 1 1 Zm Z m 1 1 1 Zs 2Zm 0 0
Z
1s 2
Z012 Z Z 2 0 Z Z 0
Z 1
1 3 m s m s m
2
1
2
Z m Z m Zs Z s Z m
1
0 0
Va1 Zs Zm Ia1
Va2 Zs Zm Ia2
Z0 Z1 or Z2
Generally
Z0 2.5Z1to 3.5Z1
Typical value
Z0 3Z1
The zero sequence currents are in phase and flow through the line conductors only if a
return conductor is provided.
If the mutual impedances in between transmission line are not same then positive,
negative & zero sequence network coupled together, at the time there is no advantage
obtained from symmetrical components. Symmetrical components give the advantage in
analysis of balanced network unbalanced voltages and currents.
Solved Examples
Draw all sequence networks. Assume equal positive, negative and zero sequence impedances
for all components.
Voltage drop across the transmission line is given by the following equation:
a Zs Zm Zm ia
V
V Z Z Z
b m s m i b
V Z Z
c m m Z s ic
Shunt capacitance of the line can be neglect. If the line has positive sequence impedance of
15 and zero sequence in impedance of 48, then the values of Zs and Zm will be
Problem: For the network shown in figure the zero sequence reactance’s in p.u. are
indicated. The zero sequence driving point reactance of the node 3 is
Solution: The zero sequence per unit reactance diagram of the given single line diagram is
as shown in figure.
Power Systems (Fault Analysis)
Solution: As both sides of the circuit are grounded we can take each branch is considered
as one circuit
Ea
I 10 00
Xa 0
5 90 A
a Eb j2
I 10 900 0
b 3.33 180 A
Xb j3
Ec
I 10 1200 0
Xc 2.530 A
c
j4
1
Positive sequence current, I1 =
(Ia + α Ib + α2 Ic)
3
1
I1 =
3 0 0 0 0
5 90 1120 3.33 180 1 240 2.5 30
0
3.510 81
0
Power Systems (Fault Analysis)
Problem: Three identical star connected resistors of 1.0 p.u. are connected to an unbalanced
3 phase supply. The load neutral is isolated. The symmetrical components of the line
voltages in p.u. Calculations are with the respective base values, the phase to neutral
sequence voltages are?
Where Van1, Vbn1, Vcn1, are +ve sequence phase voltages & Van2, Vbn2, Vcn2 are ve sequence
phase voltages
Vab1, Vab2 are +ve sequence & ve sequence Line voltages respectively
From the above phase or diagrams
0
Line voltage Leads phase voltage by 30 in +ve sequence,
0
Line voltage Lags phase voltage by 30 in ve sequence
Van1 X 300 , V
1 an2
Y 2 30
0
Here X & Y are in per unit system hence are same for line & phase values
Fault Analysis
Balanced three phase faults may be analyzed using an equivalent single phase circuit. With
asymmetrical three phase faults, the use of symmetrical components help to reduce the
complexity of the calculations.
Fault analysis is usually carried out in per-unit quantities (similar to percentage quantities) as
they give solutions which are somewhat consistent over different voltage and power ratings,
and operate on values of the order of unity.
Occurrence of SC fault
LG-70%
LL-15%
LLG-10%
LLL & LLLG-5%
Equivalent circuit
Power Systems (Fault Analysis)
Vm Vm
k 1 sin sin
Z
Put the value of k1 in eq. (b)
Vm Rt/L
Vm
i (t) e sin( ) sin(t )
f
Z Z
DC offset current AC steady state fault currnet
Power Systems (Fault Analysis)
Vm
is (t)
sin t
Z
Initial Symmetrical RMS fault current or Steady state RMS fault current
V
ISym. m VRMS
2 Z
Z
Power Systems (Fault Analysis)
component
m
e )
sin(
Rt/L
22
2 Z
V 2
IAsy. V m
Z
V 2
IAsy. m
e Rt/L
sin(
Z 1
IAsy.
) 2
ISym. 2 e sin(2 Rt/L
1
)
2
Imm
max [doubling effect ]
2Vm
Z
Im 2 steady state value of peak current
Practically, Im 2V
Zm
Xf Xdw Xa
Sub transient period will exist up to the time whenever the transient flux in the damper
winding becomes zero.
Transient Period
It starts from the instant when damper winding flux becomes zero.
Power Systems (Fault Analysis)
1
d- axis transient reactance of alternator Xd 1 1
Xl
Xa Xf
Transient period exists up to the time whenever transient field flux becomes zero.
Hence, reactance varies continuously with time whereas we have discretized it and divided it
into three levels.
The decay in symmetrical fault current is due to increase in reactance as time passes.
Since the fault is symmetrical it means the 3-phase systems is balanced, so there are no
negative or zero sequence currents are present.
Hence, we deal only with positive sequence quantities.
Before fault
System is at no load
Ia Ib Ic 0
Va ,Vb , Vc are balanced voltages
During fault
Ia Ib Ic 0
Neutral current I I I I 0
n a b c
0
Ia Ia 0 ; Ib Ib 120
0 0
; Ic Ic 120 0
And I I Ic
a b
Vn InZn 0
1
I I I 2 I I I
a1 a b c a a
3
1
I I 2 I I 0
a2 a b c
3
Va0 1 1 1 Va
1 2
Va1 3 1 Vb
V 1 2 Vc
a2
Va IaZf ; V I Z ; V I Z
1 b b f c c f
V V VV 0
a0
3 a b c
1 2
V V V V I Z
a1 a b c af
3
1 2
V V V V 0
a2 a b c
3
If Ia1
E
Z a Z
1 eq. f
In p.u. values
Ea 1pu
3
SCMVA p.u.
Zeq Zf
All impedances are in p.u.
Base MVA 3
In actual value SCMVA
| Z1 eq. Zf |pu
If Zf=0 then neutral and ground are at same potential
Vn InZn 0
Va=0, Vb 0, Vc 0
1. Circuit breaker is selected on the basis of most severe fault which is symmetrical SC fault.
2. Two important ratings
Rated momentary current
Rated symmetrical interrupting current.
Power Systems (Fault Analysis)
Solved Examples
3. Excite passive network of step-2 at fault point by negative of pre fault voltage in series
with fault impedance. Compute voltage & current at point of interest.
4. Post fault voltages & currents are obtained by adding results of step 1&3.
Solved Examples
Problem: A synchronous generator & synchronous-motor each rated 25MVA, 11kV having
15% sub-transient reactance are connected through transformer & a line as shown. The
transformer are rated 25MVA, 11/66kV & 66/11 kV with leakage reactance of 10% each. The
line has a reactance of 10% on a base of 25MVA, 66kV.
The motor is drawing 15MW at 0.8pf leading & terminal voltage at 10.6kV when a
symmetrical 3 phase fault occurs at motor terminals. Find sub transient current is gen, motor
&fault?
By Current Division
I Xdm
g
'' ''
If
(X dg
X X dm )
0.15
I I 0.25I j2.141pu
g f f
0.6
Power Systems (Fault Analysis)
I Xdg X j6.424pu
m '' ''
(X dg
X X dm )
If
Ig (post fault) Ig(pre fault) Ig
0.778336.9 2.141 90 1.7856 69.6pu
The currents have been subtracted in case of motor as he direction of current reverses in
case of fault.
Unsymmetrical Faults
Unbalanced fault analysis is very important for relay setting, single phase switch and system
stability studies. Symmetrical components are used to study the unbalanced faults.
Before fault
System is at no load
Ia Ib Ic 0
Va , Vb , Vc are balanced voltages
During fault
Ia If , I b Ic 0
V a I a Zf , V b E b , V c E c
Symmetrical components
Ia0 1 1 1 Ia
1 2
I a1 3 1 0
I 2 0
a2
1
Ia If
I I I
a0 a1 a2
3 3
Va If Zf Va1 Va2 Va0 3Zf Ia0
Since all sequence currentsEare equal, so the sequence networks will be connected in series.
a
I I I
a1 a2 a0
Z
1 eq.
Z 2 eq.
Z 0 eq. 3Z
Power Systems (Fault Analysis)
If 3Ia0 3Ea
Z Z
Z
3Z
1 eq. 2 eq. 0 eq. f
Z0 eq. Z0 3Zn
* * *
SCMVA 3 Ea1Ia1 Ea2Ia2 Ea0Ia0
Ea2 & values are zero during fault analysis
Ea0
provided that the system is under balanced
condition before fault occurrence
*
SCMVA 3Ea1Ia1
*
3Ea1E a2
SCMVA 3E
a1
Z Z
* *
1 eq. Z 2 eq. Z 0 eq. 3Zf 1 eq. Z 2 eq. Z 0 eq. 3Z
a
3E
SCMVA Z1 eq. 2Z2 eq. Z0
eq.
3Zf
In terms of p.u.
Ea 1pu
3
SCMVA
p.u.
Z1 eq. Z2 eq. Z0 eq. 3Zf
During fault
Ia 0, Ib Ic If
V a 0 , V b V c I f Zf
Ia2 2
Ib
Ia1
Ib
3
Ia2 Ia1 0
For voltages
Vb Vc I f Z f
V a0
2
2
Va1 Va2 Va0 Va1 Va2 j 3I a1Z f
2
Va1 V
2
a2
j 3I a1Z f
jVa1 jVa2 j 3Ia1Zf
Ia1 Ia2
Z
Z Z
Ea
1 eq. 2 eq. f
If j 3Ia1
Power Systems (Fault Analysis)
During unbalanced loading condition the steady state impedance of alternator has to be
taken.
During fault current calculation sub-transient reactance has to be taken.
a
3
SCMVA Z1 eq. Z2
E
Z
eq. 2 f
In pu system
Ea 1pu
3
SCMVA p.u.
Z1 eq. Z2 eq. Zf
All impedances are in p.u.
3 Base MVA3
In actual value SCMVA
Z1 eq. Z2 eq. Zf
pu
Before fault
System is at no load
Ia Ib Ic 0
Va ,Vb , Vc are balanced voltages
During fault
Ia 0, If Ib Ic
Va 0, Vb Vc If Zf
Power Systems (Fault Analysis)
Ia0 1 1 1 0
1 2
I a1 3 1 Ib
I 1 2 I
a2 1 I c
f
I I I I
3
a0 a b c
3
If 3Ia0
For voltages
Vb Vc Va1 Va2
V b V c I f Zf
2
Va0 Va1 Va2 If Zf
2
Va0 Va2 3Ia0Zf
Va0 Va2 3Zf Ia0
V V 2V
3 1
a0 a b
VV 2 V
2
V 3Z I
a0 a1
3 b b f a0
Ea
I
where Z Z 3Z
a1
Z Z || 3Z 0 eq. 0 n
Z
1 eq.
2 eq. 0 eq. f
I I Z2 eq.
a0 a1 Z || Z0 eq.
2 eq.
If 3Ia0
Z
Z
||
3Z
1 2 eq. 0 eq. f
eq.
Z 3E
a
SCMVA
Z10 eq.
eq.
2
||2f eq. 3Z
Z
In pu quantities
Ea 1pu
3
SCMVA
p.u.
Z1 eq. Z2 eq. || Z0 eq. 3Z f
All impedances are in p.u.
Whenever phase voltage magnitude is increased to line to line voltage magnitudes, then
overhead insulation will flash over such that conductor will be connected to ground
through the arc. This is called as arcing ground.
Arcing grounds will occur in the system whenever there is a LG fault & there is no closed
path provided for zero sequence currents.
To award arcing fault, we must connect neutral to ground
Power Systems (Fault Analysis)
Solved Examples
Problem: Y-connected alternator with isolated neutral, has Ve, Ve & zero sequence
impedance as 0.18, j0.12, j0.06pu respectively. Rating of alternator is 100MVA, 18kV, a LG
fault occurs on phase ‘a’ on No-load alternator what are phase voltage of ‘b’ & ’c’?
Advantage of isolated neutral is possibility of maintain a supply even with a fault on one
line.
Interference with telephone line is reduced due to absence of zero sequence currents.
Before fault
Ic / ph Vph
VphCph
Xc / ph
Al Line charging currents lead the corresponding voltages
0
By 90 .
Power Systems (Fault Analysis)
During fault
Phase voltages become line voltages
Va 3Vph
3Vph
Vb
Vc 0V
Ipa 3Vph
X / ph 3 Ic / ph
c
3Vph
Ipb 3 I c / ph
Xc / ph
Ipc If Ipa Ipb 3Ic / ph
Grounding Method
1. System grounding or Neutral Grounding
To avoid arcing ground & damage for the system and for the protection purpose or to make
the relay such that fault is identified.
2. Equipment grounding or safety grounding
For operator safety, the body or outer casing of apparatus is connected to ground.
1. Solid Grounding
Zn=0 solid grounding
X0
3 for solid grounding
X1
2. Resistance Grounding
Generally, resistance grounding is used in alternators to limit stator
fault current. It is used when charging current is small i.e, for low
voltage short lines. Helps in improving system stability during ground
faults.
3. Reactance Grounding
Zn = jXn
Used for grounding neutrals for synchronous motor, capacitor having
large charging current.
X0
3 for reactance grounding
X1
Power Systems (Fault Analysis)
Solved Examples
Problem: The severity of line-to-ground and three phase faults at the terminals of an
unloaded synchronous generator is to be same. If the terminal voltage is 1.0 p.u. and Z 1 = Z2
=j0.1 p.u., Z0 = j0.05 p.u., for the alternator, then the required inductive reactance for neutral
grounding is
Solution: For an unloaded alternator the fault current for line to ground fault is given by
If1 3 Ea
X X X
1 eq. 2 eq. 0 eq.
Problem: A 50 Hz alternator is rated 500 MVA, 20 kV, with X d = 1.0 per unit and X”d = 0.2 per
unit. It supplies a purely resistive load of 400 MW at 20 kV. The load is connected directly
across the generator terminals when a symmetrical fault occurs at the load terminals. The
initial rms current in the generator in per unit is
Base KV
2
Xd
20
2
0.2 0.16
500
For three phase symmetrical fault, 20 3
10
The initial RMS fault current, I f E E 3
X a a
X
0.16 72168.78 A
If 3Ea
X X X WhereEa = Vth = 1.0 P.u
1 eq. 2 eq. 0 eq.
3 1.0
If j0.2 j0.2 j0.49
If = 3.37 900
The voltage of neutral reactance = In Xn= If Xn = 3.37 0.05 = 0.168 P.u
Problem: At a 220 kV substation of a power system, it is given that the three-phase fault
level is 4000 MVA and single-line to ground fault level is 5000 MVA. Neglecting the
resistance and the shunt susceptances of the system. The positive and zero sequence driving
point reactance’s at the bus are?
SCMVA 3 Ea
| X1 eq. |
2
3 220
4000 | X |
1 eq.
Power Systems (Fault Analysis)
| X1 eq. | 12.1
For single line to ground fault,
2
SCMVA 3 Ea
X1 eq. X2 eq. X0 eq.
2
5000 3 220
X1 eq. X2 eq. X0 eq.
Problem: Three-phase to ground fault takes place at locations F 1and F2 in the system shown
in the figure. If the fault takes place at location F 1, then the voltage and the current at bus A
are VF1and IF1 respectively. If the fault takes place at location F 2, then the voltage and the
current at bus A are VF2 and IF2 respectively. The correct statement about voltages and
currents during faults at F1 and F2 is
(a) VF1 leads IF1 and VF2 leads IF2
(b) VF1 leads IF1 and VF2 lags IF2
(c) VF1 lags IF1 and VF2 leads IF2
(d) VF1 lags IF1 and VF2 lags IF2
Solution: If fault occurs at F1
IF EA EB0
X190 X 90
2
Where X1 is reactance from source to fault point
X2 is reactance from EB to fault
VF E 0
X B90 (–ve sign as current flows into fault but IF1 has opposite direction shown)
1 2
EB
= X2 90
X3 X3
VF1 EB0 EB X 180 = EB 1 0
2
X2
So IF1 leads VF1
For fault at F2
VF2 EA IF2 X4 90
Power Systems (Fault Analysis)
Vs1=Vs2= (i+j0)pu
Positive sequence impedance are
Zs1=Zs2=0.001+j0.001pu & ZL=0.006+j 0.06pu
3-phase base MVA=100
Voltage base =400 KV(L-L)
Nominal system frequency =50 Hz
Reference voltage for phase ‘a’ is defined as v(t)= V mcos(ωt)
A symmetrical 3 phase fault occurs at center of line i.e at point ‘F’ at time t o. The positive
sequence impedance from source S1 to point F equals 0.004+j0.04 pu. The wave from
corresponding to phase ‘a’ fault current from bus X reveals that decaying dc offset current is
negative & in magnitude at its maximum initial value. Assume that negative sequence
impedance are equal to positive sequence impedances & zero sequence impedance as 3
times positive sequence impedance.
1. The instant (to) of fault will be.
2. The rms value of ac component of fault current (Ix) will be
3. Instead of 3 phase fault, if SLG fault occurs on phase ‘a’ at F with zero fault impedance,
then rms value of ac component of fault current (Ix) for phase will be
1. i(t) A
Rt/L
2Z
cos(t )
e V
t to ,i(t) 0 m
Rt0 /L
0A
e
2Zcos(t 0 )
V
m
Power Systems (Fault Analysis)
Rt0 /L 2
Ae cos(t0 )
V
m
Z
Maximum value of DC offset current= 2
Z
V
to 0 m
2. Zeq Z 0
0.0284.29 p.u.
2
100 0
I (pu) 49.8 84.29 pu
f
Z1
100
I 49.8 7.18KA
f
3 400
0
3. Z1eq 0.0284.29 p.u.
Z2eq Z1eq 0.0284.29 p.u.
Z
I I 10
I
0 eq an a1 a2
Z Z Z
Ia 29.85pu 1eq 2eq 0eq
100
I 29.85 4.97kA
f
3 400