Medical Gas Design Guide Chapter 6 - Medical Vacuum (Suction)
Medical Gas Design Guide Chapter 6 - Medical Vacuum (Suction)
Medical Gas Design Guide Chapter 6 - Medical Vacuum (Suction)
TM
This pamphlet is presented as a service to systems designers working with medical gas and vacuum in medical
facilities. The design process used in this booklet is detailed in Chapter 1 - Design Process.
This Guide is not in any way intended to be a substitute for a properly qualified engineer, and any pretence to being
alone sufficient for the proper design of any medical gas system is explicitly disclaimed.
It is BeaconMedæs’ intent that this book should only be used as one tool among many by properly qualified engineers
who are in a position by training and experience to know it’s applications and limitations.
You will find in using the Guide that there are innumerable decisions, judgement calls, and subtleties in the design
of medical gases which cannot be incorporated in any book, but serve to dramatically emphasize the value of the
engineer’s expertise.
Comments on this booklet or on any aspect of medical gases are welcome and encouraged.
Please send to mallen@beaconmedaes.com
This Pamphlet in both print and electronic versions is Copyright 2005 BeaconMedæs. All Rights are Reserved, and
no reproduction may be made of the whole or any part without permission in writing. Distribution of the Electronic
version is permitted only where the whole is transmitted without alteration, including this notice.
Chapter 6
Medical Vacuum (Suction) Source Systems
Introduction
Medical vacuum is, compared to other medical gas The HTM method is published in the HTM 2022 standard,
source systems, quite straightforward. The most and is the method used in the U.K. We have included it
difficult part of the process comes in the selection of here as an additional method for comparison.
the technology to be used because there are so many
competing technologies, each with their own appeal Step One: Discovery
and it must be said, their own warts. NFPA and CSA
standards have relatively few requirements and those are ? 1. If existing equipment is to be retained in
readily met, so the decision becomes a balancing of the service, determine (by actual observation
clients’s concerns for risk, initial cost vs. life cycle cost, if possible) the type, size, capacity and
and maintenance requirements. current loading. Ensure the existing equipment is compliant
with the current standard.
Engineers use the term “vacuum”, but clinicians use
the term “suction”, and if you have occasion to speak 2. Determine the number type and inlet count of all
with the clinicians, you’ll find the terminology subtlely occupancies in the facility which will receive medical
different. In addition, although the average clinician vacuum inlets.
cannot articulate it, their major concern is flow. It is quite
common to have a maintenance man, having been called 3. Determine if there are unusual circumstances which
because of “poor suction”, plug in a vacuum guage and may increase vacuum use. A classic example is the long
quite accurately tell the complaining nurse “you got all I term care facility where wheelchair bound ventilator
got”. He’s right in terms of vacuum level, but the nurse is patients are taught to suction their own airway. Suction
really complaining that she has no flow. demand is enormous, because they leave the suction lines
open constantly. A system sized using traditional criteria
If we are to complete a successful design, we must grapple would burn itself out in a matter of months under such a
this problem all the way through the system. Providing load.
flow is primarily a piping problem which we will deal
with in Chapter 11, but this distinction is important to 4. Examine the location intended for the exhaust. NFPA
understand because it affects pump selection as well. mandates the exhaust be outdoors, 3m (10 feet) from any
Giving a higher ultimate vacuum may be helpful, but it other opening, at a different level (usually lower) than any
rarely solves a problem of flow. Only fat pipes can do air intake, and in a location unlikely to blow contaminated
that. Seeking a high vacuum level may actually waste air where people are likely to be or where it cannot
our client’s money and provide no solution to their real disperse. (Ref. NFPA 99 5.1.3.6.7)
problem.
Ensure the exhaust (or the intended location for the
The methods for sizing vacuum sources are always a exhaust) is located away from all other vents, windows,
surprise to new engineers, because there are so many and especially away from any intakes (e.g. compressed air
(we present three here) and because the most commonly intakes, HVAC intakes).
used are so poorly documented. The CGA P-2.1 has
been withdrawn by it’s publisher, the Compressed Gas 5. Determine a routing for the exhaust piping and note it
Association. It was essentially unchanged since the on the building drawings.
1970’s, but there is almost nothing but the patina of
age to substantiate the numbers it contains. The NFPA 6. Ensure the intended location for the vacuum plant is
method was removed from the NFPA 99 because it too adequately ventilated or is air conditioned. The plant will
was considered out of date. Fortunately, it at least has a discharge considerable heat into the enclosure, which must
research history. We continue to use these two in the US be factored in when selecting a pump site, determining
because we have used them for so long we understand the adequacy of ventilation, or BTU requirements for air
their limitations, and we know from experience that they conditioning. (BTU data is furnished on the equipment
do work. data sheets.)
3. When all occupancies have been accounted for, multiply HTM 2022 Method
by the flow for each and sum all the required flows. Add
1. Take counts by occupancy in the counting units found
1.0 in Detail 6.7.1.
.9
.8 2. Insert the count into the formulæ shown for each
Diversity Factor
.7 occupancy category.
.6 Type “A”
.5 3. Sum the requirements column for total usage.
.4 Type “B”
.3
.2 4. Go to note below.
.1
Note on Sizing Methods: All sizing methods are only
0 25 50 75 100 150 200 300 500 1000 approximations and should be used judiciously. If an existing
Number of Inlets pump is being replaced, the operating characteristics of that
system can be an important guage of likely future use. As an
example, if an existing 5 Hp. pump was seen to be adequate,
Detail 6.5
but the sizing tables yielded a much larger requirement, it
NFPA Diversity Curves
might be appropriate to use a smaller compromise unit as
(after Fig. C-4.3.4 in NFPA 99 1999 version)
Medical Vacuum (Suction) Page
BeaconMedæs Medical Gas Design Guide
Chapter 6
Comparison of Vacuum Technologies
Characteristic Liquid Ring - Lubricated Rotary Vane Oil-free Rotary Vane Dynamic Claw
Water seal
Reliability when maintained Excellent Good Moderate Moderate Good
Longevity of Pump Excellent Good Moderate Good Good
High without
Operating Cost (utilities) Low Moderate Moderate Low
recirculation
Altitude Good P No limit Poor (1) Poor Poor (1)
Tolerance for Carryover P Excellent Poor Poor Poor Poor
Maintenance Low, can be complex High, can be complex Moderate, easy Low, easy P Low, easy
Pump life, ambient
Best Feature High vacuum Maintenance Maintenance Maintenance
temperature indifferent
Worst Characteristic Use of Water High Maintenance Vane life varies Low cfm/Hp. Initial cost
Error Tolerance P Excellent Poor(2) Good Good Good
Suitability for WAGD P Excellent DO NOT USE Poor (3) Good Excellent (4)
Ambient Temperature P No limit if water is cool Limit of 100°F Limit of 100°F Limit of 100°F Limit of 100°F
dBa at 10 hp. 76 83 78 84 87
Top Vacuum 26 inHgV 29 inHgV 23 inHgV 22 inHgV 22 inHgV
• Use only with • Avoid use where main- • Good choice for smaller • Good choice for larger • Costly up front but
recirculation and tenance staffing is limited. facilities with limited facilites wanting to limit best efficiency of any dry
preferably in a Camel • Don’t undersize. maintenance staff. maintenance. pump. Evaluate on cost
BeaconMedæs Medical Gas Design Guide
configuration • Prefers continuous run. • Vane life can vary • Limited sizes and more per ft3 - can be very cost
• LOUD in larger sizes. and requires careful effective in larger sizes. effective.
application to optimize. • Not suitable for altitude • Not suitable for altitude
If you use it... • Vane life is reduced at above 4,500 ft. above 6,000 ft.
altitudes above 4,500 ft. • Prefers continuous run. • LOUD
• LOUD
P Indicates the Pump is highly recommended where this characteristic is desired.
(1) Pumps can be operated at higher elevations if a lower ultimate vacuum is accepted or life of vanes is reduced.
(2) Lubricated rotary vane machines may not easily tolerate being undersized.
(3) Oil free rotary vanes use graphite vanes which are not generally suitable with elevated oxidizer concentrations. Some manufacturers claim they can be rendered
acceptable with special preparation, however, BeaconMedæs does not recommend them for this service.
(4) In the O2Assured version.
Page
BeaconMedæs Medical Gas Design Guide
Detail 6.9
A Quick Guide to Configurations
Vertical
Vertical configurations have two Pumps stacked on a single base. This configuration is only suitable for
smaller Pumps or Pumps with very little inherent vibration. It is the most space-efficient of all medical
vacuum configurations, and oil less vertical systems are spectacularly space-efficient.
Modular
Each Pump, and the controls and receiver are mounted on individual
bases for easy handling and placement where space is at a premium.
These systems are especially well suited for retrofit or replacement
situations. Each module will fit through a standard 3-0 doorframe and
can be handled with a standard pallet jack.
Tank Mount
These systems are mounted atop their receivers and use the receivers for support. In
small sizes they are space efficient and cost effective.
Detail 6.9 for an explanation of the different architectures). clearance on the other sides. It is somtimes possible to
Where more than one architecture is available, choose the reduce this clearance with exact knowledge of maintenance
one best suited to the site conditions. If in doubt as to the access requirements. Consult with your BeaconMedæs
best system architecture for a particular situation, contact representative if circumstances allow less space.
your BeaconMedæs representative for assistance.
2. Place the equipment in elevation views as appropriate.
4. Reference the system information (SSB sheet) for the
particular system selected (Ref. Details 6.13-6.17 for 3. On the plans, finalize the routing for the exhaust.
System Selection Tables) This sheet contains all the vital
information about the system and should be pulled out for 4. Size the exhaust piping. A quick reference for exhaust
quick reference in all the following steps. sizing is contained in Detail 6.11. The sizing process is
iterative:
Step Seven: Layout
a. Start with the total actual length of piping, and based
1. Place the plant in scale on the plan drawings in the on Detail 6.11 make an estimate for the line size.
location selected. Ensure that the plant has sufficient space
on all sides for maintenance access and proper ventilation. b. Using your estimated size, add equivalent lengths for
In front, the control cabinet must have 36” clearance, and the fittings employed.
BeaconMedæs recommends 92 cm (3 feet) minimum
c. Check the size is still acceptable at the new equivalent
length. If not, re-estimate the next larger size and repeat
Medical Vacuum (Suction) Page
Calculated Demand:
NFPA Method CGA Method HTM Method
Altitude Correction:
Detail 6.10
Chapter 6
Vacuum System Sizes by Technology
Vacuum Required
M3/min.
11.1
14.5
.2
0
.14
.17
.23
.28
.31
.34
.59
.65
.74
.79
.82
.85
.96
1.0
1.1
1.2
1.4
1.5
1.6
1.6
1.7
1.7
1.8
1.9
2.1
2.3
2.5
2.5
2.5
2.7
2.8
2.8
2.9
3.1
3.2
3.3
3.4
3.5
3.6
3.9
3.9
4.1
4.1
4.7
4.7
4.8
5.0
5.0
5.5
5.7
5.9
6.2
6.8
7.1
7.6
7.7
8.5
9.5
9.5
10
.4
.5
2
2
Larger Systems
Liquid Ring (Camel) Technology Quadruplex 10 Hp 15 Hp 20 Hp 25 Hp
Triplex 5 Hp 7.5 Hp 10 Hp 15 Hp 20 Hp 25 Hp
3 Hp 5 Hp 7.5 Hp 10 Hp 15 Hp 20 Hp 25 Hp Duplex
Dynamic Technology Quadruplex 10 Hp 15 Hp 25 Hp
BeaconMedæs Medical Gas Design Guide
10 Hp 15 Hp 25 Hp Triplex
10 Hp 15 Hp 25 Hp Duplex
Claw Technology Quadruplex 5 Hp 7.5 Hp 10 Hp 15 Hp
5 Hp 7.5 Hp 10 Hp 15 Hp Triplex
3 Hp 5 Hp 7.5 Hp 10 Hp 15 Hp Duplex
0
5
6
8
10
11
12
14
18
21
23
26
28
29
30
34
37
41
42
49
52
55
58
59
60
63
68
69
73
75
82
87
88
89
97
98
10
100
112
111
112
126
120
125
136
136
148
146
167
166
167
178
177
198
204
200
217
249
250
260
277
303
330
334
366
400
508
4
SCFM
Page 10
BeaconMedæs Medical Gas Design Guide
Detail 6.11
Exhaust Pipe Sizing
Flow
Unit Basis Allowable Equivalent Run (feet)
(SCFM)(1)
Nominal Pipe Size 1.5” 2” 2.5” 3” 4” 5” 6” 8”
Duplex 1.5 Hp. 12 450
Duplex 2 Hp. 20 170 700
Duplex 3 Hp. 36 65 250 800
Duplex 5 Hp. 74 16 65 200 475
Duplex 7.5 Hp. 138 20 60 150 600 1900
Duplex 10 Hp. 178 45 100 425 1200
Duplex 15 Hp. 240 55 225 675 1600
Duplex 20 Hp. 272 45 180 525 1300
Duplex 25 Hp. 336 25 110 325 800
Triplex 5 Hp 113 30 50 225 900
Triplex 7.5 Hp. 207 75 300 900
Triplex 10 Hp. 267 45 180 550 1400
Triplex 15 Hp. 375 100 300 700
Triplex 20 Hp. 409 80 250 600
Triplex 25 Hp. 504 60 175 425 1800
Quad 7.5 Hp. 275 45 190 550 1400
Quad 10 Hp. 355 110 325 800
Quad 15 Hp. 478 65 190 450 2000
Quad 20 Hp. 542 50 150 350 1500
Quad 25 Hp. 670 35 170 425 1800
The line may also be more accurately sized by actual 1. In section 2.3 D of the Guide specification, select
calculation. Intake piping must be sized to induce no the sections appropriate to the technology and system
more than 100mm (4 inches) water column backpressure architecture desired.
at the pump outlet when all pumps are running. (use
total capacity for this calculation not NFPA capacity). 2. Write into the specification any
exceptional requirements (soft starters, etc.).
For unusual lengths or other circumstances, contact your
BeaconMedæs representative for assistance. 3. Schedule on the drawings the vacuum
plant selected. Schedule at least:
5. Finalize the connection to the distribution piping and size
the system piping (see Chapter 4 of this Guide) a. The capacity per pump (per NFPA) and total system.
Medical Vacuum (Suction) Page 11
BeaconMedæs Medical Gas Design Guide
b. Horsepower or kW per compressor. Contact your BeaconMedæs representative if you need to
c. Voltage, Hz, and phase desired. fit the systems in smaller spaces.
Notes on the System Selection Tables (Detail 6.13-6.17) All systems listed have the standard receivers. Larger
receivers usually change the envelope dimensions.
These tables represent standard systems and configurations
and do not represent all configurations. The Modular system’s envelope dimensions shown
represent a typical arrangement for minimum floor
In particular: space. However, modular systems are easily located
wherever appropriate, which will change the dimensional
Envelope dimensions do not include maintenance space. requirements. Envelope dimensions for modular systems
BeaconMedæs recommends 92 cm. (36 in.) on all sides, should be used only as rough guides.
but less space may be possible with an understanding of
the system maintenance requirements. In all cases the More details on all dimensions will be found on the SSB
National Electrical Code requires a minimum clearlnce of sheets for the system selected, and the SSB sheet should
914 mm (36 in.) in fron of the control cabinet. be consulted when doing final layout.
Page 12 Chapter 6
BeaconMedæs Medical Gas Design Guide
Detail 6.15
System Selection Table, Liquid Ring Camel, 311 – 9,500 lpm (11-334 scfm)
NFPA Complete System
Capacity Envelope Dimension (inches)
Pump Information
SCFM LPM Format HP Technology Width Height Depth Sheet
11 311 Camel Duplex (I) 3 Waterseal L.R. 35 77 90 SSB-510-05
30 849 Camel Duplex (I) 5 Waterseal L.R. 35 77 90 SSB-510-05
34 962 Camel Duplex (I) 7.5 Waterseal L.R. 35 79 92 SSB-510-05
49 1,386 Camel Duplex (I) 10 Waterseal L.R. 42 90 92 SSB-510-05
Elevations ……………………………… 19
P&ID …………………………………… 20
Electrical ………………………………… 21
Installation ……………………………… 22
Page 18 Chapter 6
7½-20
BASE MOUNT
1½-5
1½-2
BASE MOUNT
SSB-350-01
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
DUPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® “Oil-Less” Medical Rotary Vacuum
Vertical Base Mount Single Point Connection (SPC)
Duplex System (1½ - 2 HP)
SPECIFICATION
Vacuum System Intake Piping
The duplex medical vacuum system must be fully compliant Each vacuum pump shall have a factory piped intake with
with the latest edition of NFPA 99. The package will consist integral flex connector, isolation valve, and check valve.
of two "oil-less" rotary vane vacuum pumps, a control panel, Interconnecting piping shall consist of black iron pipe and
and a receiver all mounted on a common base frame. Each fittings.
system must have a maximum base size of 26" x 32". The Vacuum Receiver
receiver shall be ASME coded and have a three-valve bypass The vacuum receiver shall be ASME Code stamped, and rated
system to allow for draining of the receiver without for a minimum 150 PSIG design pressure.
interrupting the vacuum service. A manual drain shall be
provided on the receiver. Each pump and the receiver shall be Control System
connected to a common intake manifold. A single point of The duplex control system shall be NEMA 12 and U.L.
connection to the intake of the system shall be provided. A labeled. The control system shall provide automatic lead/lag
single point of connection to the electrical panel of the system sequencing with circuit breaker disconnects for each vacuum
shall also be provided. The package shall be completely tested pump with external operators, full voltage motor starters with
prior to shipment. overload protection, redundant 120V control circuit
transformers, visual and audible reserve unit alarm with
Vacuum Pump isolated contacts for remote alarm, hand-off-auto lighted
Each pump shall operate completely dry, and shall be selector switches and runtime hourmeters. A programmable
equipped with self-lubricating carbon/graphite vanes. logic controller (PLC) shall control the automatic alternation
Bearings shall be permanently lubricated and sealed. No oil of both vacuum pumps with provisions for simultaneous
shall be permitted in any pump. Each pump shall be operation if required, and automatic activation of reserve unit
completely air-cooled and have absolutely no water if required. The control system shall include a minimum run
requirements. Each pump shall have a 5-micron inlet filter and timer. A vacuum gauge shall be provided in the control panel.
shall be equipped with a vacuum relief valve, check valve to
prevent backflow through off-cycle units, flexible connector, Installation
isolation valve, and vibration isolators at each mounting The installation of this vacuum technology is limited to a
location. maximum of 4,000 feet elevation above sea level. For
installation of this equipment above 4,000 feet elevation,
Vacuum Pump Drive please contact the factory.
The pump shall be direct driven.
Vacuum Pump Motor
The motor shall be a continuous duty, TEFC, 1800 RPM,
suitable for 208V, 230, or 460V, 60 hertz, 3 phase electrical
service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-350-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 22 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 25
P&ID …………………………………… 26
Electrical ………………………………… 27
Installation ……………………………… 28
Page 24 Chapter 6
7½-20
1½-2
BASE MOUNT
1½-5
3-7½
BASE MOUNT
SSB-350-02
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
DUPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® “Oil-Less” Medical Rotary Vacuum
Vertical Base Mount Single Point Connection (SPC)
Duplex System (3 - 7½ HP)
SPECIFICATION
Vacuum System Intake Piping
The duplex medical vacuum system must be fully compliant Each vacuum pump shall have a factory piped intake with
with the latest edition of NFPA 99. The package will consist integral flex connector, isolation valve, and check valve.
of two "oil-less" rotary vane vacuum pumps, a control panel, Interconnecting piping shall consist of black iron pipe and
and a receiver all mounted on a common base frame. Each fittings.
system must have a maximum base size of 34" x 44". The Vacuum Receiver
receiver shall be ASME coded and have a three-valve bypass The vacuum receiver shall be ASME Code stamped, and rated
system to allow for draining of the receiver without for a minimum 150 PSIG design pressure.
interrupting the vacuum service. A manual drain shall be
provided on the receiver. Each pump and the receiver shall be Control System
connected to a common intake manifold. A single point of The duplex control system shall be NEMA 12 and U.L.
connection to the intake of the system shall be provided. A labeled. The control system shall provide automatic lead/lag
single point of connection to the electrical panel of the system sequencing with circuit breaker disconnects for each vacuum
shall also be provided. The package shall be completely tested pump with external operators, full voltage motor starters with
prior to shipment. overload protection, redundant 120V control circuit
transformers, visual and audible reserve unit alarm with
Vacuum Pump isolated contacts for remote alarm, hand-off-auto lighted
Each pump shall operate completely dry, and shall be selector switches and runtime hourmeters. A programmable
equipped with self-lubricating carbon/graphite vanes. logic controller (PLC) shall control the automatic alternation
Bearings shall be permanently lubricated and sealed. No oil of both vacuum pumps with provisions for simultaneous
shall be permitted in any pump. Each pump shall be operation if required, and automatic activation of reserve unit
completely air-cooled and have absolutely no water if required. The control system shall include a minimum run
requirements. Each pump shall have a 5-micron inlet filter and timer. A vacuum gauge shall be provided in the control panel.
shall be equipped with a vacuum relief valve, check valve to
prevent backflow through off-cycle units, flexible connector, Installation
isolation valve, and vibration isolators at each mounting The installation of this vacuum technology is limited to a
location. maximum of 4,000 feet elevation above sea level. For
installation of this equipment above 4,000 feet elevation,
Vacuum Pump Drive please contact the factory.
The pump shall be direct driven. Torque is transmitted from
the motor to the pump through a shaft coupling.
Vacuum Pump Motor
The motor shall be a continuous duty, NEMA rated, C-face,
TEFC, 1800 RPM, with 1.15 service factor suitable for 208V
or 230/460V, 60 hertz, 3 phase electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-350-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 28 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 30
P&ID …………………………………… 31
Electrical ………………………………… 32
Installation ……………………………… 33
Page 30 Chapter 6
DUPLEX7½-20
1½-5
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-300-01
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 01/18/2008
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® “Oil-Less” Medical Rotary Vacuum Tank Mount Duplex System (1.5 - 5 HP)
SPECIFICATION
Vacuum System Intake Piping
The duplex medical vacuum system must be fully compliant Each vacuum pump shall have a factory piped intake with
with the latest edition of NFPA 99. The package shall consist integral flex connector, isolation valve, and check valve.
of two "oil-less" rotary vane vacuum pumps and a control Interconnecting piping shall consist of galvanized pipe and
panel, mounted on a receiver sized for appropriate demand. fittings.
Each pump shall be connected to a common intake manifold. Vacuum Receiver
Each tank mount system must be designed to have a The vacuum receiver shall be ASME Code stamped, and rated
maximum width of 34" (86 cm). The receiver shall be ASME for a minimum 150 PSIG design pressure.
coded and have a three valve bypass system to allow for
draining of the receiver without interrupting the vacuum Control System
service. A manual drain shall be provided on the receiver. The The duplex control system shall be NEMA 12 and U.L.
package shall be completely tested prior to shipment. labeled. The control system shall provide automatic lead/lag
sequencing with circuit breaker disconnects for each vacuum
Vacuum Pump pump with external operators, full voltage motor starters with
Each pump shall operate completely dry, and shall be overload protection, redundant 120V control circuit
equipped with self lubricating carbon/graphite vanes. All transformers, visual and audible reserve unit alarm with
bearings shall be permanently lubricated and sealed. No oil isolated contacts for remote alarm, hand-off-auto lighted
shall be permitted in the pump. Each pump shall be selector switches and runtime hourmeters. A programmable
completely air-cooled and have absolutely no water logic controller (PLC) shall control the automatic alternation
requirements. Each pump shall have a 5 micron inlet filter and of both vacuum pumps with provisions for simultaneous
shall be equipped with a vacuum relief valve, check valve to operation if required, and automatic activation of reserve unit
prevent backflow through off-cycle units, flexible connector, if required. The control system shall include a minimum run
isolation valve, and vibration isolators at each mounting timer. A vacuum gauge shall be provided in the control panel.
location.
Installation
Vacuum Pump Drive The installation of this vacuum technology is limited to a
The pump shall be direct driven. Torque is transmitted from maximum of 4,000 feet elevation above sea level. For
the motor to the pump through a shaft coupling. installation of this equipment above 4,000 feet elevation,
Vacuum Pump Motor please contact the factory.
The 1½ and 2 hp motor shall be a continuous duty, NEMA
rated, C-face, TEFC, 1800 RPM, with 1.15 service factor
suitable for 208V or 230/460V, 60 hertz, 3-phase electrical
service.
The 3 and 5 hp motor shall be a continuous duty, NEMA
rated, C-face, open drip proof, 1800 RPM, with 1.15 service
factor suitable for 208V or 230/460V, 60 hertz, 3 phase
electrical service.
Notes: 1
Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver.
5
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-300-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 01/18/2008
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Medical Rotary Vacuum Systems to be free of defects in material and
workmanship under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 34 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 37
P&ID …………………………………… 38
Electrical
5 Hp. ………………………………… 39
7.5 & 10 Hp …………………………… 40
Installation
5 & 7.5 Hp. …………………………… 41
10 Hp. …………………………………… 42
Page 36 Chapter 6
DUPLEX7½-20
BASE MOUNT
BASE MOUNT
5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-310-01
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® “Oil-Less” Medical Rotary Vacuum Modular Duplex System (5 - 10 HP)
SPECIFICATION
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-310-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 40 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 42 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 45
P&ID …………………………………… 46
Electrical ……………………………… 47
Installation
5 & 7.5 Hp. …………………………… 48
10 Hp. …………………………………… 49
Page 44 Chapter 6
TRIPLEX7½-20
BASE MOUNT
BASE MOUNT
5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-310-02
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® “Oil-Less” Medical Rotary Vacuum Modular Triplex System (5 - 10 HP)
SPECIFICATION
Vacuum System
The triplex medical vacuum system must be fully compliant The 10 hp motor shall be a continuous duty, NEMA rated, C-
with the latest edition of NFPA 99. The package will consist face, open drip proof, 1200 RPM, with 1.15 service factor
of three "oil-less" rotary vane vacuum pumps, a control panel, suitable for 208 or 230/460V, 60 hertz, 3 phase electrical
and a receiver sized for appropriate demand. Each module service.
shall have a common intake manifold. Each vacuum module Intake Piping
must be designed to accommodate a standard pallet jack and Each vacuum pump shall have a factory piped intake with
have a maximum base width of 34" (86 cm). The receiver integral flex connector, isolation valve, and check valve.
shall be ASME coded and have a three valve bypass system to Interconnecting piping shall consist of black iron pipe and
allow for draining of the receiver without interrupting the fittings.
vacuum service. A manual drain shall be provided on the
receiver. The package shall be completely tested prior to Vacuum Receiver
shipment. The vacuum receiver shall be ASME Code stamped, and rated
for a minimum 150 PSIG design pressure.
Vacuum Pump
Each pump shall operate completely dry, and shall be Control System
equipped with self-lubricating carbon/graphite vanes. The triplex control system shall be NEMA 12 and U.L.
Bearings for the 5 and 7.5 hp shall be permanently lubricated labeled. The control system shall provide automatic lead/lag
and sealed. No oil shall be permitted in any pump. Each pump sequencing with circuit breaker disconnects for each vacuum
shall be completely air-cooled and have absolutely no water pump with external operators, full voltage motor starters with
requirements. Each pump shall have a 5-micron inlet filter and overload protection, redundant 120V control circuit
shall be equipped with a vacuum relief valve, check valve to transformers, visual and audible reserve unit alarm with
prevent backflow through off-cycle units, flexible connector, isolated contacts for remote alarm, hand-off-auto lighted
isolation valve, and vibration isolators at each mounting selector switches and runtime hourmeters. A programmable
location. logic controller (PLC) shall control the automatic alternation
of the vacuum pumps with provisions for simultaneous
Vacuum Pump Drive operation if required, and automatic activation of reserve unit
The pump shall be direct driven. Torque is transmitted from if required. The control system shall include a minimum run
the motor to the pump through a shaft coupling. timer. A vacuum gauge shall be provided in the control panel.
Vacuum Pump Motor Installation
The 5 and 7.5 hp motor shall be a continuous duty, NEMA The installation of this vacuum technology is limited to a
rated, C-face, open drip proof, 1800 RPM, with 1.15 service maximum of 4,000 feet elevation above sea level. For
factor suitable for 208V or 230/460V, 60 hertz, 3 phase installation of this equipment above 4,000 feet elevation,
electrical service. please contact the factory.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect two vacuum pumps in operation.
6
Total weight for a 5 duplex module w/control panel (1051#) and a 5 simplex module (502#).
Total weight for a 7.5 duplex module w/control panel (1201#) and a 7.5 simplex module (578#).
Total weight for a 10 duplex module w/control panel (2335#) and a 10 simplex module (1159#).
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-310-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 48 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 50 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 52
P&ID …………………………………… 53
Electrical ………………………………… 54
Installation
5 & 7.5 Hp. …………………………… 55
10 Hp. …………………………………… 56
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® “Oil-Less” Medical Rotary Vacuum Modular Quad System (5 - 10 HP)
SPECIFICATION
Vacuum System Intake Piping
The quadruplex medical vacuum system must be fully Each vacuum pump shall have a factory piped intake with
compliant with the latest edition of NFPA 99. The package integral flex connector, isolation valve, and check valve.
will consist of four "oil-less" rotary vane vacuum pumps, a Interconnecting piping shall consist of black iron pipe and
control panel, and a receiver sized for appropriate demand. fittings.
Each module shall have a common intake manifold. Each Vacuum Receiver
vacuum module must be designed to accommodate a The vacuum receiver shall be ASME Code stamped, and
standard pallet jack and have a maximum base width of 34" rated for a minimum 150 PSIG design pressure.
(86 cm). The receiver shall be ASME coded and have a three
valve bypass system to allow for draining of the receiver Control System
without interrupting the vacuum service. A manual drain The quadruplex control system shall be NEMA 12 and U.L.
shall be provided on the receiver. The package shall be labeled. The control system shall provide automatic lead/lag
completely tested prior to shipment. sequencing with circuit breaker disconnects for each vacuum
pump with external operators, full voltage motor starters with
Vacuum Pump overload protection, redundant 120V control circuit
Each pump shall operate completely dry, and shall be transformers, visual and audible reserve unit alarm with
equipped with self-lubricating carbon/graphite vanes. isolated contacts for remote alarm, hand-off-auto lighted
Bearings for the 5 and 7.5 hp shall be permanently lubricated selector switches and runtime hourmeters. A programmable
and sealed. No oil shall be permitted in any pump. Each logic controller (PLC) shall control the automatic alternation
pump shall be completely air-cooled and have absolutely no of the vacuum pumps with provisions for simultaneous
water requirements. Each pump shall have a 5 micron inlet operation if required, and automatic activation of reserve unit
filter and shall be equipped with a vacuum relief valve, check if required. The control system shall include a minimum run
valve to prevent backflow through off-cycle units, flexible timer. A vacuum gauge shall be provided in the control
connector, isolation valve, and vibration isolators at each panel.
mounting location.
Installation
Vacuum Pump Drive The installation of this vacuum technology is limited to a
The pump shall be direct driven. Torque is transmitted from maximum of 4,000 feet elevation above sea level.
the motor to the pump through a shaft coupling. For installation of this equipment above 4,000 feet elevation,
Vacuum Pump Motor please contact the factory.
The 5 and 7.5 hp motor shall be a continuous duty, NEMA
rated, C-face, open drip proof, 1800 RPM, with 1.15 service
factor suitable for 208V or 230/460V, 60 hertz, 3 phase
electrical service.
The 10 hp motor shall be a continuous duty, NEMA rated, C-
face, open drip proof, 1200 RPM, with 1.15 service factor
suitable for 208 or 230/460V, 60 hertz, 3 phase electrical
service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect three vacuum pumps in operation.
6
Total weight for a 5 duplex module w/control panel (1091#) and a 5 duplex module (897#).
Total weight for a 7.5 duplex module w/control panel (1241#) and a 7.5 duplex module (1048#).
Total weight for a 10 duplex module w/control panel (2375#) and a 10 duplex module (2185#).
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-310-03
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 54 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 56 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 59
P&ID …………………………………… 60
Electrical ………………………………… 61
Installation
5 & 7.5 Hp. …………………………… 62
10 Hp. …………………………………… 63
Page 58 Chapter 6
DUPLEX7½-20
BASE MOUNT
1½-5
BASE MOUNT
5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-320-01
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® “Oil-Less” Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Duplex System (5 - 10 HP)
SPECIFICATION
Vacuum System
The duplex medical vacuum system must be fully compliant The 10 hp motor shall be a continuous duty, NEMA rated, C-
with the latest edition of NFPA 99. The package will consist face, open drip proof, 1200 RPM, with 1.15 service factor
of two "oil-less" rotary vane vacuum pumps, a control panel, suitable for 208 or 230/460V, 60 hertz, 3 phase electrical
and a receiver sized for appropriate demand all mounted on a service.
common base frame. The receiver shall be ASME coded and Intake Piping
have a three-valve bypass system to allow for draining of the Each vacuum pump shall have a factory piped intake with
receiver without interrupting the vacuum service. A manual integral flex connector, isolation valve, and check valve.
drain shall be provided on the receiver. Each pump and the Interconnecting piping shall consist of black iron pipe and
receiver shall be connected to a common intake manifold. A fittings.
single point of connection to the intake of the system shall be
provided. A single point of connection to the electrical panel Vacuum Receiver
of the system shall also be provided. The package shall be The vacuum receiver shall be ASME Code stamped, and rated
completely tested prior to shipment. for a minimum 150 PSIG design pressure.
Vacuum Pump Control System
Each pump shall operate completely dry, and shall be The duplex control system shall be NEMA 12 and U.L.
equipped with self-lubricating carbon/graphite vanes. labeled. The control system shall provide automatic lead/lag
Bearings for the 5 and 7.5 hp shall be permanently lubricated sequencing with circuit breaker disconnects for each vacuum
and sealed. No oil shall be permitted in any pump. Each pump pump with external operators, full voltage motor starters with
shall be completely air-cooled and have absolutely no water overload protection, redundant 120V control circuit
requirements. Each pump shall have a 5 micron inlet filter and transformers, visual and audible reserve unit alarm with
shall be equipped with a vacuum relief valve, check valve to isolated contacts for remote alarm, hand-off-auto lighted
prevent backflow through off-cycle units, flexible connector, selector switches and runtime hourmeters. A programmable
isolation valve, and vibration isolators at each mounting logic controller (PLC) shall control the automatic alternation
location. of both vacuum pumps with provisions for simultaneous
operation if required, and automatic activation of reserve unit
Vacuum Pump Drive if required. The control system shall include a minimum run
The pump shall be direct driven. Torque is transmitted from timer. A vacuum gauge shall be provided in the control panel.
the motor to the pump through a shaft coupling.
Installation
Vacuum Pump Motor The installation of this vacuum technology is limited to a
The 5 and 7.5 hp motor shall be a continuous duty, NEMA maximum of 4,000 feet elevation above sea level. For
rated, C-face, open drip proof, 1800 RPM, with 1.15 service installation of this equipment above 4,000 feet elevation,
factor suitable for 208V or 230/460V, 60 hertz, 3 phase please contact the factory.
electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-320-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 62 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 64 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 66
P&ID …………………………………… 67
Electrical ………………………………… 68
Installation
5 & 7.5 Hp. …………………………… 69
10 Hp. …………………………………… 70
DUPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® “Oil-Less” Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Triplex System (5 - 10 HP)
SPECIFICATION
Vacuum System
The triplex medical vacuum system must be fully compliant The 10 hp motor shall be a continuous duty, NEMA rated, C-
with the latest edition of NFPA 99. The package will consist face, open drip proof, 1200 RPM, with 1.15 service factor
of three "oil-less" rotary vane vacuum pumps, a control panel, suitable for 208 or 230/460V, 60 hertz, 3 phase electrical
and a receiver sized for appropriate demand all mounted on a service.
common base frame. The receiver shall be ASME coded and Intake Piping
have a three-valve bypass system to allow for draining of the Each vacuum pump shall have a factory piped intake with
receiver without interrupting the vacuum service. A manual integral flex connector, isolation valve, and check valve.
drain shall be provided on the receiver. Each pump and the Interconnecting piping shall consist of black iron pipe and
receiver shall be connected to a common intake manifold. A fittings.
single point of connection to the intake of the system shall be
provided. A single point of connection to the electrical panel Vacuum Receiver
of the system shall also be provided. The package shall be The vacuum receiver shall be ASME Code stamped, and rated
completely tested prior to shipment. for a minimum 150 PSIG design pressure.
Control System
Vacuum Pump The triplex control system shall be NEMA 12 and U.L.
Each pump shall operate completely dry, and shall be labeled. The control system shall provide automatic lead/lag
equipped with self-lubricating carbon/graphite vanes. sequencing with circuit breaker disconnects for each vacuum
Bearings for the 5 and 7.5 hp shall be permanently lubricated pump with external operators, full voltage motor starters with
and sealed. No oil shall be permitted in any pump. Each pump overload protection, redundant 120V control circuit
shall be completely air-cooled and have absolutely no water transformers, visual and audible reserve unit alarm with
requirements. Each pump shall have a 5 micron inlet filter and isolated contacts for remote alarm, hand-off-auto lighted
shall be equipped with a vacuum relief valve, check valve to selector switches and runtime hourmeters. A programmable
prevent backflow through off-cycle units, flexible connector, logic controller (PLC) shall control the automatic alternation
isolation valve, and vibration isolators at each mounting of the vacuum pumps with provisions for simultaneous
location. operation if required, and automatic activation of reserve unit
Vacuum Pump Drive if required. The control system shall include a minimum run
The pump shall be direct driven. Torque is transmitted from timer. A vacuum gauge shall be provided in the control panel.
the motor to the pump through a shaft coupling. Installation
Vacuum Pump Motor The installation of this vacuum technology is limited to a
The 5 and 7.5 hp motor shall be a continuous duty, NEMA maximum of 4,000 feet elevation above sea level. For
rated, C-face, open drip proof, 1800 RPM, with 1.15 service installation of this equipment above 4,000 feet elevation,
factor suitable for 208V or 230/460V, 60 hertz, 3 phase please contact the factory.
electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect two vacuum pumps in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-320-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 68 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 70 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 73
P&ID …………………………………… 74
Electrical ………………………………… 75
Installation
5 & 7.5 Hp. …………………………… 76
10 Hp. …………………………………… 77
Page 72 Chapter 6
7½-20
BASE MOUNT
1½-5
BASE MOUNT
SSB-320-03
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® “Oil-Less” Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Quad System (5 - 10 HP)
SPECIFICATION
Vacuum System
The quadruplex medical vacuum system must be fully The 10 hp motor shall be a continuous duty, NEMA rated, C-
compliant with the latest edition of NFPA 99. The package face, open drip proof, 1200 RPM, with 1.15 service factor
will consist of four "oil-less" rotary vane vacuum pumps, a suitable for 208 or 230/460V, 60 hertz, 3 phase electrical
control panel, and a receiver sized for appropriate demand all service.
mounted on a common base frame. The receiver shall be Intake Piping
ASME coded and have a three-valve bypass system to allow Each vacuum pump shall have a factory piped intake with
for draining of the receiver without interrupting the vacuum integral flex connector, isolation valve, and check valve.
service. A manual drain shall be provided on the receiver. Interconnecting piping shall consist of black iron pipe and
Each pump and the receiver shall be connected to a common fittings.
intake manifold. A single point of connection to the intake of
the system shall be provided. A single point of connection to Vacuum Receiver
the electrical panel of the system shall also be provided. The The vacuum receiver shall be ASME Code stamped, and rated
package shall be completely tested prior to shipment. for a minimum 150 PSIG design pressure.
Control System
Vacuum Pump The quadruplex control system shall be NEMA 12 and U.L.
Each pump shall operate completely dry, and shall be labeled. The control system shall provide automatic lead/lag
equipped with self-lubricating carbon/graphite vanes. sequencing with circuit breaker disconnects for each vacuum
Bearings for the 5 and 7.5 hp shall be permanently lubricated pump with external operators, full voltage motor starters with
and sealed. No oil shall be permitted in any pump. Each pump overload protection, redundant 120V control circuit
shall be completely air-cooled and have absolutely no water transformers, visual and audible reserve unit alarm with
requirements. Each pump shall have a 5-micron inlet filter and isolated contacts for remote alarm, hand-off-auto lighted
shall be equipped with a vacuum relief valve, check valve to selector switches and runtime hourmeters. A programmable
prevent backflow through off-cycle units, flexible connector, logic controller (PLC) shall control the automatic alternation
isolation valve, and vibration isolators at each mounting of the vacuum pumps with provisions for simultaneous
location. operation if required, and automatic activation of reserve unit
Vacuum Pump Drive if required. The control system shall include a minimum run
The pump shall be direct driven. Torque is transmitted from timer. A vacuum gauge shall be provided in the control panel.
the motor to the pump through a shaft coupling. Installation
Vacuum Pump Motor The installation of this vacuum technology is limited to a
The 5 and 7.5 hp motor shall be a continuous duty, NEMA maximum of 4,000 feet elevation above sea level. For
rated, C-face, open drip proof, 1800 RPM, with 1.15 service installation of this equipment above 4,000 feet elevation,
factor suitable for 208V or 230/460V, 60 hertz, 3 phase please contact the factory.
electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect three vacuum pumps in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-320-03
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 76 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 78 Chapter 6
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … … 7 9
Elevations ……………………………… 80
P&ID …………………………………… 81
Electrical ………………………………… 82
Installation ……………………………… 83
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
TANK
LifeLine® Lubricated Medical Rotary Vacuum Tank Mount Duplex System (1.5 - 5 HP)
SPECIFICATION
Vacuum System Intake Piping
The duplex medical vacuum system must be fully compliant Each vacuum pump shall have a factory piped intake with
with the latest edition of NFPA 99. The package will consist integral flex connector, isolation valve, and check valve.
of two oil sealed rotary vane vacuum pumps, and a control Interconnecting piping shall consist of black iron pipe and
panel, mounted on a receiver sized for appropriate demand. fittings.
Each pump shall be connected to a common intake manifold. Vacuum Receiver
Each tank mount system must be designed to have a The vacuum receiver shall be ASME Code stamped, and rated
maximum width of 34" (86 cm). The receiver shall be ASME for a minimum 150 PSIG design pressure.
coded and have a three valve bypass system to allow for
draining of the receiver without interrupting the vacuum Control System
service. A manual drain shall be provided on the receiver. The The duplex control system shall be NEMA 12 and U.L.
package shall be completely tested prior to shipment. labeled. The control system shall provide automatic lead/lag
sequencing with circuit breaker disconnects for each vacuum
Vacuum Pump pump with external operators, full voltage motor starters with
Each pump shall be of an oil lubricated, dynamically balanced overload protection, redundant 120V control circuit
multi-vane design with heavy duty, aluminum alloy vanes for transformers, visual and audible reserve unit alarm with
maximum heat dissipation and extended vane life. The isolated contacts for remote alarm, visual alarms for high
minimum vane warranty shall be 50,000 hours. The oil discharge temperature shutdown with isolated contacts for
lubrication system shall be a pressure differential design with remote alarm, hand-off-auto lighted selector switches and
full re-circulation and multi-stage exhaust oil separation rated runtime hourmeters. A programmable logic controller (PLC)
at 99.998% efficiency. Water vapor condensation in the shall control the automatic alternation of both vacuum pumps
cylinder shall be prevented by means of an automatic gas with provisions for simultaneous operation if required, and
ballast valve. Additionally, a non-return valve to prevent oil automatic activation of reserve unit if required. The control
migration upon shutdown, a back pressure gauge to indicate system shall include a minimum run timer. A vacuum gauge
exhaust oil separator element change, a high discharge shall be provided in the control panel.
temperature switch, oil drain valve, oil sight glass, and
flexible connector for each pump shall be included. Statement of Warranty
BeaconMedæs warrants all LifeLine® Lubricated Medical
Vacuum Pump Drive Vacuum Systems are to be free of defects in material and
The pump shall be direct driven. Torque is transmitted from workmanship under normal use for a period not to exceed
the motor to the pump through a shaft coupling. thirty (30) months from date of shipment, or twenty four (24)
Vacuum Pump Motor months from date of start-up.
The motor shall be a continuous duty, NEMA rated, C-face,
TEFC, 1800 RPM, with 1.15 service factor suitable for 208V
or 230/460V, 60 hertz, 3 phase electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver.
5
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-400-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 82 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 84 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 86
P&ID …………………………………… 87
Electrical
5 & 7.5 Hp. …………………………… 88
10 Hp. …………………………………… 89
Installation
5 & 7.5 Hp. …………………………… 90
10 Hp. …………………………………… 91
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Modular Duplex System (5 - 10 HP)
SPECIFICATION
Vacuum System Intake Piping
The duplex medical vacuum system must be fully compliant Each vacuum pump shall have a factory piped intake with
with the latest edition of NFPA 99. The package will consist integral flex connector, isolation valve, and check valve.
of two oil sealed rotary vane vacuum pumps, a control panel, Interconnecting piping shall consist of black iron pipe and
and a receiver sized for appropriate demand. Each pump shall fittings.
be connected to a common intake manifold. Each vacuum Vacuum Receiver
module must be designed to accommodate a standard pallet The vacuum receiver shall be ASME Code stamped, and rated
jack and have a maximum base width of 34" (86 cm). The for a minimum 150 PSIG design pressure.
receiver shall be ASME coded and have a three-valve bypass
system to allow for draining of the receiver without Control System
interrupting the vacuum service. A manual drain shall be The duplex control system shall be NEMA 12 and U.L.
provided on the receiver. The package shall be completely labeled. The control system shall provide automatic lead/lag
tested prior to shipment. sequencing with circuit breaker disconnects for each vacuum
pump with external operators, full voltage motor starters with
Vacuum Pump overload protection, redundant 120V control circuit
Each pump shall be of oil lubricated, dynamically balanced transformers, visual and audible reserve unit alarm with
multi-vane design with heavy duty, aluminum alloy vanes for isolated contacts for remote alarm, visual alarms for high
maximum heat dissipation and extended vane life. The discharge temperature shutdown with isolated contacts for
minimum vane warranty shall be 50,000 hours. The oil remote alarm, hand-off-auto lighted selector switches and
lubrication system shall be a pressure differential design with runtime hourmeters. A programmable logic controller (PLC)
full re-circulation and multi-stage exhaust oil separation rated shall control the automatic alternation of both vacuum pumps
at 99.998% efficiency. The oil cooler shall be a single pass, with provisions for simultaneous operation if required, and
cross flow type with a dedicated cooling fan. Water vapor automatic activation of reserve unit if required. The control
condensation in the cylinder shall be prevented by means of system shall include a minimum run timer. A vacuum gauge
an automatic gas ballast valve. Additionally, a non-return shall be provided in the control panel.
valve to prevent oil migration upon shutdown, a back pressure
gauge to indicate exhaust oil separator element change, a high Statement of Warranty
discharge temperature switch, oil drain valve, oil sight glass, BeaconMedæs warrants all LifeLine® Lubricated Medical
and flexible connector for each pump shall be included. Vacuum Systems are to be free of defects in material and
workmanship under normal use for a period not to exceed
Vacuum Pump Drive thirty (30) months from date of shipment, or twenty four (24)
The pump shall be direct driven. Torque is transmitted from months from date of start-up.
the motor to the pump through a shaft coupling.
Vacuum Pump Motor
The motor shall be a continuous duty, NEMA rated, C-face,
TEFC, 1800 RPM, with 1.15 service factor suitable for 208V
or 230/460V, 60 hertz, 3 phase electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-410-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 88 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 90 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 92 Chapter 6
BeaconMedæs Medical Gas Design Guide
Elevations ……………………………… 94
P&ID …………………………………… 95
Electrical ………………………………… 96
Installation
5 & 7.5 Hp. …………………………… 97
10 Hp. …………………………………… 98
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
TRIPLEX
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Modular Triplex System (5 - 10 HP)
SPECIFICATION
Vacuum System Intake Piping
The triplex medical vacuum system must be fully compliant Each vacuum pump shall have a factory piped intake with
with the latest edition of NFPA 99. The package will consist integral flex connector, isolation valve, and check valve.
of three oil sealed rotary vane vacuum pumps, a control panel, Interconnecting piping shall consist of black iron pipe and
and a receiver sized for appropriate demand. Each module fittings.
shall have a common intake manifold. Each vacuum module Vacuum Receiver
must be designed to accommodate a standard pallet jack and The vacuum receiver shall be ASME Code stamped, and rated
have a maximum base width of 34" (86 cm). The receiver for a minimum 150 PSIG design pressure
shall be ASME coded and have a three-valve bypass system to
allow for draining of the receiver without interrupting the Control System
vacuum service. A manual drain shall be provided on the The triplex control system shall be NEMA 12 and U.L.
receiver. The package shall be completely tested prior to labeled. The control system shall provide automatic lead/lag
shipment. sequencing with circuit breaker disconnects for each vacuum
pump with external operators, full voltage motor starters with
Vacuum Pump overload protection, redundant 120V control circuit
Each pump shall be of an oil lubricated, dynamically balanced transformers, visual and audible reserve unit alarm with
multi-vane design with heavy duty, aluminum alloy vanes for isolated contacts for remote alarm, visual alarms for high
maximum heat dissipation and extended vane life. The temperature shutdown with isolated contacts for remote alarm,
minimum vane warranty shall be 50,000 hours. The oil hand-off-auto lighted selector switches and runtime
lubrication system shall be a pressure differential design with hourmeters. A programmable logic controller (PLC) shall
full re-circulation and multi-stage exhaust oil separation rated control the automatic alternation of the vacuum pumps with
at 99.998% efficiency. The oil cooler shall be a single pass, provisions for simultaneous operation if required, and
cross flow type with a dedicated cooling fan. Water vapor automatic activation of reserve unit if required. The control
condensation in the cylinder shall be prevented by means of system shall include a minimum run timer. A vacuum gauge
an automatic gas ballast valve. Additionally, a non-return shall be provided in the control panel.
valve to prevent oil migration upon shutdown, a back pressure
gauge to indicate exhaust oil separator element change, a high Statement of Warranty
discharge temperature switch, oil drain valve, oil sight glass, BeaconMedæs warrants all LifeLine® Lubricated Medical
and flexible connector for each pump shall be included. Vacuum Systems are to be free of defects in material and
workmanship under normal use for a period not to exceed
Vacuum Pump Drive thirty (30) months from date of shipment, or twenty four (24)
The pump shall be direct driven. Torque is transmitted from months from date of start-up.
the motor to the pump through a shaft coupling.
Vacuum Pump Motor
The motor shall be a continuous duty, NEMA rated, C-face,
TEFC, 1800 RPM, with 1.15 service factor suitable for 208 or
230/460V, 60 hertz, 3 phase electrical service.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-410-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Page 96 Chapter 6
BeaconMedæs Medical Gas Design Guide
Page 98 Chapter 6
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 0 0
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Modular Quad System (5 - 10 HP)
SPECIFICATION
Vacuum System Intake Piping
The quadruplex medical vacuum system must be fully Each vacuum pump shall have a factory piped intake with
compliant with the latest edition of NFPA 99. The package integral flex connector, isolation valve, and check valve.
will consist of four oil sealed rotary vane vacuum pumps, a Interconnecting piping shall consist of black iron pipe and
control panel, and a receiver sized for appropriate demand. fittings.
Each module shall have a common intake manifold. Each Vacuum Receiver
vacuum module must be designed to accommodate a standard The vacuum receiver shall be ASME Code stamped, and rated
pallet jack and have a maximum base width of 34" (86 cm). for a minimum 150 PSIG design pressure.
The receiver shall be ASME coded and have a three-valve
bypass system to allow for draining of the receiver without Control System
interrupting the vacuum service. A manual drain shall be The quadruplex control system shall be NEMA 12 and U.L.
provided on the receiver. The package shall be completely labeled. The control system shall provide automatic lead/lag
tested prior to shipment. sequencing with circuit breaker disconnects for each vacuum
pump with external operators, full voltage motor starters with
Vacuum Pump overload protection, redundant 120V control circuit
Each pump shall be of oil lubricated, dynamically balanced transformers, visual and audible reserve unit alarm with
multi-vane design with heavy duty, aluminum alloy vanes for isolated contacts for remote alarm, visual alarms for high
maximum heat dissipation and extended vane life. The temperature shutdown with isolated contacts for remote alarm,
minimum vane warranty shall be 50,000 hours. The oil hand-off-auto lighted selector switches and runtime
lubrication system shall be a pressure differential design with hourmeters. A programmable logic controller (PLC) shall
full re-circulation and multi-stage exhaust oil separation rated control the automatic alternation of the vacuum pumps with
at 99.998% efficiency. The oil cooler shall be a single pass, provisions for simultaneous operation if required, and
cross flow type with a dedicated cooling fan. Water vapor automatic activation of reserve unit if required. The control
condensation in the cylinder shall be prevented by means of system shall include a minimum run timer. A vacuum gauge
an automatic gas ballast valve. Additionally, a non-return shall be provided in the control panel.
valve to prevent oil migration upon shutdown, a back pressure
gauge to indicate exhaust oil separator element change, a high Statement of Warranty
discharge temperature switch, oil drain valve, oil sight glass, BeaconMedæs warrants all LifeLine® Lubricated Medical
and flexible connector for each pump shall be included. Vacuum Systems are to be free of defects in material and
workmanship under normal use for a period not to exceed
Vacuum Pump Drive thirty (30) months from date of shipment, or twenty four (24)
The pump shall be direct driven. Torque is transmitted from months from date of start-up.
the motor to the pump through a shaft coupling.
Vacuum Pump Motor
The motor shall be a continuous duty, NEMA rated, C-face,
TEFC, 1800 RPM, with 1.15 service factor suitable
for 208 or 230/460V, 60 hertz, 3 phase electrical service.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect three vacuum pumps in operation.
6
Total weight for a 5 duplex module w/control panel (1203#) and a 5 duplex module (1009#).
Total weight for a 7.5 duplex module w/control panel (1547#) and a 7.5 duplex module (1354#).
Total weight for a 10 duplex module w/control panel (2065#) and a 10 duplex module (1875#).
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-410-03
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 0 6
Electrical
5 & 7.5 Hp. ……………………………… 109
10 Hp. ………………………………… 110
Installation
5 & 7.5 Hp. ……………………………… 111
10 Hp. ………………………………… 112
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Duplex System (5 - 10 HP)
SPECIFICATION
Vacuum System Vacuum Pump Motor
The duplex medical vacuum system must be fully compliant The motors shall be a continuous duty, NEMA rated, C-face,
with the latest edition of NFPA 99. The package will consist TEFC, 1800 RPM, with 1.15 service factor suitable for 208 or
of two oil sealed rotary vane vacuum pumps, a control panel, 230/460V, 60 hz, 3 phase electrical service.
and a receiver sized for appropriate demand all mounted on a Intake Piping
common base frame. The receiver shall be ASME coded and Each vacuum pump shall have a factory piped intake with
have a three-valve bypass system to allow for draining of the integral flex connector, isolation valve, and check valve.
receiver without interrupting the vacuum service. A manual Interconnecting piping shall consist of black iron pipe and
drain shall be provided on the receiver. Each pump and the fittings.
receiver shall be connected to a common intake manifold. A
single point of connection to the intake of the system shall be Vacuum Receiver
provided. A single point of connection to the electrical panel The vacuum receiver shall be ASME Code stamped, and rated
of the system shall also be provided. The package shall be for a minimum 150 PSIG design pressure.
completely tested prior to shipment. Control System
Vacuum Pump The duplex control system shall be NEMA 12 and U.L.
Each pump shall be of oil lubricated, dynamically balanced Labeled. This control system shall provide automatic lead/lag
multi-vane design with heavy duty, aluminum alloy vanes for sequencing with circuit breaker disconnects for each vacuum
maximum heat dissipation and extended vane life. The pump with external operators, full voltage motor starters with
minimum vane warranty shall be 50,000 hours. The oil overload protection, redundant 120V control circuit
lubrication system shall be a pressure differential design with transformers, visual and audible reserve unit alarm with
full re-circulation and multi-stage exhaust oil separation rated isolated contacts for remote alarm, visual alarms for high
at 99.998% efficiency. The oil cooler shall be a single pass, temperature shutdown with isolated contacts for remote alarm,
cross flow type with a dedicated cooling fan. Water vapor hand-off-auto lighted selector switches and runtime
condensation in the cylinder shall be prevented by means of hourmeters. A programmable logic controller (PLC) shall
an automatic gas ballast valve. Additionally, a non-return control the automatic alternation of both vacuum pumps with
valve to prevent oil migration upon shutdown, a back pressure provisions for simultaneous operation if required, and
gauge to indicate exhaust oil separator element change, a high automatic activation of reserve unit if required. The control
discharge temperature switch, oil drain valve, oil sight glass, system shall include a minimum run timer. A vacuum gauge
and flexible connector for each pump shall be included. shall be provided in the control panel.
Vacuum Pump Drive Statement of Warranty
The pump shall be direct driven. Torque is transmitted from BeaconMedæs warrants all LifeLine® Lubricated Medical
the motor to the pump through a shaft coupling. Vacuum Systems to be free of defects in material and
workmanship under normal use for a period not to exceed
thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-420-01
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 1 4
Installation
15 Hp. ………………………………… 118
20 & 25 Hp. …………………………… 119
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
DUPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
DUPLEX
BASE
LifeLine® Lubricated Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Duplex System (15 - 25 HP)
SPECIFICATION
Vacuum System Vacuum Pump Motor
The duplex medical vacuum system must be fully compliant The motor shall be a continuous duty, NEMA rated, C-face,
with the latest edition of NFPA 99. The package will consist TEFC, 1200 RPM, with 1.15 service factor suitable for 208 or
of two oil sealed rotary vane vacuum pumps, a control panel, 230/460V, 60 hertz, 3 phase electrical service.
and a receiver sized for appropriate demand all mounted on a Intake Piping
common base frame. The receiver shall be ASME coded and Each vacuum pump shall have a factory piped intake with
have a three-valve bypass system to allow for draining of the integral flex connector, isolation valve, and check valve.
receiver without interrupting the vacuum service. A manual Interconnecting piping shall consist of black iron pipe and
drain shall be provided on the receiver. Each pump and the fittings.
receiver shall be connected to a common intake manifold. A
single point of connection to the intake of the system shall be Vacuum Receiver
provided. A single point of connection to the electrical panel The vacuum receiver shall be ASME Code stamped, and rated
of the system shall also be provided. The package shall be for a minimum 150 PSIG design pressure.
completely tested prior to shipment. Control System
Vacuum Pump The duplex control system shall be NEMA 12 and U.L.
Each pump shall be of oil lubricated, dynamically balanced labeled. The control system shall provide automatic lead/lag
multi-vane design with heavy duty, aluminum alloy vanes for sequencing with circuit breaker disconnects for each vacuum
maximum heat dissipation and extended vane life. The pump with external operators, full voltage motor starters with
minimum vane warranty shall be 50,000 hours. The vane overload protection, redundant 120V control circuit
housing shall be a double walled cylinder construction. The transformers, visual and audible reserve unit alarm with
oil lubrication system shall be a pressure differential design isolated contacts for remote alarm, visual alarms for high
with full re-circulation and multi-stage exhaust oil separation temperature shutdown with isolated contacts for remote alarm,
rated at 99.998% efficiency. The oil cooler shall be a two hand-off-auto lighted selector switches and runtime
pass, cross flow air to oil type. Water vapor condensation in hourmeters. A programmable logic controller (PLC) shall
the cylinder shall be prevented by means of an automatic gas control the automatic alternation of both vacuum pumps with
ballast valve. Each pump shall have a 5-micron inlet filter. provisions for simultaneous operation if required, and
Additionally, a non-return valve to prevent oil migration upon automatic activation of reserve unit if required. The control
shutdown, a back pressure gauge to indicate exhaust oil system shall include a minimum run timer. A vacuum gauge
separator element change, a high discharge temperature shall be provided in the control panel.
switch, oil drain valve, oil sight glass, and flexible connector Statement of Warranty
for each pump shall be included. BeaconMedæs warrants all LifeLine® Lubricated Medical
Vacuum Pump Drive Vacuum Systems are to be free of defects in material and
The pump shall be direct driven. Torque is transmitted from workmanship under normal use for a period not to exceed
the motor to the pump through a shaft coupling. thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-420-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 2 1
Installation
5 & 7.5 Hp. ……………………………… 125
10 Hp. ………………………………… 126
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
TRIPLEX
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Triplex System (5 - 10 HP)
SPECIFICATION
Vacuum System Vacuum Pump Motor
The triplex medical vacuum system must be fully compliant The motor shall be a continuous duty, NEMA rated, C-face,
with the latest edition of NFPA 99. The package will consist TEFC, 1800 RPM, with 1.15 service factor suitable for 208 or
of three oil sealed rotary vane vacuum pumps, a control panel, 230/460V, 60 hertz, 3 phase electrical service.
and a receiver sized for appropriate demand all mounted on a Intake Piping
common base frame. The receiver shall be ASME coded and Each vacuum pump shall have a factory piped intake with
have a three-valve bypass system to allow for draining of the integral flex connector, isolation valve, and check valve.
receiver without interrupting the vacuum service. A manual Interconnecting piping shall consist of black iron pipe and
drain shall be provided on the receiver. Each pump and the fittings.
receiver shall be connected to a common intake manifold. A
single point of connection to the intake of the system shall be Vacuum Receiver
provided. A single point of connection to the electrical panel The vacuum receiver shall be ASME Code stamped, and rated
of the system shall also be provided. The package shall be for a minimum 150 PSIG design pressure.
completely tested prior to shipment. Control System
Vacuum Pump The triplex control system shall be NEMA 12 and U.L.
Each pump shall be of oil lubricated, dynamically balanced labeled. The control system shall provide automatic lead/lag
multi-vane design with heavy duty, aluminum alloy vanes for sequencing with circuit breaker disconnects for each vacuum
maximum heat dissipation and extended vane life. The pump with external operators, full voltage motor starters with
minimum vane warranty shall be 50,000 hours. The oil overload protection, redundant 120V control circuit
lubrication system shall be a pressure differential design with transformers, visual and audible reserve unit alarm with
full re-circulation and multi-stage exhaust oil separation rated isolated contacts for remote alarm, visual alarms for high
at 99.998% efficiency. The oil cooler shall be a single pass, temperature shutdown with isolated contacts for remote alarm,
cross flow type with a dedicated cooling fan. Water vapor hand-off-auto lighted selector switches and runtime
condensation in the cylinder shall be prevented by means of hourmeters. A programmable logic controller (PLC) shall
an automatic gas ballast valve. Additionally, a non-return control the automatic alternation of the vacuum pumps with
valve to prevent oil migration upon shutdown, a back pressure provisions for simultaneous operation if required, and
gauge to indicate exhaust oil separator element change, a high automatic activation of reserve unit if required. The control
discharge temperature switch, oil drain valve, oil sight glass, system shall include a minimum run timer. A vacuum gauge
and flexible connector for each pump shall be included. shall be provided in the control panel.
Vacuum Pump Drive Statement of Warranty
The pump shall be direct driven. Torque is transmitted from BeaconMedæs warrants all LifeLine® Lubricated Medical
the motor to the pump through a shaft coupling. Vacuum Systems are to be free of defects in material and
workmanship under normal use for a period not to exceed
thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect two vacuum pumps in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-420-03
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 2 8
Installation
15 Hp. ………………………………… 132
20 & 25 Hp. …………………………… 133
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
TRIPLEX
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Triplex System (15 – 25 HP)
SPECIFICATION
Vacuum System Vacuum Pump Motor
The triplex medical vacuum system must be fully compliant The motor shall be a continuous duty, NEMA rated, C-face,
with the latest edition of NFPA 99. The package will consist TEFC, 1200 RPM, with 1.15 service factor suitable for 208 or
of three oil sealed rotary vane vacuum pumps, a control panel, 230/460V, 60 hertz, 3 phase electrical service.
and a receiver sized for appropriate demand all mounted on a Intake Piping
common base frame. The receiver shall be ASME coded and Each vacuum pump shall have a factory piped intake with
have a three-valve bypass system to allow for draining of the integral flex connector, isolation valve, and check valve.
receiver without interrupting the vacuum service. A manual Interconnecting piping shall consist of black iron pipe and
drain shall be provided on the receiver. Each pump and the fittings.
receiver shall be connected to a common intake manifold. A
single point of connection to the intake of the system shall be Vacuum Receiver
provided. A single point of connection to the electrical panel The vacuum receiver shall be ASME Code stamped, and rated
of the system shall also be provided. The package shall be for a minimum 150 PSIG design pressure.
completely tested prior to shipment. Control System
Vacuum Pump The triplex control system shall be NEMA 12 and U.L.
Each pump shall be of an oil lubricated, dynamically balanced labeled. The control system shall provide automatic lead/lag
multi-vane design with heavy duty, aluminum alloy vanes for sequencing with circuit breaker disconnects for each vacuum
maximum heat dissipation and extended vane life. The pump with external operators, full voltage motor starters with
minimum vane warranty shall be 50,000 hours. The vane overload protection, redundant 120V control circuit
housing shall be a double walled cylinder construction. The transformers, visual and audible reserve unit alarm with
oil lubrication system shall be a pressure differential design isolated contacts for remote alarm, visual alarms for high
with full re-circulation and multi-stage exhaust oil separation temperature shutdown with isolated contacts for remote alarm,
rated at 99.998% efficiency. The oil cooler shall be a two hand-off-auto lighted selector switches and runtime
pass, cross flow air to oil type. Water vapor condensation in hourmeters. A programmable logic controller (PLC) shall
the cylinder shall be prevented by means of an automatic gas control the automatic alternation of the vacuum pumps with
ballast valve. Each pump shall have a 5-micron inlet filter. provisions for simultaneous operation if required, and
Additionally, a non-return valve to prevent oil Additionally, a automatic activation of reserve unit if required. The control
non-return valve to prevent oil migration upon shutdown, a system shall include a minimum run timer. A vacuum gauge
back pressure gauge to indicate exhaust oil separator element shall be provided in the control panel.
change, a high discharge temperature switch, oil drain valve, Statement of Warranty
oil sight glass, and flexible connector for each pump shall be BeaconMedæs warrants all LifeLine® Lubricated Medical
included. Vacuum Systems are to be free of defects in material and
Vacuum Pump Drive workmanship under normal use for a period not to exceed
The pump shall be direct driven. Torque is transmitted from thirty (30) months from date of shipment, or twenty four (24)
the motor to the pump through a shaft coupling. months from date of start-up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-420-04
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 3 5
Installation
5 & 7.5 Hp. ……………………………… 139
10 Hp. ………………………………… 140
QUAD 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
LifeLine® Lubricated Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Quad System (5 - 10 HP)
SPECIFICATION
Vacuum System Vacuum Pump Motor
The quadruplex medical vacuum system must be fully The motor shall be a continuous duty, NEMA rated, C-face,
compliant with the latest edition of NFPA 99. The package TEFC, 1800 RPM, with 1.15 service factor suitable for 208 or
will consist of four oil sealed rotary vane vacuum pumps, a 230/460V, 60 hertz, 3 phase electrical service.
control panel, and a receiver sized for appropriate demand all Intake Piping
mounted on a common base frame. The receiver shall be Each vacuum pump shall have a factory piped intake with
ASME coded and have a three-valve bypass system to allow integral flex connector, isolation valve, and check valve.
for draining of the receiver without interrupting the vacuum Interconnecting piping shall consist of black iron pipe and
service. A manual drain shall be provided on the receiver. fittings.
Each pump and the receiver shall be connected to a common
intake manifold. A single point of connection to the intake of Vacuum Receiver
the system shall be provided. A single point of connection to The vacuum receiver shall be ASME Code stamped, and rated
the electrical panel of the system shall also be provided. The for a minimum 150 PSIG design pressure.
package shall be completely tested prior to shipment. Control System
Vacuum Pump The quadruplex control system shall be NEMA 12 and U.L.
Each pump shall be of oil lubricated, dynamically balanced labeled. The control system shall provide automatic lead/lag
multi-vane design with heavy duty, aluminum alloy vanes for sequencing with circuit breaker disconnects for each vacuum
maximum heat dissipation and extended vane life. The pump with external operators full voltage motor starters with
minimum vane warranty shall be 50,000 hours. The oil overload protection, redundant 120V control circuit
lubrication system shall be a pressure differential design with transformers, visual and audible reserve unit alarm with
full re-circulation and multi-stage exhaust oil separation rated isolated contacts for remote alarm, visual alarms for high
at 99.998% efficiency. The oil cooler shall be a single pass, temperature shutdown with isolated contacts for remote alarm,
cross flow type with a dedicated cooling fan. Water vapor hand-off-auto lighted selector switches and runtime
condensation in the cylinder shall be prevented by means of hourmeters. A programmable logic controller (PLC) shall
an automatic gas ballast valve. Additionally, a non-return control the automatic alternation of the vacuum pumps with
valve to prevent oil migration upon shutdown, a back pressure provisions for simultaneous operation if required, and
gauge to indicate exhaust oil separator element change, a high automatic activation of reserve unit if required. The control
discharge temperature switch, oil drain valve, oil sight glass, system shall include a minimum run timer. A vacuum gauge
and flexible connector for each pump shall be included. shall be provided in the control panel.
Vacuum Pump Drive Statement of Warranty
The pump shall be direct driven. Torque is transmitted from BeaconMedæs warrants all LifeLine® Lubricated Medical
the motor to the pump through a shaft coupling. Vacuum Systems are to be free of defects in material and
workmanship under normal use for a period not to exceed
thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect three vacuum pumps in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-420-05
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
General Specification … … … … … … 1 4 2
Installation
15 Hp. ………………………………… 146
20 & 25 Hp. …………………………… 147
QUAD15-25
5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
TRIPLEX
(803) 817-5600 or (803) 817-5750 (fax) for further information.
DUPLEX
QUAD
LifeLine® Lubricated Medical Rotary Vacuum Base Mount Single Point Connection (SPC)
Quad System (15 - 25 HP)
SPECIFICATION
Vacuum System Vacuum Pump Motor
The quadruplex medical vacuum system must be fully The motor shall be a continuous duty, NEMA rated, C-face,
compliant with the latest edition of NFPA 99. The package TEFC, 1200 RPM, with 1.15 service factor suitable for 208 or
will consist of four oil sealed rotary vane vacuum pumps, a 230/460V, 60 hertz, 3 phase electrical service.
control panel, and a receiver sized for appropriate demand all Intake Piping
mounted on a common base frame. The receiver shall be Each vacuum pump shall have a factory piped intake with
ASME coded and have a three-valve bypass system to allow integral flex connector, isolation valve, and check valve.
for draining of the receiver without interrupting the vacuum Interconnecting piping shall consist of black iron pipe and
service. A manual drain shall be provided on the receiver. fittings.
Each pump and the receiver shall be connected to a common
intake manifold. A single point of connection to the intake of Vacuum Receiver
the system shall be provided. A single point of connection to The vacuum receiver shall be ASME Code stamped, and rated
the electrical panel of the system shall also be provided. The for a minimum 150 PSIG design pressure.
package shall be completely tested prior to shipment. Control System
Vacuum Pump The quadruplex control system shall be NEMA 12 and U.L.
Each pump shall be of an oil lubricated, dynamically balanced labeled. The control system shall provide automatic lead/lag
multi-vane design with heavy duty, aluminum alloy vanes for sequencing with circuit breaker disconnects for each vacuum
maximum heat dissipation and extended vane life. The pump with external operators, full voltage motor starters with
minimum vane warranty shall be 50,000 hours. The vane overload protection, redundant 120V control circuit
housing shall be a double walled cylinder construction. The transformers, visual and audible reserve unit alarm with
oil lubrication system shall be a pressure differential design isolated contacts for remote alarm, visual alarms for high
with full re-circulation and multi-stage exhaust oil separation temperature shutdown with isolated contacts for remote alarm,
rated at 99.998% efficiency. The oil cooler shall be a two hand-off-auto lighted selector switches and runtime
pass, cross flow air to oil type. Water vapor condensation in hourmeters. A programmable logic controller (PLC) shall
the cylinder shall be prevented by means of an automatic gas control the automatic alternation of the vacuum pumps with
ballast valve. Each pump shall have a 5-micron inlet filter. provisions for simultaneous operation if required, and
Additionally, a non-return valve to prevent oil migration upon automatic activation of reserve unit if required. The control
shutdown, a back pressure gauge to indicate exhaust oil system shall include a minimum run timer. A vacuum gauge
separator element change, a high discharge temperature shall be provided in the control panel.
switch, oil drain valve, oil sight glass, and flexible connector Statement of Warranty
for each pump shall be included. BeaconMedæs warrants all LifeLine® Lubricated Medical
Vacuum Pump Drive Vacuum Systems are to be free of defects in material and
The pump shall be direct driven. Torque is transmitted from workmanship under normal use for a period not to exceed
the motor to the pump through a shaft coupling. thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-420-06
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
DUPLEX 3-10
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Liquid Ring “Delta Camel” Medical Vacuum Base Mount Single Point Connection (SPC)
Duplex System (3 - 10 HP)
SPECIFICATION
Vacuum System Re-circulation and Seal Water
The duplex medical vacuum system must be fully compliant Under normal operation, the system shall not use more than
with the latest edition of NFPA 99. The package will consist 3/4 gpm seal water. The system shall include a reservoir
of two oil-free liquid ring vacuum pumps, a control panel, sufficient for up to 48 hours of operation without a fresh
and a receiver sized for appropriate demand all mounted on a water supply. The system is self contained and air-cooled. No
common base frame. The receiver shall be ASME coded and cooling water is required for the operation of the re-
have a three valve bypass system to allow for draining of the circulation system.
receiver without interrupting the vacuum service. A manual Intake Piping
drain shall be provided on the receiver. The pumps and Each vacuum pump shall have a factory piped intake.
receiver shall be connected to a common intake manifold. A Interconnecting piping shall consist of a combination of
single point of connection to the intake of the system shall be brazed ASTM B-819 copper tubing, brass pipe and fittings.
provided. A single point of connection to the electrical panel
of the system shall also be provided. The package shall be Vacuum Receiver
completely tested prior to shipment. The vacuum receiver shall be ASME Code stamped, and
rated for a minimum 150 PSIG design pressure. The receiver
Vacuum Pump vessel shall include a sight glass with manual drain and
The pumps shall be a NASH Delta oil-free, single-stage, factory pre-piped three-valve receiver bypass.
positive displacement, and non-pulsating liquid ring type.
The pump will be fitted with mechanical seals. Each pump Control System
The duplex control system shall be NEMA 12 and U.L.
shall be equipped with a check valve to prevent backflow labeled. The control system shall provide automatic lead/lag
through off-cycle units, a vacuum relief valve and an sequencing with circuit breaker disconnects for each vacuum
isolation valve. pump with external operators, full voltage motor starters with
Vacuum Pump Drive overload protection, redundant 120V control circuit
The pumps shall be direct driven. Torque is transmitted from transformers, visual and audible reserve unit alarm with
the motor to the pump through a shaft coupling. isolated contacts for remote alarm, hand-off-auto lighted
selector switches and runtime hourmeters. A programmable
Vacuum Pump Motor logic controller (PLC) shall control the automatic alternation
The motor shall be a continuous duty, NEMA rated, open of both vacuum pumps with provisions for simultaneous
drip proof, 1800 RPM, with 1.15 service factor suitable for operation if required, and automatic activation of reserve unit
208V or 230/460V, 60 hertz, 3 phase electrical service. if required. The control system shall include an automatic
minimum run time adjustment to control run time based on
demand. A vacuum gauge shall be provided in the control
panel.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
Standard receiver
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-510-05
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
BASE MOUNT
TRIPLEX 5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Liquid Ring “Delta Camel” Medical Vacuum Base Mount Single Point Connection (SPC)
Triplex System (5 - 10 HP)
SPECIFICATION
Vacuum System Re-circulation and Seal Water
The triplex medical vacuum system must be fully compliant Under normal operation, the system shall not use more than
with the latest edition of NFPA 99. The package will consist 3/4 gpm of seal water per operating pump. The system shall
of three oil-free liquid ring vacuum pumps, a control panel, include a reservoir sufficient for up to 48 hours of operation
and a receiver sized for appropriate demand all mounted on a without a fresh water supply. The system is self contained
common base frame. The receiver shall be ASME coded and and air-cooled. No cooling water is required for the operation
have a three valve bypass system to allow for draining of the of the re-circulation system.
receiver without interrupting the vacuum service. A manual Intake Piping
drain shall be provided on the receiver. The pumps and Each vacuum pump shall have a factory piped intake.
receiver shall be connected to a common intake manifold. A Interconnecting piping shall consist of a combination of
single point of connection to the intake of the system shall be brazed ASTM B-819 copper tubing, brass pipe and fittings.
provided. A single point of connection to the electrical panel
of the system shall also be provided. The package shall be Vacuum Receiver
completely tested prior to shipment. The vacuum receiver shall be ASME Code stamped and rated
for a minimum 150 PSIG design pressure. The receiver
Vacuum Pump vessel shall include a sight glass with manual drain and
The pumps shall be a NASH Delta oil-free, single-stage, factory pre-piped three-valve receiver bypass.
positive displacement, and non-pulsating liquid ring type.
The pump will be fitted with mechanical seals. Each pump Control System
The triplex control system shall be NEMA 12 and U.L.
shall be equipped with a check valve to prevent backflow
labeled. The control system shall provide automatic lead/lag
through off-cycle units, a vacuum relief valve and an
sequencing with circuit breaker disconnects for each vacuum
isolation valve.
pump with external operators, full voltage motor starters with
Vacuum Pump Drive overload protection, redundant 120V control circuit
The pumps shall be direct driven. Torque is transmitted from transformers, visual and audible reserve unit alarm with
the motor to the pump through a shaft coupling.
isolated contacts for remote alarm, hand-off-auto lighted
Vacuum Pump Motor selector switches and runtime hourmeters. A programmable
The motor shall be a continuous duty, NEMA rated, open logic controller (PLC) shall control the automatic alternation
drip proof, 1800 RPM, with 1.15 service factor suitable for of the vacuum pumps with provisions for simultaneous
208V or 230/460V, 60 hertz, 3 phase electrical service.
operation if required, and automatic activation of reserve unit
if required. The control system shall include an automatic
minimum run time adjustment to control run time based on
demand. A vacuum gauge shall be provided in the control
panel.
1
Notes: Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
Standard receiver
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-510-06
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
DUPLEX 3-5
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 01/16/2008
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Notes: 1
Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-700-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 01/16/2008
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and
workmanship under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Installation
5-7.5 Hp. …………………………… 259
10-15 Hp. …………………………… 260
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
DUPLEX 5-15
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Notes: 1
Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-710-05
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Installation
The installation of this vacuum technology is limited to a maximum of 4,000 feet elevation above sea level. For installation of this
equipment above 4,000 feet elevation, please contact the factory.
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and workmanship
under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24) months from date of start-
up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
TRIPLEX 5
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Notes: 1
Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect two vacuum pumps in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-710-08
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and workmanship
under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24) months from date of start-
up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Installation
7.5 Hp. ……………………………… 272
10-15 Hp. …………………………… 273
TRIPLEX 7.5-15
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Notes: 1
Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
* Indicates standard receiver
5
All noise levels are shown in dB(A) and reflect two vacuum pumps in operation.
6
Total weight for a 7.5 duplex module w/triplex control panel (1950#) and a 7.5 simplex module (909#)
Total weight for a 10 duplex module w/triplex control panel (2088#) and a 10 simplex module (1018#)
Total weight for a 15 duplex module w/triplex control panel (2236#) and a 15 simplex module (1092#)
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-710-06
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and workmanship
under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24) months from date of start-
up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Installation
5-7.5 Hp. …………………………… 279
10-15 Hp. …………………………… 280
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
QUAD 5-15
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-710-07
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and workmanship
under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24) months from date of start-
up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Installation
5-7.5 Hp. …………………………… 286
10-15 Hp. …………………………… 287
BASE MOUNT
DUPLEX 5-15
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
LifeLine® Oil-Less O2 Assured Claw Medical Vacuum Base Mount Single Point Connection (SPC)
Duplex System (5 - 15 HP)
SPECIFICATION
Vacuum System Intake Piping
The duplex medical vacuum system is fully compliant with Each vacuum pump has a factory piped intake with integral
the latest edition of NFPA 99. The package consists of two flex connector, isolation valve, and check valve.
"oil-less" rotary claw vacuum pumps, a control panel, and a Interconnecting piping consists of black iron pipe and fittings.
receiver sized for appropriate demand all mounted on a Vacuum Receiver
common base frame. The receiver is ASME coded and has a The vacuum receiver is ASME Code stamped, and rated for a
three-valve bypass system to allow for draining of the receiver minimum 150 PSIG design pressure.
without interrupting the vacuum service. A manual drain is
provided on the receiver. Each pump and the receiver is Control System
connected to a common intake manifold. A single point of The duplex control system is NEMA 12 and U.L. labeled. The
connection to the intake of the system is provided. A single control system provides automatic lead/lag sequencing, circuit
point of connection to the electrical panel of the system is also breaker disconnects with external operators for each vacuum
provided. The package is completely tested prior to shipment. pump, full voltage motor starters with overload protection,
and redundant 120V control circuit transformers. The control
Vacuum Pump system provides visual and audible reserve unit alarm for high
Each pump is a direct driven, non-contacting claw type, discharge temperature and high inlet vacuum shutdowns with
capable of operating at 27” Hg (sea level) continuous duty for isolated contacts for remote alarm, hand-off-auto lighted
a 5 hp, and 22.5” Hg (sea level) continuous duty for the 7.5, selector switches and runtime hourmeters. A programmable
10 & 15 hp. The pumping chamber is oil free. The pump is logic controller (PLC) controls the automatic alternation of the
completely air-cooled with no water requirements. The pump vacuum pumps with provisions for simultaneous operation
has an inlet air filter and is equipped with a vacuum relief along with the automatic activation of reserve unit if required.
valve, check valve to prevent backflow through off-cycle A vacuum gauge is provided in the control panel.
units, flexible connector, isolation valve, high discharge
temperature switch, high inlet vacuum switch, oil drain valve, Oxygen Compatibility
oil sight glass, and exhaust muffler at each pump location. Each vacuum pump is capable of operating safely with up to
60% oxygen content in the compression chamber. All parts in
Vacuum Pump Drive contact with the flow stream, gear casing, and bearing
The pump is direct driven. Torque is transmitted from the
surfaces are cleaned with oxygen compatible cleaner. The
motor to the pump through a shaft coupling. The claws are
pump is assembled and tested in a clean room with dedicated
synchronized by heavy-duty precision timing gears.
tools. The inlet filter is constructed of a fiberglass media to
Vacuum Pump Motor insure there is no fuel to ignite in the compression chamber.
The motor is a continuous duty, NEMA rated, C-face, TEFC, The lubricant in the gear casing as well as the grease used to
3450 RPM, suitable for 208 or 230/460V, 60 hertz, 3-phase lubricate the bearings (10 & 15 hp models only) is a special
electrical service. oxygen compatible formula. Safe for WAGD applications.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-720-05
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Installation
The installation of this vacuum technology is limited to a maximum of 4,000 feet elevation above sea level. For installation of this
equipment above 4,000 feet elevation, please contact the factory
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and workmanship
under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24) months from date of start-
up
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
BASE MOUNT
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
TRIPLEX 5
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
LifeLine® Oil-Less O2 Assured Claw Medical Vacuum Base Mount Single Point Connection (SPC)
Triplex System (5 HP)
SPECIFICATION
Vacuum System Intake Piping
The triplex medical vacuum system is fully compliant with the Each vacuum pump has a factory piped intake with integral
latest edition of NFPA 99. The package consists of three "oil- flex connector, isolation valve, and check valve.
less" rotary claw vacuum pumps, a control panel, and a Interconnecting piping consists of black iron pipe and fittings.
receiver sized for appropriate demand all mounted on a Vacuum Receiver
common base frame. The receiver is ASME coded and has a The vacuum receiver is ASME Code stamped, and rated for a
three-valve bypass system to allow for draining of the receiver minimum 150 PSIG design pressure.
without interrupting the vacuum service. A manual drain is
provided on the receiver. Each pump and the receiver is Control System
connected to a common intake manifold. A single point of The triplex control system is NEMA 12 and U.L. labeled. The
connection to the intake of the system is provided. A single control system provides automatic lead/lag sequencing, circuit
point of connection to the electrical panel of the system is also breaker disconnects with external operators for each vacuum
provided. The package is completely tested prior to shipment. pump, full voltage motor starters with overload protection,
and redundant 120V control circuit transformers. The control
Vacuum Pump system provides visual and audible reserve unit alarm for high
Each pump is a direct driven, non-contacting claw type, discharge temperature and high inlet vacuum shutdowns with
capable of operating at 27” Hg (sea level) continuous duty. isolated contacts for remote alarm, hand-off-auto lighted
The pumping chamber is oil free. The pump is completely air- selector switches and runtime hourmeters. A programmable
cooled with no water requirements. The pump has an inlet air logic controller (PLC) controls the automatic alternation of the
filter and is equipped with a vacuum relief valve, check valve vacuum pumps with provisions for simultaneous operation
to prevent backflow through off-cycle units, flexible along with the automatic activation of reserve unit if required.
connector, isolation valve, high discharge temperature switch, A vacuum gauge is provided in the control panel.
high inlet vacuum switch, oil drain valve, oil sight glass, and
exhaust muffler at each pump location. Oxygen Compatibility
Each vacuum pump is capable of operating safely with up to
Vacuum Pump Drive 60% oxygen content in the compression chamber. All parts in
The pump is direct driven. Torque is transmitted from the
contact with the flow stream, gear casing, and bearing
motor to the pump through a shaft coupling. The claws are
surfaces are cleaned with oxygen compatible cleaner. The
synchronized by heavy-duty precision timing gears.
pump is assembled and tested in a clean room with dedicated
Vacuum Pump Motor tools. The inlet filter is constructed of a fiberglass media to
The motor is a continuous duty, NEMA rated, C-face, TEFC, insure there is no fuel to ignite in the compression chamber.
3450 RPM, suitable for 208 or 230/460V, 60 hertz, 3-phase The lubricant in the gear casing as well as the grease used to
electrical service. lubricate the bearings (10 & 15 hp models only) is a special
oxygen compatible formula. Safe for WAGD applications.
Installation
The installation of this vacuum technology is limited to a
maximum of 4,000 feet elevation above sea level. For
installation of this equipment above 4,000 feet elevation,
please contact the factory
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-720-08
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and
workmanship under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Installation
5-7.5 Hp. …………………………… 299
10-15 Hp. …………………………… 300
TRIPLEX 7.5-15
This product has been designed to meet U.S. NFPA 99, latest edition.
BASE MOUNT
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
LifeLine® Oil-Less O2 Assured Claw Medical Vacuum Base Mount Single Point Connection (SPC)
Triplex System (7.5 - 15 HP)
SPECIFICATION
Vacuum System Vacuum Receiver
The triplex medical vacuum system is fully compliant with the The vacuum receiver is ASME Code stamped, and rated for a
latest edition of NFPA 99. The package consists of three "oil- minimum 150 PSIG design pressure.
less" rotary claw vacuum pumps, a control panel, and a
receiver sized for appropriate demand all mounted on a Control System
common base frame. The receiver is ASME coded and has a The triplex control system is NEMA 12 and U.L. labeled. The
three-valve bypass system to allow for draining of the receiver control system provides automatic lead/lag sequencing, circuit
without interrupting the vacuum service. A manual drain is breaker disconnects with external operators for each vacuum
provided on the receiver. Each pump and the receiver is pump, full voltage motor starters with overload protection,
connected to a common intake manifold. A single point of and redundant 120V control circuit transformers. The control
connection to the intake of the system is provided. A single system provides visual and audible reserve unit alarm for high
point of connection to the electrical panel of the system is also discharge temperature and high inlet vacuum shutdowns with
provided. The package is completely tested prior to shipment. isolated contacts for remote alarm, hand-off-auto lighted
selector switches and runtime hourmeters. A programmable
Vacuum Pump logic controller (PLC) controls the automatic alternation of the
Each pump is a direct driven, non-contacting claw type, vacuum pumps with provisions for simultaneous operation
capable of operating at 22.5” Hg (sea level) continuous duty. along with the automatic activation of reserve unit if required.
The pumping chamber is oil free. The pump is completely air- A vacuum gauge is provided in the control panel.
cooled with no water requirements. The pump has an inlet air
filter and is equipped with a vacuum relief valve, check valve Oxygen Compatibility
to prevent backflow through off-cycle units, flexible Each vacuum pump is capable of operating safely with up to
connector, isolation valve, high discharge temperature switch, 60% oxygen content in the compression chamber. All parts in
high inlet vacuum switch, oil drain valve, oil sight glass, and contact with the flow stream, gear casing, and bearing
exhaust muffler at each pump location. surfaces are cleaned with oxygen compatible cleaner. The
pump is assembled and tested in a clean room with dedicated
Vacuum Pump Drive
tools. The inlet filter is constructed of a fiberglass media to
The pump is direct driven. Torque is transmitted from the
insure there is no fuel to ignite in the compression chamber.
motor to the pump through a shaft coupling. The claws are
The lubricant in the gear casing as well as the grease used to
synchronized by heavy-duty precision timing gears.
lubricate the bearings (10 & 15 hp models only) is a special
Vacuum Pump Motor oxygen compatible formula. Safe for WAGD applications.
The motor is a continuous duty, NEMA rated, C-face, TEFC,
Installation
3450 RPM, suitable for 208 or 230/460V, 60 hertz, 3-phase
The installation of this vacuum technology is limited to a
electrical service.
maximum of 4,000 feet elevation above sea level. For
Intake Piping installation of this equipment above 4,000 feet elevation,
Each vacuum pump has a factory piped intake with integral please contact the factory.
flex connector, isolation valve, and check valve.
Interconnecting piping consists of black iron pipe and fittings.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-720-06
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and workmanship
under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24) months from date of start-
up.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
Installation
5-7.5 Hp. …………………………… 259
10-15 Hp. …………………………… 260
BASE MOUNT
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
QUAD 5-15
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
LifeLine® Oil-Less O2 Assured Claw Medical Vacuum Base Mount Single Point Connection (SPC)
Quad System (5 - 15 HP)
SPECIFICATION
Vacuum System Vacuum Receiver
The quadruplex medical vacuum system is fully compliant The vacuum receiver is ASME Code stamped, and rated for a
with the latest edition of NFPA 99. The package consists of minimum 150 PSIG design pressure.
four "oil-less" rotary claw vacuum pumps, a control panel, and Control System
a receiver sized for appropriate demand all mounted on a The quadruplex control system is NEMA 12 and U.L. labeled.
common base frame. The receiver is ASME coded and has a The control system provides automatic lead/lag sequencing,
three-valve bypass system to allow for draining of the receiver circuit breaker disconnects with external operators for each
without interrupting the vacuum service. A manual drain is vacuum pump, full voltage motor starters with overload
provided on the receiver. Each pump and the receiver is protection, and redundant 120V control circuit transformers.
connected to a common intake manifold. A single point of The control system provides visual and audible reserve unit
connection to the intake of the system is provided. A single alarm for high discharge temperature and high inlet vacuum
point of connection to the electrical panel of the system is also shutdowns with isolated contacts for remote alarm, hand-off-
provided. The package is completely tested prior to shipment. auto lighted selector switches and runtime hourmeters. A
Vacuum Pump programmable logic controller (PLC) controls the automatic
Each pump is a direct driven, non-contacting claw type, alternation of the vacuum pumps with provisions for
capable of operating at 27” Hg (sea level) continuous duty for simultaneous operation along with the automatic activation of
a 5 hp, and 22.5” Hg (sea level) continuous duty for the 7.5, reserve unit if required. A vacuum gauge is provided in the
10 & 15 hp. The pumping chamber is oil free. The pump is control panel.
completely air-cooled with no water requirements. The pump
Oxygen Compatibility
has an inlet air filter and is equipped with a vacuum relief
Each vacuum pump is capable of operating safely with up to
valve, check valve to prevent backflow through off-cycle
60% oxygen content in the compression chamber. All parts in
units, flexible connector, isolation valve, high discharge
contact with the flow stream, gear casing, and bearing
temperature switch, high inlet vacuum switch, oil drain valve,
surfaces are cleaned with oxygen compatible cleaner. The
oil sight glass, and exhaust muffler at each pump location.
pump is assembled and tested in a clean room with dedicated
Vacuum Pump Drive tools. The inlet filter is constructed of a fiberglass media to
The pump is direct driven. Torque is transmitted from the insure there is no fuel to ignite in the compression chamber.
motor to the pump through a shaft coupling. The claws are The lubricant in the gear casing as well as the grease used to
synchronized by heavy-duty precision timing gears. lubricate the bearings (10 & 15 hp models only) is a special
Vacuum Pump Motor oxygen compatible formula. Safe for WAGD applications.
The motor is a continuous duty, NEMA rated, C-face, TEFC, Installation
3450 RPM, suitable for 208 or 230/460V, 60 hertz, 3-phase The installation of this vacuum technology is limited to a
electrical service. maximum of 4,000 feet elevation above sea level. For
Intake Piping installation of this equipment above 4,000 feet elevation,
Each vacuum pump has a factory piped intake with integral please contact the factory
flex connector, isolation valve, and check valve.
Interconnecting piping consists of black iron pipe and fittings.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-720-07
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Standard Configuration
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and
workmanship under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
BeaconMedæs Medical Gas Design Guide
DUPLEX 3-5
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Notes: 1
Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2
All capacities are shown as NFPA system capacities (reserve vacuum pump on standby).
3
All system BTU/HR are shown with reserve vacuum pump on standby.
4
All noise levels are shown in dB(A) and reflect one vacuum pump in operation.
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-750-02
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 12/31/2007
(803) 817-5600 or (803) 817-5750 (fax) for further information.
Statement of Warranty
BeaconMedæs warrants all LifeLine® Oil-Less Claw Medical Vacuum Systems to be free of defects in material and
workmanship under normal use for a period not to exceed thirty (30) months from date of shipment, or twenty four (24)
months from date of start-up
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750
TM
13325 Carowinds Blvd • Charlotte, NC 28273 • Phone 1 888 4 MED GAS • Fax 704 588 4949
www.beaconmedaes.com