Fire Alarm Systems - Conventional Manual Call Points For Ex Areas

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Fire Alarm Systems | Conventional Manual Call Points for Ex Areas

Conventional Manual Call Points for Ex


Areas
www.boschsecurity.com

The Conventional Manual Call Points for Ex Areas are System Overview
used to manually activate the alarm in zones 1 and 2 at
risk of explosion.
The K type call points are encapsulated, intrinsically 1 2
EOL22(Ex)
safe call points and do not require any safety barriers.
The DM 1103 B‑Ex Manual Call Points for ex zones
must be connected via a Safety Barrier SB 3 incl.
DFA1101A-Ex
Input/Output Module DCA1192 (see system overview).

FLM-420/4-CON
DO1101A-Ex

DCA1192 SB3
DO1101A-Ex

DCA1192 SB3 DM 1103 B-Ex DM 1103 B-Ex

For DM 1103 B‑Ex:


Pos. Description
1 Non-ex area
2 Ex area zone 1 or 2
2 | Conventional Manual Call Points for Ex Areas

Functions – UEZ 1000 LSN


– UEZ 2000 LSN
In the event of an alarm, the glass pane (2) is broken – UGM 2020 LSN
first, then the pushbutton (3) is pressed hard. Thus
DKM 2014/2‑ex‑UGM Manual Call Point Type K, for
the switch triggers the alarm. Connection to UGM Conventional
A locking mechanism holds the pressed manual call • Can be connected directly to the UGM‑GLT Universal
point. Danger Detection System
The pushbutton can be reset with the reset lever.
This does not reset the alarm on the fire panel. DM 1103 B-Ex manual call point for ex area
• For connection to the LSN, an NBK 100 LSN interface
Certifications and Approvals is required.
• For use in explosive areas of zones 1 and 2, a safety
barrier and an input/output module are required,
Region Certification
which must be mounted in front of the ex area.
Europe CE DM 1103 • Cables can be inserted surface-mounted or flush-
mounted
CE DKM2014
Germany VdS G 297060 DKM 2014/2-ex/-GLU Parts Included

VdS G 295036 DM 1103 B-Ex Type Qt Components


y.
PTB 97 ATEX 3197 DKM 2014/2 / DKM
2014/2-GLU DKM 2014/2‑ex 1 Manual Call Point Type K, for ex areas,
Europe BASEE- Ex 98E2304 DM 1103 B-Ex for surface mounting
FA
DKM 2014/2‑ex‑UG 1 Manual Call Point Type K, for
M Connection to UGM Conventional, for
Installation/Configuration Notes ex areas, for surface mounting
• Manual call points must be illuminated sufficiently DM 1103 B-Ex 1 DM 1103 B-Ex manual call point, color
with daylight or another light source (including 1 red
emergency lighting, if present). 2 Key for DM1103B-Ex manual call point
• An installation height of 1400 mm ±200 mm, PG11 cable screws
measured from the middle of the manual call point to
the floor, must be maintained. Technical Specifications
• Manual call points must be installed along escape and
DKM 2014/2‑ex Manual Call Point Type K
rescue routes (e.g. exits, passageways, stairwells). DKM 2014/2‑ex‑UGM Manual Call Point Type K, for
• Further standards, guidelines and planning Connection to UGM Conventional
recommendations regarding the installation location
etc., should also be taken into consideration (see Fire Operating voltage 24 V DC
Detection manual).
• Regulations of local fire departments must be Switch contact Type 366 (encapsulated), II 2 G
EEx d II C
observed.
Maximum contact load 5 A / 250 V AC
Installation/configuration notes in accordance with
VdS/VDE 0,25 A / 250 V DC
• The distance between manual call points should not Cable entry • 1x M16 x 1.5 tightening
exceed 100 m according to DIN 14675 or 80 m diameter 4‑8 mm, EEx e II
according to VdS. • Blind plug: 1x M16 x1.5
• In high risk areas, manual call points should be EEx e II
installed at a distance of max. 40 m (VDE 0833 Part 2,
Point 7.2.6). Housing material Polyester, glass fiber reinforced
• According to VdS, up to 10 manual call points can be Colors Red, RAL 3001
connected to a primary line.
Dimensions (W x H x D) 136 x 138 x 88 mm
DKM 2014/2‑ex Manual Call Point Type K
• For connection to the LSN, an NBK 100 LSN Fire Weight Approx. 1800 g
Interface is required.
• Can be connected directly to the following Protection class as per EN 60529 IP 66
conventional control panels:
Permissible operating -25 °C to +40 °C
– BZ 1012 temperature
– BZ 1060
– UEZ 1000 GLT. Ex classification Eex emd IIC T6
• With an NBK 100 LSN Fire Interface, can be
connected to the following control panels:
– BZ 500 LSN
3 | Conventional Manual Call Points for Ex Areas

Test certificate / PTB No. 97-37001

ATEX approval no. PTB 97 ATEX 3197

DM 1103 B‑Ex Manual Call Point

Operating voltage 16V DC to 28V DC

Cable duct PG11 screws (2x)

Connection terminals 0.2 mm to 1.5 mm

Housing material Plastic, PC

Color Red, RAL 3000

Dimensions (W x H x D) 134.4 x 134.4 x 43.5 mm

Weight Approx. 200 g

Protection class as per EN 60529 IP 54

Permissible operating -25 °C to +60 °C


temperature

Permissible storage temperature -30 °C to +75 °C

Permissible relative humidity ≤100% at T≤34 °C

Ex classification EEx ib IIC T4

Ordering Information

DKM 2014/2‑ex Manual Call Point Type K


for ex area, surface-mounted, indirect alarm triggering,
conventional technology
Order number DKM 2014/2-ex

Key for Fire Detector Type K


Order number FMX-7743.0.0500

DKM 2014/2‑ex‑UGM Manual Call Point Type K, for Con-


nection to UGM Conventional
for ex area, surface-mounted, indirect alarm triggering
Order number DKM 2014/2-ex-UGM

Key for Fire Detector Type K


Order number FMX-7743.0.0500

DM 1103 B‑Ex Manual Call Point


for zone 1 and 2 areas at risk of explosion,
conventional technology
Order number DM1103B-Ex

SB3 Safety Barrier incl. DCA1192 Input/Output Module


limits the electrical energy between non-inherently
safe and inherently safe circuits
Order number SB3
Accessories
FMC‑SPGL‑DEIL Spare Glasses
For manual call points of Series DM, DKM, SKM,
FMC‑120 and FMC‑210.
1 unit = 5 spare glasses
Order number FMC-SPGL-DEIL
4 | Conventional Manual Call Points for Ex Areas

Represented by:

Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:


Bosch Security Systems, Inc. Bosch Security Systems B.V. Robert Bosch (SEA) Pte Ltd, Security Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
130 Perinton Parkway P.O. Box 80002 Systems 201 Building, No. 333 Fuquan Road Via Anhanguera, Km 98
Fairport, New York, 14450, USA 5617 BA Eindhoven, The Netherlands 11 Bishan Street 21 North IBP CEP 13065-900
Phone: +1 800 289 0096 Phone: + 31 40 2577 284 Singapore 573943 Changning District, Shanghai Campinas, Sao Paulo, Brazil
Fax: +1 585 223 9180 Fax: +31 40 2577 330 Phone: +65 6571 2808 200335 China Phone: +55 19 2103 2860
security.sales@us.bosch.com emea.securitysystems@bosch.com Fax: +65 6571 2699 Phone +86 21 22181111 Fax: +55 19 2103 2862
www.boschsecurity.us www.boschsecurity.com apr.securitysystems@bosch.com Fax: +86 21 22182398 al.securitysystems@bosch.com
www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com

© Bosch Security Systems 2012 | Data subject to change without notice