Vamp 59: Line Differential Protection Relay
Vamp 59: Line Differential Protection Relay
Vamp 59: Line Differential Protection Relay
User Manual
Trace back information:
Workspace VAMP Range version a4
Checked in 2018-02-13
Skribenta version 5.2.027
Table of Contents
Table of Contents
1 General ..................................................................................... 7
1.1 Legal notice ...................................................................... 7
1.2 Safety information ............................................................ 7
1.3 EU directive compliance .................................................. 9
1.4 Periodical testing .............................................................. 9
1.5 Purpose ............................................................................ 10
1.6 Relay features .................................................................. 10
1.6.1 User interface ...................................................... 11
1.7 Abbreviations ................................................................... 12
4 Introduction ............................................................................. 45
4.1 Main features ................................................................... 45
4.2 Principles of numerical protection techniques ................. 46
V59/en M/A010 3
Table of Contents
4 V59/en M/A010
Table of Contents
10 Application ...............................................................................187
10.1 Line protection and auto-reclosing ...................................187
V59/en M/A010 5
Table of Contents
11 Connections .............................................................................198
11.1 Rear panel ....................................................................... 198
11.2 Auxiliary voltage ...............................................................200
11.3 Output relays ....................................................................201
11.4 Serial communication connection .................................... 201
11.4.1 Front panel USB connector ................................. 201
11.4.2 Pin assignments of the optional communication
interface cards .....................................................202
11.5 Input/output card B = 4 x DI + 1 x DI/DO ......................... 203
11.6 Arc protection card C = Arc (2 x Arc sensor + BIO) ......... 203
11.7 Arc protection card D = Advanced arc (3 x Arc sensor +
BIO) ..................................................................................204
11.8 External option modules .................................................. 205
11.8.1 Third-party external input / output modules ........ 205
11.9 Block optional diagram .....................................................211
11.10 Block diagrams of optional modules ................................ 212
11.11 Connection examples ...................................................... 214
6 V59/en M/A010
1 General
1 General
V59/en M/A010 7
1.2 Safety information 1 General
DANGER
DANGER indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if
not avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if
not avoided, can result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical
injury.
User qualification
Electrical equipment should be installed, operated, serviced, and
maintained only by trained and qualified personnel. No responsibility
is assumed by Schneider Electric for any consequences arising out
of the use of this material. A qualified person is one who has skills
and knowledge related to the construction, installation, and operation
of electrical equipment and has received safety training to recognize
and avoid the hazards involved.
Password protection
Use the IED's password protection feature to protect untrained
persons from interacting with this device.
WARNING
WORKING ON ENERGIZED EQUIPMENT
Do not choose lower Personal Protection Equipment while
working on energized equipment.
Failure to follow these instructions can result in death or
serious injury.
8 V59/en M/A010
1 General 1.3 EU directive compliance
2014/30/EU
Product safety
2014/35/EU
V59/en M/A010 9
1.5 Purpose 1 General
1.5 Purpose
This document contains instructions on the installation,
commissioning and operation of VAMP 59.
This document is intended for persons who are experts on electrical
power engineering, and it covers the device models as described
by the ordering code in Chapter 14 Order information.
Related documents
Document Identification*)
VAMP Relay Mounting and Commissioning Instructions VRELAY_MC_xxxx
VAMPSET Setting and Configuration Tool User Manual VVAMPSET_EN_M_xxxx
10 V59/en M/A010
1 General 1.6 Relay features
V59/en M/A010 11
1.7 Abbreviations 1 General
1.7 Abbreviations
ANSI American National Standards Institute. A standardization organisation.
CB Circuit breaker
CBFP Circuit breaker failure protection
cosφ Active power divided by apparent power = P/S. (See power factor PF). Negative sign indicates reverse
power.
CT Current transformer
CTPRI Nominal primary value of current transformer
CTSEC Nominal secondary value of current transformer
Dead band See hysteresis.
DI Digital input
DO Digital output, output relay
Document file Stores information about the IED settings, events and fault logs.
DSR Data set ready. An RS232 signal. Input in front panel port of VAMP relays to disable rear panel local
port.
DST Daylight saving time. Adjusting the official local time forward by one hour for summer time.
DTR Data terminal ready. An RS232 signal. Output and always true (+8 Vdc) in front panel port of VAMP
relays.
FFT Fast Fourier transform. Algorithm to convert time domain signals to frequency domain or to phasors.
FPGA Field-programmable gate array
HMI Human-machine interface
Hysteresis I.e. dead band. Used to avoid oscillation when comparing two near by values.
IN Nominal current. Rating of CT primary or secondary.
ISET Another name for pick up setting value I>
I0N Nominal current of I0 input in general
IEC International Electrotechnical Commission. An international standardization organisation.
IEC-101 Abbreviation for communication protocol defined in standard IEC 60870-5-101
IEC-103 Abbreviation for communication protocol defined in standard IEC 60870-5-103
IED Intelligent electronic device, refers to VAMP 59 in this document
IEEE Institute of Electrical and Electronics Engineers
LAN Local area network. Ethernet based network for computers and IEDs.
Latching Output relays and indication LEDs can be latched, which means that they are not released when the
control signal is releasing. Releasing of lathed devices is done with a separate action.
LCD Liquid crystal display
LED Light-emitting diode
Local HMI IED front panel with display and push-buttons
NTP Network Time Protocol for LAN and WWW
P Active power. Unit = [W]
PF Power factor. The absolute value is equal to cosφ, but the sign is '+' for inductive i.e. lagging current
and '-' for capacitive i.e. leading current.
PM Nominal power of the prime mover. (Used by reverse/under power protection.)
PT See VT
pu Per unit. Depending of the context the per unit refers to any nominal value. For example for overcurrent
setting 1 pu = 1 x IN.
12 V59/en M/A010
1 General 1.7 Abbreviations
V59/en M/A010 13
2 Local panel user interface
1. Navigation push-buttons
2. LED indicators
3. LCD
4. Local port
INFO push-button for viewing additional information, for entering the password view and for adjusting
the LCD contrast.
arrow UP navigation push-button for moving up in the menu or increasing a numerical value.
arrow DOWN navigation push-button for moving down in the menu or decreasing a numerical value.
arrow LEFT navigation push-button for moving backwards in a parallel menu or selecting a digit in a
numerical value.
arrow RIGHT navigation push-button for moving forwards in a parallel menu or selecting a digit in a
numerical value.
14 V59/en M/A010
2 Local panel user interface 2.1 Relay front panel
LED indicators
The LEDs on the local HMI can be configured in VAMPSET. To
customise the LED texts on the local HMI, the texts can be written
on a template and then printed on a transparency. The transparencies
can be placed to the pockets beside the LEDs.
LED indicator Meaning Measure/ Remarks
Power LED lit The auxiliary power has been switched on Normal operation state
Status LED lit Internal fault, operates in parallel with the self su- The relay attempts to reboot [RE-
pervision output relay BOOT]. If the error LED remains lit,
call for maintenance.
A- H LED lit Application-related status indicators. Configurable
F1 / F2 LED lit Corresponding function key pressed / activated Depending of function programmed to
F1 / F2
V59/en M/A010 15
2.1 Relay front panel 2 Local panel user interface
2.1.1 Display
The relay is provided with a backlighted 128x64 LCD dot matrix
display. The display enables showing 21 characters is one row and
eight rows at the same time. The display has two different purposes:
one is to show the single line diagram of the relay with the object
status, measurement values, identification etc (Figure 2.1). The other
purpose is to show the configuration and parameterization values of
the relay (Figure 2.2).
16 V59/en M/A010
2 Local panel user interface 2.2 Local panel operations
Backlight control
Display backlight can be switched on with a digital input, virtual input
or virtual output. LOCALPANEL CONF/Display backlight ctrl setting
is used for selecting trigger input for backlight control. When the
selected input activates (rising edge), display backlight is set on for
60 minutes.
OK
I pick-up setting
OK OK
V59/en M/A010 17
2.2 Local panel operations 2 Local panel user interface
NOTE: To enter the parameter edit mode, give the password. When the
value is in edit mode, its background is dark.
Main menu
The menu is dependent on the user’s configuration and the options
according the order code. For example only the enabled protection
stages will appear in the menu.
18 V59/en M/A010
2 Local panel user interface 2.2 Local panel operations
V59/en M/A010 19
2.2 Local panel operations 2 Local panel user interface
Notes
3. The menu is visible only if protocol "ExternalIO" is selected for one of the serial ports.
Serial ports are configured in menu "Bus".
6. There are two extra menus, which are visible only if the access level "operator" or
"configurator" has been opened with the corresponding password.
20 V59/en M/A010
2 Local panel user interface 2.2 Local panel operations
I>> STATUS 50 / 51
ExDO Status -
Prot SCntr 5
I> TCntr 2
I>> SetGrp 1
Iv> SGrpDI -
I > Force OFF
This is the status, start and trip counter and setting group menu.
• Status –
The stage is not detecting any fault at the moment. The stage
can also be forced to pick-up or trip is the operating level is
“Configurator” and the force flag below is on. Operating levels
are explained in Chapter 2.2.4 Operating levels.
• SCntr 5
The stage has picked-up a fault five times since the last reset or
restart. This value can be cleared if the operating level is at least
“Operator”.
• TCntr 2
The stage has tripped two times since the last reset or restart.
This value can be cleared if the operating level is at least
“Operator”.
• SetGrp 1
The active setting group is one. This value can be edited if the
operating level is at least “Operator”. Setting groups are explained
in Chapter 2.2.2 Setting groups
• SGrpDI –
The setting group is not controlled by any digital input. This value
can be edited if the operating level is at least “Configurator”.
• Force Off
The status forcing and output relay forcing is disabled. This force
flag status can be set to “On” or back to “Off” if the operating
level is at least “Configurator”. If no front panel button is pressed
within five minutes and there is no VAMPSET communication,
the force flag will be set to “Off” position. The forcing is explained
in Chapter 2.3.4 Forced control (Force).
V59/en M/A010 21
2.2 Local panel operations 2 Local panel user interface
I>> SET 50 / 51
Stage setting group 1
ExDI ILmax 403A
ExDO Status -
Prot I>> 1013A
I>> I>> 2.50xIn
CBWE t>> 0.60s
OBJ
22 V59/en M/A010
2 Local panel user interface 2.2 Local panel operations
SetGrp 1
Figure 2.6: Third and last menu (next on the right) of I>> 50/51 stage
This is the menu for registered values by the I>> stage. Fault logs
are explained in Chapter 2.2.3 Fault logs.
• FAULT LOG 1
This is the latest of the eight available logs. You may move
between the logs by pressing push buttons and then
or .
• 2006-09-14
Date of the log.
• 12:25:10.288
Time of the log.
• Type 1-2
The overcurrent fault has been detected in phases L1 and L2 (A
& B, red & yellow, R/S, u&v).
• Flt 2.86 x IN
The fault current has been 2.86 per unit.
• Load 0.99 x IN
The average load current before the fault has been 0.99 pu.
• EDly 81%
The elapsed operation delay has been 81% of the setting 0.60
s = 0.49 s. Any registered elapsed delay less than 100 % means
that the stage has not tripped, because the fault duration has
been shorter that the delay setting.
• SetGrp 1
The setting group has been 1. This line can be reached by
pressing and several times .
V59/en M/A010 23
2.2 Local panel operations 2 Local panel user interface
24 V59/en M/A010
2 Local panel user interface 2.2 Local panel operations
To see the values of, for example, log two, press then to select
the current log (log one). The current log number is then indicated
in the down-left corner of the display (SeeFigure 2.10, Log2 = log
two). The log two is selected by pressing once.
V59/en M/A010 25
2.2 Local panel operations 2 Local panel user interface
OPERATOR level
Use: Possible to control objects and to change e.g. the settings of the
protection stages
Opening: Default password is 1
Setting state:
Push
Closing: The level is automatically closed after 10 minutes idle time. Giving
the password 9999 can also close the level.
CONFIGURATOR level
Use: The configurator level is needed during the commissioning of the
relay. E.g. the scaling of the voltage and current transformers can
be set.
Opening: Default password is 2
Setting state:
Push
Closing: The level is automatically closed after 10 minutes idle time. Giving
the password 9999 can also close the level.
26 V59/en M/A010
2 Local panel user interface 2.2 Local panel operations
Opening access
1.
Push and on the front panel
ENTER PASSWORD
*** 0
2. Enter the password needed for the desired level: the password
can contain four digits. The digits are supplied one by one by
first moving to the position of the digit using and then setting
the desired digit value using .
3. Push .
Password handling
The passwords can only be changed using VAMPSET software
connected to the USB -port in front of the relay.
It is possible to restore the password(s) in case the password is lost
or forgotten. In order to restore the password(s), a relay program is
needed. The virtual serial port settings are 38400 bps, 8 data bits,
no parity and one stop bit. The bit rate is configurable via the front
panel.
Command Description
get pwd_break Get the break code (Example: 6569403)
get serno Get the serial number of the relay (Example: 12345)
V59/en M/A010 27
2.3 Operating measures 2 Local panel user interface
- Using and /
1. Push . The previously activated object starts to blink.
2. Select the object to control by using arrow keys. Please note that
only controllable objects can be selected.
3. Push . A control dialog opens.
4. Select the “Open” or “Close” command by using the or .
5. Confirm the operation by pushing . The state of the object
changes.
28 V59/en M/A010
2 Local panel user interface 2.3 Operating measures
V59/en M/A010 29
2.3 Operating measures 2 Local panel user interface
30 V59/en M/A010
2 Local panel user interface 2.3 Operating measures
4. Push .
5. Push the or to change the "OFF" text to "ON", that is,
to activate the Force function.
6. Push to return to the selection list. Choose the signal to be
controlled by force with the and , for instance the T1
signal.
7. Push to confirm the selection. Signal T1 can now be
controlled by force.
8. Push the or to change the selection from "0" (not alert)
to "1" (alert) or vice versa.
9. Push to execute the forced control operation of the selected
function, e.g., making the output relay of T1 to pick up.
10. Repeat the steps 7 and 8 to alternate between the on and off
state of the function.
11. Repeat the steps 1 – 4 to exit the Force function.
12.
Push to return to the main menu.
NOTE: All the interlockings and blockings are bypassed when the force
control is used.
V59/en M/A010 31
2.4 Configuration and parameter setting 2 Local panel user interface
V59/en M/A010 33
2.4 Configuration and parameter setting 2 Local panel user interface
The allowed setting range is shown in the display in the setting mode.
Disturbance settings
1. Manual trigger (ManTrg)
2. Status (Status)
3. Clear oldest record (Clear)
4. Clear all records (ClrAll)
5. Recording completion (Stored)
6. Count of ready records (ReadyRec)
34 V59/en M/A010
2 Local panel user interface 2.4 Configuration and parameter setting
Recorder settings
1. Manual trigger (ManTrig)
2. Sample rate (SR)
3. Recording time (Time)
4. Pre trig time (PreTrig)
5. Mximum time (MaxLen)
6. Count of ready records (ReadyRec)
Rec. channels
• Add a link to the recorder (AddCh)
• Clear all links (ClrCh)
Available links
• DO, DI
• IL
• I2/In, I2/I1, I2, I1, IoCalc
• f
• Io
• IoRMS
• IL3, IL2, IL1
• IL1Rem, IL2Rem, IL3Rem
• THDIL1, THDIL2, THDIL3
• IL1RMS, IL2RMS, IL3RMS
• ILmin
• ILmax
• T
• Uo
NOTE: The amount of Trip and Alarm relays depends on the relay type and
optional hardware.
Analog output
• Value of AO1 (AO1)
• Forced control of analogue output (Force)
Analog output 1 – 4
• Value linked to the analogue output (Lnk1)
• (See list available links)
• Scaled minimum of linked value (Min)
• Scaled maximum of linked value (Max)
• Scaled minimum of analogue output (AOmin)
• Scaled maximum of analogue output (AOmax)
• Value of analogue output (AO1)
36 V59/en M/A010
2 Local panel user interface 2.4 Configuration and parameter setting
Available links:
• IL1, IL2, IL2
• F
• IL
• Io, IoCalc
• Uo
Device setup
• Bit rate for the command line interface in communication ports
and the USB-port in the front panel. The front panel is always
using this setting. If SPABUS is selected for the rear panel port,
the bit rate is according SPABUS settings.
• Access level [Acc]
• PC access level [PCAcc]
Language
• List of available languages in the relay
V59/en M/A010 37
2.4 Configuration and parameter setting 2 Local panel user interface
Current scaling
• Rated phase CT primary current (Inom)
• Rated phase CT secondary current (Isec)
• Rated input of the relay [Iinput] is 5 A
• Rated value of I0 CT primary current (Ionom)
• Rated value of I0 CT secondary current (Iosec)
• Rated I0 input of the relay [Ioinp] is 1 A / 5 A or 0.2 A / 1 A. This
is specified in the order code of the device.
The rated input values are usually equal to the rated secondary value
of the CT.
The rated CT secondary may be greater than the rated input but the
continuous current must be less than four times the rated input. In
compensated, high impedance earthed and isolated networks using
cable transformer to measure residual current I0, it is quite usual to
use a relay with 1 A or 0.2 A input although the CT is 5 A or 1A. This
increases the measurement accuracy.
The rated CT secondary may also be less than the rated input but
the measurement accuracy near zero current will decrease.
Voltage scaling
• Rated U0 VT secondary voltage (Uosec)
Device info
• Relay type (Type VAMP 59)
• Serial number (SerN)
• Software version (PrgVer)
• Bootcode version (BootVer)
Date/time setup
• Day, month and year (Date)
• Time of day (Time)
• Date format (Style). The choices are "yyyy-mm-dd", "dd.nn.yyyy"
and "mm/dd/yyyy".
38 V59/en M/A010
2 Local panel user interface 2.4 Configuration and parameter setting
Clock synchronisation
• Digital input for minute sync pulse (SyncDI). If any digital input
is not used for synchronization, select "-".
• Daylight saving time for NTP synchronization (DST).
• Detected source of synchronization (SyScr).
• Synchronization message counter (MsgCnt).
• Latest synchronization deviation (Dev).
The following parameters are visible only when the access level is
higher than "User".
• Offset, i.e. constant error, of the synchronization source (SyOS).
• Auto adjust interval (AAIntv).
• Average drift direction (AvDrft): "Lead" or "lag".
• Average synchronization deviation (FilDev).
SW options
• Application mode, fixed Feeder (ApplMod)
• External led module installed (Ledmodule)
• Mimic display selection (MIMIC)
V59/en M/A010 39
2.4 Configuration and parameter setting 2 Local panel user interface
Remote port
• Communication protocol for remote port [Protocol].
• Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
• Communication error counter [Errors]
• Communication time-out error counter [Tout].
• Information of bit rate/data bits/parity/stop bits. This value is not
directly editable. Editing is done in the appropriate protocol setting
menus.
The counters are useful when testing the communication.
PC (Local/SPA-bus)
This is a second menu for local port. The VAMPSET communication
status is showed.
• Bytes/size of the transmitter buffer [Tx].
• Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
• Communication error counter [Errors]
• Communication time-out error counter [Tout].
• Same information as in the previous menu.
Extension port
• Communication protocol for extension port [Protocol].
• Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
• Communication error counter [Errors]
• Communication time-out error counter [Tout].
• Information of bit rate/data bits/parity/stop bits. This value is not
directly editable. Editing is done in the appropriate protocol setting
menus.
40 V59/en M/A010
2 Local panel user interface 2.4 Configuration and parameter setting
Ethernet port
These parameters are used by the ethernet interface module. For
changing the nnn.nnn.nnn.nnn style parameter values, VAMPSET
is recommended.
• Ethernet port protocol [Protoc].
• IP Port for protocol [Port]
• IP address [IpAddr].
• Net mask [NetMsk].
• Gateway [Gatew].
• Name server [NameSw].
• Network time protocol (NTP) server [NTPSvr].
• TCP Keep alive interval [KeepAlive]
• MAC address [MAC]
• IP Port for VAMPSET [VS Port]
• Message counter [Msg#]
• Error counter [Errors]
• Timeout counter [Tout]
Modbus
• Modbus address for this slave device [Addr]. This address has
to be unique within the system.
• Modbus bit rate [bit/s]. Default is "9600".
• Parity [Parity]. Default is ”Even”.
For details, see Chapter 9.2.2 Modbus TCP and Modbus RTU.
V59/en M/A010 41
2.4 Configuration and parameter setting 2 Local panel user interface
DNP3
Only one instance of this protocol is possible.
• Bit rate [bit/s]. Default is "9600".
• [Parity].
• Address for this device [SlvAddr]. This address has to be unique
within the system.
• Master's address [MstrAddr].
For details, see Chapter 9.2.3 DNP 3.0.
Ba y 0 L
0A
0.000A
0kW
0Kva r
42 V59/en M/A010
3 VAMPSET PC software
3 VAMPSET PC software
The PC user interface can be used for:
• On-site parameterization of the relay
• Loading relay software from a computer
• Reading measured values, registered values and events to a
computer
• Continuous monitoring of all values and events
A USB port is available for connecting a local PC with VAMPSET to
the relay. A standard USB-B cable can be used.
The VAMPSET program can also use the TCP/IP LAN connection.
Optional hardware is required for Ethernet connection.
There is a free of charge PC program called VAMPSET available
for configuration and setting of VAMP relays. Please download the
latest VAMPSET.exe from our web page. For more information about
the VAMPSET software, please refer to the user’s manual with the
code VVAMPSET/EN M/xxxx. Also the VAMPSET user’s manual is
available at our web site.
When the relay is connected to a PC with a USB, a virtual comport
will be created. The comport number may vary depending on your
computer hardware. In order to check the correct port number, please
go to Windows Device Manager: Control
Panel->System->Hardware->Device Manager and under Ports
(COM&LPT) for “USB Serial Port”. The correct comport must be
selected from the VAMPSET menu: Settings->Communication
Settings. Speed setting can be set up to 187500 bps. Default setting
in the relay is 38400 bps which can be manually changed from the
front panel of the device.
By default every new relay will create a new comport. To avoid this
behavior, the user needs to add a REG_BINARY value called
IgnoreHWSerNum04036001 to the Windows registry and set it to
01. The location for this value is
HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Control\UsbFlags\.
V59/en M/A010 43
3.1 Folder view 3 VAMPSET PC software
NOTE: It is possible to enable/ disable the folder view only when VAMPSET
is disconnected from the relay and there is no configuration file
opened.
44 V59/en M/A010
4 Introduction
4 Introduction
The numerical device includes all the essential overcurrent and
earthfault protection functions needed. Further, the device includes
several programmable functions, such as thermal, trip circuit
supervision and circuit breaker protection and communication
protocols for various protection and communication situations.
V59/en M/A010 45
4.2 Principles of numerical protection techniques 4 Introduction
46 V59/en M/A010
4 Introduction 4.2 Principles of numerical protection techniques
V59/en M/A010 47
5 Protection functions
5 Protection functions
Each protection stage can independently be enabled or disabled
according to the requirements of the intended application.
Example
Any digital input could be used to control setting groups but in this
example DI1, DI2, DI3 and DI4 are chosen to control setting groups
1 to 4. This setting is done with a parameter “Set group x DI control”
where x refers to the desired setting group.
48 V59/en M/A010
5 Protection functions 5.2 General features of protection stages
Figure 5.1: DI1, DI2, DI3, DI4 are configured to control Groups 1 to 4 respectively.
Figure 5.2: SetGrp priority setting is located in the Valid Protection stages view.
Assuming that DI2 and DI3 are active at a same time and SetGrp
priority is set to “1 to 4” setting group 2 will become active. In case
SetGrp priority is reversed i.e. it is set to “4 to 1” setting group 3
would be active.
V59/en M/A010 49
5.2 General features of protection stages 5 Protection functions
Output matrix
Using the output matrix the user connects the internal start and trip
signals to the output relays and indicators. For more details, see
Chapter 8.5 Output matrix.
Blocking
Any protection function, except arc protection, can be blocked with
internal and external signals using the block matrix (Chapter 8.6
Blocking matrix). Internal signals are for example logic outputs and
start and trip signals from other stages and external signals are for
example digital and virtual inputs.
When a protection stage is blocked, it won't pick-up in case of a fault
condition is detected. If blocking is activated during the operation
delay, the delay counting is frozen until the blocking goes off or the
pick-up reason, i.e. the fault condition, disappears. If the stage is
already tripping, the blocking has no effect.
50 V59/en M/A010
5 Protection functions 5.2 General features of protection stages
Retardation time
Retardation time is the time a protection relay needs to notice that
a fault has been cleared during the operate time delay. This
parameter is important when grading the operate time delay settings
between relays.
RetardationTime
tFAULT
tRET < 50 ms
TRIP CONTACTS
Figure 5.3: Definition for retardation time. If the delay setting would be slightly
shorter, an unselective trip might occur (the dash line pulse).
The maximum reset time for each stage is specified in Chapter 12.3
Protection functions. For most stages it is less than 95 ms.
tSET
tCB
tRESET
TRIP CONTACTS
Figure 5.4: Reset time is the time it takes the trip or start relay contacts to open
after the fault has been cleared.
Start level
> Start
Hysteresis_LT
Start level
< Start
52 V59/en M/A010
5 Protection functions 5.3 Application modes
V59/en M/A010 53
5.5 Overcurrent protection I> (50/51) 5 Protection functions
Figure 5.8: Block diagram of the three-phase overcurrent stage I>> and I>>>
54 V59/en M/A010
5 Protection functions 5.5 Overcurrent protection I> (50/51)
the currently used inverse delay curve graph on the local panel
display.
Setting groups
There are four settings groups available for each stage. Switching
between setting groups can be controlled by digital inputs, virtual
inputs (communication, logic) and manually. See Chapter 5.2 General
features of protection stages for more details.
Table 5.1: Parameters of the overcurrent stage I> (50/51)
Parameter Value Unit Description Note
Status - Current status of the stage -
Blocked -
Start F
Trip F
TripTime s Estimated time to trip
SCntr Cumulative start counter C
TCntr Cumulative trip counter C
SetGrp 1, 2, 3, 4 Active setting group Set
SGrpDI Digital signal to select the active setting group Set
- None
DIx Digital input
VIx Virtual input
LEDx LED indicator signal
VOx Virtual output
Fx Function key
Force Off Force flag for status forcing for test purposes. This is a common Set
flag for all stages and output relays, too. This flag is automatic-
On ally reset 5 minutes after the last front panel push button
pressing.
ILmax A The supervised value. Max. of IL1, IL2 and IL3
Status Current status of the stage
I> A Pick-up value scaled to primary value
I> xIN Pick-up setting Set
V59/en M/A010 55
5.5 Overcurrent protection I> (50/51) 5 Protection functions
DT Definite time
IEC, IEEE, Inverse time. See Chapter 5.17 Inverse time operation.
IEEE2, RI, PrgN
Type - Delay type Set
DT Definite time
NI, VI, EI, LTI, Inverse time. See Chapter 5.17 Inverse time operation.
Parameters
t> s Definite operate time (for definite time only) Set
k> Inverse delay multiplier (for inverse time only) Set
Dly20x s Delay at 20xImode
Dly4x s Delay at 4xImode
Dly2x s Delay at 2xImode
Dly1x s Delay at 1xImode
IncHarm On/off Include Harmonics
Delay curves Graphic delay curve picture (only local display)
A, B, C, D, E User's constants for standard equations. Type=Parameters. Set
Chapter 5.17 Inverse time operation.
Recorded values LOG1 Date and time of trip
Type Fault type
Flt xIN Fault current
Load xIN Pre-fault current
Edly % Elapsed delay time
SetGrp Active set group during fault
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Blocked -
Start F
Trip F
SCntr Cumulative start counter C
TCntr Cumulative trip counter C
SetGrp 1, 2, 3, 4 Active setting group Set
56 V59/en M/A010
5 Protection functions 5.5 Overcurrent protection I> (50/51)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
V59/en M/A010 57
5.5 Overcurrent protection I> (50/51) 5 Protection functions
In the Figure 5.9 can be seen the affect of remote scaling. After
enabling group is changed from group one to group two and all
settings from group one are copied to group two. The difference is
that group two uses scaled pick-up settings.
NOTE: When remote scaling function is used, it replaces all the settings of
group 2. So this function cannot be used simultaneously with normal
group change.
58 V59/en M/A010
5 Protection functions 5.6 Current unbalance stage I2/I1> (46)
1 3
a = 1∠120° = − + j
2 2 , a phasor rotating constant
Table 5.4: Setting parameters of the current unbalanced stage I2/I1> (46)
Parameter Value Unit Default Description
I2/I1> 2 – 70 % 20 Setting value, I2/I1
t> 1.0 – 600.0 s 10.0 Definite operate time
Type DT - DT The selection of time characteristics
INV
S_On Enabled; Disabled - Enabled Start on event
S_Off Enabled; Disabled - Enabled Start off event
T_On Enabled; Disabled - Enabled Trip on event
T_Off Enabled; Disabled - Enabled Trip off event
Table 5.5: Measured and recorded values of the current unbalanced stage
I2/I1> (46)
Parameter Value Unit Description
Measured value I2/I1 % Relative negative sequence component
Recorded values SCntr Cumulative start counter
TCntr Cumulative trip counter
Flt % Maximum I2/I1 fault component
EDly % Elapsed time as compared to the set oper-
ate time, 100% = tripping
V59/en M/A010 59
5.7 Directional earth fault protection I0φ> (67N) 5 Protection functions
Polarization
The negative zero sequence voltage U0 is used for polarization i.e.
the angle reference for I0. The -U0 voltage is measured via energizing
input U0.
• 3LN+U0: the zero sequence voltage is measured with voltage
transformer(s) for example using a broken delta connection. The
setting values are relative to the VT0 secondary voltage defined
in configuration.
60 V59/en M/A010
5 Protection functions 5.7 Directional earth fault protection I0φ> (67N)
• ResCap
This mode consists of two sub modes, Res and Cap. A digital
signal can be used to dynamically switch between these two sub
modes. This feature can be used with compensated networks,
when the Petersen coil is temporarily switched off.
- Res
The stage is sensitive to the resistive component of the
selected I0 signal. This mode is used with compensated
networks (resonant grounding) and networks earthed with
a high resistance. Compensation is usually done with a
Petersen coil between the neutral point of the main
transformer and earth. In this context "high resistance"
means, that the fault current is limited to be less than the
rated phase current. The trip area is a half plane as drawn
in Figure 5.11. The base angle is usually set to zero degrees.
- Cap
The stage is sensitive to the capacitive component of the
selected I0 signal. This mode is used with unearthed
networks. The trip area is a half plane as drawn in
Figure 5.11. The base angle is usually set to zero degrees.
• Sector
This mode is used with networks earthed with a small
resistance. In this context "small" means, that a fault current
may be more than the rated phase currents. The trip area has a
shape of a sector as drawn in Figure 5.12. The base angle is
usually set to zero degrees or slightly on the lagging inductive
side (i.e. negative angle).
• Undir
This mode makes the stage equal to the undirectional stage I0>.
The phase angle and U0 amplitude setting are discarded. Only
the amplitude of the selected I0 input is supervised.
V59/en M/A010 61
5.7 Directional earth fault protection I0φ> (67N) 5 Protection functions
Setting groups
There are four settings groups available for each stage. Switching
between setting groups can be controlled by digital inputs, virtual
inputs (communication, logic) and manually. See Chapter 5.2 General
features of protection stages for more details.
62 V59/en M/A010
5 Protection functions 5.7 Directional earth fault protection I0φ> (67N)
Figure 5.10: Block diagram of the directional earth fault stages I0φ>, I0φ>>
Figure 5.11: Operation characteristic of the directional earth fault protection in Res
or Cap mode. Res mode can be used with compensated networks and Cap mode
is used with ungrounded networks.
V59/en M/A010 63
5.7 Directional earth fault protection I0φ> (67N) 5 Protection functions
70
70
Figure 5.12: Two example of operation characteristics of the directional earth fault
stages in sector mode. The drawn I0 phasor in both figures is inside the trip area. The
angle offset and half sector size are user’s parameters.
Table 5.6: Parameters of the directional earth fault stages I0φ>, I0φ>> (67N)
Parameter Value Unit Description Note
Status - Current status of the stage -
Blocked -
Start F
Trip F
TripTime s Estimated time to trip
SCntr Cumulative start counter Clr
TCntr Cumulative trip counter Clr
SetGrp 1, 2, 3, 4 Active setting group Set
SGrpDI Digital signal to select the active setting group Set
- None
DIx Digital input
VIx Virtual input
LEDx LED indicator signal
VOx Virtual output
Fx Function key
Force Off Force flag for status forcing for test purposes. This Set
is a common flag for all stages and output relays,
On too. Automatically reset by a 5-minute timeout.
Io pu The supervised value according the parameter "In-
put" below.
IoCalc
(I0φ> only)
IoPeak
IoRes pu Resistive part of I0 (only when "InUse"=Res)
IoCap pu Capacitive part of I0 (only when "InUse"=Cap)
Ioφ> A Pick-up value scaled to primary value
64 V59/en M/A010
5 Protection functions 5.7 Directional earth fault protection I0φ> (67N)
DT Definite time
DT Definite time
NI, VI, EI, LTI, Inverse time. Chapter 5.17 Inverse time operation.
Parameters
t> s Definite operate time (for definite time only) Set
k> Inverse delay multiplier (for inverse time only) Set
Mode ResCap High impedance earthed nets Set
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
V59/en M/A010 65
5.8 Earth fault protection I0> (50N/51N) 5 Protection functions
-U0 = 0°
Uo % Max. U0 voltage during the fault
SetGrp 1, 2, 3, 4 Active setting group during fault
66 V59/en M/A010
5 Protection functions 5.8 Earth fault protection I0> (50N/51N)
Figure 5.14: Block diagram of the earth fault stages I0>>, I0>>>, I0>>>>
V59/en M/A010 67
5.8 Earth fault protection I0> (50N/51N) 5 Protection functions
Using the directional earth fault stages (Chapter 5.7 Directional earth
fault protection I0φ> (67N)) in undirectional mode, two more stages
with inverse operate time delay are available for undirectional earth
fault protection.
Setting groups
There are four settings groups available for each stage. Switching
between setting groups can be controlled by digital inputs, virtual
inputs (communication, logic) and manually. See Chapter 5.2 General
features of protection stages for more details.
Table 5.8: Parameters of the undirectional earth fault stage I0> (50N/51N)
Parameter Value Unit Description Note
Status - Current status of the stage -
Blocked -
Start F
Trip F
TripTime s Estimated time to trip
SCntr Cumulative start counter Clr
TCntr Cumulative trip counter Clr
SetGrp 1, 2, 3, 4 Active setting group Set
SGrpDI Digital signal to select the active setting group Set
- None
DIx Digital input
VIx Virtual input
LEDx LED indicator signal
VOx Virtual output
Fx Function key
Force Off Force flag for status forcing for test purposes. This Set
is a common flag for all stages and output relays,
On too. Automatically reset by a 5-minute timeout.
68 V59/en M/A010
5 Protection functions 5.8 Earth fault protection I0> (50N/51N)
DT Definite time
DT Definite time
NI, VI, EI, LTI, Inverse time. Chapter 5.17 Inverse time operation.
Parameters
t> s Definite operate time (for definite time only) Set
k> Inverse delay multiplier (for inverse time only) Set
Input Io X1:7, 8, 9. See Chapter 11 Connections. Set
IoCalc IL1 + IL2 + IL3
IoPeak X1:7, 8, 9. peak mode (I0> only).
Intrmt s Intermittent time Set
Dly20x s Delay at 20 x I0N
Dly4x s Delay at 4 x I0N
Dly2x s Delay at 2 x I0N
Dly1x Delay at 1 x I0N
A, B, C, D, E User’s constants for standard equations. Set
Type=Parameters. See Chapter 5.17 Inverse time
operation.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 5.9: Parameters of the undirectional earth fault stage I0>>, I0>>>, I0>>>>
(50N/51N)
Parameter Value Unit Description Note
Status - Current status of the stage -
Blocked -
Start F
Trip F
TripTime s Estimated time to trip
SCntr Cumulative start counter Clr
TCntr Cumulative trip counter Clr
SetGrp 1, 2, 3, 4 Active setting group Set
V59/en M/A010 69
5.8 Earth fault protection I0> (50N/51N) 5 Protection functions
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
70 V59/en M/A010
5 Protection functions 5.8 Earth fault protection I0> (50N/51N)
V59/en M/A010 71
5.8 Earth fault protection I0> (50N/51N) 5 Protection functions
• FWD L1-L2
Phase L1 and L2 increase above the set limit and phase L3
remains inside the set (delta) limit. Io current angle is between
L1 and L2 phase angles.
• FWD L2-L3
Phase L2 and L3 increase above the set limit and phase L1
remains inside the set (delta) limit. Io current angle is between
L2 and L3 phase angles.
• FWD L3-L1
Phase L3 and L1 increase above the set limit and phase L2
remains inside the set (delta) limit. Io current angle is between
L3 and L3 phase angles.
• FWD L1-L2-L3
All three phase currents increase above the set delta limit.
• REV 1 (any one phase)
One phase decreases below the set delta limit and other two
phases remain inside the delta limit.
• REV 2 (any two phase)
Two phases decrease below the set delta limit and third phase
remains inside the delta limit.
• REV 3 (all three phases)
All three phase currents decrease below the set delta limit.
Below are simulated different fault scenarios:
72 V59/en M/A010
5 Protection functions 5.8 Earth fault protection I0> (50N/51N)
V59/en M/A010 73
5.9 Zero sequence voltage protection U0> (59N) 5 Protection functions
Setting groups
There are four settings groups available for both stages. Switching
between setting groups can be controlled by digital inputs, virtual
inputs (communication, logic) and manually. See Chapter 5.2 General
features of protection stages for more details.
74 V59/en M/A010
5 Protection functions 5.9 Zero sequence voltage protection U0> (59N)
Figure 5.18: Block diagram of the zero sequence voltage stages U0>, U0>>
Blocked -
Start F
Trip F
SCntr Cumulative start counter C
TCntr Cumulative trip counter C
SetGrp 1, 2, 3, 4 Active setting group Set
SGrpDI Digital signal to select the active setting group Set
- None
DIx Digital input
VIx Virtual input
LEDx LED indicator signal
VOx Virtual output
Fx Function key
Force Off Force flag for status forcing for test purposes. This Set
is a common flag for all stages and output relays, too.
On Automatically reset by a 5-minute timeout.
Uo %
The supervised value relative to Un/
Uo>, Uo>> % Set
Pick-up value relative to Un/
t>, t>> s Definite operate time Set
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
V59/en M/A010 75
5.9 Zero sequence voltage protection U0> (59N) 5 Protection functions
Table 5.12: Recorded values of the residual overvoltage stages U0>, U0>>
Parameter Value Unit Description
yyyy-mm-dd Time stamp of the recording, date
hh:mm:ss.ms Time stamp, time of day
Flt %
Fault voltage relative to Un/
EDly % Elapsed time of the operate time setting. 100% = trip
SetGrp 1, 2, 3, 4 Active setting group during fault
76 V59/en M/A010
5 Protection functions 5.10 Thermal overload protection T> (49)
Thermal model
The temperature is calculated using rms values of phase currents
and a thermal model according IEC 60255-8. The rms values are
calculated using harmonic components up to the 15th.
2
I 2 − IP
Trip time: t = τ ⋅ ln 2
I − a 2 , ȫ unit: second
Trip: a = k ⋅ kΘ ⋅ I N
2
I
Release time: t = τ ⋅ Cτ ⋅ ln 2 P 2
a − I , ȫ unit: second
Trip release: a = 0.95 × k × I N
T= operate time
V59/en M/A010 77
5.10 Thermal overload protection T> (49) 5 Protection functions
I MAX = k ⋅ k Θ ⋅ I N
kQ AmbientTemperatureCompensation
1.2
IMAX40
1.0
0.8 IMAX70
0.6
10 20 30 40 50 60 70 80
QAMB (°C)
78 V59/en M/A010
5 Protection functions 5.10 Thermal overload protection T> (49)
Alarm function
The thermal overload stage is provided with a separately settable
alarm function. When the alarm limit is reached the stage activates
its start signal.
V59/en M/A010 79
5.11 Magnetishing inrush If2 > (68F2) 5 Protection functions
Blocked -
Start F
Trip F
Time hh:mm:ss Estimated time to trip
SCntr Cumulative start counter C
TCntr Cumulative trip counter C
Force Off Force flag for status forcing for test purposes. Set
This is a common flag for all stages and output
On relays, too. Automatically reset by a 5-minute
timeout.
T % Calculated temperature rise. Trip limit is 100 %. F
MaxRMS Arms Measured current. Highest of the three phases.
Imax A k xIN. Current corresponding to the 100 % temper-
ature rise.
k> xIN Allowed overload (service factor) Set
Alarm % Alarm level Set
tau min Thermal time constant Set
ctau xtau Coefficient for cooling time constant. Default = Set
1.0
kTamb xIN Ambient temperature corrected max. allowed
continuous current
Imax40 %IN Allowed load at Tamb +40 °C. Default = 100 %. Set
Imax70 %IN Allowed load at Tamb +70 °C. Set
Tamb °C Ambient temperature. Editable Samb=n/a. Default Set
= +40 °C
Samb Sensor for ambient temperature Set
n/a No sensor in use for Tamb
ExtAI1 – 16 External Analogue input 1 – 16
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
80 V59/en M/A010
5 Protection functions 5.11 Magnetishing inrush If2 > (68F2)
Im1
&
Im2
Im3
MAX > ts tr
Start
Block
& Register
event
Trip
t
& Register
event
V59/en M/A010 81
5.12 Transformer over exicitation If5> (68F5) 5 Protection functions
Table 5.17: Measured and recorded values of over exicitation blocking (68F5)
Parameter Value Unit Description
Measured values IL1H5. % 5. harmonic of IL1, proportional to the
fundamental value of IL1
IL2H5. % 5. harmonic of IL2
IL3H5. % 5. harmonic of IL3
Recorded values Flt % The max. fault value
EDly % Elapsed time as compared to the set
operate time; 100% = tripping
82 V59/en M/A010
5 Protection functions 5.13 Circuit breaker failure protection CBFP (50BF)
Blocked -
Start F
Trip F
SCntr Cumulative start counter C
TCntr Cumulative trip counter C
Force Off Force flag for status forcing for test purposes. This is Set
a common flag for all stages and output relays, too.
On Automatically reset by a 5-minute timeout.
Cbrelay The supervised output relay*). Set
1 Relay T1
2 Relay T2
t> s Definite operate time. Set
*) This setting is used by the circuit breaker condition monitoring, too. See Chapter 6.5 Circuit breaker condition monitoring.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
V59/en M/A010 83
5.13 Circuit breaker failure protection CBFP (50BF) 5 Protection functions
Table 5.19: Recorded values of the circuit breaker failure stage (8 latest
faults) CBFP (50BF)
Parameter Value Unit Description
yyyy-mm-dd Time stamp of the recording, date
hh:mm:ss.ms Time stamp, time of day
EDly % Elapsed time of the operate time setting. 100% = trip
84 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
Settings:
IPick-Up = 20 – 50%
Start of slope1 = 0.5 – 1.0 x IN
Slope1 = 0 – 100%
Start of slope2 = 1.0 – 3.0 x IN
Slope2 = 50 – 200%
V59/en M/A010 85
5.14 Line differential protection LdI> (87L) 5 Protection functions
1+1
Ib = = 1× I N
2
I d = 1∠0° − 1∠0° = 0 × I N
86 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
2.4 + 7
Ib = = 4. 7 × I N
2
I d = 2.4∠ − 35° − 7∠135° = 9.37 × I N
V59/en M/A010 87
5.14 Line differential protection LdI> (87L) 5 Protection functions
88 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
V59/en M/A010 89
5.14 Line differential protection LdI> (87L) 5 Protection functions
90 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
For details of setting ranges, see Table 12.17, Table 12.18, Table 12.19.
V59/en M/A010 91
5.14 Line differential protection LdI> (87L) 5 Protection functions
Testing mode
Test mode for commissioning can be enabled from the protection
stage also. When protection stage in test mode does not receive
currents from the other relay, this way the tests can be carried out
without interference from the other relay. In test mode, the relay still
sends it’s measurements to the other relay. When test mode is
activated, it is shown in the protection stage.
Figure 5.30: When VI1 was activated, “Operation mode” changed from normal to
test.
The other end relay tripping should be blocked during testing. This
can be achieved by sending block signal with POC-messages to the
other side and activating blocking for differential protection from that
signal.
Figure 5.33: Using the block signal for differential protection blocking
92 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
Differential CTS method uses the ratio between positive and negative
sequence currents in both ends of the protected line to determine
CT failure. This algorithm relies on ANSI85 communication and is
inbuilt to LdI> stage.
When this ratio is small (zero), one of four conditions is present:
• The system is unloaded – both I2 and I1 are zero
• The system is loaded but balanced – I2 is zero
• The system has three phase fault – I2 is zero
• There is 3-phase CT failure – Unlikely to happen
When the ratio in non-zero one of the two conditions is present:
• The system has an asymmetric fault – both I2 and I1 are non-zero
• There is a 1 or 2 phase CT fault – both I2 and I1 are non-zero
I2 to I1 ratio is calculated in both ends of the protected line. Both
relays calculate their own ratio and other end ratio from the own
measurements and via ANSI85 received measurements. With this
information we can assume:
• If the ratio is non-zero in both ends we have real fault in the
network and the CTS should not operate.
• If the ratio is non-zero only in one end there is a change of CT
failure and CTS should operate.
A second criteria for CTS is to check whether the differential system
is loaded or not. For this purpose the positive sequence current I1
is checked at both ends. If load current is detected only in one end,
it is assumed that there is internal fault condition and CTS is
prevented from operating, but if load current is detected at both line
ends, CTS operation is permitted.
V59/en M/A010 93
5.14 Line differential protection LdI> (87L) 5 Protection functions
I C = l 2πfCU ⋅ 10 −3
l= Cable length (km)
IC = Charging current (amperes)
f= Frequency
C= Cable capacitance ( µF / km)
U= Voltage to neutral (kV)
µF 15kV
I C = 32km ⋅ 2 ⋅ 3.14 ⋅ 50 Hz ⋅ 0.23 ⋅ ⋅ 10 −3
km 3
94 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
VO1 – 6
Logic1 – 20
V59/en M/A010 95
5.14 Line differential protection LdI> (87L) 5 Protection functions
Figure 5.37: Frequency adaptation mode has to be set as “Fixed” when line
differential protection is used
96 V59/en M/A010
5 Protection functions 5.14 Line differential protection LdI> (87L)
Figure 5.38: Second harmonic blocking can be enabled in the LdI menus
V59/en M/A010 97
5.14 Line differential protection LdI> (87L) 5 Protection functions
Figure 5.39: Fifth harmonic blocking can be enabled in the LdI> and LdI>> menus.
98 V59/en M/A010
5 Protection functions 5.15 Programmable stages (99)
V59/en M/A010 99
5.15 Programmable stages (99) 5 Protection functions
Disabled
Priority ms Software task priority of the protected stage Set
Status - Current status of the stage -
Blocked -
Start F
Trip F
SetGrp 1, 2, 3, 4 Active setting group Set
SGrpDI Digital signal to select the active setting group Set
- None
DIx Digital input
VIx Virtual input
LEDx LED indicator signal
VOx Virtual output
Fx Function key
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
5.16.1 2S+BIO
Delayed light indication signal
Relay output matrix has a delayed light indication output signal
(Delayed Arc L>) available for building selective arc protection
systems. Any light source combination and a delay can be configured
starting from 0.01 s to 0.15 s. The resulting signal is available in the
output matrix to be connected to BO, output relays etc.
Pick up scaling
The per unit (pu) values for pick up setting are based on the current
transformer values.
ArcI>: 1 pu = 1 x IN = rated phase current CT value
ArcI0>: 1 pu = 1 x I0N = rated residual current CT value for input I0.
Table 5.25: Parameters of arc protection stages ArcI>, ArcI0>
(50ARC/50NARC)
Parameter Value Unit Description Note
Status - Current status of the stage -
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
For details of setting ranges, see Chapter 12.3.8 Arc fault protection (option)
5.16.2 3S+BIO
The arc option card is inserted in the upper option card slot in the
back of the device. The card is fastened to the relay with two screws.
The optional arc protection card includes three arc sensor channels
for light detection and fast overcurrent detection for combined phase
currents and Io. The arc sensors are connected to the terminals 6 –
7, 8 9, and 10 – 11.
The arc information can be transmitted and/or received through digital
input and output channels BIO. The output signal is 30 V dc when
active. The input signal has to be 12 – 40 V dc to be activated.
1 Binary output +
2 Binary output GND
3 Binary input +
4 Binary input GND
5 no connection
6-7 Arc sensor 1 (VA 1 DA)
8-9 Arc sensor 2 (VA 1 DA)
9-10 Arc sensor 3 (VA 1 DA)
Binary input
The binary input (BI) on the arc option card can be used to get either
light or current indication from another relay to build selective arc
protection systems. The BI signal can also be routed to BO or T1
from 3S+BIO output matrix. BI is a dry input for signal from binary
outputs of other VAMP relays or dedicated arc protection devices
by VAMP.
Binary output
The binary output (BO) on the arc option card (see Chapter 11.6 Arc
protection card C = Arc (2 x Arc sensor + BIO)) can be used to give
the light indication signal or any other signal or signals to another
relay's binary input to build selective arc protection systems. Selection
of the BO connected signal(s) is done with the 3S+BIO output matrix.
BO is an internally wetted 30 Vdc signal for BI of other VAMP relays
or dedicated arc protection devices by VAMP.
In the matrix all inputs are on left hand side and can be connected
to outputs on top of each column by placing dots to the matrix. It
should be noted that “Output latch” isn’t a real input. Instead, a dot
in that line indicates that the corresponding output is latched on
activation.
Arc events
There are number of events that can be set to trigger on changes in
arc protection signals. For each signal there is separately selectable
on and off event. Those events can be enabled or disabled from the
3S+BIO event matrix shown in Figure 5.42.
Operation modes
There are three operation modes to use the inverse time
characteristics:
• Standard delays
Using standard delay characteristics by selecting a curve family
(IEC, IEEE, IEEE2, RI) and a delay type (Normal inverse, Very
inverse etc). See Chapter 5.17.1 Standard inverse delays IEC,
IEEE, IEEE2, RI.
• Standard delay formulae with free parameters
selecting a curve family (IEC, IEEE, IEEE2) and defining one's
own parameters for the selected delay formula. This mode is
activated by setting delay type to ‘Parameters’, and then editing
the delay function parameters A – E. See Chapter 5.17.2 Free
parameterization using IEC, IEEE and IEEE2 equations.
• Fully programmable inverse delay characteristics
Building the characteristics by setting 16 [current, time] points.
The relay interpolates the values between given points with 2nd
degree polynomials. This mode is activated by setting curve
family to ‘PrgN’'. There are maximum three different
programmable curves available at the same time. Each
programmed curve can be used by any number of protection
stages. See Chapter 5.17.3 Programmable inverse time curves.
Limitations
The maximum measured secondary phase current is 50 x IN and the
maximum directly measured earth fault current is 10 x I0N for residual
current input. The full scope of inverse delay curves goes up to 20
times the setting. At high setting the maximum measurement
capability limits the scope of inverse curves according the following
table.
Current input Maximum measured Maximum secondary scaled set-
secondary current ting enabling inverse delay times
up to full 20x setting
IL1, IL2, IL3 and I0Calc 250 A 12.5 A
I0 = 5 A 50 A 2.5 A
I0 = 1 A 10 A 0.5 A
I01 = 0.2 A 2A 0.1 A
I0 = 0.2 A
1. Example of limitation
CT = 750 / 5
CT0= 100 / 1 (cable CT is used for residual current)
The CT0 is connected to a 1 A terminals of input I0.
For overcurrent stage I> the table above gives 12.5 A. Thus the
maximum setting for I> stage giving full inverse delay range is
12.5 A / 5 A = 2.5 xIN = 1875 APrimary.
For earth fault stage I0> the table above gives 0.5 A. Thus the
maximum setting for I0> stage giving full inverse delay range is
0.5 A / 1 A = 0.5 xI0N = 50 APrimary.
108 V59/en M/A010
5 Protection functions 5.17 Inverse time operation
Limitations
The minimum definite time delay start latest, when the measured
value is twenty times the setting. However, there are limitations at
high setting values due to the measurement range. Chapter 5.17
Inverse time operation for more details.
Table 5.27: Available standard delay families and the available delay types
within each family.
Delay type Curve family
DT IEC IEEE IEEE2 RI
DT Definite time X
NI Normal inverse X X
VI Very inverse X X X
EI Extremely inverse X X X
LTI Long time inverse X X
LTEI Long time extremely inverse X
LTVI Long time very inverse X
MI Moderately inverse X X
STI Short time inverse X
STEI Short time extremely inverse X
RI Old ASEA type X
RXIDG Old ASEA type X
There are three different delay types according IEC 60255-3, Normal
inverse (NI), Extremely inverse (EI), Very inverse (VI) and a VI
extension. Additional there is a de facto standard Long time inverse
(LTI).
Table 5.28: Constants for IEC inverse delay equation
Delay type Parameter
A B
NI Normal inverse 0.14 0.02
EI Extremely inverse 80 2
VI Very inverse 13.5 1
LTI Long time inverse 120 1
0.50 ⋅ 0.14
t= 0.02
= 5 .0
4
−1
2
The operate time in this example will be 5 seconds. The same result
can be read from Figure 5.43.
Figure 5.43: IEC normal inverse delay. Figure 5.44: IEC extremely inverse delay.
Figure 5.45: IEC very inverse delay. Figure 5.46: IEC long time inverse delay.
Equation 5.5:
t = Operation delay in seconds
k = User’s multiplier
I = Measured value
A
t=k C
+ B IPICKUP = User’s pick up setting
I − 1
I START A,B,C = Constant parameter according Table 5.29.
0.0515
t = 0.50 ⋅ + 0.1140 = 1.9
4 0.02
−1
2
The operate time in this example will be 1.9 seconds. The same
result can be read from Figure 5.50.
Figure 5.47: ANSI/IEEE long time inverse delay Figure 5.48: ANSI/IEEE long time very inverse delay
Figure 5.49: ANSI/IEEE long time extremely inverse Figure 5.50: ANSI/IEEE moderately inverse delay
delay
Figure 5.51: ANSI/IEEE short time inverse delay Figure 5.52: ANSI/IEEE short time extremely inverse
delay
Equation 5.6:
B D E
t = k A + + 2
+ 3
I
− C I − C I
− C
I
START I START I START
0.6791 − 0.08 0.127
t = 0.5 ⋅ 0.1735 + + 2
+ 3
= 0.38
4 4 4
− 0. 8 − 0. 8 − 0.8
2 2 2
The operate time in this example will be 0.38 seconds. The same
result can be read from Figure 5.53.
Figure 5.53: IEEE2 moderately inverse delay Figure 5.54: IEEE2 normal inverse delay
Figure 5.55: IEEE2 very inverse delay Figure 5.56: IEEE2 extremely inverse delay
k I
t RI = t RXIDG = 5.8 − 1.35 ln
0.236 k I START
0.339 −
I
I START
0.5
t RI = = 2.3
0.236
0.339 −
4
2
The operate time in this example will be 2.3 seconds. The same
result can be read from Figure 5.57.
4
t RXIDG = 5.8 − 1.35 ln = 3.9
0.5 ⋅ 2
The operate time in this example will be 3.9 seconds. The same
result can be read from Figure 5.58.
Figure 5.57: Inverse delay of type RI. Figure 5.58: Inverse delay of type RXIDG.
0.8630 − 0.4180 0.1947
t = 0.5 ⋅ 0.2078 + + 2
+ 3
= 0.37
4 4 4
− 0.8 − 0.8 − 0.8
2 2 2
Limitations
The minimum definite time delay start latest, when the measured
value is twenty times the setting. However, there are limitations at
high setting values due to the measurement range. See Chapter 5.17
Inverse time operation for more details.
Limitations
The minimum definite time delay start latest, when the measured
value is twenty times the setting. However, there are limitations at
high setting values due to the measurement range. See Chapter 5.17
Inverse time operation for more details.
6 Supporting functions
Events are the major data for a SCADA system. SCADA systems
are reading events using any of the available communication
protocols. Event log can also be scanned using the front panel or
using VAMPSET. With VAMPSET the events can be stored to a file
especially in case the relay is not connected to any SCADA system.
Only the latest event can be read when using communication
protocols or VAMPSET. Every reading increments the internal read
pointer to the event buffer. (In case of communication interruptions,
the latest event can be reread any number of times using another
parameter.) On the local panel scanning the event buffer back and
forth is possible.
Event enabling/masking
In case of an uninteresting event, it can be masked, which prevents
the particular event(s) to be written in the event buffer. As a default
there is room for 200 latest events in the buffer. Event buffer size
can be modified from 50 to 2000.
All events are stored in non-volatile memory.
Indication screen (popup screen) can also be enabled in this same
menu when VAMPSET setting tool is used. The oldest one will be
overwritten, when a new event does occur. The shown resolution of
a time stamp is one millisecond, but the actual resolution depends
of the particular function creating the event. For example most
protection stages create events with 5ms, 10 ms or 20 ms resolution.
The absolute accuracy of all time stamps depends on the time
Clear
Order Old-New Order of the event buffer for local display Set
New-Old
FVSca Scaling of event fault value Set
PU Per unit scaling
Pri Primary scaling
Display On Indication dispaly is enabled Set
(for available date formats, see Chapter 6.6 System clock and synchronization)
hh:mm:ss.nnn Time
This value depends on sample rate, number and type of the se-
lected channels and the configured recording length.
Status Status of recording
- Not active
Run Waiting a triggering
Trig Recording
FULL Memory is full in saturated mode
ManTrig -, Trig Manual triggering Set
ReadyRec n/m n = Available recordings / m = maximum number of recordings
*) This is the fundamental frequency rms value of one cycle updated every 10 ms.
**) This is the fundamental frequency rms value of one cycle updated every 20 ms.
NOTE: The sample rate of the comtrade file has to be 32/cycle (625 micro
seconds when 50 Hz is used). The channel names have to
correspond to the channel names in VAMP relays: IL1, IL2, IL3, I0,
U12, U23, UL1, UL2, UL3 and U0.
1 3 4
Pick-up
Idle
Cold
load
1. No activation because the current has not been under the set
IDLE current.
2. Current dropped under the IDLE current level but now it stays
between the IDLE current and the pick-up current for over 80ms.
3. No activation because the phase two lasted longer than 80ms.
4. Now we have a cold load activation which lasts as long as the
operate time was set or as long as the current stays above the
pick-up setting.
Table 6.4: Parameters of the cold load & inrush detection function
Parameter Value Unit Description Note
ColdLd - Status of cold load detection:
Trip Timeout
Inrush - Status of inrush detection:
Trip Timeout
ILmax A The supervised value. Max. of IL1, IL2 and IL3
Pickup A Primary scaled pick-up value
Idle A Primary scaled upper limit for idle current
MaxTime s Set
Idle xIMODE Current limit setting for idle situation Set
Pickup xImode Pick-up setting for minimum start current Set
80 ms Maximum transition time for start recognition
100000
Number of permitted operations
10000
1000
100
50
20
10
100 200 500 1000 10000 100000
Breaked current (A) CBWEARcharacteristics
(kA) operations
1 0 (mechanical age) 10000
2 1.25 (rated current) 10000
3 31.0 (maximum breaking current) 80
4 100 1
5 100 1
6 100 1
7 100 1
8 100 1
Logarithmic interpolation
The permitted number of operations for currents in between the
defined points are logarithmically interpolated using equation
Equation 6.1:
a
C=
In
C = permitted operations
I = interrupted current
a = constant according Equation 6.2
n = constant according Equation 6.3
Ck a = C k I k2
ln
C k +1
n=
I
ln k +1
Ik
10000
ln
n= 80 = 1.5038
31000
ln
1250
Using Equation 6.1 the relay gets the number of permitted operations
for current 6 kA.
454 ⋅ 10 6
C= = 945
60001.5038
454 ⋅ 10 6
C10 kA = = 313
125001.5038
Equation 6.4:
C AlarmMax
∆=
C
945
∆ L1 = ∆ L 2 = =3
313
time
IL1 A Broken current of phase L1
The daylight saving rules for Finland are the device defaults (24-hour
clock):
- Daylight saving time start: Last Sunday of March at 03.00
- Daylight saving time end: Last Sunday of October at 04.00
604.8
AAIntv =
DriftInOneWeek
If the auto-adjust interval "AAIntv" has not been zero, but further
trimming is still needed, the following equation can be used to
calculate a new auto-adjust interval.
1
AAIntvNEW =
1 DriftInOneWeek
+
AAIntvPREVIOUS 604.8
used. For example if the drift has been 37 seconds in 14 days, the
relative drift is 37*1000/(14*24*3600) = 0.0306 ms/s.
Example 1
If there has been no external sync and the relay's clock is leading
sixty-one seconds a week and the parameter AAIntv has been zero,
the parameters are set as
AvDrft = Lead
604.8
AAIntv = = 9. 9 s
61
With these parameter values the system clock corrects itself with –1
ms every 9.9 seconds which equals –61.091 s/week.
Example 2
If there is no external sync and the relay's clock has been lagging
five seconds in nine days and the AAIntv has been 9.9 s, leading,
then the parameters are set as
1
AAIntv NEW = = 10.6
1 5000
−
9.9 9 ⋅ 24 ⋅ 3600
AvDrft = Lead
When the internal time is roughly correct – deviation is less than four
seconds – any synchronizing or auto-adjust will never turn the clock
backwards. Instead, in case the clock is leading, it is softly slowed
down to maintain causality.
Table 6.9: System clock parameters
Parameter Value Unit Description Note
Date Current date Set
Time Current time Set
Style Date format Set
y-d-m Year-Month-Day
d.m.y Day.Month.Year
m/d/y Month/Day/Year
SyncDI - DI not used for synchronizing ***)
*) A range of -11 h – +12 h would cover the whole Earth but because the International Date Line does not follow the 180°
meridian, a more wide range is needed.
***) Set the DI delay to its minimum and the polarity such that the leading edge is the synchronizing edge.
****) Relay needs to be equipped with suitable hardware option module to receive IRIG-B clock synchronization signal.
(Chapter 14 Order information).
Synchronisation with DI
Clock can be synchronized by reading minute pulses from digital
inputs, virtual inputs or virtual outputs. Sync source is selected with
SyncDI setting. When rising edge is detected from the selected input,
system clock is adjusted to the nearest minute. Length of digital input
pulse should be at least 50 ms. Delay of the selected digital input
should be set to zero.
Synchronisation correction
If the sync source has a known offset delay, it can be compensated
with SyOS setting. This is useful for compensating hardware delays
or transfer delays of communication protocols. A positive value will
compensate a lagging external sync and communication delays. A
negative value will compensate any leading offset of the external
synch source.
Sync source
When the device receives new sync message, the sync source
display is updated. If no new sync messages are received within
next 1.5 minutes, the device will change to internal sync mode.
Antenna
GPS-Clock
IRIG-B signal
from clock
IRIG-B
Distribution z
Module
Recommended wiring: shieled cable of twisted-pair or coaxial type with a maximum length of 10 meters.
Deviation
The time deviation means how much system clock time differs from
sync source time. Time deviation is calculated after receiving new
sync message. The filtered deviation means how much the system
clock was really adjusted. Filtering takes care of small deviation in
sync messages.
Auto-lag/lead
The device synchronizes to the sync source, meaning it starts
automatically leading or lagging to stay in perfect sync with the
master. The learning process takes few days.
Run
DI - Select the supervised signal Set
- None
6.8 Timers
The VAMP protection platform includes four settable timers that can
be used together with the user's programmable logic or to control
setting groups and other applications that require actions based on
calendar time. Each timer has its own settings. The selected on-time
and off-time is set and then the activation of the timer can be set to
be as daily or according the day of week (See the setting parameters
for details). The timer outputs are available for logic functions and
for the block and output matrix.
The user can force any timer, which is in use, on or off. The forcing
is done by writing a new status value. No forcing flag is needed as
in forcing i.e. the output relays.
The forced time is valid until the next forcing or until the next reversing
timed act from the timer itself.
The status of each timer is stored in non-volatile memory when the
auxiliary power is switched off. At start up, the status of each timer
is recovered.
- Not in use
0 Output is inactive
1 Output is active
On hh:mm:ss Activation time of the timer
Off hh:mm:ss De-activation time of the timer
Mode For each four timers there are 12 different modes available:
- The timer is off and not running. The output is off i.e. 0 all the time.
Daily The timer switches on and off once every day.
Monday The timer switches on and off every Monday.
Tuesday The timer switches on and off every Tuesday.
Wednesday The timer switches on and off every Wednesday.
Thursday The timer switches on and off every Thursday.
Friday The timer switches on and off every Friday.
Saturday The timer switches on and off every Saturday.
Sunday The timer switches on and off every Sunday.
MTWTF The timer switches on and off every day except Saturdays and Sundays
MTWTFS The timer switches on and off every day except Sundays.
SatSun The timer switches on and off every Saturday and Sunday.
AlrL3 1 1 = Start is on
OCs - Combined overcurrent start status.
FltL3 1 1 = Fault is on
OCt - Combined overcurrent trip status.
*) Used with IEC 60870-105-103 communication protocol. The alarm screen will show the latest if it's the biggest registered
fault current, too. Not used with Spabus, because Spabus masters usually don't like to have unpaired On/Off events.
**) Used with SPA-bus protocol, because most SPA-bus masters do need an off-event for each corresponding on-event.
The fault that can be seen in the Figure 6.4 was 3 times to nominal
and it started as an one phase fault L1-E. At the moment when one
of the protection stages tripped the fault was already increased in to
a two phase short circuit L1-L2. All signals those are stated as “1”
are also activated in the output matrix. After the fault disappears the
activated signals will release.
Combined over current status can be found from VAMPSET menu
“protection stage status 2”.
6.10 Self-supervision
The functions of the microcontroller and the associated circuitry, as
well as the program execution are supervised by means of a separate
watchdog circuit. Besides supervising the relay, the watchdog circuit
attempts to restart the micro controller in an inoperable situation. If
the micro controller does not resart, the watchdog issues a
self-supervision signal indicating a permanent internal condition.
When the watchdog circuit detects a permanent fault, it always blocks
any control of other output relays (except for the self-supervision
output relay). In addition, the internal supply voltages are supervised.
Should the auxiliary supply of the device disappear, an indication is
automatically given because the device status inoperative (SF) output
relay functions on a working current principle. This means that the
SF relay is energized when the auxiliary supply is on and the arc
flash protection is healthy.
6.10.1 Diagnostics
The device runs self-diagnostic tests for hardware and software in
boot sequence and also performs runtime checking.
Permanent inoperative state
If permanent inoperative state has been detected, the device releases
SF relay contact and status LED is set on. Local panel will also
display a detected fault message. Permanet inoperative state is
entered when the device is not able to handle main functions.
Temporal inoperative state
When self-diagnostic function detects a temporal inoperative state,
Selfdiag matrix signal is set and an event (E56) is generated. In case
the inoperative state was only temporary, an off event is generated
(E57). Self diagnostic state can be reset via local HMI.
Diagnostic registers
There are four 16-bit diagnostic registers which are readable through
remote protocols. The following table shows the meaning of each
diagnostic register and their bits.
7 Measurement functions
All the direct measurements are based on fundamental frequency
values. Most protection functions are also based on the fundamental
frequency values.
The figure shows a current waveform and the corresponding
fundamental frequency component f1, second harmonic f2 and rms
value in a special case, when the current deviates significantly from
a pure sine wave.
Current (PU)
Load = 0%
100
-5
IL2
-10
Squelch limit:
2 2 2
I RMS = I f 1 + I f 2 + ... + I f 15
THD = i =2 h2 – 15 = Harmonics
h1
Example
h1 = 100 A, h3 = 10 A, h7 = 3 A, h11 = 8 A
10 2 + 3 2 + 8 2
THD = = 13.2%
100
Clear
* This is the fundamental frequency rms value of one cycle updated every 20 ms.
L1 L2 L3
10
U0
"U0" The device is connected to zero sequence voltage.
11 Directional ground fault protection is available.
(see Figure 7.2 and Figure 11.8).
S 0 1 1 1 U
S = 1 1 a a V
2
1 3
S 2 1 a 2 a W
1 3
a = 1∠120° = − + j
2 2 , a phasor rotating constant
CTPRI
secondary → primary I PRI = I SEC ⋅
CTSEC
CTSEC
primary → secondary I SEC = I PRI ⋅
CTPRI
IN
per unit → secondary I SEC = I PU ⋅ CTSEC ⋅ I SEC = I PU ⋅ CTSEC
CTPRI
Examples:
1. Secondary to per unit for phase currents excluding ArcI>
CT = 750/5
IMODE = 525 A
Current injected to the relay's inputs is 7 A.
Per unit current is IPU = 7 x 750 / (5 x 525) = 2.00 pu = 2.00 x
IMODE = 200 %
2. Per unit to secondary for phase currents excluding ArcI>
CT = 750 / 5
IMODE = 525 A
The relay setting is 2 x IMODE = 2 pu = 200 %.
Secondary current is ISEC = 2 x 5 x 525 / 750 = 7 A
3. Secondary to per unit for residual current
Input is I0.
CT0 = 50 / 1
Current injected to the relay's input is 30 mA.
Per unit current is IPU = 0.03 / 1 = 0.03 pu = 3 %
U SEC
secondary ->per unit U PU =
U 0 SEC
Examples:
1. Secondary to per unit. Voltage measurement mode is "U0".
U0SEC = 110 V (This is a configuration value corresponding to
U0 at full ground fault.)
Voltage connected to the device's input UC is 22 V.
Per unit voltage is UPU = 22 / 110 = 0.20 pu = 20 %
Analogue mAScaling_1
output (mA)
20
16
12
4
IL
300 (A)
Figure 7.3: The average of the three phase currents. At 0 A the transducer ouput
is 0 mA, at 300 A the output is 20 mA
8 Control functions
1
A1 0 Status of alarm output relay F
1
SF 0 Status of the SF relay F
F = Editable when force flag is on. Set = An editable parameter (password needed).
The digital inputs need an external control voltage (ac or dc). The
voltage nominal activation level can be selected in Chapter 14 Order
information.
When 110 or 220 V ac voltage is used to activate the digital Inputs,
the AC mode should be selected as shown in Figure 8.1
Default is "VIn", n = 1 – 4
Description String of max. 32 characters Long name for VIs. Default is "Virtual input n", Set
n=1–4
The six virtual outputs do act like output relays, but there are no
physical contacts. Virtual outputs are shown in the output matrix and
the block matrix. Virtual outputs can be used with the user's
programmable logic and to change the active setting group etc.
NOTE: "Release all latches" signal clears and resets FPGA controlled
latches.
NOTICE
RISK OF NUISANCE TRIPPING
• The blocking matrix is dynamically controlled by selecting
and deselecting protection stages.
• Activate the protection stages first, then store the settings in
a relay. After that, refresh the blocking matrix before
configuring it.
Failure to follow these instructions can result in unwanted
shutdown of the electrical installation.
Max ctrl pulse 0.02 – 600 s Pulse length for open and close
length commands
Completion 0.02 – 600 s Timeout of ready indication
timeout
If changing states takes longer than the time defined by “Max ctrl
pulse length” setting, object is inoperative and “Object failure” matrix
signal is set. Also undefined-event is generated. “Completion timeout”
is only used for the ready indication. If “DI for ‘obj ready’” is not set,
completion timeout has no meaning.
If the device is in local control state, the remote control inputs are
ignored and vice versa. Object is controlled when a rising edge is
detected from the selected input. Length of digital input pulse should
be at least 60 ms.
General
The basic idea is that normal protection functions will detect the fault.
Then the protection function will trigger the AR function. After tripping
the circuit-breaker (CB), the AR function can reclose the CB.
Normally, the first reclose (or shot) is so short in time that consumers
cannot notice anything. However, the fault is cleared and the feeder
will continue in normal service.
Terminology
Even though the basic principle of AR is very simple; there are a lot
of different timers and parameters that have to be set.
In VAMP relays, there are five shots. A shot consists of open time
(so called “dead” time) and close time (so called “burning” time or
discrimination time). A high-speed shot means that the dead time is
less than 1 s. The time-delayed shot means longer dead times up
to 2-3 minutes.
There are four AR lines. A line means an initialization signal for AR.
Normally, start or trip signals of protection functions are used to
initiate an AR-sequence. Each AR line has a priority. AR1 has the
highest and AR4 has the lowest one. This means that if two lines
are initiated at the same time, AR will follow only the highest priority
line. A very typical configuration of the lines is that the instantaneous
overcurrent stage will initiate the AR1 line, time-delayed overcurrent
stage the AR2 line and earth-fault protection will use lines AR3 and
AR4.
For more information about auto-reclosing, please refer to our
application note “Auto-reclosing function in VAMP protection relays”.
The auto-reclose (AR) matrix in the following Figure 8.6 describes
the start and trip signals forwarded to the auto-reclose function.
.
.
I>>s
I>t
I>s
AR-request)
Critical
AR1 On
AR2 On
Off
On
discrim
e,
e,
Figure 8.6: Auto-reclose matrix
The AR matrix above defines which signals (the start and trip signals
from protection stages or digital input) are forwarded to the
auto-reclose function. In the AR function, the AR signals can be
configured to initiate the reclose sequence. Each shot from 1 to 5
has its own enabled/disabled flag. If more than one AR signal
activates at the same time, AR1 has highest priority and AR2 the
lowest. Each AR signal has an independent start delay for the shot
1. If a higher priority AR signal activates during the start delay, the
start delay setting will be changed to that of the highest priority AR
signal.
After the start delay the circuit-breaker (CB) will be opened if it is
closed. When the CB opens, a dead time timer is started. Each shot
from 1 to 5 has its own dead time setting.
After the dead time the CB will be closed and a discrimination time
timer is started. Each shot from 1 to 5 has its own discrimination time
setting. If a critical signal is activated during the discrimination time,
the AR function makes a final trip. The CB will then open and the
AR sequence is locked. Closing the CB manually clears the “locked”
state.
After the discrimination time has elapsed, the reclaim time timer
starts. If any AR signal is activated during the reclaim time or the
discrimination time, the AR function moves to the next shot. The
reclaim time setting is common for every shot.
If the reclaim time runs out, the auto-reclose sequence is successfully
executed and the AR function moves to ready -state and waits for a
new AR request in shot 1.
Manual closing
When CB is closed manually with the local panel, remote bus, digital
inputs etc, the reclaim-state is activated. Within the reclaim time all
AR requests are ignored. It is up to protection stages to take care of
tripping. Trip signals of protection stages must be connected to a
trip relay in the output matrix.
Manual opening
Manual CB open command during AR sequence will stop the
sequence and leaves the CB open.
Blocking of AR shots
Each AR shot can be blocked with a digital input, virtual input or
virtual output. Blocking input is selected with Block setting. When
selected input is active the shot is blocked. A blocked shot is treated
like it doesn’t exist and AR sequence will jump over it. If the last shot
in use is blocked, any AR request during reclaiming of the previous
shot will cause final tripping.
Starting AR sequence
Each AR request has own separate starting delay counter. The one
which starting delay has elapsed first will be selected. If more than
one delay elapses at the same time, an AR request of the highest
priority is selected. AR1 has the highest priority and AR4 has the
lowest priority. First shot is selected according to the AR request.
Next AR opens the CB and starts counting dead time.
Critical AR request
Critical AR request stops the AR sequence and cause final tripping.
Critical request is ignored when AR sequence is not running and
also when AR is reclaiming.
Critical request is accepted during dead time and discrimination time.
DI to block AR setting
This setting is useful with an external synchro-check device. This
setting only affects re-closing the CB. Re-closing can be blocked
with a digital input, virtual input or virtual output. When the blocking
input is active, CB won’t be closed until the blocking input becomes
inactive again. When blocking becomes inactive the CB will be
controlled close immediately.
Table 8.5: Setting parameters of AR function
Parameter Value Unit Default Description
ARena ARon; ARoff - ARon Enabling/disabling the autoreclose
ExtSync None, - - The digital input for blocking CB close. This can be
used for Synchrocheck.
any digital input, virtual
input or virtual output
AR_DI None, - - The digital input for toggling the ARena parameter
CLOSE;
OPEN_REQUEST;
CLOSE_REQUEST;
READY;
NOT_READY;
INFO_NOT_AVAILABLE;
FAIL
Status INIT; - AR-function state
RECLAIM_TIME;
READY;
WAIT_CB_OPEN;
WAIT_CB_CLOSE;
DISCRIMINATION_TIME;
LOCKED;
FINAL_TRIP;
CB_FAIL;
INHIBIT
Shot# 1–5 - The currently running
shot
ReclT RECLAIMTIME; - The currently running
time (or last executed)
STARTTIME;
DEADTIME;
DISCRIMINATIONTIME
SCntr - Total start counter
Fail - The counter for failed
AR shots
Shot1* - Shot1 start counter
Shot2* - Shot2 start counter
Shot3* - Shot3 start counter
Shot4* - Shot4 start counter
Shot5* - Shot5 start counter
* There are 5 counters available for each one of the two AR signals.
I> setting
Current
Open command
CB
Close command
CB
CBclose
state
CBopen
state
Figure 8.7: Example sequence of two shots. After shot 2 the fault is cleared.
1. Current exceeds the I> setting; the start delay from shot 1 starts.
2. After the start delay, an OpenCB relay output closes.
3. A CB opens. The dead time from shot 1 starts, and the OpenCB
relay output opens.
4. The dead time from shot 1 runs out; a CloseCB output relay
closes.
5. The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 1 starts. The current is still over the
I> setting.
6. The discrimination time from the shot 1 runs out; the OpenCB
relay output closes.
7. The CB opens. The dead time from shot 2 starts, and the
OpenCB relay output opens.
8. The dead time from shot 2 runs out; the CloseCB output relay
closes.
9. The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 2 starts. The current is now under
I> setting.
10. Reclaim time starts. After the reclaim time the AR sequence is
successfully executed. The AR function moves to wait for a new
AR request in shot 1.
Figure 8.8: Logic can be found and modified in “logic” menu in VAMPSET setting tool
1 2
3
4
1 3
2 5
1
2 4
3
NOTE: Whenever writing new logic to the device the unit has to be restarted.
CommunicationPorts50
COMMUNICATION PORTS
Communication
option
Front panel in use
Ethernet
RS-232
D-
USB
2 1
FRONT PANEL
3 4
D+
GND
Figure 9.1: Communication ports and connectors. The DSR signal from the front
panel port selects the active connector for the RS232 local port.
0.0.0.0 = no SNTP
KeepAlive nn TCP keepalive interval Set 1)
FTP server on/off Enable FTP server Set
FTP speed 4 Kb/s (default) Maximum transmission speed for FTP Set
FTP password ? (user) FTP password Set
config (configurator)
MAC address 001ADnnnnnnn MAC address
VS Port nn IP port for VAMPSET Set
23 (default)
Msg# nnn Message counter
Errors nnn Error counter
Tout nnn Timeout counter
EthSffEn on/off Sniffer port enable Set
SniffPort Port2 Sniffer port
1) KeepAlive: The KeepAlive parameter sets in seconds the time between two keepalive packets are sent from the IED.
The setting range for this parameter is between zero (0) and 20 seconds; with the exception that zero (0) means actually
120 seconds (2 minutes). A keep alive’s packet purpose is for the VAMP IED to send a probe packet to a connected client
for checking the status of the TCP-connection when no other packet is being sent e.g. client does not poll data from the
IED. If the keepalive packet is not acknowledged, the IED will close the TCP connection. Connection must be resumed
on the client side.
(TCP PORT 2nd INST) None Command line interface for VAMPSET
ModbusTCPs Modbus TCP slave
IEC 61850 IEC-61850 protocol
EtherNet/IP Ethernet/IP protocol
DNP3 DNP/TCP
Port nnn Ip port for protocol, default 502 Set
Msg# nnn Message counter
Errors nnn Error counter
Tout nnn Timeout counter
9.2.1 PC communication
PC communication is using a VAMP specified command line
interface. The VAMPSET program can communicate using the local
USB-port or using optional Ethernet interface.
For Ethernet configuration, see Chapter 9.1.4 Ethernet port.
2400
4800
9600
19200
Parity None Parity for Modbus RTU Set
Even
Odd
9600 (default)
19200
38400
Parity None (default) Parity Set
Even
Odd
SlvAddr 1 – 65519 An unique address for the device within the Set
system
MstrAddr 1 – 65519 Address of master Set
255 = default
LLTout 0 – 65535 ms Link layer confirmation timeout Set
LLRetry 1 – 255 Link layer retry count Set
1 = default
APLTout 0 – 65535 ms Application layer confirmation timeout Set
5000 = default
CnfMode EvOnly (default); All Application layer confirmation mode Set
DBISup No (default); Yes Double-bit input support Set
SyncMode 0 – 65535 s Clock synchronization request interval. Set
0 = only at boot
9.2.6 EtherNet/IP
The device supports communication using EtherNet/IP protocol which
is a part of CIP (Common Industrial Protocol) family. EtherNet/IP
protocol is available with the optional inbuilt Ethernet port. The
protocol can be used to read / write data from the device using
request / response communication or via cyclic messages
transporting data assigned to assemblies (sets of data).
For more detailed information and parameter lists for EtherNet/IP,
refer to a separate application note “Application Note
EtherNet/IP.pdf”.
For the complete data model of EtherNet/IP, refer to the document
“Application Note DeviceNet and EtherNetIP Data Model.pdf”.
No
FTP password Max 33 characters Required to access the FTP server with an FTP Set
client. Default is “config”. The user name is al-
ways “VAMP”.
FTP max speed 1 – 10 KB/s The maximum speed at which the FTP server Set
will transfer data.
9.2.8 DeviceNet
The device supports communication using DeviceNet protocol which
is a part of CIP (Common Industrial Protocol) family. DeviceNet
protocol is available with the optional external VSE009 module. The
protocol can be used to read / write data from the device using
request / response communication or via cyclic messages
transporting data assigned to assemblies (sets of data).
For more detailed information about DeviceNet, refer to a separate
application note “Application Note DeviceNet.pdf”.
For the complete data model of DeviceNet, refer to the document
“Application Note DeviceNet and EtherNetIP Data Model.pdf”.
10 Application
VAMP 59 can be used for protection of medium voltage networks
with grounded or low-resistance grounded neutral point. The relay
has the required functions to be applied as a backup relay in high
voltage networks or to a transformer differential relay.
The relays provide circuit-breaker control functionality, additional
primary switching devices (earthing switches and disconnector
switches) can also be controlled from the relay HMI or the control or
SCADA/automation system. Programmable logic functionality is also
implemented in the relay for various applications e.g interlockings
schemes. For details about the functionality in the relays, see
Table 1.1.
Master Slave
Figure 10.1: Line differential protection and auto-reclosing
52b 52a
Figure 10.2: Trip circuit supervision using a single digital input and an external resistor
R. The circuit-breaker is in the closed position. The supervised circuitry in this CB
position is double-lined. The digital input is in active state when the trip circuit is
complete.
NOTE: The need for the external resistor R depends on the application and
circuit breaker manufacturer's specifications.
52a
Figure 10.3: Alternative connection without using circuit breaker 52b auxiliary contacts.
Trip circuit supervision using a single digital input and an external resistor R. The
circuit-breaker is in the closed position. The supervised circuitry in this CB position
is double-lined. The digital input is in active state when the trip circuit is complete.
52b 52a
Figure 10.4: Trip circuit supervision using a single digital input, when the circuit breaker
is in open position.
52a
Figure 10.5: Alternative connection without using circuit breaker 52b auxiliary contacts.
Trip circuit supervision using a single digital input, when the circuit breaker is in open
position.
Figure 10.6: An example of digital input DI1 configuration for trip circuit supervision
with one digital input.
Figure 10.7: An example of output matrix configuration for trip circuit supervision with
one digital input.
Equation 10.1:
U MIN − U DI − I DI ⋅ RCoil
R=
I DI
Equation 10.2:
2
P = 2 ⋅ I DI ⋅R
Equation 10.3:
2
U MAX
P=
R
A 0.5 W resistor will be enough for this short time peak power, too.
However, if the trip relay is closed for longer time than a few seconds,
a 1 W resistor should be used.
52b 52a
Figure 10.8: Trip circuit supervision with two digital inputs. The CB is closed. The
supervised circuitry in this CB position is double-lined. The digital input is in active
state when the trip circuit is complete.
52b 52a
Figure 10.9: Trip circuit supervision with two digital inputs. The CB is in the open
position. The two digital inputs are now in series.
Figure 10.10: An example of digital input configuration for trip circuit supervision
with two dry digital inputs DI1 and DI2.
Figure 10.11: An example of logic configuration for trip circuit supervision with two
dry digital inputs DI1 and DI2.
Figure 10.12: An example of output matrix configuration for trip circuit supervision
with two digital inputs.
11 Connections
X1
X3
1
8
20
2 7
19
6
3 18
5
17
4 4
16
3
15
5 2
14
1
6 13
12
7
11
8 10
9
9 8
10 7
6
48...230V AC/DC
11 5
4
24VDC
3
X2 2
1
1
2
Terminal X1
No Symbol Description
Terminal X2
No Symbol Description
Terminal X3
No Symbol Description
11 11 T4 Trip relay 4
10 10 T4 Trip relay 4
2 1 1 VBUS
2 D-
3
3 D+
4
4 GND
Figure 11.2: Pin numbering of the front Shell Shield
panel USB type B connector
7 = GND
9 = +12V
VCM 232+IR LB CLOCK SYNC TTL 2-pole screw con- 1= Data
(IRIG-B ) nector
RS-232 interface 2= GND
with timesyn-
cronisation input
VCM 232+FI LC EXTENSION Light Snap-in connector
4=Reserved
5=Reserved
6=Receive-
7=Reserved
8=Reserved
VCM 232+L6 LG ETHERNET Light 100Mbps LC-connector TX=Lower LC-con-
nector
RS-232 interface
with IEC 61850 RX=Upper LC-con-
Ethernet fibre inter- nector
face
NOTE: Pay special attention when using DI7 (terminals numbers X6:1 –
X6:2) as digital input use. Never configure, operate or control T5
output if DI7 is used as an imput. Should the control of T5 happen
the output contact will short-circuit DI7 and will lead to equipment
damage and loss of data.
The optional arc protection card includes two arc sensor channels.
The arc sensors are connected to terminals X6: 5 – 6 and 7 – 8.
The arc information can be transmitted and/or received through digital
input and output channels. This is a 48 V dc signal.
The arc option card is inserted in the upper option card slot in the
back of the unit.
V59/en M/A010 203
11.7 Arc protection card D = Advanced arc (3 x Arc sensor + BIO) 11 Connections
The optional arc protection card includes two arc sensor channels.
The arc sensors are connected to terminals X6: 6 – 7, 8 – 9 and 10
– 11.
The arc information can be transmitted and/or received through digital
input and output channels. This is a 48 V dc signal.
The arc option card is inserted in the upper option card slot in the
back of the unit.
For this block information, please see Figure 11.7.
The arc information can be transmitted and/or received through digital
input and output channels BIO. The output signal is 48 V dc when
active. The input signal has to be 18 – 48 V dc to be activated.
The GND must be connected together between the GND of the
connected devices.
The binary output of the arc option card may be activated by one or
both of the connected arc sensors, or by the binary input. The
connection between the inputs and the output is selectable via the
output matrix of the device. The binary output can be connected to
an arc binary input of another VAMP protection relay or arc protection
system.
-
Scaling Y2 Scaled value Point 2
-
X2 Modbus value
X: -32000 – 32000 -
-
X1 Modbus value
-
Offset Subtracted from Modbus value, before
-32000 – 32000
running XY scaling
-
-
- -
-
- -
-
- -
- -
-
C, F, K, mA, Ohm or V/A Unit selection
- -
-
Active value
- -
-
- Alarm >> -
-
- -
-
- Alarm > -
-
- -
-
-
Active value
- -
- -
-
- -
-
On / Off Enabling for measurement
Analog input alarms have also matrix signals, “Ext. Aix Alarm1” and “Ext. Aix Alarm2”.
-
-
-
- -
CoilS, InputS,
InputR or HoldingR
-
- -
-
- -
-
- -
- -
- -
On / Off Enabling for measurement
Communication errors
-
- -
- -
-
- -
- -
-
- -
- -
-
- Enabling for measurement
Communication errors
-
-
-32768 – +32767 -
(0 – 65535) -
-
- -
-
- -
-
- -
-
-
0 – 42x108, -
-21x108 – +21x108 -
-
-
Link selection
-
- -
-
Active value
-
On / Off Enabling for measurement
X2:1
~ VAMP 59 Front
87L 67N
Ldl> I0φ>
Remote
Ldl>> I0φ>>
X1:1
50/51 59N
X1:8 I0 5A
T>
T4 X3:11
1A 50ARC
X1:9 50N/51N
ArcI> X3:10
X1:10 X3:7
I0>, I02>
50NARC A1
U0 I0>>, I02>> ArcI0> X3:9
X1:11
X3:8
I/O extension
module 79
* order option
I0
1A
0.2A
Figure 11.4: Block diagram of overcurrent and earthfault protection relay VAMP 59
X6:1 +DI7 / T5
X6:2 -DI7 / T5
X6:3 DI3
X6:4 COMM
X6:5 DI4
X6:6 DI5
X6:7 COMM
X6:8 DI6
Figure 11.6: Block diagram of optional arc protection card C = Arc (2 x Arc sensor
+ BIO)
X6:6 S1
X6:7 S1 L>
X6:8 S2
X6:9 S2
X6:10 S3
X6:11 S3
Figure 11.7: Block diagram of advanced optional arc protection card D = Advanced
Arc (3 x Arc sensor + BIO)
L2
L3
+ 1 -
X2:1
~
Front - 0
X2:2 Comm. option
Remote
VAMP 59
X1:1
X1:2 IL1 T1
X3:17
X1:3 X3:16
X1:4 IL2 T2 X3:15 +
X1:5 X3:14
+
X1:6 IL3 T3 X3:13
X1:7 * X3:12
dn da
I
X1:8 0 5A T4 X3:11
X1:9 1A
X3:10
X1:10
A1 X3:7
X1:11 U0/UL1/U12
U0 X3:9
I/O extension
X3:8
module
X6:1
X6:2
Arc option
X6:3
X6:4 or SF X3:18
X6:5 X3:19
DI / DO module
X6:6
X6:7
X3:20
mA out option
X6:8
Figure 11.8: Block diagram of overcurrent and earthfault protection relay VAMP 59.
12 Technical data
12.1 Connections
Table 12.1: Measuring circuits
Phase current inputs -
- 100 A (for 10 s)
- 500 A (for 1 s)
- Burden 0.075 VA
- 100 A (for 10 s)
- 500 A (for 1 s)
- Burden 0.075 VA
- 20 A (for 10 s)
- 100 A (for 1 s)
- Burden 0.02 VA
- 4 A (for 10 s)
- 20 A (for 1 s)
- Burden 0.02 VA
Frequency -
Measuring range 16 – 95 Hz
Note! Polarity
B: 75 V dc
C: 155 V dc
Current drain < 4 mA (typical approx. 3mA)
Activation time dc/ac < 11 ms / < 15 ms
Reset time dc/ac < 11 ms / < 15 ms
Terminal block: Maximum wire dimension:
Ethernet 10 Base-T
Protocols IEC 60870-5-101
DNP 3.0
IEC 61850
Ethernet IP
Device de-energized
- Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 2Gn, 10Hz – 150 HZ
- Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 30Gn/11ms
- Bump IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 20Gn/16ms
10 ppb CL2
Flowing mixed gas corrosion test, IEC 60068-2-60, Ke 25°C (77°F), 75% RH,
method 4
10 ppb H2S, 200 ppb NO2,
Device in storage
- Dry heat EN / IEC 60068-2-2, Bb 75°C (167°F)
- Cold EN / IEC 60068-2-1, Ab -40°C (-40°F)
**) This is the instantaneous time i.e. the minimum total operational time including the
fault detection time and operation time of the trip contacts.
Inaccuracy:
- 2nd harmonic blocking ±1% - unit
- 5th harmonic blocking ±1% - unit
- Starting ±5% of set value or 0.05 x IN when currents
are > 200 mA
- Operating time (3.5 x ISET) typically 35 ms
NOTE: The amplitude of second harmonic content has to be at least 2% of the nominal
of CT. If the nominal current is 5 A, the 100 Hz component needs to exceed 100
mA.
IDMT function:
- Delay curve family (DT), IEC, IEEE, RI Prg
- Curve type EI, VI, NI, LTI, MI…, depends on the family*
- Time multiplier k 0.05 – 20.0, except
Inaccuracy:
- Starting ±3% of the set value or 5 mA secondary
- Operate time at definite time function ±1% or ±25 ms
- Operate time at IDMT function ±5% or at least ±25 ms**
Inaccuracy:
- Starting ±3% of the set value or 5 mA secondary
- Operate time DT (IM/ISET ratio > 1.5) ±1% or ±15 ms
- Operate time DT (IM/ISET ratio 1.03 – 1.5) ±1% or ±25 ms
IDMT function:
- Delay curve family (DT), IEC, IEEE, RI Prg
- Curve type EI, VI, NI, LTI, MI..., depends on the family*
- Time multiplier k 0.05 – 20.0, except
Inaccuracy:
- Starting ±2% of the set value or ±0.3% of the rated
value
- Starting (Peak mode) ±5% of the set value or ±2% of the rated
value (Sine wave <65 Hz)
- Operate time at definite time function ±1% or ±25 ms
- Operate time at IDMT function ±5% or at least ±25 ms**
Inaccuracy:
- Starting ±2% of the set value or ±0.3% of the rated
value
- Starting (Peak mode) ±5% of the set value or ±2% of the rated
value (Sine wave <65 Hz)
- Operate time ±1% or ±25 ms
IDMT function:
- Delay curve family (DT), IEC, IEEE, RI Prg
- Curve type EI, VI, NI, LTI, MI…, depends on the family*
- Time multiplier k 0.05 – 20.0, except
Inaccuracy:
- Starting U0 & I0 (rated value In= 1 – 5A) ±3% of the set value or ±0.3% of the rated
value
- Starting U0 & I0 (Peak Mode when, rated ±5% of the set value or ±2% of the rated value
value I0n= 1 – 10A) (Sine wave <65 Hz)
- Starting U0 & I0 (I0Calc) ±3% of the set value or ±0.5% of the rated
value
- Angle ±2° when U> 1V and I0> 5% of I0N or > 50 mA
else ±20°
- Operate time at definite time function ±1% or ±30 ms
- Operate time at IDMT function ±5% or at least ±30 ms**
NOTE: The amplitude of second harmonic content has to be at least 2% of the nominal
of CT. If the moninal current is 5 A, the 100 Hz component needs to exceed 100
mA.
NOTE: The amplitude of fifth harmonic content has to be at least 2% of the nominal of
CT. If the moninal current is 5 A, the 250 Hz component needs to exceed 100 mA.
Continuous carry 5A
at 48 V dc: 1.0 A
NOTE: Approximately 2 mA of current is going trough the T5 (X6:1 & X6:2) circuit even
when used as a digital output. This has to be noticed when T5 is used with certain
type of applications (if 2 mA is enough to control for example a breaker).
0.01 – 0.15 s
Reset time <95 ms
Reset time (Delayed ARC L) <120 ms
Reset time (BO) < 85 ms
Reset ratio 0.90
Inaccuracy: -
- Operate time ±5 ms
2. 3S+BIO
The operation of the arc protection depends on the setting value of
the I>int and I0>int current limits.
The arc current limits cannot be set, unless the relay is provided with
the optional arc protection card.
Table 12.33: Advanced arc protection stage
Pick-up value 0.5 – 10.0 x IN for I>
- Operate time 7 ms
Inaccuracy: -
Sample rate:
- Waveform recording 32/cycle, 16/cycle, 8/cycle
- Trend curve recording 10, 20, 200 ms
1, 5, 10, 15, 30 s
1 min
Recording time (one record) 0.1 s – 12 000 min (According recorder set-
ting)
Pre-trigger rate 0 – 100%
Number of selected channels 0 – 12
The recording time and the number of records depend on the time setting and the
number of selected channels.
Table 12.35: Inrush current detection
Cold load settings: -
13 Mounting
PANEL MOUNTING VAMP 50 SERIES
mm
in 158 128 213 80
6.22 5.04 8.39 3.15
Vamp 50 series
137 OK
171 186
5.39 6.73 7.32
F1 F2
9.0
82 0.35
1 3 3.23
9.0 5.0
0.2
0.35
9.5
0.37
series
Vamp 50
120 2
4.72
OK
F2
139
5.47
F1
series
Vamp 50
OK
1
0.0 .0-10 F1
F2
4-
0.3
9
>2
0
0.79
series
Vamp 50
series
Vamp 50
OK
F2
F1
OK
F2
F1
V50WAF
1
1a
Vamp 52
OK
1c F1
F2
2 1b
185
mm 7.28 32
in 1 21
32 1.26
4.76
1.26
OK
F2
F1
1 20
4.72
3 4
OK
F2
F1
OK
F2
F1
14 Order information
When ordering, please state:
• Type designation:
• Quantity:
• Accessories (see respective ordering code):
Relay type
= Default
mA output option
A = None
B = mA output
DI nominal voltage
1 = 24 VDC / 110 VAC
2 = 110 VDC / 220VAC
3 = 220 VDC
Note:
(* Option available only with communication module 1: L and M
Accessories
Order code Description Note
VSE001GG Fibre optic Interface Module (glass - glass) Max. distance 1 km (0.63 miles)
3P032 WESTERMO ODW-720-F1 (Base module)
3P033 WESTERMO SLC20 (1310 nm) Max. distance 20 km (12.43 miles)
3P034 WESTERMO SLC40 (1310 nm) Max. distance 40 km (24.86 miles)
3P035 WESTERMO SLC80 (1550 nm) Max. distance 80 km (49.71 miles)
3P036 WESTERMO SLC120 (1550 nm) Max. distance 120 km (74.57 miles)
VX063 RS232 converter cable for WESTERMO ODW-720-F1 Cable length 3 m (9.85 ft)
3P014 MOXA TCF-90 Max. distance 40 km (24.86 miles)
VX048 RS232 converter cable for MOXA TCF-90 Cable length 3 m (9.85 ft)
3P022 MOXA TCF-142-S-ST Max. distance 40 km (24.86 miles)
VX062 RS232 converter cable for MOXA TCF-142-S-ST Cable length 3 m (9.85 ft)
VX052-3 USB programming cable (VAMPSET) Cable length 3 m (9.85 ft)
VX044 Interface cable to VIO 12 (RTD module) Cable length 2 m (6.57 ft)
VIO 12 AA RTD Module, 12 x RTD inputs, Optical Tx Communication
(24-230 Vac/dc)
VIO 12 AC RTD/mA Module, 12 x RTD inputs, PTC, mA inputs/outputs,
RS232, RS485 and Optical Tx/Rx Communication (24 Vdc)
VIO 12 AD RTD/mA Module, 12 x RTD inputs, PTC, mA inputs/outputs,
RS232, RS485 and Optical Tx/Rx Communication (48-230
Vac/dc)
VA 1 DA-6 Arc sensor Cable length 6 m (19.69 ft)
VA 1 DA-20 Arc sensor Cable length 20 m (65.62 ft)
V50WAF V50 wall assembly frame
15 Firmware revision
10.xx Maximum rated power increased to 400000 kVA from 200000 kVA
Logic output numbering is not changed when changes are made in the logic
HMI changes:
• Order of the first displays changed, 1.measurement, 2. mimic, 3. title
• timeout does not apply if the first 3 displays are active
10.122 Stages renamed:
• If2> = MAGNETISING INRUSH 68F2
• If5> = OVER EXCITATION 68F5
• P< = DIRECTIONAL POWER 32
• P<< = DIRECTIONAL POWER 32
- I>: Pick-up limit setting minimum value changed from 0.10 to 0.05
Schneider Electric