8 Transient Analysis: 8.1. SYNOPSIS
8 Transient Analysis: 8.1. SYNOPSIS
8 Transient Analysis: 8.1. SYNOPSIS
Chapter 8
Transient Analysis
173
Copyright (C) 2012 American Water Works Association All Rights Reserved
174 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
fluids. Transient flow analysis of the piping system is often more important than the
analysis of the steady-state operating conditions that engineers normally use as the
basis for system design. Transient pressures are most significant when the rate of flow
is changed rapidly, such as rapid valve closures or pump stoppages. Such flow distur-
bances, whether caused by design or accident, may create traveling pressure waves of
excessive magnitude. These transient pressures are superimposed on the steady-state
conditions present in the line at the time the transient occurs. The total force acting
within a pipe is obtained by summing the steady-state and transient pressures in the
line. The severity of transient pressures must thus be accurately determined so that
the pipes can be properly designed to withstand these additional shock loads. In fact,
pipes are often characterized by pressure ratings (or pressure classes) that define their
mechanical strength and have a significant influence on their cost.
Transient events may be associated with equipment failure, pipe rupture, sepa-
ration at bends, and the introduction of contaminated water into the distribution sys-
tem via unprotected cross-connections or intrusion. High-flow velocities can remove
protective scale and tubercles and increase the contact of the pipe with oxygen, all of
which will increase the rate of corrosion. Uncontrolled pump shutdown can lead to the
undesirable occurrence of cavitation and water-column separation, which can result in
catastrophic pipeline failures due to severe pressure rises following the collapse of the
vapor cavities. Vacuum conditions can create high stresses and strains that are much
greater than those occurring during normal operating regimes. They can cause the col-
lapse of thin-walled pipes or reinforced concrete sections, particularly if these sections
were not designed to withstand such strains (e.g., pipes with a low pressure rating).
Cavitation occurs when the local pressure is lowered to the value of vapor pres-
sure at the ambient temperature. At this pressure, gas within the liquid is released
and the liquid starts to vaporize. When the pressure recovers, liquid enters the cavity
caused by the gases and collides with whatever confines the cavity (i.e., another mass
of liquid or a fixed boundary) resulting in a pressure surge. In this case, both vacuum
and strong pressure surges are present, a combination that may result in substantial
damage. The main difficulty here is that accurate estimates are difficult to achieve,
particularly because the parameters describing the process are not yet determined
during design. Moreover, the vapor cavity collapse cannot be effectively controlled.
In less drastic cases, strong pressure surges may cause cracks in internal lining or
damage connections between pipe sections and, in more serious cases, can destroy
or cause deformation to equipment such as pipeline valves, air valves, or other surge
protection devices. Sometimes the damage is not realized at the time but results in
intensified corrosion that, combined with repeated transients, may cause the pipeline
to collapse in the future. Transient events in pipelines also damage seals that often
lead to increase leakage and significant water loss.
Transient events can have significant water quality and health implications.
These events can generate high intensities of fluid shear and may cause resuspension
of settled particles as well as biofilm detachment. Moreover, low pressure caused by
transients may promote the collapse of water mains; leakage into the pipes at loose
joints, cracks, and seals under subatmospheric conditions; backsiphonage at cross-
connections; and potential intrusion of untreated, possibly contaminated groundwater
in the distribution system. Pathogens or chemicals in close proximity to the pipe can
become potential contamination sources, where continuing consumption or leakage
can pull contaminated water into the depressurized main.
Recent studies have confirmed that soil and water samples collected immediately
adjacent to water mains can contain various levels of microorganisms, an indicator
of fecal pollution (fecal coliforms, E. coli, Clostridium perfringens, coliphages) and in
some cases enteric viruses (Besner et al. 2008; Karim et al. 2003; Kirmeyer et al.
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 175
2001). This is especially significant in systems with leaking pipes below the water
table. Problems with low or negative pressure transients have been reported in the
literature (Walski and Lutes 1994; LeChevallier et al. 2003). Gullick et al. (2004)
studied transient pressure occurrences in actual distribution systems and observed 15
surge events that resulted in a negative pressure. Hooper et al. (2006) and Besner et
al. (2007) also reported such events in full-scale systems.
The most often identified cause for the events reported in the literature was the
sudden shutdown of pumps, either unintentional (power failure) or intentional (pump
tests). Using a pilot-scale test rig, Friedman et al. (2004) confirmed that negative
pressure transients can occur in the distribution system and that the intruded water
can travel downstream from the site of entry. Locations with the highest potential for
intrusion were identified as sites experiencing leaks and breaks, areas of high water
table, and flooded air-vacuum valve vaults. Preliminary results by Besner et al. (2007)
showed that significant concentrations of indicator microorganisms could be detected
in the water found in flooded air-vacuum valve vaults. In the event of a large intrusion
of pathogens, the chlorine residual normally sustained in drinking water distribution
systems may be insufficient to disinfect contaminated water, which could lead to dam-
aging health effects. A recent case study in Kenya (Ndambuki 2006) showed that in
the event of a 0.1 percent raw sewage contamination, the available residual chlorine
within the distribution network would not render the water safe.
Transient events that can allow intrusion to occur are caused by sudden changes
in the water velocity due to loss of power, sudden valve or hydrant closure or opening,
a main break, fire flow, or an uncontrolled change in on/off pump status (Boyd et al.
2004). Transient-induced intrusions can be minimized by knowing the causes of pres-
sure surges, defining the system’s response to surges, and estimating the system’s
susceptibility to contamination when surges occur (Friedman et al. 2004). Therefore,
water utilities should never overlook the effect of pressure surges in their distribution
systems. Even some common transient protection strategies, such as relief valves or
air chambers, if not properly designed and maintained, may permit pathogens or other
contaminants to find a “backdoor” route into the potable water distribution system.
Any optimized design that fails to properly account for pressure surge effects is likely
to be, at best, suboptimal, and at worst completely inadequate.
Pressure transients in water distribution systems are inevitable and will nor-
mally be most severe at pump stations and control valves, in high-elevation areas, in
locations with low static pressures, and in remote locations that are distanced from
overhead storage (Fleming et al. 2006; Friedman et al. 2004). All systems will, at some
time, start up, switch off, undergo unexpected flow changes, and will likely experience
the effects of human errors, equipment breakdowns, earthquakes, or other risky dis-
turbances. Although transient conditions can result in many abnormal situations and
breaches in system integrity, the engineer is most concerned with those that might
endanger the safety of a plant and its personnel, that have the potential to cause
equipment or device damage, or that result in operational difficulties or pose a risk to
the public health.
Transient pressures are difficult to predict and are system dependent, including
specific system layout, configuration, design, and operation. Engineers must carefully
consider all potential dangers for their pipe designs and estimate and eliminate the
weak spots. They should then perform a detailed transient analysis to make informed
decisions on how best to strengthen their systems and ensure safe, reliable operations
(McInnis and Karney 1995; Karney and McInnis 1990).
Copyright (C) 2012 American Water Works Association All Rights Reserved
176 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 177
In municipal water systems, most surge problems occur as a result of closing (or
opening) valves too rapidly or when pumps trip due to an unplanned power failure.
Both high and low surge pressures may cause problems. If special precautions are not
taken, the magnitude of the resulting transient pressures can be sufficient to cause
severe damage. Figures 8-2 to 8-5 describe four typical hydraulic transient problems.
The problem of shutting down a pump is illustrated in Figure 8-2. When the pump is
suddenly shut down, the pressure at the discharge side of the pump rapidly decreases
and a negative pressure wave (which reduces pressure) begins to propagate down the
pipeline toward the downstream reservoir causing low pressures at the pump and else-
where in the system. When the negative pressure wave reaches the high point (which
already has a relatively low pressure due to the higher elevation) in the pipe, the pres-
sure can drop below atmospheric to reach vapor pressure. At this pressure, gas within
the water is gradually released and the water starts to vaporize (water-column separa-
tion). On subsequent cycles of the transient when the pressure recovers, the cavity can
collapse generating a large pressure surge spike. On the suction side of the pump, the
solid sloping line represents the initial hydraulic grade and the dashed straight line
depicts the final hydraulic grade, while startup transients are not shown.
It should be noted that when the pipeline velocity reverses and the water column
returns toward the pump, it is suddenly stopped by the check valve on the discharge
side of the pump causing very high pressures. If no check valve exists, the pump can
spin backward, perhaps reaching speeds that can be damaging to the equipment. Dur-
ing normal pump operation, transients can typically be controlled by using slow clos-
ing and slow opening pump control valves, or with variable frequency drives (VFDs)
and soft start/stop controllers on the pump motors.
The problem of pump startup transient is illustrated in Figure 8-3. When a pump
is started, the pressure at the discharge side of the pump rises, sending a positive
pressure wave (which increases pressure) down the pipeline toward the downstream
reservoir. The resulting peak pressure can cause the pipe to collapse if the pressure
rating of the pipe is less than the maximum surge pressure. When the initial positive
pressure wave reaches the downstream reservoir, it is converted into a negative pres-
sure wave that propagates back to the pump and may induce cavitation. On the suction
side of the pump, the solid straight line represents the initial hydraulic grade and the
dashed sloping line depicts the final hydraulic grade, while shutdown transients are
not shown.
Copyright (C) 2012 American Water Works Association All Rights Reserved
178 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 179
Copyright (C) 2012 American Water Works Association All Rights Reserved
180 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 181
(A) Best pipeline profile (surge pressures will be lower for this type of pipeline profile)
(B) Fair pipeline profile (some potential for surge problems due to varying terrain)
(C) Worst pipeline profile (knees and high points cause more severe surge problems)
Copyright (C) 2012 American Water Works Association All Rights Reserved
182 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
should include a detailed surge analysis. Jung et al. (2007a) studied the need for com-
prehensive transient analysis of water distribution systems and concluded that only
systematic and informed surge analysis can be expected to resolve the complex tran-
sient characterizations and adequately protect water distribution systems from the
vagaries and challenges of rapid transient events.
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 183
Figure 8-9 Pressure surge fluctuations (field measurements) following routine pump shutdown
Copyright (C) 2012 American Water Works Association All Rights Reserved
184 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
During the short time ∆t, the pressure on the left side of the wave front is P + ∆P
while the right side of the wave front is P. This unbalanced pressure causes the fluid
to accelerate. The momentum principle is:
ǻQ (8-1)
( P+ǻ P−P) A = ȡǻ x
ǻt
where A is the pipe cross-sectional area; and R is the liquid density. Canceling and
rearranging give:
P = Q xA t (8-2)
The term ∆x ⁄∆t is the propagation speed of the pressure wave. The wave speed
is equal to the sonic velocity (c) in the system if the mean velocity of the liquid in the
line is neglected. Because the mean velocity of the liquid is usually several orders of
magnitude smaller than the sonic velocity, this is acceptable. Thus:
ȡ cǻ Q
ǻP= (8-3)
A
H = cQgA (8-4)
c V
H= ± g (8-5)
where g is the acceleration of gravity. The resulting head rise equation is called the
Joukowsky relation, sometimes called the fundamental equation of water hammer. The
equation is derived with the assumption that head losses due to friction are negligible
and no interaction takes place between pressure waves and boundary conditions at
the end points of the pipe. The negative sign in this equation is applicable for a dis-
turbance propagating upstream and the positive sign for one moving downstream.
Because values of wave speed in many pipelines are in the range of 3,000–4,000 ft/sec
(915–1,220 m/sec), typical values of c/g in Eq. 8-5 are large, often 100 or more. Thus,
this relationship predicts large values of head rise that highlights the importance of
transient analysis. For example, if an initial velocity of 3 ft/sec (0.9 m/sec) is suddenly
arrested at the downstream end of pipeline and c/g equals 100 m/sec, a head rise of
300 ft (91 m) will result.
c = Ef / (1+K r E f D/ Ec t l ) (8-6)
where Ef and Ec are the elastic modulus of the fluid and conduit, respectively; D is
the pipe diameter; tl is the pipe thickness; and Kr is the coefficient of restraint for
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 185
longitudinal pipe movement. Typically, three types of pipeline support are considered
for restraint. These are
(8-7)
Kr = 1− µ p / 2
(8-8)
K r = 1 − µ P2
(8-9)
Kr =1
where MP is the Poisson’s ratio for the pipe material. Table 8-1 lists physical properties
of common pipe materials.
g A
2 jin jin
c
Tjin =
jin
gA (8-10)
jcj j
where the summation j refers to all pipes connecting at the junctions (incoming and
outgoing). A reflection back in pipe jin occurs and is of magnitude Rjin $H where:
Copyright (C) 2012 American Water Works Association All Rights Reserved
186 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
For the simultaneous impingement of waves arriving in more than one leg the
effects are superimposed.
Eq. 8-10 provides the basis for evaluating the effect of wave action at two special
junction cases: dead end junctions and open ends or connections to reservoirs. A dead
end is represented as a two pipe junction with A2 equal to zero. With A2 equal to zero,
Tjin equals 2 and Rjin is 1, which indicates that the wave is reflected positively from the
dead end. This condition implies that the effects of pressure waves on dead ends can
be of significant importance in transient consideration. If the pressure wave reaching
the dead end is positive, the wave is reflected with twice the pressure head of the inci-
dent wave. If the pressure wave reaching the dead end is negative, the wave reflection
will cause a further decrease in pressure that can lead to the formation and collapse of
vapor cavity. For a reservoir connection, A2 is infinite so Tjin is zero and Rjin equals −1,
which indicates that a negative reflection occurs at a reservoir.
H3 = H1 + 1 (Qb − Qa ) (8-13)
H4 = H2 + 2 (Qa − Qb ) (8-14)
Where:
c1 c2
1 = and 2 = (8-15)
gA1 gA2
H3 = H1 + H1 + H3 (8-16)
Copyright (C) 2012 American Water Works Association All Rights Reserved
188 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
and
H4 = H2 + H2 + H4 (8-17)
The characteristic equation relating the pressure head change across and the
flow through the control element after the action is:
The coefficients of the characteristic equation, A(t), B(t) and C(t), represent the
values at the time of the wave action and may vary with time.
Substituting Eqs. 8-16 and 8-17 into Eq. 8-18 and rearranging results in a qua-
dratic relationship for Qa or:
C(t) Qa Qa + ( B(t) − 1 − 2 ) Qa
(8-19)
( )t + H1 + 2 H1 − H2 −2 H
+A ( 1 + )2 Qb = 0
2 +
Eq. 8-19 can be solved directly for Qa using the quadratic formula or iteratively
using the Newton-Raphson method. Eqs. 8-13 and 8-14 are then solved to give the
magnitude of the pressure waves produced by the action, and Eqs. 8-16 and 8-17 yield
the pressure head after the action takes place.
This general analysis represents a wide variety of control elements that can be
subject to a range of conditions.
8.4.4.1. Control Element Characteristics. The coefficients of the control ele-
ment characteristic equation (8-12) are determined using head-flow operating data
for the control element. Some control elements such as pumps will use all three coef-
ficients to represent the head-flow variation. In some cases, the characteristic equa-
tion will be based on data, which represents the head-flow relationship for a relatively
small range of operation. For these applications, the coefficients used for the control
element analysis will be based on data valid for the operation in the vicinity of the
operating point and will be recalculated as the operating point changes. This is true
for the analysis of variable speed pumps and for pumps using data representing a wide
range of operating conditions, including abnormal situations such as flow reversal.
Many control elements, such as valves, can be modeled using only the C coeffi-
cient. These are referred to as resistive control elements where the head-flow relation
is adequately described by a single resistive term. For this application, the coefficient
C(t) is defined as the control element resistance. The term resistance is defined as the
head drop divided by the square of the flow (∆H⁄Q2). Here, the head drop is in feet
(meters), and the flow is in ft3 /sec (m3 /sec).
The control element resistance is directly related to other resistive parameters
such as minor loss (K M), valve flow coefficient (Cv), sprinkler constant (Ks), and others,
which characterize the head-flow characteristic of a resistive control element.
8.4.4.2. Wave Propagation With Friction. Because all pipeline systems con-
tain friction, the pressure wave is attenuated as it travels down a line. Line loss can
be simulated by concentrating the losses in length L at an orifice as shown in Figure
8-13. This orifice will then partially transmit and reflect pressure waves and account
for the effect of wall shear. The friction orifice will therefore attenuate a pressure wave
in a manner similar to the total attenuation that will occur as the wave travels the
length L in the pipe.
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 189
where f is the friction factor; g is the acceleration of gravity; D is the pipe diameter;
and A is the pipe area.
In this case, the coefficients of the characteristic equation (Eq. 8-12) for the line
friction orifice are:
and
fL
C(t) = − (8-22)
2gDA2
The friction factor can be determined using the flow rate through the orifice prior
to the wave action. Although it is true that some approximation errors will be intro-
duced if excessively long reaches are used, these errors are generally very small and
can be minimized or eliminated using shorter pipe reaches. Ramalingam et al. (2009)
developed sound guidelines in the form of error study for selecting the optimal number
of friction orifices to ensure accurate results.
Momentum (Dynamic)
1
Hx + Qt − f (Q) = 0 (8-24)
gA
where f(Q) is a pipe resistance (nonlinear) term that is a function of flow rate.
Copyright (C) 2012 American Water Works Association All Rights Reserved
190 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 191
Copyright (C) 2012 American Water Works Association All Rights Reserved
192 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
8.7.1.3. Feed Tank (One-Way Surge Tank). The purpose of feed tanks is to
prevent initial low pressures and potential water-column separation by admitting
water into the pipe subsequent to a downsurge. They can be either open or closed, will
have a check valve to allow flow only into the pipe system, and can be installed any-
where on the line.
8.7.1.4. Pressure Relief Valve. A pressure relief valve ejects water out of a side
orifice to prevent excessive high-pressure surges. It is activated when the line pressure
at a specified location (not necessarily at the valve) reaches a preset value. The valve
opens and closes at prescribed rates over which the designer often has some degree of
control. It can eject water into the atmosphere or a pressurized region, or into an open
or closed surge tank.
8.7.1.5. Surge Anticipation Valve. A surge anticipation valve is much like a
pressure relief valve, but it gets triggered to open on a downsurge in pressure (sensed
at a specified location) in anticipation of an upsurge to follow. This valve, when acti-
vated, follows and completes a cycle of opening and closing based on valve opening and
closing rates. For systems where water-column separation will not occur, the surge
anticipation valve can solve the problem of upsurge at the pump due to reverse flow or
wave reflection. However, this valve must always be used with caution for it can make
low pressure conditions in a line worse than they would be without the valve.
8.7.1.6. Air Release/Vacuum Valve. Air release/vacuum breaking valves are
installed at high points in a pipeline to prevent low pressure (cavitation) by admitting
air into the pipe when the line pressure drops below atmospheric conditions. The air
is then expelled (ideally at a lower rate) when the line pressure exceeds atmospheric
pressure. Two-stage air valves release the air through a smaller orifice to prevent
the “air slam” that occurs when all the air is released and the water column rejoins.
A three-stage air valve can be designed to release the air through a second (smaller)
orifice to further reduce the air slam.
8.7.1.7. Check Valve. A check valve allows flow only in one direction and closes
when flow reversal is impending. For transient control, check valves are usually
installed with other devices such as a pump bypass line as described below. Pumps are
often equipped with a check valve to prevent flow reversal. Because check valves do
not close instantaneously, it is possible that a substantial backflow may occur before
closure that can produce additional and sometimes large surges in the system. Check
valve modeling includes a time delay between check valve activation and complete clo-
sure of the check valve. The check valve is often treated as a valve closing in a linear
fashion that is activated by flow reversal and closes completely over the delay period.
Check valves can also be used to isolate high pressure waves from reaching a section
of a pipeline. One of the great advantages of a check valve is that it can prevent pipes
from draining, and keeping the pipe full of fluid tends to reduce startup transients.
8.7.1.8. Pump Bypass Line. In low-head pumping systems that have a positive
suction head, a bypass line around the pumps can be installed to allow water to be
drawn into the discharge line following power failure and a downsurge. Bypass lines
are generally short line segments equipped with a check valve (nonreturn valve) pre-
venting back flow (from the pump discharge to the suction side) and installed parallel
to the pump in the normal flow direction. They are activated when the pump suc-
tion head exceeds the discharge head. They help prevent high-pressure buildup on the
pump suction side and cavitation on the pump discharge side.
8.7.1.9. Flywheel. Increasing the pump rotational inertia by attaching a fly-
wheel (Figure 8-14), a large-diameter steel plate, to the pump motor is sometimes a
useful surge control device, especially for sewage pumping systems, because the fly-
wheel is not in contact with the foul water. When power fails, the rotational energy
provided by the flywheel will reduce pump speed gradually, allowing the pumping
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 193
system to slowly come to rest, thus avoiding unacceptable transient pressures. Three
problems accompany flywheel installations:
s They must be large and heavy enough to provide additional rotating inertia
to be effective. Pump and motor bearings and supports must then be designed
to accommodate the extra weight, and additional space is required.
s Pump startup requires extra power to overcome the inertia of flywheels.
s Pump startup must be gradual to keep the motors from burning out.
Nonetheless, flywheels are useful type of surge control and can be found in many
pumping installations.
8.7.1.10. In-Line Pump Control Valve. For large pumping systems with large-
diameter headers and high flows, in-line pump control valves are a viable option. In-
line pump control can be operated similarly to surge anticipator valves, which open
when line pressure drops below a specified set point, remain open for a preset period
of time, and then close in a manner that prevents high pressures resulting from rapid
valve closure. Properly installed, these valves prevent high pressures at pump sta-
tions, but the valve movements must be set with care; otherwise, more severe problems
can occur. Four quadrant pump curves have to be analyzed in conjunction with the
other transient parameters to develop a solution. Of course, these valves have no abil-
ity to prevent low pressures and column separation from occurring in the downstream
pipe lines.
Copyright (C) 2012 American Water Works Association All Rights Reserved
194 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
release/vacuum valves, pump bypass lines, or any combination of that group. The over-
riding objective is to reduce the rate at which changes to the flow occur.
Surge protection devices are normally installed at or near the point where the
disturbance is initiated such as at the pump discharge or by the closing valve (with
the exception of air relief/vacuum breaking valves and feed tanks). Figure 8-15 illus-
trates typical locations for the various surge protection devices in a water distribution
system. A comprehensive transient flowchart for considering the transient protection
of the system is shown in Figure 8-16. This flowchart is discussed in detail by Boulos
et al. (2005, 2006). When developing a protection strategy, it must be recognized that
no two systems are hydraulically the same; hence, no general rules or universally
applicable guidelines are available to eliminate unacceptable pressures in a water
distribution system. Any surge protection devices and/or operating strategies must be
chosen accordingly (Boulos et al. 2005, 2006; Wood et al. 2005a; Walski et al. 2003;
Thorley 1991).
The final choice will be based on the initial cause and location of the transient
disturbance(s), the system itself, the consequences if remedial action is not taken, and
the cost of the protection measures themselves. A combination of devices may prove
to be the most effective and most economical. Final checking of the adequacy and
efficacy of the proposed solution should be conducted and validated using a detailed
transient analysis.
8.7.2.1. Pump Station and Downstream Pipeline Protection. Because
pump stations are aboveground, surge failures and remedial solutions can be readily
observed. However, failures to buried downstream pipelines are sometimes undetected
and become subject to unseen and overlooked failures. It is important to recognize that
some surge control solutions protect only the pump station but do not necessarily pro-
tect the downstream pipelines from column separation and negative pressures. Both
the pump station and the downstream pipelines should be protected.
8.7.2.2. Float-Operated Air Valves Versus Surge Resistant Air Valves. A
number of vacuum relief valves are often needed for filling and draining pipelines.
Also, additional air valves may be required to protect the pipelines from extreme low
pressures due to surge transients. The total number of air valves depends on pipeline
profile and initial pipeline velocities. Of course, the number of air valves should be
limited and carefully considered, because adding large volumes of air to pipelines can
create other types of operational problems, such as air binding. If pipeline profiles are
too steep and the initial velocities are too high, numerous air valves would be required.
In that case, other types of surge control devices should be considered instead.
Because float-operated air valves require water to close the float, some pipe sys-
tems with high static head require surge resistant air valves to prevent damaging the
float. Damage to the air valve and high pressures occur when water column slams the
float closed, pushing the low density air out around the float.
A safer air valve solution would be the so called surge-resistant air valves that
trap the air inside the air valve body, using it as a cushion, and then slowly releasing
the air to prevent high pressures and damage to the valves.
8.7.2.3. Normal Pump Operation Protection Versus Power Failure Pro-
tection. Normal pump operation for a surge-vulnerable system can include slow clos-
ing and slow opening pump control valves or variable frequency drives on the pump
motors to eliminate undesirable surges during day-to-day operation.
Power failure on surge-vulnerable systems requires the surge-control devices.
Backup power and generators do not come on-line quickly enough to prevent transients
from occurring. It should be noted that the use of surge chambers requires quick-
closing check valves immediately downstream of the pumps. The quick-closing check
valves prevent the surge chamber from spilling water back through the pumps during
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 195
pump shutdown. Slow-closing pump control valves would not be used in conjunction
with a surge chamber. If a surge chamber is required for surge control, it would also
be used for normal pump shutdown and startup and pump control valves would not be
required.
This section focused on pumps. There are other control strategies such as educa-
tion of operators to slowly open/close valves, adjusting speed of mechanically operated
valves, and not operating tanks such that the altitude valve closes and cannot absorb
the transient.
Copyright (C) 2012 American Water Works Association All Rights Reserved
196 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 197
Copyright (C) 2012 American Water Works Association All Rights Reserved
198 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
of operating conditions during the transient analysis. All system components (pumps,
valves, etc.) should be initially in a balanced state (the initial pressure change across
the component and flow through the component should be compatible with the charac-
teristic relationship for that component). The characteristic data for a component must
account for changes in the set point of the component (valve opening, pump speed,
etc.) that occur during the transient analysis. Normally, the steady-state character-
istics are used. Figure 8-17 shows typical valve closure characteristics for a linear
stem movement for several types of valves (Boulos et al. 2006; Wood et al. 2005a). It
is assumed that the valves will operate on these curves during transient conditions.
Pump steady-state head-flow-speed curves are often used to model pump opera-
tion. However, if during the transient the pump operates in abnormal zones (turbining,
etc.), it is necessary to use more detailed four quadrant pump operating characteristics
(i.e., ± speed and ± flow). Of the many methods developed for this purpose, the Suter
curve is the most widely used (Thorley 1991; Suter 1966). A typical four quadrant
pump characteristic curve is shown in Figure 8-18. In this figure, the x-axis repre-
sents the four quadrants of pump operation, and the y-axis represents the correspond-
ing head and torque characteristics. These data are normally not provided by pump
manufacturers. However, many of these four quadrant curves are available for a range
of pump specific speeds. Typically, one of these curves is selected by matching the spe-
cific speed of the pump to the available curves. The additional pump data required for
transient analysis include the efficiency and the total inertia (pump and motor).
A characteristic equation that relates the pressure change and flow to the operat-
ing point of all hydraulic surge control devices along with their locations must also be
available. All such devices (surge tanks, air valves, etc.) should be initially in a bal-
anced state (the initial pressure change across the component and flow through the
component should be compatible with the initial characteristic relationship for that
component). The characteristic equation for a surge control device must account for
changes in the set point of the device (relief valve, nonslam air valve, etc.) that occur
during the transient analysis.
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 199
Finally, the exact nature of the disturbance and its intended timescale must be
specified. The disturbance can be either a change in the open area ratio for a valve,
the speed ratio for a pump, or any other change in operation (check valve closing, pipe
rupture, etc.) that results in a change in flow.
Copyright (C) 2012 American Water Works Association All Rights Reserved
200 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Copyright (C) 2012 American Water Works Association All Rights Reserved
TRANSIENT ANALYSIS 201
8.12. REFERENCES
Besner, M.C., Lavoie, J., Morissette, C., and Chaudhry, M.H. 1979. Applied Hydraulic
Prevost, M. 2008. Effect of Water Main Transients. New York: Van Nostrand
Repairs on Water Quality. Jour. AWWA, Reinhold Co.
100(7):95–109. Fleming, K.K., Gullick, R.W., Dugandzic,
Besner, M.C., Lavoie, J., Payment, P., and J.P., and LeChevallier, M.W. 2006. Sus-
Prevost, M. 2007. Assessment of Tran- ceptibility of Distribution Systems to
sient Negative Pressures at the Site of Negative Pressure Transients. Denver,
the Payment’s Epidemiological Studies. Colo.: AwwaRF.
In Proceedings of the American Water Friedman, M., Radder, L., Harrison, S.,
Works Association WQTC, Charlotte, Howie, D.C., Britton, M.D., Boyd, G.R.,
N.C. Denver, Colo.: AWWA. Wang, H., Gullick, R.W., Wood, D.J., and
Boulos, P.F., Lansey, K.E., and Karney, B.W. Funk, J.E. 2004. Verification and Con-
2006. Comprehensive Water Distribution trol of Pressure Transients and Intrusion
Systems Analysis Handbook for Engi- in Distribution Systems. Denver, Colo.:
neers and Planners. 2nd edition. Broom- AwwaRF.
field, Colo.: MWH Soft. Gullick, R.W., LeChevallier, M.W., Svind-
Boulos, P.F., Karney, B.W., Wood, D.J., and land, R.C., and Friedman, M.J. 2004.
Lingireddy, S. 2005. Hydraulic Tran- Occurrence of Transient Low and Nega-
sient Guidelines for Protecting Water tive Pressures in Distribution Systems.
Distribution Systems. Jour. AWWA, Jour. AWWA, 96(11):52–66.
97(5):111–124. Hooper, S.M., Moe, C.L., Uber, J.G., and
Boulos, P.F., Wood, D.J., and Funk, J.E. 1990. Nilsson, K.A. 2006. Assessment of
A Comparison of Numerical and Exact Microbiological Water Quality After
Solutions for Pressure Surge Analysis. Low Pressure Events in a Distribution
In Proc. of the 6th International BHRA System. In Proceedings of the 8th Annu-
Conf. on Pressure Surges, A.R.D. Thorley al International Water Distribution Sys-
editor. Cambridge, UK. tems Analysis Symposium, Cincinnati,
Boyd, G.R., Wang, H., Britton, M.D., Howie, Ohio.
D.C., Wood, D.J., Funk, J.E., and Fried- Jung, B.S., Boulos, P.F., and Wood, D.J.
man, M.J. 2004. Intrusion Within a Sim- 2009a. Effect of Pressure Sensitive
ulated Water Distribution System Due Demand on Surge Analysis. Jour.
to Hydraulic Transients. 1: Description AWWA, 101(4):100–111.
of Test Rig and Chemical Tracer Meth- Jung, B.S., Boulos, P.F., Wood, D.J., and
od. Journal of Environmental Engineers, Bros, C.M. 2009b. A Lagrangian Wave
ASCE, 130(7):774–783. Characteristic Method for Simulating
Transient Water Column Separation.
Jour. AWWA, 101(6):64–73.
Copyright (C) 2012 American Water Works Association All Rights Reserved
202 COMPUTER MODELING OF WATER DISTRIBUTION SYSTEMS
Jung, B.S., Karney, B.W., Boulos, P.F., and Environmentally Sound Technology in
Wood, D.J. 2007a. The Need for Com- Water Resources Management. Gabo-
prehensive Transient Analysis of Water rone, Bostwana.
Distribution Systems. Jour. AWWA, Ramalingam; D., Lingireddy, S., and Wood,
99(1):112–123. D.J. 2009. Using the WCM for Transient
Jung, B.S., Boulos, P.F., and Wood, D.J. Modeling of Water Distribution Net-
2007b. Pitfalls of Water Distribution works. Jour. AWWA, 101(2):75–89.
Model Skeletonization for Surge Analy- Suter, P. 1966. Representation of Pump
sis. Jour. AWWA, 99(12):87–98. Characteristics for Calculation of Water
Karim, M.R., Abbaszadegan, M., and Hammer. Sulzer Tech. Rev., 66:45–48.
LeChevallier, M.W. 2003. Potential for Thorley, A.R.D. 1991. Fluid Transients in
Pathogen Intrusion During Pressure Pipeline Systems. Herts, UK: D&L
Transient. Jour. AWWA, 95(5):134–146. George.
Karney, B.W., and McInnis, D.A. 1990. Tran- Tullis, J.P. 1989. Hydraulics of Pipelines.
sient Analysis of Water Distribution New York: John Wiley & Sons.
Systems. Jour. AWWA, 82(7):62–70. Walski, T.M. 2009. Not So Fast! Close
Kirmeyer, G.J., Friedman, M., Martel, K., Hydrants Slowly. Opflow, 35(2):14–16.
Howie, D., LeChevallier, M., Abbaszade- Walski, T.M., and Lutes, T. 1994. Low Pres-
gan, M., Karim, M., Funk, J., and Har- sure Problems Caused by Hydraulic
bour, J. 2001. Pathogen Intrusion Into Transients. Jour. AWWA, 86(12):24–32.
the Distribution System. Denver. Colo.: Walski, T.M., Chase, D.V., Savic, D.A., Gray-
AWWA and AwwaRF. man, W.M., Beckwith, S. and Koelle,
LeChevallier, M.W., Gullick, R.W., Karim, S. 2003. Advanced Water Distribution
M.R., Friedman, M., and Funk, J.E. Modeling and Management. Waterbury,
2003. The Potential for Health Risks Conn.: Haestad Press.
From Intrusion of Contaminants Into Wood, D.J., Dorsch, R.G., and Lightner, C.
Distribution Systems From Pressure 1966. Wave Plan Analysis of Unsteady
Transients, Journal Water Health, Flow in Closed Conduits. Journal of
1(1):3–14. Hydraulics Division, ASCE, 92:83–110.
McInnis, D.A., and Karney, B.W. 1995. Tran- Wood, D.J., Lingireddy, S., and Boulos, P.F.
sients in Distribution Networks: Field 2005a. Pressure Wave Analysis of Tran-
Tests and Demand Models. Journal of sient Flow in Pipe Distribution Systems.
Hydraulic Engineering, ASCE, 121(3): Broomfield, Colo.: MWH Soft.
218–231. Wood, D.J., Lingireddy, S., Boulos, P.F., Kar-
National Research Council. 2006. Drinking ney, B.W., and McPherson, D.L. 2005b.
Water Distribution Systems: Assessing Numerical Methods for Modeling Tran-
and Reducing Risks. Washington, D.C.: sient Flow in Distribution Systems.
National Academies Press. Jour. AWWA, 97(7):104–115.
Ndambuki, J.M. 2006. Water Quality Wylie, E.B., and Streeter, V.L. 1993. Fluid
Variation Within a Distribution Sys- Transient in Systems. Englewood Cliffs,
tem: A Case Study of Eldoret Munici- N.J.: Prentice Hall.
pality, Kenya. In Proceedings of the
Copyright (C) 2012 American Water Works Association All Rights Reserved