38 KV, 16 Ka, 1200 A: OVR-38 Outdoor Vacuum Recloser Instruction Manual
38 KV, 16 Ka, 1200 A: OVR-38 Outdoor Vacuum Recloser Instruction Manual
38 KV, 16 Ka, 1200 A: OVR-38 Outdoor Vacuum Recloser Instruction Manual
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are
not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment
addressed in this manual must satisfy themselves that each intended application is suitable and acceptable,
including that any applicable safety or other operational requirements are compiled with. In particular, any risk in
applications where a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying
the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This product has been designed to be connected to medium voltage distribution networks. It is the sole responsibility
of the person or entity responsible for the network administration to ensure a secure connection to the network and
take necessary measures to protect the product and the network, its system and interface included against any kind
of security breaches, unauthorised access, interference, intrusion, leakage and /or thefts. ABB is not liable for any
such damages and/or losses.
This product is intended to be operated and maintained by qualified personnel, thoroughly trained and
knowledgeable with regard to the associated hazards involved. This publication is written only for such qualified
personnel and is not intended to be a substitute for adequate training and experience in the safety procedures for
this device.
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors
are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual
commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use if this
manual or the application of the equipment.
List of Illustrations
List of tables:
For the safety of the personnel performing maintenance operations on the recloser or connecting equipment, all
components should be electrically disconnected by means of a visible break and securely grounded.
This manual uses terms “ground” & “grounding” as per IEEE. These are equivalent to IEC terms” earth” and
“earthing”.
This product is intended to be operated and maintained by qualified personnel, thoroughly trained and
knowledgeable with regard to the associated hazards involved. This publication is written only for such qualified
personnel and is not intended to be a substitute for adequate training and experience in the safety procedures for
this device.
This manual contains terms and expressions commonly used to describe this kind of equipment.
These instructions do not attempt to provide the user of this equipment every possible answer to questions which
may appear in the application, operation and maintenance of the product.
Whenever it is required to work on HV &/OR LV units, it is mandatory to follow following minimum procedures:
1.1 Isolate the recloser from the power system on its both sides. Put recloser in OPEN condition by
operating the emergency manual trip handle (yellow handle).
Once recloser is opened, the handle gets locked & blocks close operation both electrically &
mechanically till the handle is reset to its original (not operated) position.
1.2 Confirm the OPEN status of the recloser from the mechanical ON/OFF indicator, from SLD on LCD
display & the indication LEDs on RER615 HMI.
1.3 Always switch OFF the MCBs D10-31 & D10-24 and also lock the SERVICE /DISCHARGE selector
switch in the LV cabinet to DISCHARGE Position.
1.4 Follow the safety warning instructions on various warning labels provided on the LV & HV units
1.5 Remove the control cable from both HV & LV cabinets & cover the 24 pin male connectors by plastic
caps provided.
Warning texts:
Warning texts mentioned are stated based on different degrees of urgency, which should be carefully observed.
These are described below:
Warning Symbols
Following warning symbols may appear on warning sticker as a part of the product.
Although warning hazards are related to personal injury, it is necessary to understand that under certain operational
conditions, operation of damaged equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
These instructions do not attempt to provide the user of this equipment with every possible answer to questions,
which may occur in the application, operation and maintenance of the product. Also, as improvements in parts and
assemblies are made, some parts may differ in appearance than depicted in illustrations; however, functionality will
be equivalent.
The OVR-38 Recloser is a medium voltage (38 kV), three-phase device incorporating three vacuum interrupters
assembled in poles cast with an advanced Hydrophobic Cycloaliphatic Epoxy (HCEP). Together with the specialized
control functions, the recloser will sense a pickup current (or other pre-configured condition) and automatically open,
or “trip”. After a pre-configured Open Interval Time, the recloser will close again. If the tripping condition still exists,
the recloser will trip again and reclose. The standard OVR-38 Recloser control, the RER615, when set for auto
reclosing on faults ; will allow up to four opening operations (3 reclosing attempts) before the recloser will “lock out”
in the open position.
Satisfactory performance of the recloser is contingent upon correct installation, adequate maintenance and service of
the product. Careful study of these instructions will permit the user to obtain maximum benefit from this device.
Each recloser is assembled and tested at the factory. Prior to shipment, the equipment is thoroughly inspected to
ensure a quality product free from defects. If damage is noticed, call the carrier at once for inspection, and request
an inspection report. Afterwards, file a formal claim with the carrier, supported with the Airway/Roadway Bill. The
local ABB sales office should be notified immediately.
: Do not place the recloser high voltage unit on an uneven surface. Placing the HV unit on an uneven surface
may cause tilting/galling of the HV unit causing damage to the equipment and injuries to the person nearby.
: Spreader bar should be used if necessary to ensure lifting straps do not press against and damage the poles, &
mechanical ON/OFF indicator.
: Do not use forklift to move recloser as it may damage the mechanical ON/OFF position indicator, Yellow
Trip Handle and associated interlock
3.3. Storage
The HV & LV cabinets must be stored in the upright position to avoid moisture accumulation.
For prolonged storage, indoor storage is recommended. Recommended storage temperature range
is -20 Deg C to + 40Deg C.
The low voltage control cabinet has rechargeable batteries inside. A periodic check of battery voltage
(24V)& periodic charging of the batteries (typically every three months) may be required in case of
prolonged storage. Please refer Annexure-13 of this document for the typical functional characteristics
of lead acid batteries. For the batteries in your control cabinet, please refer to technical documentation
of the respective battery manufacturer. Please also refer the section “Inspection & Maintenance” for
further information.
: If the recloser is not placed in service immediately, it is essential that proper care be exercised in
handling and storage to ensure good operating condition in the future. Please consult ABB if the
recloser will be in storage for an extended period of time before installation.
4.1.1. Housing
The bottom cover of the recloser housing (high voltage cabinet) is removable. The ON/OFF position indicator are
visible from ground. The recloser nameplate that shows rating information, serial number, and manufacturing year is
mounted on the front side of the high voltage cabinet. A 50W heater is provided in the high voltage cabinet, to
prevent condensation and must be energized at all times. The MCB for ON/OFF control of this heater is installed in
the Low Voltage cabinet. The high voltage cabinet heater is not provided with thermostat control.
Combisensor cable
Shielded cable with CT & CVD
Secondary cable
: In the event the control cable is disconnected from the recloser, resistors installed across the CT
secondary leads in the high voltage cabinet will prevent voltage build up on the open circuited CT
secondary.
: Disassembly of the magnetic actuator is not allowed. Lubrication or maintenance is not required
and will void the warranty. Should an actuator fail to operate, contact ABB Customer Service Group.
The Unit is supplied by default as per IEC convention, unless specifically asked for ANSI convention.
4.2. Control
4.2.1. Control cabinet (LV Cabinet)
A separate weatherproof cabinet, IP-55 rated, houses the low voltage control components. The outer hinged swing
door has provision for padlocking. Two inner hinged swing doors allow front and rear access to the control
components. Other devices are mounted on the side/rear walls of the cabinet.
The floor of the LV cabinet is equipped with removable gland plate to provide entries for Auxiliary power cable,
communication cables, radio modem antenna/cable.
On the inside walls of the control cabinet, there is assigned space for mounting optional radio modem. Contact your
ABB representative for more information.
A 50W thermostatically controlled heater is provided to prevent condensation in the LV cabinet.
For additional details it is recommended to refer battery manufacturer documentation. Please also refer the section
- Due to frequent and long duration external power outages, battery frequently undergoes discharge
and charge cycles. This reduces battery capacity, charging efficiency & overall service life.
- Due a consistent long duration outage, if the battery bank voltage drops below 18V (9V per battery)
then this indicates, battery has got deep discharged & now cannot be charged further. Thus at
this point, the battery needs complete replacement by a brand new, fully charged equivalent battery.
- Connection of any additional load to battery is strictly prohibited and ABB will not be liable
for any adverse impact it can create to recloser performance including life of battery.
- For long duration Auxiliary power outages (typically more than 72 hours), it is recommended to
Physically disconnect the battery bank from ACU, by switching OFF the MCB D10-24 in the LV
cabinet. This is to avoid the risk of battery getting deep discharge. Once the Auxiliary supply
resumes, it is mandatory to Switch ON the MCB D10-24 and reconnect the battery to ACU
for charging the battery bank.
Service Mode: For normal operation of recloser; the selector switch must be put in service mode & MCBs D10-24 &
D10-31 should be kept ON. In this mode the capacitors are kept fully charged by the ACU.
Discharge Mode: Since the LV cabinet houses charged capacitors, it is mandatory for operator’s safety to put the
unit in Discharge mode & wait till capacitor are fully discharged before any checks, inspections are carried out inside
the LV cabinet. To put the unit in discharge mode, turn the selector switch to discharge position . It is mandatory thatf
the MCBs D10-24 & D10-31 are switched OFF. This way, the external auxiliary supply & batteries are disconnected
from the ACU. Thus Capacitors are no longer charged; instead they are discharged through the discharge circuit.
The LED on the discharge circuit glows only till the capacitor voltage drops below 2V. In this mode the protection &
control is not available for the recloser since external auxiliary power & battery back up to ACU are switched OFF;
which in turn switches OFF the RER615 relay. When the capacitor voltage drops below 100V, recloser is
OPENED/TRIPPED by the “Safe Trip” command by ACU; to ensure that recloser is in OPEN condition in
DISCHARGE Mode.
If in DISCHARGE mode, the Operator chooses not to switch off the MCBs D10-24 & D10-34, ACU remains
connected to external auxiliary supply & batteries. Thus it keeps charging the Capacitor while they are also getting
simultaneously discharged through the discharge circuit. Thus the LED on the discharge circuit (visible on inner
swing door) glows continuously since the capacitors are charged by ACU while they also discharged through the
discharge circuit. Hence it is mandatory to switch OFF the MCBs D10-24 & D10-31 when the selector switch is put in
Discharge position.
The RER615 implements a draw out case design for easy removal and internal upgrades. This design has two main
parts: the frame and the case.
The frame is fixed on the inner swing door of the LV cabinet. The case is removable via a handle and houses various
cards. Please refer figure-8. All card connections are made with terminal blocks that are affixed to the frame of the
IED.
The RER615 is not intended for “hot swapping.” Read section 8.1 before removing the relay from its
case. When the RER615 is removed from its case, the current (I) input terminals automatically short
Circuit the CT inputs. No card should be removed from the RER615 in the field. If removal is required,
contact the ABB Customer Service Group.
The OVR-38 recloser is shipped duly calibrated with the current /voltage correction factors (as applicable)
already applied and set in the RER615 relay. It is mandatory that these correction factors are not modified
after shipment.
A standard test report with a summary of results is shipped as a part of documentation package.
: All metal mounting frames and structures must be commonly grounded to the grounding grid at site.
For the proper operation of the electronic components it is mandatory that the total impedance of the
grounding grid at site should be less than one Ohm (1 Ohm).
It is also mandatory to ensure that all the grounding connections to the welded star grounding pad
inside the LV cabinet are always intact and secured.
High voltage applied across an open gap in a vacuum can produce X-ray radiation. No radiation is emitted when the
recloser is closed since no gap exists. Also, when the recloser is open to the specified contact spacing in service or
tested within the voltages specified, X-ray radiation at one meter is below the level of concern. A danger could exist
at voltages above that specified on the rating plate. During the test, it is mandatory that the HV cabinet is properly
grounded.
- With the recloser in the open position, with a jumper connect all the three upper terminals together. Connect all the
three lower together with a jumper. Ground the lower terminals and the cabinet housing. Connect the high voltage
to the top terminals.
- Stand clear more than three meters before energizing the high voltage source.
- Do not exceed 56kV AC. Do not apply voltage for more than 60 seconds.
- If internal flashover occurs, isolate the phases and test each one independently to identify the defective interrupter.
Any defective pole assembly must be replaced prior to the recloser is installed & placed in service.
6.2. Mounting
The HV Cabinet is shipped with either a pole mounting frame OR substation frame. The next section explains
the recommended installation procedure for each frame type.
: Do not use forklift to move recloser as it may damage the mechanical ON/OFF position indicator,
Yellow Handle and associated interlock.
2. Complete the HV cabinet & LV cabinet mounting on pole, as per detailed procedure in Annexure-2.
Also refer figures 9 &10,
Annexure 2 (A) Cylindrical Pole Mounting Arrangement,
Annexure 2 (B) Rectangular Pole Mounting Arrangement,
3. If Voltage Transformers (VTs) are used, it is recommended to install the frame without the transformers and then
install the VT’s once the recloser and VT mounting brackets (not in ABB’s scope of supply) are on the pole.
Do not exceed 6000N cantilever force on any of the bushing terminals in any direction. Failure to comply will result in
permanent damage
Follow your company’s instructions for electrical products/assemblies. This operation should be done once it is
secured that; there is no hazard or unsafe condition to the operator, such as energized-or – live conductors.
The heights of pole structure and Recloser location shown are for reference purpose only.
These depend on user’s installation.
XXX: To be decided by the user.
Supply of pole is not in ABB’s scope.
OVR-38 | Instruction Manual 20
The grounding cables used shall be same for all components.
2. Complete the HV cabinet & LV cabinet mounting on substation structure, as per detailed procedure in Annexure-3.
Also refer figures 11 & 12)
3. If Voltage Transformers (VTs) are used, it is recommended to install the frame without the transformers and then
install the VT’s once the recloser and VT mounting brackets are on the pole.
Do not exceed 6000N cantilever force on any of the bushing terminals in any direction.
Failure to comply will result in permanent damage.
Follow your company’s instructions for electrical products/assemblies. This operation should be done once
it is secured that; there is no hazard or unsafe condition to the operator, such as energized-or – live conductors.
The heights of the structure and recloser location shown are for reference purpose only. These depend on
user’s installation.
XXX: To be decided by the user.
Supply of support structure is not in ABB's scope of supply.
The structure shown in the figure is only for reference purpose.
All metal mounting frames and structures must be commonly grounded to the grounding grid at site. Grounding is
important to ensure proper operation of all electronic components, as well as to prevent penetration of EMC noise
and other transients into the sensitive electronic circuits (RER615 relay, ACU, radios, etc.). Each of the HV & LV
cabinets includes two stainless steel welded grounding pads on their rear for grounding. Each pad is 50X16 Sq.mm
with 2 holes (M8 each) drilled, welded stainless steel pad. Please refer figure 13. 80 Sq.mm cross-section, solid
copper strip is recommended for grounding.
Any voltage transformers used, should be grounded to the main ground wire leading from the recloser HV Cabinet to
ground. It is mandatory that both the high voltage cabinet and low voltage control cabinet are firmly grounded
separately & independently, when installed. See Figures 10 and 12 for more details.For the proper operation of the
electronic components it is mandatory that the total impedance of the grounding grid at site should be less than one
Ohm (1 Ohm). It is also mandatory to ensure that all the grounding connections to the welded star grounding pad
inside the LV cabinet are always intact and secured.
If it is desired to obtain control power from pole mounted VT (PT), then the power rating of VT (PT) should be
minimum 250VA . Unless specified such VT (PT) will not be in ABB’s scope of supply.
Before connecting the external auxiliary power source to the LV cabinet, make sure that the
SERVICE/DISCHARGE selector switch in the LV cabinet is in DISCHARGE mode.
: Please follow the instructions on the warning label provided on the inner swing panel (door).
The voltage transformer (VT) used for providing external AC auxiliary power to the LV cabinet, then this VT must be
installed/connected on the source side of the recloser in order to avoid unnecessary drain on the battery backup
system when the circuit is open at the recloser.
The upper & lower terminal connectors fasteners must be torqued to between 50 to 60 Nm (442 to 531 inch lbf)
Do not ground either side of the battery or attach ground to the terminals of the actuator operating coils.
This will result in permanent damage to the unit.
:
When the recloser has been installed and all mechanical and electrical connections completed, before energising the
recloser on the main lines, following inspections are mandatory:
7.1. Closing
OVR-38 recloser can be closed only electrically. With RER615 in LOCAL mode, the recloser can be closed from the
“I” pushbutton on the RER615 front HMI. The recloser also can be closed from remote SCADA via communication,
with RER615 relay in REMOTE mode.
7.2. Opening
OVR-38 recloser can be opened mechanically as well as electrically. With RER615 in LOCAL mode, the recloser can
be opened from the “O” pushbutton on the RER615 front HMI. The recloser also can be opened from remote SCADA
via communication, with RER615 relay in REMOTE mode.
: Mechanical ON/OFF status indicator on HV cabinet indicates the ON (CLOSED) /OFF (OPEN)
status of the recloser.
a. The ANSI color convention for CLOSE is GREEN and OPEN is RED.
b. The IEC color convention for CLOSE is RED and OPEN is GREEN.
ACTIVATION* DEACTIVATION**
Virtual
HLT
HLT LED on Virtual HLT Button
Relay Mode Button Deactivation LED on Relay
Activation Relay on LCD display
on LCD
display
Turns Steady One layer Turns WHITE Turns OFF Indicating HLT is
Black GREEN deactivation: Indicating that HLT deactivated
LOCAL Through Indicating Indicating possible only is deactivated
LHMI that HLT HLT is through LHMI
is active active
By Pressing Turns Blinking Two layer On releasing the First Turns Steady GREEN on
and Black RED deactivation: push button; releasing the push button,
Locking the Indicating Indicating When push button remains BLACK indicating that HLT is locally
Optional that HLT HLT is is unlocked and indicating that HLT active; Then turns OFF after
External is active activated released is locally active. local deactivation through
LOCAL/REMOTE Pushbutton by additional second On Local LHMI, Indicating HLT is
Pushbutton layer deactivation deactivation deactivated.
through LHMI is through LHMI
MUST ,Turns WHITE
Indicating that HLT
is deactivated
Through Turns Steady One layer Turns WHITE Turns OFF Indicating HLT is
WEB HMI Black GREEN deactivation: Indicating that HLT Deactivated
REMOTE Indicating Indicating possible only is deactivated
that HLT HLT is through WEBHMI
is active active
1 Initial Conditions at the time of OVR-38 recloser are shipped from the factory with
Shipping
- The recloser in OPEN(OFF) condition
- The emergency manual trip (K69) handle locked & "BLOCK CLOSE" activated.
2 Checks and preparations before Please follow the procedure of this manual and complete:
Power ON.
2.1: Installation of LV & HV Units (please refer section-6)
2.2: Installation of other optional equipments (such as Surge arrestors, Auxiliary
control transformer/Auxiliary PT) (please refer section-6)
2.3: Connecting & routing the control cable between LV & HV Units. (please refer
section-6 & Annexure-4 )
2.4: Connecting & routing all the ground connections (please refer section-6)
2.5: Reset the emergency manual trip (k69) handle & release the BLOCK CLOSE.
2.6; Check and firmly connect the 2Pin Green Coloured Male-Female connectors
F26 & F27 as per Schematic Diagram. This will connect the two 12V batteries in
series .
3 To Power ON the LV Cabinet 3.1: Connect the Auxiliary power cable to the LV Cabinet (please refer
with Auxiliary power section-6 & Annexure-5)
3.2: Switch ON the auxiliary power from the source
3.3: Check the availability of the auxiliary power on terminals "201-202" in LV
cabinet
3.4: Switch ON the MCB- AUX SUPPLY MAINS (D10-33) inside the LV Cabinet.
4 To Power ON the cubicle - Switch ON the MCB : D10-31 :MCB for LAMP AND AUX. POWER OUTLET.
illumination & Auxiliary power - Cubicle Illumination Lamp : ON/OFF is controlled by door limit switch; hence
outlet glows when and till the outer swing door is opened.
- Auxiliary power outlet socket has an inbuilt toggle switch for switching ON/OFF
the auxiliary power from the aux. power outlet.
5 To Power ON the heaters for LV - Switch ON the MCBs D10-29 & B10-30 to power the heaters in HV & LV Units
& HV units respectively.
- Heater in LV unit is thermostatically controlled. The thermostat is built in part of
ACU.
- Heater in HV unit does not have thermostat control. Thus it can be either kept
ON or OFF by the MCB B10-29.It is recommended to keep this heater always
ON to avoid condensation in HV cabinet.
6 To connect the Auxiliary Supply - Switch ON the MCB : D10-31 : MCB for ACU
to ACU
7 To connect the batteries to ACU - Switch ON the MCB: D10-24 MCB for Battery. Check and firmly connect the
2Pin Green Coloured Male-Female connectors F26 & F27 as per Schematic
Diagram. This will connect the two 12V batteries in series . Check the voltage
across Battery Terminals .It should be 24V.
8 To Power ON the Auxiliary - Switch ON the MCB : B10-36 : MCB for Radio Modem.
.Supply to Radio Modem - Note that the radio modem & the MCB for radio modem are optional provisions.
(Optional)
9 To Start Capacitor Charging - Put the Service /DISCHARGE selector in the LV cabinet from "DISCHARGE
position" to "Service" position.
- This step connects the ACU to capacitor
11 AR Ready Indication on Relay When ACU completes all the internal checks and fully charges the capacitors; the
LED LED "AR Ready" on RER615 relay turns GREEN, indicating that the recloser is
ready for operations.
(Please refer the approved/as built wiring diagram for detailed description on
RER615 LED indications applicable for your unit).
12 CLOSE Operation. - Confirm that the emergency manual trip (K69) handle is reset.
- Confirm the recloser status as OPEN (from Relay LED, from recloser
OPEN symbol of the single line diagram on relay LCD screen; from the
ON/OFF indicator on HV unit).
- Press the (I) button on relay HMI. Relay will display a message "CLOSE
CBXCBR1? YES/NO". Press the ENTER push button on YES option.
This closes the recloser.
13 OPEN Operation - Confirm the recloser status as CLOSE (from Relay LED, from recloser
CLOSE symbol of the single line diagram on relay LCD screen; from the
mechanical ON/OFF indicator on HV unit).
- Press the (O) button on relay HMI. Relay will display a message "OPEN
CBXCBR1? YES/NO". Press the ENTER push button on YES option.
This opens the recloser.
To a large extent, the safety and successful functioning of any apparatus or system connected with the recloser
depends on the proper installation, commissioning, programming and configuration of the unit.
To provide long, reliable service, the recloser should be inspected at regular intervals. Operating experience,
environmental conditions, the number of operations, the magnitude of current interrupted and any unusual service
conditions will guide you in establishing a maintenance schedule.
Recommended Recommended
Interval Interval
Sr. Tests/
Work to be performed (for installations (for installations
no. Inspections
in normal in dusty and
ambient) polluted ambient)
18 months
12 months
Check for all the Ground (earth) connections to be secured (adjust the
Visual (adjust the interval
1 and undamaged interval
inspections according to
according to
experience)
experience)
All nameplates/rating plates, labels clearly legible & secured
Recommended Recommended
Interval Interval
Sr. Tests/
`Work to be performed (for installations (for installations
no. Inspections
in normal in dusty and
ambient) polluted ambient)
handle
Battery Replacement
(Please refer to the battery product documentation by the
3 Replacements manufacturer for instructions on optimal utilization of battery 3 Years 3 years
life; based on frequency/duration of external auxiliary supply
failures and extent of battery discharge during such
conditions)
It may be required to remove the RER615 relay & Batteries for replacements. Please refer sections 8.1 & 8.2 for more
information.
Please follow the mandatory safety procedures as mentioned under section 1.0 of this document.
Once the RER615 relay is powered OFF, with the inner door closed, move the relay handle upward by 90 Deg.
Then pull the handle in horizontal plane .This removes the relay from its case. The movement is guided by the guide
rails.
(Please read this table in conjunction with the approved/ as built wiring diagram)
Sr. Remedy/Trouble
Trouble/Malfunction Indication/Observation Possible Causes
no. Shooting
Sr.
Trouble/Malfunction Indication/Observation Possible Causes Remedy/Trouble Shooting
no.
Blinking RED LED on ACU Manual Lock out activated. The Reset the emergency manual
(near ACU bottom) emergency manual trip (k69) trip handle & release the
handle has been operated and manual lock out
is locked in operated/tripped
position.
The wiring of the 52a/b aux. limit - Check, secure and correct
- In the SLD on the LCD switch may be loose or wrong the wiring of 52a/b aux.
screen of relay HMI, (52a/b aux. limit switch is limit switch as per
wrong recloser ON/OFF mounted in HV unit) approved /as built
status (either not schematic
matching with the recloser
The mounting/setting of the 52a/b - Check and correct the
status on mechanical
aux. limit switch may be wrong/ mounting/setting of the
ON/OFF indicator/ Relay
loose 52a/b aux. limit switch
LEDs) -OR-
-OR- - Replacement of the 52a/b
- Relay LED or SLD on The 52a/b aux .limit switch is switch may be needed if
relay LCD shows both faulty/damaged found faulty/damaged
( ON/OFF) or no status (52a/b aux. limit switch is - Contact ABB Customer
mounted in HV unit) Service Group
Table-4 continued on next page….
Sr.
Trouble/Malfunction Indication/Observation Possible Causes Remedy/Trouble Shooting
no.
When disposing of OVR-38 recloser or its parts, contact a local waste handler who is authorized and specialized in
disposing electronic waste including lead-acid batteries. These handlers can sort the material by using dedicated
sorting processes and dispose of the product according to the local requirements.
Back side
Front side
After assembly it will look like as below, Please use the hardwares mentioned in the below with *.
Use below mentioned hardware for assembling structure & apply 50 Nm torque.
*
M12x40 Hex. Bolt (Hot Dip. Galvanised)
M12 conical SS washer
M12 Hex. Nut (Hot Dip. Galvanised)
HV Clamp
2REA033606P0001
Assembled frame
Stud
2REA030181P000
Support Plate
2REA031957P0001
Mounting Pole
*
M20 conical SS washer
M20 Hex. Nut (Hot Dip. Galvanised)
Lifting Sling
HV Cabinet
*
M10X30 SS hex Bolt
M10 conical SS washer
M10 SS Hex. Nut
Note: Throughout the step 2 the HV cabinet should be hanging by crane/hydra or any suitable arrangement.
1. Unpack LV cabinet from packing case & lift with the help of crane/hydra or any suitable
arrangement.
2. Fix the LV mounting clamp to LV box with M20X40 bolt , also fix the M20X350 studs
As shown in fig.
Bolt: M20X40
Nut: M20
Back Side of LV Box
Washer: M20
Note:
Remove the lifting belt/hook only after confirming the secured mounting of LV/HV cabinet on the pole.
Back side
Front side
B. Follow the below step to complete the substation mounting setup (Step1 to 6).
1. Prepare the concrete foundation with 4 foundation bolt of M20 (Not in ABB Scope)
Maintain the centre to centre distance between foundation bolts & height as shown in
figure below
1244±4
1166±4
2. Mount the leg weld assembly on foundation bolts & fixe it with M20 conical
Washers & M20 Hex Nut as shown in figure below.
3. Repeat the step 2nd for second leg weld assembly & maintained the distances mentioned.
Maintain the inside edge to edge distance 1184mm as shown in fig.
(Maintain Centre to centre distance between the slots 1257 mm)
1174±4
4. Assemble the two cross support angles with nut, bolt & washer as shown in figure below.
5. Assemble the Horizontal support angles with nut, bolt & washer as shown in figure below.
6. Assemble the LV mounting support angles with nut, bolt & washer as shown below
C. Mount the HV cabinet+ mounting fame (as shown in step A) with nut, bolt & washer
on the structure prepared in the step B, as shown in figure below
HV Cabinet+ HV Mounting
Frame (As shown in step A)
.
D. Mount the LV cabinet on LV mounting support angles with nut, bolt & washer as shown in figure
below (Note : Fix the bolts to structure first & then assemble the LV)
LV Cabinet
Please also refer Annexure-6 for information on connection of control cable to LV cabinet
: 1. Minimum Bending Radius for the control cable is 12 inches. Please do not bend the cable with radius at bending
less than 12 inch .This may damage the cable.
2. The control cable has to be clamped to the pole throughout the length at regular intervals as per best practices.
4. Route & take out the aux power cable through the hole provided on the gland plate. Secure and seal the cable in
gland plate hole with the M16 gland & M16 hexa nut provided.
5. Connect the free ends of the cable to the external AC source through a appropriate connector plug (not is ABB’s
scope of supply.
1. Insert the 24 pin connector (attached to the control cable end) through the cut out provided on the bottom of the
LV cabinet.
2. Connect the 24 pin male connector to the female counter part inside the LV cabinet and secure by locking clips.
3. Fix the floating gland plate (on the cable) so as to cover the cut out. This can be done by inserting the 4 nos. M6
threaded welded studs on the floating gland plates through the 4 nos. holes provided at the four corners of the cut
out. From inside the LV cabinet, fix the 4nos. M6 nuts & the M40 nut on the floating gland plate. This secures the
floating gland plate and the control cable firmly to the bottom of the LV cabinet.
1 Manufacturer ABB
2 Type and Designation OVR-38
from ABB.
1. Trip Logic
ü TRPPTRC: 1
ü Master Trip (1)
ü Operation On
ü Trip pulse time 70 ms 20 60000
ü Trip output mode Non-latched
2.Condition Monitoring
5. Generic Timers
6. Generic Logic
ü SPCGGIO1: 1
ü General
ü Loc Rem restriction False
ü Output 1
ü Operation mode Toggle
ü Pulse length 1000 ms 10 3600000
ü Description SPCGGIO1 Output 1 64 character
ü Output 2
ü Operation mode Toggle
ü Pulse length 1000 ms 10 3600000
ü Description SPCGGIO1 Output 2 64 character
ü Output 3
Similarly following settings decide the accuracy of current/voltage measurements for the product configuration applicable to
your recloser. These settings also SHOULD NOT BE CHANGED changed during the life time of the recloser, without prior
permission
from ABB.
Discharge Characteristics:
This characteristic shows drop in terminal voltage of each of the two batteries w.r.t time at various values
(56A,28A,14A,5.6A,2.8A &1.4A) discharge current. Thus with 1.4A discharge current a fully charged battery 24 V plus) will take
20hrs to reach the cut off voltage (10V per battery) in 20Hrs at 20Deg C. Under recloser standby condition, battery discharge
current is 1A.As per stand by back up internal test at 20Deg, a fully charged (24V plus) battery takes minimum 24Hrs to reach
the cut off voltage =21V (10V per battery). Thus provides minimum back up of 24 Hrs.
This characteristic explains, the remaining capacity on the battery w.r.t. to open circuit voltage across each terminal. In recloser
, BATTERY NOT OK indication is displayed when battery bank voltage drops below 21.5V ( 10.75 V per Battery). Thus at this
voltage battery has been fully discharged (0% residual capacity)
This characteristics explains the reduction in capacity of the battery as a result of self-discharge, when battery is stored and not
charged. Hence, under circumstances of extended storage of recloser control cabinet, it is recommended to charge the
batteries typically after every three months.
This characteristic explains battery capacity as a function of temperature. Actual capacity is a function of ambient temperature
and rate of discharge. At 20°C (68°F) rated capacity is 100%.The capacity increases slowly above this temperature and
decreases as the temperature falls. At any ambient temperature, the higher the rate of discharge, the lower the available
capacity. Here C means the battery AH capacity. Thus 0.05 C means 0.05*28=1.4A of discharge current. In recloser control
cabinet, in standby mode the battery discharge current is 1A. While raising ambient temperature increases capacity, it also
decreases useful service life. Please refer the curve “service life at various ambient temperature” above. It is estimated that
battery life is halved for each 10°C (18°F) above normal room temperature.
The number of charge/discharge cycles depends on the capacity taken from the battery (a function of discharge rate and depth
of discharge), operating temperature and the charging method.
The recloser battery, provides minimum back up of 26 hrs at 20 Deg C when fully charged .
Under standby, it discharges at the rate of 1A. During discharging, when the battery bank voltage drops to 21.5 V, BATTERY
NOT OK indication is displayed on RER615. At this point battery is fully discharged, i.e discharge depth =100%. Then it needs
charging. Thus after such 200 no of charging & 100% discharge depth cycles , battery will reach its end of life (60% capacity)
and may need replacement.
Hence typically it is important that, in case of external auxiliary power outage power resume quite well before the battery backup
period of 26 hours, so that battery does not discharge to 100% discharge depth and undergoes a full discharging-charging cycle
.in short the duration of external power outage should be well below 26 hours (battery back-up period).
It is also important the frequency and no. of outages of external auxiliary power also affect the battery capacity, back up hours
offered and overall service life.
Service life:
The characteristic shows that with usage at 20Deg, in 5 years the battery will reach its end of life (60% of AH capacity) & will need
replacement. Considering the cyclic use (charge and discharge cycle), higher ambient temperature at site, for batteries in recloser
control cubicle, replacement period of 3 years is recommended.
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------------------
Customer.service.group@in.abb.com
www.abb.com/mediumvoltage