PIM-530 Series Protectowire Linear Heat Detector Interface Module
PIM-530 Series Protectowire Linear Heat Detector Interface Module
PIM-530 Series Protectowire Linear Heat Detector Interface Module
Interface Module
F eatures
• Provides a single zone interface for Protectowire Digital
Linear Heat Detectors
• Capable of Class A (Style D) or Class B (Style B)
monitoring of up to 6560 Feet (2000 Meters) of
Protectowire Linear Heat Detector
• Integrated Protectowire Alarm Point Location Meter with
“on-screen” field calibration
• 64 Event History Log (FIFO)
• 4x20 LED backlit LCD display
• Individual Power, Alarm and Fault indicators
• Modbus over RS-485 communications
• 4-20mA outputs for Status and Alarm Point Location
• Optional intrinsically safe detection circuit available for
use in hazardous locations
General
The PIM-530 is a detection control module that acts as an inter- In order to ensure proper operation, each PIM-530 module re-
face between a main fire alarm control panel detection circuit or quires regulated resettable 24 VDC external power which is nor-
addressable node and Protectowire Digital Linear Heat Detector. mally provided by the host fire alarm panel. Each module
The module provides one (1) supervised detection circuit that contains a green “Power-On” LED indicator, one (1) red “Alarm”
may be field wired for either Class A (Style D) or Class B (Style B) LED indicator, and one (1) yellow “Trouble” LED indicator. One
service. The alarm initiating circuit is capable of operating up to (1) set of Form C alarm contacts and one (1) set of Form C trou-
6560 feet (2000 meters) of Standard PHSC or PLR Digital Type ble contacts to connect the unit to the host fire alarm panel. The
Protectowire Linear Heat Detectors. The PIM-530 initiating cir- module also provides Modbus over RS-485 communications and
cuit is also compatible with other types of non-resistive normally two 4-20mA outputs one which allows monitoring of the module
open contact alarm initiating devices. status and the other for monitoring alarm point location informa-
tion.
Description
The standard PIM-530 module contains a built in Protectowire
The PIM-530 operates using conventional initiating device circuit
Alarm Point Location Meter. This meter will automatically display
technology and contains an integrated on-board Protectowire
the distance from the beginning of the detector run to the heat ac-
Alarm Point Location Meter. The module also includes a time and
tuated (shorted) portion of the detector. The Alarm Point Location
date clock, 64 event history log, Form C contacts for host panel
Meter can be programmed to display distance in either standard
interface and dual 4-20mA status outputs.
units (Feet) or metric units (Meters). The meter display provides a
The module is designed for easy installation and can be optionally simple “on screen” calibration procedure allowing the measure-
provided in a NEMA-4X* rated enclosure for mounting outside ment to be field calibrated to the installed detector length and am-
of the host fire alarm control panel or remotely near the hazard to bient temperature for optimal accuracy.
be protected.
The Protectowire Company, Inc. n60 Washington Street, Pembroke, MA 02359 U.S.A. n p:781-826-3878 n f:781-826-2045
web: www.protectowire.com n email: pwire@protectowire.com
© 2018 The Protectowire Co., Inc. SPECIAL HAZARD FIRE DETECTION SYSTEMS DS 9260B-0219 (2C)