Intelligent Underfrequency Load Shedding For 500kV Java-Bali Electrical Power System
Intelligent Underfrequency Load Shedding For 500kV Java-Bali Electrical Power System
Intelligent Underfrequency Load Shedding For 500kV Java-Bali Electrical Power System
Abstract-- This paper presents a new method for solving underfrequency load shedding (UFLS) problem by using fuzzy logic
controller. Gradient frequency method is used for gaining the active power deficit, then fuzzy decision making will breakdown the
amount of the active power energy in every bus needed for load shedding. This method is implemented at 500 kV Java-Bali electrical
power system. The results showed during the disturbance for a trip of 1510 MW Paiton generation, the system voltage is decrease, the
load decreased 205 MW, df/dt is 0.5967 Hz/s and the total load to shed is 1003 MW. Comparing with load shedding from scheme of
PLN Java-Bali, the above disturbance give df/dt 0.6 Hz/s and total load to shed 1181 MW.
Index Terms-- underfrequency; electrical power system; load shedding;fuzzy decision making.
the first and the second action cannot restore the balance of
Heq n (1)
active power, then it needed a shedding.
Si
i 1
UFLS schemes according to [1] can be categorized into three The quantities in (1) are:
groups:
the traditional UFLS schemes; Heq : inertia constant of an equivalent generating unit
the semi-adaptive UFLS schemes; H : inertia constant of the ith generating unit
the adaptive UFLS schemes.
i
P PL 0 U
i
There is four factors the influence the active power deficit PL 0 i 1 (6)
tur
dt 2 H eq S eq i 1 0i
value [2]:
1. Initial mechanical turbine powers ( Ptur , 0 )
2. Initial active load power in the system ( PL 0 )
3. Spinning reserve ( Ptur ) III. METHODS
4. Active load power changing due to voltage variations
( PL )
Start
Stop
Knowing the load change after the disturbance, the value
of the deficit active power can be calculated
Figure 1. Flowchart for Intelligent Load Shedding
Pdef Ptur PL (4)
For intelligent UFLS method to the problem are shown
Inserting the load change due to voltage variations (3) to (4)
below:
and combine in (2), the value of the load to be shed Ptrip (in 1. Determining data on the 500 kV Java-Bali electrical power
percent) and the frequency gradient can be calculated system for the power flow calculation.
3
FDM U
12 Bandung Load 477 254 0 0
i Selatan
i 1 13 Mandiracan Load 293 65 0 0
14 Ungaran Load 193 118 0 0
The output from FDM is a value from load in each bus. 15 Tanjung Jati Generator 0 0 1321,6 90.0
16 Surabaya Barat Load 508 265 0 0
17 Gresik Generator 127 92 900,0 366.3
18 Depok Load 342 95 0 0
19 Tasikmalaya Load 133 33 0 0
20 Pedan Load 365 101 0 0
21 Kediri Load 498 124 0 0
22 Paiton Generator 448 55 3180,0 917.3
23 Grati Generator 180 132 398,6 100.0
24 Balaraja Load 732 287 0 0
25 Ngimbang Load 264 58 0 0
TABLE II. TRANSMISSION LINE DATA OF 500 KV JAVA-BALI In this simulation the disturbance occur in Paiton power
ELECTRICAL POWER SYSTEM [10]
plant, the magnitude of the disturbance is 1510 MW, and the
No. Line R (p.u.) X (p.u.) ½ B (p.u.) spinning reserve is 300 MW. The result given:
1 1 2 0.000626496 0.007008768 0
2 1 24 0.003677677 0.035333317 0 B. UFLS scheme from PLN Java-Bali
3 2 5 0.013133324 0.146925792 0.003530571
4 3 4 0.001513179 0.016928308 0 Java-Bali EPS have a UFLS scheme listed below:
5 4 18 0.000694176 0.006669298 0
6 5 7 0.004441880 0.042675400 0 TABLE III. DATA UFLS OF 500 KV JAVA-BALI EPS [11]
7 5 8 0.006211600 0.059678000 0
8 5 11 0.004111380 0.045995040 0.004420973
9 6 7 0.001973648 0.018961840 0
10 6 8 0.005625600 0.054048000 0
11 8 9 0.002822059 0.027112954 0
12 9 10 0.002739960 0.026324191 0
13 10 11 0.001474728 0.014168458 0
14 11 12 0.001957800 0.021902400 0
15 12 13 0.006990980 0.067165900 0.006429135
16 13 14 0.013478000 0.129490000 0.012394812
17 14 15 0.013533920 0.151407360 0.003638261
18 14 16 0.015798560 0.151784800 0.003632219
19 14 20 0.009036120 0.086814600 0
20 16 17 0.001394680 0.013399400 0
21 16 23 0.003986382 0.044596656 0
22 18 5 0.000818994 0.007868488 0
23 18 19 0.014056000 0.157248000 0.015114437
24 19 20 0.015311000 0.171288000 0.016463941
25 20 21 0.010291000 0.115128000 0.011065927
𝑑𝑓
26 21 22 0.010291000 0.115128000 0.011065927 In the simulation the values of 𝐻𝑧 is 0.5967 Hz/s. If we use
𝑑𝑡
27 22 23 0.004435823 0.049624661 0.004769846
28 24 4 0.002979224 0.028622920 0
UFLS data from 500 kV Java-Bali EPS, the load must be
29 25 14 0.023479613 0.225580588 0.010097035 shedding is 1181 MW consist of:
30 25 16 0.005966652 0.057324466 0 From RJKB 463 MW
From RJBR 194 MW
A one line diagram of 500 kV Java-Bali electrical power From RJTD 156 MW
system is shown in Fig. 3. From RJTB 299 MW
C. Intelligent UFLS
The loads to be shed are listed in table IV:
TABLE IV. DATA UFLS OF PROPOSED METHOD [11]
No bus Bus Name Load Shedding (MW)
1 Bus Generator Suralaya 0
2 Cilegon 0
3 Kembangan 48.828
4 Gandul 47.2159
5 Cibinong 45.4815
6 Cawang 51.9089
7 Bekasi 60.1495
8 Bus Generator Muara Tawar 0
9 Cibatu 26.6796
10 Bus Generator Cirata 32.17
11 Bus Generator Saguling 32.17
12 Bandung Selatan 51.5927
13 Mandiracan 74.7447
14 Ungaran 78.7922
15 Bus Generator Tanjung Jati 0
16 Surabaya Barat 13.48
17 Bus Generator Gresik 0
18 Depok 49.3349
19 Tasikmalaya 119.184
20 Pedan 118.2175
21 Kediri 97.6892
22 Bus Generator Paiton 0
Figure 3. One Line Diagram in 500kV Java-Bali electrical power system 23 Bus Generator Grati 0
[10] 24 Ngimbang 22.5327
25 Balaraja 32.9561
Total 1003.1274
5
V. CONCLUSIONS
In this paper, the proposed method (Intelligent UFLS) is
used to determine the amount load must be shed in each bus.
Test results by using the 500 kV Java-Bali EPS show that the
Intelligent UFLS method gives better result to minimize the
total load to shed than the standard given by PLN Java-Bali.
The simulation show that for the disturbance of 1510 MW and
the spinning reserve is 300 MW the total load to be shed is
1003.1274 MW.
VI. REFERENCES
[1] B. Delfino, S. Massucco, A. Morini, P. Scalera, and F. Silvestro,
“Implementation and Comparison of Different Underfrequency Load-
Shedding Schemes,” in Proc. Power Engineering Society Summer
Meeting 2001, Jul. 15–19, 2001, vol. 1, pp. 307–312.
[2] Urban Rudez, Rafael Mihalic, “Analysis of Underfrequency Load
Shedding using a Frequency Gradient”, IEEE transactions on power
delivery, vol. 26, no. 2, april 2011.
[3] P. M. Anderson and M. Mirheydar, “A Low Order System Frequency
Response Model,” IEEE Trans. Power Syst., vol. 5, no. 3, pp. 720–729,
Aug. 1990.
[4] H. Seyedi, M. Sanaye-Pasand “Design of New Load Shedding Special
Protection Schemes for a Double Area Power System”, American
Journal of Applied Sciences 6 (2): 317-327, 2009.
[5] M. S. Pasand and H. Seyedi, “New Centralized Adaptive Under
Frequency Load Shedding Algorithms,” in Proc. Power Engineering-
Large Engineering Systems Conf., Oct. 10–12, 2007, pp. 44–48.
[6] M. Etezadi-Amoli, “On Underfrequency Load Shedding Schemes,” in
Proc. Power Symp.—22nd Annu. North American Conf., Oct. 15–16,
1990, pp. 172–180.
[7] A. Li and Z. Cai, “A Method For Frequency Dynamics Analysis And
Load Shedding Assessment Based On The Trajectory Of Power System
Simulation” in Proc. 3rd Int. Conf. Electric Utility Deregulation and
Restructuring and Power Technologies (DRPT), Apr. 6–9, 2008, pp.
[8] Chapter 14. Federico Milano, “Power System Modelling and Scripting,”
Electrical Power and Energy Systems, Springer-Verlag London 2010.
[9] P.K. Hota, A.K. Barisal, R. Chakrabarti, “Economic Emission Load
Dispatch Through Fuzzy Based Bacterial Foraging Algorithm”, Elsevier,
Electric Power and Energy Systems, 2010.
[10] Refi Aulia Krisida, Adi Soeprijanto, Heri Suryoadmojo, “Optimal
Reactive Power and Voltage Control in Java-Bali 500 kV
Interconnection System Using Quantum Behaved Particle Swarm
Optimization”, undergraduate research final report, Institut Teknologi
Sepuluh Nopember, 2011.
[11] PT PLN P3B Jawa-Bali, “Greed Code(aturan Jaringan)” PT PLN, 2007.