Primary & Backup Generator Specification and Testing: Eeb/Esd
Primary & Backup Generator Specification and Testing: Eeb/Esd
Primary & Backup Generator Specification and Testing: Eeb/Esd
and Testing
EEB/ESD
Feb-2021
1
Primary & Backup Generator
Specification and Testing Standards
Table of Contents
1 Primary & Backup Generator Specification..................................................................................3
1.1 General...................................................................................................................................3
2 Conflict and deviation...................................................................................................................3
2.1 Codes and Standards..............................................................................................................3
2.2 Primary & Backup Generator System....................................................................................4
3 Purpose.........................................................................................................................................4
4 Primary & Backup Generator documents.....................................................................................4
5 Primary & Backup Generator Specification……………………………………………………………………….
……...5
6 Primary & Backup Generator Testing………………………………………………………………………………………
10
7 Installation & Configuration
Requirements…………………………………………………………………………….12
8 Fuel Tank Requirements…………………………………………………………………………………………………………
13
9 ATS Specification and
Testing………………………………………………………………………………………………….15
2
Primary & Backup Generator
Specification and Testing Standards
1.1 General
This standard aims to clarify all the requirements / needs to satisfy the environment for
Primary & Backup Generator Specification and Testing.
3
Primary & Backup Generator
Specification and Testing Standards
2. Scope
This standard contains requirements covering the performance of emergency and standby
power systems providing an alternate source of electrical power to loads in buildings and
facilities in the event that the primary power source fails.
3 Purpose
An emergency power system is an independent source of electrical power that supports
important electrical systems on loss of normal power supply.
8- Warranty Certificate.
4
Primary & Backup Generator
Specification and Testing Standards
General. The EPSS shall provide a source of electrical power of required capacity, reliability, and
quality to loads for a length of time as specified in [Table 2] and within a specified time
following loss or failure of the normal power supply as specified in [Table 1].
Class. The class defines the minimum time, in hours, for which the EPSS is designed to operate
at its rated load without being refueled or recharged. [See Table 2]
Type. The type defines the maximum time, in seconds, that the EPSS will permit the load
terminals of the transfer switch to be without acceptable electrical power. [Table 1] provides
the types defined by this standard.
Level. This standard recognizes two levels of equipment installation, performance, and
maintenance.
Level 1 systems shall be installed where failure of the equipment to perform could result in loss
of human life or serious injuries.
Level 2 systems shall be installed where failure of the EPSS to perform is less critical to human
life and safety.
All equipment shall be permanently installed.
Level 1 and Level 2 systems shall ensure that all loads served by the EPSS are supplied with
alternate power that meets all the following criteria:
(1) Of a quality within the operating limits of the load
(2) For a duration specified for the class as defined in [Table 2]
(3) Within the time specified for the type as defined in [Table 1]
1 2
5
Primary & Backup Generator
Specification and Testing Standards
Rotating Equipment
6
Primary & Backup Generator
Specification and Testing Standards
Prime movers and accessories shall comply with NFPA 37, Standard for the Installation and Use
of Stationary Combustion Engines and Gas Turbines, except as modified in this standard.
Prime Mover Ratings. Proper derating factors, such as altitudes, ambient temperature, fuel
energy content, accessory losses, and site conditions as recommended by the manufacturer of
the generator set shall be used in determining whether or not brake power meets the
connected load requirements.
Prime Mover Starting Equipment
Starting Systems shall be accomplished using either an electric starter or a stored energy
starting system.
Electric starter systems shall start using a positive shift solenoid to engage the starter
motor and to crank the prime mover for the period specified in NFPA110 section 5.6.4.2
without overheating, at a speed at least equal to that recommended by the
manufacturer of the prime mover and at the lowest ambient temperature anticipated at
the installation site.
Other types of stored energy starting systems (except pyrotechnic) shall be permitted to
be used where recommended by the manufacturer of the prime mover and subject to
approval of the authority having jurisdiction, under the following conditions:
(1) Where two complete periods of cranking cycles are completed without
replacement of the stored energy
(2) Where a means for automatic restoration from the emergency source of the
stored energy is provided
(3) Where the stored energy system has the cranking capacity specified in NFPA110
section 5.6.4.2.1
(4) Where the stored energy system has a “black start” capability in addition to
normal discharge capability
Otto or Diesel Cycle Prime Movers. For otto or diesel cycle prime movers, the type and duration
of the cranking cycle shall be as specified in NFPA110 Table 5.6.4.2.
A complete cranking cycle shall consist of an automatic crank period of approximately 15
seconds followed by a rest period of approximately 15 seconds. Upon starting and
running the prime mover, further cranking shall cease.
Two means of cranking termination shall be utilized so that one serves as backup to
prevent inadvertent starter engagement.
Otto cycle prime movers of 15 kW and lower and all diesel prime movers shall be
permitted to use continuous cranking methods.
Number of Batteries. Each prime mover shall be provided with both of the following:
7
Primary & Backup Generator
Specification and Testing Standards
Prime Mover Exhaust Piping. Where applicable, the exhaust system shall include a muffler or
silencer sized for the unit and a flexible exhaust section.
Generators, Exciters, and Voltage Regulators. Genera‐ tors shall comply with Article 445 of
NFPA 70, National Electrical Code, and with the requirements of 5.6.9.1 through 5.6.9.9.
The generator shall be of drip proof construction and have amortisseur windings.
The generator shall be suitable for the environmental conditions at the installation
location.
Control Functions.
A control panel shall be provided and shall contain the following:
Automatic remote start capability
“Run-off-automatic” switch
Controls to shut down and lock out the prime mover under any of the following
conditions:
(a) Failing to start after specified cranking time
8
Primary & Backup Generator
Specification and Testing Standards
(b) Overspeed
(c) Low lubricating-oil pressure
(d) High engine temperature (An automatic engine shutdown device for high
lubricating-oil temperature shall not be required.)
(e) Operation of remote manual stop station
Individual alarm indication to annunciate any of the conditions listed in NFPA110 table
5.6.5.2 and with the following characteristics:
(a) Battery powered
(b) Visually indicated
(c) Have additional contacts or circuits for a common audible alarm that signals locally
and remotely when any of the itemized conditions occurs
(d) Have a lamp test switch(es) to test the operation of all alarm lamps
Controls to shut down the prime mover upon removal of the initiating signal or manual
emergency shutdown
Remote Controls and Alarms. A remote, common audible alarm shall be provided as specified in
NFPA 110 Section 5.6.5.2(4). Alarms and annunciation shall be powered by the prime mover
starting battery unless operational constraints make this impracticable. In that circumstance an
alternate source from the EPS, such as a storage battery, UPS, or branch circuit supplied by the
EPSS, shall be permitted. The following annunciation shall be provided at a minimum:
(1) For Level 1 EPS, local annunciation and facility remote annunciation, or local annunciation
and network remote annunciation
(2) For Level 2 EPS, local annunciation
For the purposes of defining the types of annunciation the following shall apply:
(1) Local annunciation is located on the equipment itself or within the same equipment room.
(2) Facility remote annunciation is located on site but not within the room where the
equipment is located.
(3) Network remote annunciation is located off site.
An alarm-silencing means shall be provided, and the panel shall include repetitive alarm
circuitry so that, after the audible alarm has been silenced, it reactivates after the fault
condition has been cleared and has to be restored to its normal position to be silenced again.
Miscellaneous Requirements
9
Primary & Backup Generator
Specification and Testing Standards
Where applicable, the prime mover and generator shall be factory mounted on a common
base, rigid enough to maintain the dynamic alignment of the rotating element of the system
prior to shipment to the installation site.
A certification shall be supplied with the unit that verifies the torsional vibration
compatibility of the rotating element of the prime mover and generator for the intended use
of the energy converter.
Vibration isolators shall be furnished where necessary to minimize vibration transmission to
the permanent structure.
The manufacturer of the EPS shall submit complete schematic, wiring, and interconnection
diagrams showing all terminal and destination markings for all EPS equipment, as well as the
functional relationship between all electrical components.
The energy converter supplier shall stipulate compliance and performance with this
standard for the entire unit when installed.
Where requested, the short circuit current capability at the generator output terminals shall
be furnished.
6 Primary & Backup Generator Testing
1) Maintenance and testing are critical to the continued reliability of SANS emergency
generator and must be performed in accordance with manufacturer’s recommendations,
instruction manuals, and the minimum requirements of NFPA 110 and the authority having
jurisdiction (AHJ) [see: NFPA 110(10), Section 8.1.1].
2) SANS facility should have at least two sets of instruction manuals for all major generator
components. One set should be kept in a secure, convenient location near the equipment. The
other set should be kept in a different secure location [see: NFPA 110(10), Section 8.2.2]. These
manuals must, at a minimum, contain the following:
a) A detailed explanation of the operation of the emergency power supply system
b) Instructions for routine maintenance
c) Detailed repair instructions
d) An illustrated parts list and part numbers
e) Illustrated and schematic drawings of electrical wiring systems, including operating and
safety devices, control panels, instrumentation, and annunciators Page 2 of 6 June 2016
3) Special tools and testing devices necessary for routine maintenance must be available for use
when needed [see: NFPA 110(10), Sec. 8.2.3].
4) Routine maintenance, inspection and operational testing of the emergency generator and
associated components must be overseen by a properly trained person [see MSFC (15), Sec.
604.6; NFPA 99(12), Sec. 6.4.4.1.1.4(C); NFPA 110(10), Sec. 8.4.8]. Evidence of such training
10
Primary & Backup Generator
Specification and Testing Standards
should be kept in the designated employees’ personnel file. In the absence of a properly trained
person on-site, an outside vendor may need to be contracted to oversee the performance of all
or part of these services.
5) NFPA 110 does not establish a specific date and time of day for required testing. Those are to
be determined by management and are typically scheduled so as to provide minimum
disruption of facility operations. [see NFPA 110(10), Sections 8.4.2.1 and 8.4.2.4.1]. NFPA 99(12),
Sec. 6.4.4.1.1.4(A), however, requires that generator sets be tested 12 times a year, with testing
intervals of not less than 20 days nor more than 40 days.
Generator Tests
Insulation resistance
Dielectric and partial discharge tests
Tests for short-circuited field turn
Polarity test of field poles
Shaft current and bearing insulation
Phase sequence
Telephone-influence factor
Balanced telephone-influence factor
Residual-component telephone-influence factor
Line to natural telephone influence factor
Stator terminal voltage-waveform deviation and distortion factors
Over speed test
Line-charging capacitance
Acoustic noise
Temperature tests
Torque test
Sudden short-circuit test
11
Primary & Backup Generator
Specification and Testing Standards
Upon completion of the installation of the EPSS, the EPS shall be tested to ensure
conformity to the requirements of the standard with respect to both power output and
function.
An on-site acceptance test shall be conducted as a final approval test for all EPSSs.
For new Level 1 installations, the EPSS shall not be considered as meeting this standard
until the acceptance tests have been conducted and test requirements met.
The test shall be conducted after completion of the installation with all EPSS accessory
and support equipment in place and operating.
The authority having jurisdiction shall be given advance notification of the time at which
the acceptance test is to be performed so that the authority can witness the test.
The EPSS shall perform within the limits specified in this standard.
When the EPSS consists of paralleled EPSs, the system control function for paralleling
and load shedding shall be verified in accordance with system design documentation.
Any method recommended by the manufacturer for the cycle crank test shall be utilized
to prevent the prime mover from running.
The control switch shall be set at “run” to cause the prime mover to crank.
The battery charge rate shall be recorded at 5- minute intervals for the first 15 minutes
or until charge rate stabilization.
Items (1) through (4) shall be made available to the authority having jurisdiction at the
time of the acceptance test:
(1) Evidence of the prototype test as specified in NFPA section 5.2.1.2 (for Level 1 systems)
(2) A certified analysis as specified in 5.6.10.2
(3) A letter of compliance as specified in 5.6.10.5
(4) A manufacturer’s certification of a rated load test at rated power factor with the ambient
temperature, altitude, and fuel grade recorded
12
Primary & Backup Generator
Specification and Testing Standards
All fuel tanks and systems shall be installed and maintained in accordance with (NFPA 30,
Flammable and Combustible Liquids Code; NFPA 37, Standard for the Installation and Use of
Stationary Combustion Engines and Gas Turbines; NFPA 54, National Fuel Gas Code; and NFPA
58, Liquefied Petroleum Gas Code).
Fuel system design shall provide for a supply of clean fuel to the prime mover.
Tanks shall be sized so that the fuel is consumed within the storage life, or provisions
shall be made to remediate fuel that is stale or contaminated or to replace stale or
contaminated fuel with clean fuel.
Fuel tanks shall be close enough to the prime mover for the fuel lift (suction head) of the
prime mover fuel pump to meet the fuel system requirements, or a fuel transfer pump
and day tank shall be provided.
If the engine manufacturer's fuel pump static head pressure limits are exceeded when
the level of fuel in the tank is at a maximum, a day tank shall be utilized.
Fuel piping shall be of compatible metal to minimize electrolysis and shall be properly
sized, with vent and fill pipes located to prevent entry of groundwater or rain into the
tank.
Galvanized fuel lines shall not be used.
Approved flexible fuel lines shall be used between the prime mover and the fuel piping.
Day tanks on diesel systems shall be installed below the engine fuel return elevation.
The return line to the day tank shall be below the fuel return elevation.
Gravity fuel oil return lines between the day tank and the main supply tank shall be sized
to handle the potential fuel flow and shall be free of traps so that fuel can flow freely to
the main tank.
Integral tanks of the following capacities shall be permitted inside or on roofs of
structures, or as approved by the authority having jurisdiction:
(a) Maximum of 2498 L (660 gal) diesel fuel
(b) Maximum of 95 L (25 gal) gasoline fuel
The fuel supply for gas-fueled and liquid-fueled prime movers shall be installed in
accordance with applicable standards.
Where the gas supply is connected to the building gas supply system, it shall be
connected on the supply side of the main gas shutoff valve and marked as supplying an
emergency generator.
The building's main gas shutoff valve shall be marked or tagged to indicate the existence
of the separate EPS shutoff valve.
The fuel supply for gas-fueled and liquid-fueled prime movers shall be designed to meet
the demands of the prime mover for all of the following factors:
13
Primary & Backup Generator
Specification and Testing Standards
14
Primary & Backup Generator
Specification and Testing Standards
15
Primary & Backup Generator
Specification and Testing Standards
NFPA 110 has the following rules stated in terms of Automatic Transfer Switch testing
16