CSI 6500 Machinery Health™Monitor: A6125, Dual Channel Bearing Vibration Monitor

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Quick Start Guide

MHM-97444
NC: 6540-90069
Rev.: 1.032

CSI 6500 Machinery Health™Monitor


A6125, Dual Channel Bearing Vibration Monitor
Emerson Process Management ©2010, Emerson Process Management.
Machinery Health Management The contents of this publication are presented for informational purposes only, and while every effort has
835 Innovation Drive been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
Knoxville, TN 37932 USA or implied, regarding the products or services described herein or their use or applicability. All sales are
T 1(865) 675-2400 governed by our terms and conditions, which are available on request.We reserve the right to modify or
F 1(865) 218-1401 improve the designs or specifications of our products at any time without notice.
www.EmersonProcess.com All rights reserved. Machinery Health is a mark of one of the Emerson Process Management group of
companies. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are
the property of their respective owners.
GB
Explanation of symbols

If this symbol is printed on a device, according to IEC 61010 it means that the
documentation of the device must be completely read and understood before

! installation and commissioning of the device. All safety−related instructions


of this document must be observed. These safety−related instructions are
marked by the “STOP” symbol in this document.

If this symbol is printed on a device, according to IEC 61010 it means that this
device must be operated with DC voltage.

i
This symbol identifies text that contains important information.

!
Not following instructions identified with this symbol can result in functional
issues and incorrect measurements without damaging the machine.

Safety and warning instructions are identified with this symbol.


Failure to observe these instructions can result in material damage or
STOP personal injury.

D
Symbolerklärung

Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010
aus, das es zur Installation und Inbetriebnahme des Gerätes zwingend

!
erforderlich ist, die Dokumentation des Gerätes vollständig gelesen und
verstanden zu haben. Sicherheitsrelevante Hinweise in dieser
Dokumentation sind unweigerlich zu beachten und im weiteren Verlauf dieser
Dokumentation durch das “STOP” Symbol (siehe unten) gekennzeichnet.

Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010
aus, dass es mit Gleichspannung betrieben wird.

i Dieses Symbol kennzeichnet Textstellen, die wichtige Informationen


enthalten.

!
Hinweise, die bei Nichtbeachtung zu Funktionsstörungen und
Fehlmessungen führen, ohne das Gerät zu beschädigen, sind mit diesem
Symbol gekennzeichnet.

Sicherheits- und Warnhinweise sind mit diesem Symbol gekennzeichnet.


STOP Die Nichtbeachtung solcher Hinweise kann zu Sachbeschädigungen oder
Personenschäden führen.
Product Service Centers Incoming goods inspection
Check the content of the shipment to ensure that it is
America complete; visibly inspect the goods to determine if the
device may possibly have been damaged during
Emerson Process Management
transport. The following parts are included in the scope
835 Innovation Drive of delivery and must be contained in the shipment.
Knoxville, TN 37932
1. A6125
Tel: 865−675−2110
Fax: 865−218−1401 2. Product information
If the contents are incomplete, or if any defects are
Brazil observed, a complaint must be filed with the carrier
Emerson Process Management Ltd. immediately. Moreover, the responsible Emerson sales
organization must be informed to enable repair or
Av Hollingsworth 325
replacement of the device. Repairs or calibration that
Sorocaba, SP
may be required, are only possible at the Emerson
BRAZIL 18087−000 factory.
Phone: 55 15 2383788 In this case, a non−detachable tag with customer name,
Fax: 55 15 22823300 defect observed and version of the A6910 configuration
software must be attached to the device.
Europe, Middle East, Africa
Emerson Process Management Repair and maintenance
div. ESAD During operation, monitors do not require any mainte-
MHM Repair Center nance.
Piestanska 1202/44 Repair or calibration of monitors is only possible at
Emerson.
915 28 Nove Mesto nad Vahom

i
Slowakia The additional PCB (controller board)
Tel: +421/32/7700 538 is calibrated with the main board and
Fax: +421/32/7700 884 must not be replaced.

Asia If work with the opened device on−site is


Emerson Process Management / Asia unavoidable, this should only be performed by a
specialist who is familiar with the associated
Pacific Private Ltd.
hazards.
3904 Room Central Plaza
Capacitors in the device can still be
18 Harbour Road Wan−Chai
energized, even if the device has
Hong Kong STOP been disconnected from all power
Tel: 852−2802−9223 sources.
Fax: 852−2802−8227
If repair or recalibration of a monitor is required, it G Description of the hardware
must be sent to Emerson. Attach a non−detachable problem
tag to the monitor with customer name, defect
G Return shipping address including a
observed and version of the A6910 configuration
phone number (No P.O. boxes).
software.
G Any special request regarding the
Guidelines for Returning Equipment to the return shipment.
Product Service Center
G A list of the model numbers of each
If repair or calibration of a monitor is required, it must item(s) being returned, along with
be sent to Emerson. the serial number.
Occasionally, concerns with CSI technology
hardware could arise. Should this happen, customers G Your name, address, telephone
under warranty or a current support agreement are number and email address.
entitled to no−charge repairs.
G Company Name.
Follow the checklist below to minimize return time
and ensure proper processing of your equipment.
A form for completing this information has
Before returning any equipment to a Product Support
been provided.
Center, please review this information:
1. Obtain a Return Materials Authorization (RMA)
Make a copy of the form, complete all lines,
number and the address of the appropriate
and return a copy in each return shipment.
Product Service Center by calling 865.675.4274*.

Listen to the options for receiving an RMA. You Out of warranty? Need to get under
will be routed to support personnel who will support? Get a customized quote for
document your concern and give you an RMA bringing all your CSI technologies under a
number if you are under support or warranty. If support agreement:
your hardware is not under support or warranty, Phone: 865.675.2400*, ext. 2130
you must have a Purchase Order for the amount Fax: 865.218.1478*
of the repair service before you can receive an Email:
RMA number. Pricing for your repair can be mhm.supportagreement@emersonproces
obtained from support personnel or by calling s.com
your local sales representative. Once you have
your purchase order, call 865.675.4274* for an
*Customers outside the Americas and
RMA.
Canada: please refer to the list of service
2. Once you have received your RMA, send your centers and contact the service center near
hardware to the appropriate product service you.
center. Your hardware package should include:
All rights are strictly reserved
G RMA Number (plus Purchase Order if
Reproduction or divulgation in any form
applicable)
whatsoever is not permitted without written
authority from the copyright owner.
RMA Required Information
Company Name:

RMA number issued by Product Contact Name:


Service Center:
Contact Address:

For all items beingreturned, please


list Model / Serial Number:

Contact Phone:

Contact Fax:

Contact Email:

Please describe the problem you are experiencing:


Are you under warranty or a current
support agreement (circle one)?

Yes No

If you answered no, what is your


purchase order number? If we are to send the return shipment to someone other than the
Contact Name/Address above, please provide that address here,
including Contact Name and Phone Number:

Are there any special instructions regarding the return?

Please provide invoice address (if a purchase order was required):

Support customers − your instrument is shipped back to you the same


way that it is sent to our service center. For example, if you ship via
ground transportation, it is shipped back via ground.
Product Information / Produktinformation A6125
Page/Seite 7

GB
1 Bearing Vibration Monitor . . . . . . . . . . . . . . . . . . . . . . 8
1.1 Scope of Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 CSA Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 CSA − Conditions of acceptability . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Advice for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Installation and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6.1 Signal conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.6.2 Channel monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.6.3 Limit value formation and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.6.4 Communication interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.6.5 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.6.6 Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.6.7 Mechanical structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

D
2 Lagerschwingungsmonitor . . . . . . . . . . . . . . . . . . . . . 21
2.1 Lieferumfang . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2 CSA Zertifizierung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.3 CSA − Akzeptanzkriterien . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.4 Hinweis zur Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.5 Installation und Montage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.6 Technische Daten . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.6.1 Signalkonditionierung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.6.2 Kanalüberwachung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.6.3 Grenzwertbildung und Alarme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.6.4 Kommunikationsschnittstellen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.6.5 Spannungsversorgung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.6.6 Umgebungsbedingungen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.6.7 Mechanischer Aufbau . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

3 Connection Diagrams and Figures / Anschlusspläne und Abbil-


dungen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

4 PI Revision List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 8

GB
1 BEARING VIBRATION MONITOR
The two−channel Bearing Vibration Monitor for piezoelectric sensors A6125 is part of the A6000
machine monitoring system. The micro−processor controlled monitor is used in conjunction with
two piezoelectric sensors or capacitive sensors (e. g.: epro PR 9264) to measure and monitor
the absolute bearing vibrations at all kind of turbines, compressors, fans and gear boxes, etc.

The monitor A6125 permit the use of piezoelectric sensors, which provide signals proportional
to the vibration acceleration or vibration velocity.

The two channels of the monitor operate independently from each other. Each channel may be
configured for one of the following signal processing:

• Vibration acceleration

• Vibration velocity

The characteristic values can be output via a 0/4...20mA current output per channel.

In this product information the mounting and electrical connection of the


monitor is described.
For secure use of the monitor, observe the direction for use “Bearing Vibration
Monitor A6125” (order number: 6110−90069). You can find this direction on

i
the configuration software CD as pdf−data file. Amongst others, it contains
useful informations for configuration and use of the A6125.
To ensure the safe operation of the monitor and to permit setting of all
functions, it is indispensable to use only the latest version of configuration
software (version 2.08 or newer) and operating manual.
The use of old operating manuals or configuration programs out of date may
lead to malfunctions or limitations of the measuring functions.

1.1 Scope of Delivery


The following parts are included in the scope of delivery and must be contained in the shipment:

• Bearing Vibration Monitor A6125

• This product information.

Accessories (not included in delivery):

• MMS ParaKit (order no.: 9510−00027)

If the contents are incomplete or if is there any damage, so directly complain at the bearer. The
competent epro−sales agency must be also informed, to enable repair or replacement for the
monitor. Repair or calibration of this instrument may only be done at epro.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 9

1.2 CSA Certification

For valid CSA certification, all devices (IMR 6000/xx and A6000 modules)
must be marked with the respective CSA lable.
STOP If no CSA lable is available on the respective device, this device is not CSA
certified!

The respective CSA lable looks as shown in the following picture.

1.3 CSA − Conditions of acceptability


This device must be supplied with safety low voltage SELV LPS (C22.2 60950−1) 24V. The
voltage required for operation must be drawn from a separate power supply.

The IMR system should be placed in a suitable fire enclosure.

The IMR system is evaluated for an ambient of 0°C to 45°C.

Adequate ventilation space has to be provided so that heat does not build up. The ventilation
space must be at least 1 RU (13/4 inch) in all directions. If the ambient temperature of the rack
rises above 45 °C, cool this instrument with a forced air fan, cooler, or similar.

When mounting several IMR units above each other in one cabinet, install cooling fan racks in
between instead of the ventilation space. The necessary specifications for cooling fan racks
result from the environmental and sitting criterions of the cabinet and thus cannot be defined
generally.

1.4 Advice for Installation


According to the IEC 61010 directive, permanently installed systems must be
equipped with a power disconnect device (e.g. a switch or circuit−breaker
according to IEC60947−1 and IEC60947−3). When using an IMR rack, in
STOP compliance with this directive, such a switch or breaker must be implemented
into the cabinet installation and easily accessible for the user. Furthermore,
each disconnect devices must be labeled in accordance to the associated
system.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 10

1.5 Installation and Mounting


A prepared 3U slot in a 19” rack, or other Intermas−compatible enclosure, is required for
mounting the MMS 6125 monitor. The slot must be fitted with a 48−pin plug connector (DIN
41612, design F 48 M). The pin assignment is listed in the following table.

d b z
2 UN+ (+ 24V) U− (0V/Common) UB+ (+24V, redundant) 2
4 A (RS 485) GND (BP, Common, RS 485) B (RS 485) 4
6 Supply2+ (sensor) Supply1− (sensor) Supply1+ (sensor) 6
8 AIN2− (Input) Supply2− (sensor) AIN1− (Input) 8
10 AIN2+ (Input) GND AIN1+ (Input) 10
12 NGL2 (scaled dc−output) GND NGL1 (scaled dc−output) 12
14 EO1 (voltage output1) EI1 (voltage input1) AC1 (sensor raw signal1) 14
16 EO2 (voltage output2) EI2 (voltage input2) AC2 (sensor raw signal2) 16
18 GWM (limit value) I1− (current output common) I1+ (current output CH1) 18
20 NC I2− (current output common) I2+ (current output CH2) 20
22 KEY−N (key signal input) GND ES (external lock) 22
24 SC−A (oper. principle alert) GND SC−D (oper. principle danger) 24
26 D1−C (danger1 collector) A1−C (alert1 collector) CC1−C (ch. clear1 collector) 26
28 D1−E (danger1 emitter) A1−E (alert1 emitter) CC1−E (ch. clear1 emitter) 28
30 D2−C (danger2 collector) A2−C (alert2 collector) CC2−C (ch. clear2 collector) 30
32 D2−E (danger2 emitter) A2−E (alert2 emitter) CC2−E (ch. clear2 emitter) 32

Jumper RS 485

RS 485 bus operation requires an electrical terminator on the first and last bus device.

This is done with plug−in jumpers, that are on the controller board. The figure shows the position
of the jumpers.

To activate the bus terminator and to place lines “A” and “B” on the references, plug the jumpers
as shown in Fig. b). Fig. a) shows the jumper position for deactivated bus termination and open
references (delivery status).

• Plug−in jumper 1−2 closed: Bus line “B” via pull−down resistor on ground

• Plug−in jumper 3−4 closed: 120 Ω Resistor between “A” and “B”

• Plug−in jumper 5−6 closed: Bus line “A” via pull−up resistor on +5 V
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 11

2 4 6 2 4 6

1 3 5 1 3 5

a) b)

i
For trouble−free operation of the RS 485 bus, the lines “A” and “B” in one
monitor must be connected on their references (+5 V, ground), this is only
possible if the bus terminator jumper is also set in this monitor.

Sensor raw−signal

The raw sensor signal (in−phase output signal of the converter without Bias−voltage) applied
to the front panel SMB sockets, can be switched over with the J2 jumpers on terminals z14:
channel 1 and z16: channel 2 of the connection strip. The controller board must be removed in
order to switch the signal on the connection strip. The following points describe the procedure:

i
The reference point for the raw sensor signal from channel 1 is the connection
strip terminal b22: GND, and for the raw sensor from channel 2 the terminal
b24: GND.

When working at the monitor, ensure that there is adequate protection against
STOP electrostatic discharge. For examle, wear an ESD bracelet to prevent
electrostatic discharge via the monitor electronics.

3. Use a cross−head screwdriver to remove the four cross−headed screws, identified with the
arrows, in the following figure.

4. Carefully pull the controller board off the main board without tilting it. The position of the J2
jumpers on the main bard is identified with a white frame in the following figure.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 12

5. To switch the raw sensor signal to terminals z14 and z16 place the jumpers as shown in b).
If the jumpers are set as shown in a) then the dynamic portion of the sensor signal is applied
on terminals z14 and z16.

SENS1 AC1 SENS1 AC1

z14: z14:
J2 J2
z16: z16:

SENS2 AC2 SENS2 AC2


a) b)

6. Place the controller board back on the main board and secure it with the four screws. Now,
the raw sensor signal is on the connection strip.

Installation

1. Check the slot wiring prior to installing the monitor.

2. Push the A6125 monitor into the prepared slot and press it with light pressure into the plug
connector.

3. Hand tighten the two anchoring screws on the front panel to secure the monitor.

Any other information, e. g. shielding and grounding, configuration of the monitor, etc., can be
found in the direction for use “Bearing Vibration Monitor A6125”, order number: 6110−90069.

1.6 Technical Data


Only information with tolerances and limit values are considered as binding data. Data without
tolerances or error limits are provided as information only. We reserve the right to make technical
changes − particularly to the software.

All of the following information applies uniformly for channel 1 and channel 2, if not otherwise
specified.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 13

1.6.1 Signal conditioning

Two separate signal inputs for channel 1 and channel 2 with uncoupled signal conditioning.

Measured value inputs

Differential voltage amplification inputs, non−reactive, open−circuit and short−circuit proof.

Channel 1 z8: SENS1H (+); z10: SENS1L (− Signal)

Channel 2 d8: SENS2H (+); d10: SENS2L (− Signal)

Input nominal range 0 ... +20 V

Limit range ±30 V DC

Signal voltage range 4,0 Vss

Input resistance > 100 kΩ

Signal conditioning

Sensor signal outputs Front sockets SMB and/or z14 / z16*, decoupled,
open circuit and short circuit proof, non reactive.

Channel 1 − SENS 1 SMB K1

Channel 2 − SENS 2 SMB K2

Signal output ±10 V; signal 1:1 to sensor input signal


(without Bias−voltage)

Precision ±1 % of f.s.d.

Frequency range hardware−filter 0,12 ... 8 kHz (−3 dB) ±20 %

Per. load resistance > 100 kΩ

Internal resistance 1 kΩ

*Depends on the jumper setting J2.

Dynamic outputs

The outputs are physically present however they do not supply a usable dynamic signal.
With the J2 jumpers the raw sensor signal (in−phase sensor signal) that is applied to the SMB
sockets on the front panel can be switched over to these terminals.

Channel 1 / channel 2 z14 / z16* open circuit and short circuit proof, non
reactive

*Depends on the jumper setting J2.


Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 14

Signal conditioning for characteristic values

The input signals are conditioned by adjusting amplifier, range−dependent amplifier, high
pass, and low pass prior to digitalization.

Range setting Is determined in the configuration

Maximum measuring range 4,0 V ss

Frequency range

High pass filter Butterworth filter 2nd order

− Parameters can be set fu 2 Hz (−3 dB) for work frequency 5 Hz


fu 4 Hz (−3 dB) for work frequency 10 Hz

− Tolerance ±20 %

Low pass filter Butterworth filter 5th order


Parameter range 50 Hz ... 8000 Hz

Characteristic value formation Depends on the configuration

Vibration velocity Root mean square value vrms

Digital filter

Filter settings are made by means of software configuration

Operating Evaluation Dig. Filter High Dig. Filter Med Dig. Filter Low
mode

Acceleration Acceleration 30 ... 8000 Hz 10 ... 2000 Hz 6 ... 1000 Hz

Velocity −−−−−−−−

Velocity Velocity 10 ... 2000 Hz 6 ... 1500 Hz 2 ... 250 Hz

Amplitude

Current outputs−characteristic values

Characteristic value formation and evaluation depends on the functions specified in the
configuration.

Current output 1 − I1+ /I1− z18 / b18 (0 V / common)

Current output 2 − I2+ / I2− z20 / b20 (0 V / common)

Nominal range 0 ... 20 mA or 4 ... 20 mA, depending on the


configuration

−Life zero operation in 4 ... 20 mA operation you can specify via the
configuration that the output is set to 0 mA if a fault is
detected.

Precision / resolution ±1 % of f.s.d. / 16 Bit

Per. load resistance 500 Ω


Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 15

Signal outputs EO 1 / EO 2

d14 / d16
Voltage outputs 0...10V proportional to the bearing vibration, measuring range and signal
evaluation according to the characteristical variables channel 1 (EO 1) andchannel 2 (EO 2).
Open circuit and short circuit proof, non reactive.

Nominal range 0 ... +10 V DC

Resolution 8−bit

Per. load resistance > 10 kΩ

Internal resistance Approximately 50 Ω

Signal inputs EI1 / EI2

Inputs for single−channel measurement values 0 ... +10 V for connection with EO outputs
(not relevant for MMS 6125).

Voltage input EI1 / EI2 b14 / b16

Nominal voltage range 0 ... +10 V DC

Resolution 10−bit

Internal resistance > 100 kΩ

Signal input KEY

The key pulse is required for internal RPM determination for checking the measurements in
the measured value analysis.

Signal input KEY (N) d22

Signal level 24 V logic,: LOW = 0 ... 3 V; HIGH = 13 ... 48 V

Input resistance > 10 kΩ

1.6.2 Channel monitoring

Supervision function

permanent supervision

of the measuring chains (sensors) by supervising the input signal levels on short−circuit
and cable breaks

System voltages Voltage − OK

μP function (watchdog) WD − OK

Configuration & setting C&P − OK


parameters

External disable signal ES


Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 16

Status channel monitoring

Channel status = no error (OK) if ( voltage _OK = yes )


AND (WD_OK = yes)
AND ( K&P_OK = yes )
AND (Sensor signal within good range)

Channel status = error If the previous condition is not satisfied

Channel status = enable delayed an enable delay of 15 s (±2 s) will get active in the
moment of switching from the error to the OK status or
after power on of the monitor.

Internal effect In case of an error or during enable delay the channel


supervision does only affect the characteristical value
and the limit value,and only if the limit suppression has
been activated.

Visualization

Green LED on the front panel

Channel status = no error (OK) Continuous light

Channel status = error Dark

Channel status = release delayed Flashing light

Channel Clear outputs

Opto−decoupled collector / emitter segments

Channel Clear channel 1, C1C / C1E z26 (collector) / z28 (emitter)

Channel Clear channel 2, C2C / C2E z30 (collector) / z32 (emitter)

Ext. disabled or status = error or C−E disabled, max. perm. voltage: 48 V


release delayed

Not ext. disabled and status = OK and C−E conducting, max. perm. current: 100 mA
not release delayed

Input external disable ES

z22 − for disabling the limit value alarms; e.g. for service work etc.

Disable function Input LOW = disable the channel monitoring and limit
value formation

Release Input HIGH or not switched = enable of channel


monitoring and limit value formation

Signal level LOW: 0 ... +3 V, HIGH: +13 ... +48 V


Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 17

1.6.3 Limit value formation and alarms

Two alarm channels, each with an alarm output ALERT and DANGER, and separate limit value
adjustment. Alarming if the characteristic value exceeds the limit value parameters. (Actual
value > limit value)

Setting the limit value

Through setting parameters, depending on the configuration for measurement operation,


characteristic value formation, range etc.

Setting condition Limit value ALERT < limit value DANGER

Setting range 0 ... 100 % of the measuring range parameters

Resolution and reproducibility 1 % based on the measuring range end value

Hysteresis Configurable, 0 ... 20 % based on the measuring range


end value
The hysteresis is only effective with decreasing actual
value.

Alarm delay

Can be configured to 0 (off), 1,2,3,4,5 sec.; effective on the alarm outputs.

Alarm blocking

Blocking If (C&P active = yes) OR


(Voltage or watchdog not OK) OR
(Ext. disable = disable) OR
(Channel status = error and limit value
suppression on*) OR
(Channel status = release delayed) AND
Channel monitoring effect = yes

No blocking If the above condition is not satisfied

* In the configuration it is specified whether the alarm outputs will be blocked through channel
monitoring.

Alarm visualization

Through one red LEDs each for channel 1 and channel 2

No limit value exceeded or alarm LED off


blocked

ALERT, no DANGER LED flashes at 2 Hz (pulse/pause 1:1)

DANGER LED on continuously


Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 18

Alarm outputs

Opto−decoupled collector / emitter segments

Alert channel 1 A1−C / A1−E b26 (collector) / b28 (emitter)

Danger channel 1 D1−C / D1−E d26 (collector) / d28 (emitter)

Alert channel 2 A2−C / A2−E b30 (collector) / b32 (emitter)

Danger channel 2 D2−C / D2−E d30 (collector) / d32 (emitter)

Maximum value for alarm outputs C−E disabled: max. perm. UCE: 48 V
C−E conductive: max. perm. UCE: 100 mA

Alarm status of the alarm outputs Conducting in open circuit mode, disabled in closed−
circuit mode

Open circuit mode / closed−circuit mode

The digital inputs SC−A and SC−D can be selected with external signals.

Switchover ALERT d24 − SC−A = HIGH / blank


= open circuit mode
d24 − SC−A = LOW = closed−circuit mode

Switchover DANGER z24 − SC−D = HIGH / blank


= open circuit mode
z24 − SC−D = LOW = closed−circuit mode

Switch level LOW = 0 ... +3 V


HIGH = 13 ... 48 V

Input resistance > 10 kΩ

1.6.4 Communication interfaces

Interface RS 232

Front socket for connecting a laptop / computer for configuration and visualization purposes

Round plug connector on the front Mini DIN socket type TM 0508A/6 for parameterization
side cable (included in the operating kit)

Interface RS 485

d4, z4 bus interface for communication with an MMS 68xx epro analysis and diagnostic
system and the configuration software.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 19

1.6.5 Power supply

The monitor system voltages, and thus the 0 V / common connections for the measurement
and monitoring inputs and outputs, are galvanically separated.

Supply voltage inputs Two redundant, diode decoupled inputs for nominal
+24 V with common 0 V reference

Voltage input UB+ / UN+ d2 / z2

Common reference 0 V U− b2

Perm. voltage range 19 ... 31.2Vdc (IEC 654−2 class DC 4)


CSA: 24Vdc; SELV LPS

Power consumption max. 6 W, at 24 V max. 250 mA

Monitor system voltage

The system voltages required for the internal supply are constantly monitored on overvoltage.
If undervoltage is detected an error message is generated.

Sensor supply

For both channels of the monitor

Separation Decoupled and galvanically separated from the


supply voltage,
can be operated in parallel with other monitors, open
circuit and short circuit proof, non reactive.

Sensor supply channel 1 SENS1− / SENS1+ b6/z6

Sensor supply channel 2 SENS2− / SENS2+ b8/d6

Current setting 2...8 mA, configurable in steps of 40 μA

Tolerance ±0,5 % of f.s.d, +0,5 % of the adjusted value


max. burden 3,4 kΩ at 8 mA,
13,6 kΩ at 2 mA
open−circuit and short−circuit proof
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 20

1.6.6 Environmental conditions

Application class KTF in accordance with DIN 40040

Ambient temperature

Reference temperature +25°C

Nominal use range 0 ... +45°C (CSA requirement and recommended range)
max. range −10°C ... +65°C (not CSA conform)

Storage, transport temperature −30 ... +85°C

Operating altitude up to 2000m above sea level

Relative humidity ≤ 95 % non condensing

Vibration In accordance with IEC−68 − 2 Part 6

Path 0.15 mm at 10 ... 55 Hz

Acceleration 19.6 mm/s2 at 55 ... 150 Hz

Shock In accordance with IEC−68 − 2 Part 29


Peak acceleration value 98 m/s2
Nominal duration of shock 15 ms

Enclosure protection class IP 00, open design in accordance with DIN 40050

EMC immunity In accordance with EN 50 081−1 / EN 50 082−2


satisfied

Allowed degree of pollution Category 2 (According to IEC 61010−1)

Enviromental Area Indoor use only

1.6.7 Mechanical structure

PCB Euro format (100 mm x 160 mm) in accordance with


DIN 41494

Width 6 TE (approximately 30 mm)

Plug connector DIN 41612, form F 48 M

Front element

2 LEDs green Channel Clear channel 1 / 2

2 LEDs red Alarms channels 1 / 2

2 SMB socket connectors For sensor channel 1 / 2

1 mini DIN round socket connector RS 232 for connecting a laptop / computer
(for configuration and visualization purposes)

Weight Approximately 320 g without packaging,


approximately 450 g with standard packaging
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 21

D
2 LAGERSCHWINGUNGSMONITOR
Der zweikanalige Lagerschwingungsmonitor für piezoelektrische Sensoren A6125 ist eine
Baugruppe des A6000 Maschinenüberwachungssystems. Der mikrocontrollergesteuerte
Monitor dient in Verbindung mit zwei piezoelektrischen Sensoren (Sensorelement: PZT
Keramik) oder kapazitiven Sensoren der epro−Typenreihe PR 9264 der Messung und
Überwachung von absoluten Lagerschwingungen an Turbinen aller Art, Kompressoren, Lüftern,
Getrieben usw.

Der Monitor A6125 erlaubt den Einsatz von piezoelektrischen Aufnehmern, die ein beschleuni-
gungs− oder geschwindigkeitsproportionales Signal liefern.

Die beiden Kanäle des Monitors arbeiten unabhängig voneinander. Mittels Konfiguration
können für den Monitor folgende Betriebsarten eingestellt werden:

• Schwingbeschleunigung

• Schwinggeschwindigkeit

Die Kenngrößen können je Kanal über einen Stromausgang 0/4 ... 20 mA ausgegeben werden.

In dieser Produktinformation wird die Montage und der elektrische Anschluss


des Monitors beschrieben.
Für den sicheren Betrieb des Monitors muss die Gebrauchsanleitung
“Lagerschwingungsmonitor A6125” (Bestellnr. 6100−90069) unbedingt
beachtet werden. Die Gebrauchsanleitung befindet sich im pdf−Format auf
der CD mit der Konfigurationssoftware. Sie enthält unter anderem

i Informationen zur Konfiguration und Bedienung des A6125.


Um den sicheren Betrieb des Monitors zu gewährleisten und um alle
Funktionen des Gerätes einstellen zu können ist es erforderlich, die jeweils
aktuellste Version von Konfigurationssoftware (ab Version 2.08) und
Gebrauchsanleitung zu verwenden.
Die Verwendung älterer Konfigurationsprogramme oder Gebrauchs−
anleitungen kann Funktionseinschränkungen oder Fehlfunktionen zur Folge
haben.

2.1 Lieferumfang
Folgende Teile gehören zum Lieferumfang und müssen in der Sendung enthalten sein:

• Lagerschwingungsmonitor A6125

• diese Produktinformation

Zubehör (nicht im Lieferumfang enthalten):

• MMS ParaKit (Best.−Nr. 9510−00027)

Sollte der Inhalt unvollständig sein oder irgend welche Defekte vorliegen, so muss beim
Überbringer sofort reklamiert werden. Außerdem muss die zuständige epro Verkaufsstelle ver-
ständigt werden, um Reparatur oder Ersatz des Gerätes zu ermöglichen. Eventuell erforderliche
Reparaturen oder Kalibrierung von A6000 Monitoren sind nur im epro−Werk möglich.
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 22

2.2 CSA Zertifizierung

Zur gültigen CSA Zertifizierung müssen alle Geräte (IMR 6000/xx und A6000)
mit einem entsprechenden CSA Label versehen worden sein.
STOP Für den Fall das kein CSA Lable auf dem Gerät angebracht wurde ist dieses
Gerät nicht CSA zugelassen!

Das entspechende CSA Label sieht wie nachfolgend dargestellt aus.

2.3 CSA − Akzeptanzkriterien


Dieses Gerät muss mit Schutzkleinspannung SELV LPS (C22.2 60950−1) 24V betrieben
werden. Diese Betriebsspannung muss von einem seperaten Speisegerät bezogen werden.

Das IMR− System sollte in einem zweckmäßigen Feuerschutzgehäuse installiert werden.

Das IMR− System ist bewertet für einen Umgebungstemperaturbereich von 0°C bis 45°C.

Es muss angemessener Zirkulationsfreiraum vorgesehen werden damit sich keine Hitze


aufstauen kann. Der Zirkulationsfreiraum muss mindestens 1 HE (13/4 inch) in allen Richtungen
betragen. Für den Fall das die Umgebungstemperatur des Racks über 45°C steigt müssen die
gerätschaften mit einem festen Lüfter, einer Kühlvorrichtung etc. auf den entsprechend
zugelassenen Temperaturbereich heruntergekühlt werden.

Werden mehrere 19” Rahmen übereinander in einem Schaltschrank installiert so sollten


anstelle des Zirkulationsfreiraum entsprechende 1HE Lüftereinschübe installiert werden. Da die
notwendigen Spezifikationen derartiger Lüfter aus den Umgebungs− und Standortbedingungen
des Schaltschrankes resultieren können keine generellen Lüfterspezifikationen festgelegt
werden.
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 23

2.4 Hinweis zur Installation

Gemäß der IEC 61010 Richtlinie müssen fest installierte Systeme mit einer
Trenneinrichtung (ggf. einem Schalter und/ oder einem Leitungsschutz−
schalter nach IEC60947−1 und IEC60947−3) zum unterbrechen der
Spannungsversorgung ausgestattet sein. Bei Verwendung eines IMR
Systems kann dies, unter Beachtung dieser Richtlinie, durch einen Schalter
oder Leistungsschalter erfolgen.
STOP
Dazu muss sich dieser in der Gebäude− bzw. Schaltschrankinstallation
befinden, in unmittelbarer Nähe zum System implementiert sein und für den
Anwender leicht zugänglich sein.
Des weiteren muss jede derartige Trenneinrichtung entsprechend dem
zugehörigen System gekennzeichnet bzw. beschriftet sein.

2.5 Installation und Montage


Für die Montage des A6125 Monitors wird ein vorbereiteter Steckplatz in einem 19”
Baugruppenträger mit 3 HE oder ein anderes Intermas−Kompatibles Gehäuse benötigt. Der
Steckplatz muss mit einem 48−poligen Steckverbinder (DIN 41612, Bauform F 48 M)
ausgestattet sein. Die Pin−Belegung ist in der nachfolgenden Tabelle aufgeführt.

d b z
2 UN+ (+ 24V) U− (0V/Common) UB+ (+24V, redundant) 2
4 A (RS 485) GND (BP, Common, RS 485) B (RS 485) 4
6 Supply2+ (sensor) Supply1− (sensor) Supply1+ (sensor) 6
8 AIN2− (Input) Supply2− (sensor) AIN1− (Input) 8
10 AIN2+ (Input) GND AIN1+ (Input) 10
12 NGL2 (scaled dc−output) GND NGL1 (scaled dc−output) 12
14 EO1 (voltage output1) EI1 (voltage input1) AC1 (sensor raw signal1) 14
16 EO2 (voltage output2) EI2 (voltage input2) AC2 (sensor raw signal2) 16
18 GWM (limit value) I1− (current output common) I1+ (current output CH1) 18
20 NC I2− (current output common) I2+ (current output CH2) 20
22 KEY−N (key signal input) GND ES (external lock) 22
24 SC−A (oper. principle alert) GND SC−D (oper. principle danger) 24

26 D1−C (danger1 collector) A1−C (alert1 collector) CC1−C (ch. clear1 collector) 26
28 D1−E (danger1 emitter) A1−E (alert1 emitter) CC1−E (ch. clear1 emitter) 28
30 D2−C (danger2 collector) A2−C (alert2 collector) CC2−C (ch. clear2 collector) 30
32 D2−E (danger2 emitter) A2−E (alert2 emitter) CC2−E (ch. clear2 emitter) 32
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 24

Jumper für RS 485

Der Betrieb des RS 485 Busses erfordert einen elektrischen Abschluss jeweils am ersten und
letzten Gerät des Busses.

Dies geschieht mit Steckbrücken, die sich auf dem Kontrollerboard befinden. Das Bild zeigt die
Position der Jumper.

Um den Bus−Abschluss zu aktivieren und die Leitungen “A” und “B” auf die Bezüge zu legen,
stecken Sie die Jumper wie in Bild b) gezeigt. Das Bild a) zeigt die Jumperposition für einen
deaktivierten Bus−Abschluss und offene Bezüge (Auslieferungszustand).

• Steckbrücke 1−2 geschlossen: Busleitung “B” über Pull−down Widerstand an Masse

• Steckbrücke 3−4 geschlossen: 120 Ω Widerstand zwischen “A” und “B”

• Steckbrücke 5−6 geschlossen: Busleitung “A” über Pull−up Widerstand an +5 V

2 4 6 2 4 6

1 3 5 1 3 5

a) b)

Für einen störungsfreien Betrieb des RS 485 Busses müssen die Leitungen

i “A” und “B” in einem Monitor auf ihre Bezüge (+5 V; Masse) gelegt werden,
dies ist nur möglich wenn in diesem Monitor auch der Busabschluss−Jumper
gesetzt ist.

Sensorrohsignal

Das, an den SMB−Buchsen der Frontplatte anliegende Sensorrohsignal (phasenrichtige


Ausgangssignal des Konverters ohne Bias−Spannung) kann mit den Jumpern J2 auf die
Klemmen z14: Kanal 1 und z16: Kanal 2 der Steckleiste umgeschaltet werden. Hierfür muss das
Kontrollerboard entfernt werden. Die folgenden Punkte beschreiben die Vorgehensweise:
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 25

i
Der Bezugspunkt für das Sensorrohsignal von Kanal 1 ist die Steckleisten-
klemme b22: GND und für das Sensorrohsignal von Kanal 2 die Klemme b24:
GND.

Achten Sie bei Arbeiten an dem Monitor auf ausreichenden Schutz vor
STOP elektrostatischen Entladungen. Tragen Sie z.B., um elektrostatische
Entladungen über die Monitorelektronik zu verhindern, ein ESD−Armband.

1. Lösen Sie mit einem Kreuzschraubendreher die vier, im folgenden Bild mit den Pfeilen
gekennzeichneten Kreuzschrauben.

2. Ziehen Sie das Kontrollerboard vorsichtig, ohne zu verkanten von dem Mainboard ab. Die
Position der Jumper J2 auf dem Mainboard sind im folgenden Bild mit einem weißen
Rahmen gekennzeichnet.

3. Um das Sensorrohsignal auf die Klemmen z14 und z16 zu schalten, stecken Sie die Jumper
wie in b) dargestellt. Sind die Jumper wie in a) gesetzt, liegt an den Klemmen z14 und z16
ein nicht verwertbares Signal.
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 26

SENS1 AC1 SENS1 AC1

z14: z14:
J2 J2
z16: z16:

SENS2 AC2 SENS2 AC2


a) b)

4. Stecken Sie das Kontrollerboard wieder auf das Mainboard und sichern Sie es mit den vier
Schrauben. Das Sensorrohsignal liegt nun auf der Steckleiste.
Monitor−Einbau
1. Überprüfen Sie vor Einbau des Monitors die Steckplatzverdrahtung.
2. Schieben Sie den A6125 Monitor in den vorbereiteten Steckplatz und drücken Sie ihn mit
leichtem Druck in den Steckverbinder.
3. Zur Sicherung des Monitors ziehen Sie die beiden Befestigungsschrauben auf der Front-
platte leicht handfest an.
Alle weiteren Informationen, wie z. B. Schirmung und Erdung, Konfiguration des Monitors, usw.,
finden Sie in der Gebrauchsanleitung “Lagerschwingungsmonitor A6125”, Bestellnr.
6100−90069.

2.6 Technische Daten


Nur Angaben mit Toleranzen sind verbindliche Daten. Daten ohne Toleranzen bzw. ohne
Fehlergrenzen sind informative Daten. Technische Änderungen, vor allem der Software, bleiben
vorbehalten.

Alle folgenden Angaben gelten, sofern nicht anders angeben, für Kanal 1 und Kanal 2
gleichermaßen.

2.6.1 Signalkonditionierung

Zwei separate Signaleingänge für Kanal 1 und Kanal 2 mit voneinander entkoppelter Signal-
konditionierung.

Messwerteingänge

Differenzspannungsverstärkereingänge, rückwirkungsfrei, leerlauf− und kurzschlussfest.

Kanal 1 z8: SENS1H (+); z10: SENS1L (− Signal)

Kanal 2 d8: SENS2H (+); d10: SENS2L (− Signal)

Eingangsnennbereich 0 ... +20 V

Grenzbereich ±30 V DC

Signalspannungsbereich 4,0 Vss

Eingangswiderstand > 100 kΩ


Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 27

Signalkonditionierung

Sensorsignalausgänge Frontbuchsen SMB und/oder z14 / z16* entkoppelt,


leerlauf− und kurzschlussfest, rückwirkungsfrei

Kanal 1 − SENS 1 SMB K1

Kanal 2 − SENS 2 SMB K2

Signalausgang ±10 V; Signal 1:1 zum Sensoreingangssignal


(ohne Bias−Spannung)

Genauigkeit ±1 % vom Endwert

Frequenzbereich 0,12 ... 8 kHz (−3 dB) ±20 %

Zul. Belastungswiderstand >100 kΩ

Innenwiderstand 1 kΩ

*Abhängig von der Jumperstellung J2.

Dynamische Ausgänge

Die Ausgänge sind physikalisch vorhanden liefern jedoch kein verwendbares dynamisches
Signal.
Mit den Jumpern J2 kann das Sensorrohsignal (phasenrichtiges Sensorsignal), das an den
SMB−Buchsen auf der Frontplatte anliegt auf diese Klemmen umgeschaltet werden.

Kanal 1 / Kanal 2 z14 / z16* leerlauf− und kurzschlussfest, rück-


wirkungsfrei

*Abhängig von der Jumperstellung J2.

Signalkonditionierung für Kenngröße

Die Eingangssignale werden vor der Digitalisierung konditioniert durch Anpassverstärker,


bereichsabhängigem Verstärker, Hochpass und Tiefpass.

Bereichseinstellung wird bei der Konfiguration bestimmt

maximaler Messbereich 4,0 V ss

Frequenzbereich Hardwarefilter

Hochpass 2 pol. Butterworth−Charakteristik

− parametrierbar fu 2 Hz (−3 dB) für Arbeitsfrequenz 5 Hz


fu 4 Hz (−3 dB) für Arbeitsfrequenz 10 Hz

− Toleranz ±20 %

Tiefpass 5 pol. Butterworth−Charakteristik


Parametrierbereich 50 Hz ... 8000 Hz

Kenngrößenbildung abhängig von der Konfiguration


Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 28

Digitales Filter MMS 6125/00

Filtereinstellung mittels Konfiguration

Betriebsart Bewertung Dig. Filter High Dig. Filter Med Dig. Filter Low

Beschleunigung Beschleunigung 30 ... 8000 Hz 10 ... 2000 Hz 6 ... 1000 Hz

Geschwindigkeit −−−−−−−−

Geschwindigkeit Geschwindigkeit 10 ... 2000 Hz 6 ... 1500 Hz 2 ... 250 Hz

Amplitude

Stromausgänge−Kenngröße

Die Kenngrößenbildung und Bewertung ist abhängig von den bei der Konfiguration
bestimmten Funktionen.
Stromausgang 1 − I1+ / I1− z18 / b18 (0 V / common)
Stromausgang 2 − I2+ / I2− z20 / b20 (0 V / common)
Nennbereich 0 ... 20 mA oder 4 ... 20 mA, abhängig von der
Konfiguration
− Life zero−Betrieb im 4 ... 20 mA Betrieb kann mittels der Konfiguration
bestimmt werden, dass der Ausgang bei Erkennung
einer Störung auf 0 mA gesetzt wird.
Genauigkeit / Auflösung ±1 % vom Messbereichsendwert / 16 Bit
Zul. Belastungswiderstand 500 Ω

Spannungausgänge EO1 / EO2

d14 / d16
Spannungsausgänge 0 ... 10 V proportional der Lagerschwingung, Messbereich und Be-
wertung entsprechend der Kenngrößen Kanal 1 (EO 1) und Kanal 2 (EO 2).
leerlauf− und kurzschlussfest, rückwirkungsfrei.

Nennbereich 0 ... +10 V DC

Auflösung 8 Bit

Zul. Belastungswiderstand > 10 kΩ

Innenwiderstand ca. 50 Ω

Signaleingänge EI1 / EI2

Eingänge für Kenngrößenspannung 0 ... +10 V zur Verknüpfung mit EO−Ausgängen.


(für Modul MMS 6125 nicht vorgesehen)

Spannungseingang EI1 / EI2 b14 / b16

Nennspannungsbereich 0 ... +10 V DC

Auflösung 10 Bit

Eingangswiderstand >100 kΩ
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 29

Signaleingang KEY

Der Key−Impuls wird als Drehpositionsreferenz bei der Ordnungsanalyse benötigt.

Signaleingang KEY (N) d22

Signalpegel 24 V Logik,: LOW = 0 ... 3 V; HIGH = 13 ... 48 V

Eingangswiderstand >10 kΩ

2.6.2 Kanalüberwachung

Überwachungsfunktion

ständige Überwachung

der Messkreise (Sensoren) Durch Überwachung der Eingangsspannungspegel


auf Kurzschluss und Leitungsbruch

Systemspannungen Spannung − OK

μP Funktion (watchdog) WD − OK

Konfiguration & Parametrierung K&P − OK

externes Sperrsignal ES

Status Kanalüberwachung

Kanalstatus = kein Fehler (OK) wenn ( Spannung_OK = Ja )


UND (WD_OK = Ja)
UND (K&P_OK = Ja)
UND (Sensorsignal im GUT−Bereich)

Kanalstatus = Fehler falls die vorherige Bedingung nicht erfüllt ist

Kanalstatus = Freigabe verzögert bei Umschaltung vom Fehlerfall in den OK−Status


oder beim Einschalten des Moduls wird eine
Freigabeverzögerung von 15 s (±2 s) aktiv

Interne Wirkung Im Fehlerfall oder während der Freigabeverzögerung


wirkt die Kanalüberwachung auf die Kenngröße und
die Grenzwertbildung, im Fehlerfall nur, wenn die
Unterdrückung in der Konfiguration aktiviert worden
ist.

Visualisierung

Grüne LED auf der Frontplatte

Kanalstatus = kein Fehler (OK) Dauerlicht

Kanalstatus = Fehler Dunkel

Kanalstatus = Freigabe verzögert Blinklicht (siehe Abschnitt 4.5.5)


Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 30

Ausgänge Channel Clear

Opto−entkoppelte Kollektor / Emitter−Strecken

Channel Clear Kanal 1, C1C / C1E z26 (Kollektor) / z28 (Emitter)

Channel Clear Kanal 2, C2C / C2E z30 (Kollektor) / z32 (Emitter)

Ext. gesperrt oder Status = Fehler C−E gesperrt, max. zul. Spannung: 48 V
oder Freigabe verzögert

nicht ext. gesperrt und Status = OK C−E leitend, max. zul. Strom: 100 mA
und nicht Freigabe verzögert

Eingang extern Sperren ES

z22 − zum Sperren der Grenzwertalarme; z. B. bei Wartungsarbeiten etc.

Funktion Sperren Eingang LOW = Sperren der Kanalüberwachung und


Grenzwertbildung

Freigabe Eingang HIGH oder unbeschaltet = kein Sperren der


Kanalüberwachung und Grenzwertbildung

Signalpegel LOW: 0 ... +3 V, HIGH: +13 ... +48 V

2.6.3 Grenzwertbildung und Alarme

Zwei Alarmkanäle mit je einem Alarmausgang ALERT und DANGER und separater
Grenzwerteinstellung. Alarmierung, wenn die Kenngröße den parametrierten Grenzwert
überschreitet. (Istwert > Grenzwert)

Grenzwerteinstellung

Durch Parametrierung, abhängig von der Konfiguration für Messbetrieb, Kenngrößenbildung,


Bereich etc.

Einstellbedingung Grenzwert ALERT < Grenzwert DANGER

Einstellbereich 0 ... 100 % des parametrierten Messbereiches

Auflösung und Reproduzierbarkeit 1 % bezogen auf den Messbereichsendwert

Hysterese Konfigurierbar, 0 ... 20 % bezogen auf den


Messbereichsendwert
Die Hysterese ist nur bei sinkendem Istwert wirksam.

Ansprechverzögerung

konfigurierbar auf 0 (aus),1,2,3,4,5 sek.; wirksam auf die Alarmausgänge.


Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 31

Alarmblockierung

Blockierung wenn (K&P aktiv = ja) ODER


(Spannung oder watchdog nicht ok) ODER
(Ext. Sperren = sperren) ODER
(Kanalstatus = Fehler und Grenzwert−
unterdrückung = an*) ODER
(Kanalstatus = Freigabe verzögert) UND
Kanalüberwachungseinwirkung = Ja
Keine Blockierung Wenn obige Bedingung nicht erfüllt ist
* In der Konfiguration wird festgelegt, ob die Blockierung der Alarmausgänge durch die Kanal-
überwachung erfolgen soll.

Alarmvisualisierung

Durch je ein rotes LED für Kanal 1 und 2


Keine Grenzwertüberschreitung oder LED Aus
Alarme blockiert
Voralarm (ALERT), kein Hauptalarm LED blinkt mit 2 Hz (Puls/Pause 1:1)
Hauptalarm LED hat Dauerlicht

Alarmausgänge

Opto−entkoppelte Kollektor / Emitter−Strecken


Voralarm Kanal 1 A1−C / A1−E b26 (Kollektor) / b28 (Emitter)
Hauptalarm Kanal 1 D1−C / D1−E d26 (Kollektor) / d28 (Emitter)
Voralarm Kanal 2 A2−C / A2−E b30 (Kollektor) / b32 (Emitter)
Hauptalarm Kanal 2 D2−C / D2−E d30 (Kollektor) / d32 (Emitter)
Maximalwerte für Alarmausgänge C−E gesperrt: max. zuläss. UCE: 48 V
C−E leitend: max. zuläss. ICE: 100 mA
Alarmzustand der Alarmausgänge leitend im Arbeitsstrombetrieb, gesperrt im Ruhe-
strombetrieb

Arbeitsstrom− / Ruhestrombetrieb

Durch externe Verdrehung der Digitaleingänge SC−A und SC−D wählbar.


Umschaltung ALERT d24 − SC−A = HIGH / unbeschaltet
= Arbeitsstrom
d24 − SC−A = LOW = Ruhestrombetrieb
Umschaltung DANGER z24 − SC−D = HIGH / unbeschaltet
= Arbeitsstrom
z24 − SC−D = LOW = Ruhestrombetrieb
Schaltpegel LOW = 0 ... +3 V
HIGH = 13 ... 48 V
Eingangswiderstand > 10 kΩ
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 32

2.6.4 Kommunikationsschnittstellen
Schnittstelle RS 232

Frontbuchse zum Anschluss eines Laptops / Rechners zwecks Konfiguration und


Visualisierung
Rundsteckverbinder auf Frontseite Mini−DIN−Buchse Typ TM 0508A/6 für Parametrier-
kabel (im Operating Kit enthalten)

Schnittstelle RS 485

d4, z4 Busschnittstelle für Kommunikation mit z. B. einem epro−Analyse− und Diagnose−


system MMS 68xx und der Konfigurationssoftware.

2.6.5 Spannungsversorgung

Die Monitorsystemspannungen und somit auch die 0 V / common−Anschlüsse für die Mess−
und Überwachungsein− und −ausgänge sind voneinander galvanisch getrennt.
Versorgungsspannungseingänge zwei redundante, diodenentkoppelte Eingänge für
nominal +24 V mit gemeinsamen 0 V Bezug
Spannungseingang UB+ / UN+ d2 / z2
Gemeinsamer Bezug, 0 V U− b2
Zul. Spannungsbereich 19 ... 31,2 Vdc (IEC 654−2 Klasse DC 4)
CSA: 24Vdc; SELV LPS
Leistungsaufnahme max. 6 W, bei 24 V max. 250 mA

Monitorsystemspannung

Die für die interne Versorgung benötigten Monitor−Systemspannungen werden ständig auf
Unterspannung überwacht. Bei Erkennung einer Unterspannung wird eine Fehlermeldung
generiert.

Sensorspeisung

Für beide Kanäle des Monitors, als Speisestrom für Ladungsverstärker.

Trennung entkoppelt und zu den übrigen Systemspannungen


und zur Versorgungsspannung galvanisch getrennt,
mit anderen Monitoren parallel rückwirkungsfrei
betreibbar,
leerlauf− und kurzschlussfest.

Sensorspeisung Kanal 1 SENS1− /SENS1+ b6/z6

Sensorspeisung Kanal 2 SENS2− / SENS2+ b8/d6

Stromeinstellung 2 ... 8 mA, einstellbar mittels Konfiguration in 40 μA


Schritten

Toleranz ±0,5 % vom Endwert, +0,5 % vom Einstellwert


max. Bürde 3,4 kΩ bei 8 mA,
13,6 kΩ bei 2 mA
leerlauf− und kurzschlussfest
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 33

2.6.6 Umgebungsbedingungen

Anwendungsklasse KTF nach DIN 40040

Umgebungstemperatur

Bezugstemperatur +25°C

Nenngebrauchsbereich 0 ... +45°C (CSA Anforderung und empfohlener Bereich)


max. Bereich −10°C ... +65°C (nicht CSA konform)

Lagerungs−, Transporttemperatur −30 ... +85°C

Betriebshöhe bis zu 2000m über NN

Relative Feuchte ≤ 95 % ohne Betauung

Schwingung nach IEC−68 − 2 Teil 6

Weg 0,15 mm bei 10 ... 55 Hz

Beschleunigung 19,6 mm/s2 bei 55 ... 150 Hz

Schock nach IEC−68 − 2 Teil 29


Beschleunigungsspitzenwert 98 m/s2
Nominelle Schockdauer 16 ms

Gehäuseschutzart IP 00, offene Bauweise nach DIN 40050

EMV−Festigkeit nach EN 50 081−1 / EN 50 082−2 erfüllt

Zulässiger Verschutzungsgrad Kategorie 2 (nach IEC 61010−1)

Betriebsumgebung Gebrauch ausschließlich in geschlossenen Räumen

2.6.7 Mechanischer Aufbau

Leiterplatte Euro−Format (100 mm x 160 mm) nach DIN 41494

Breite 6 TE (ca. 30 mm)

Steckverbinder DIN 41612, Bauform F 48 M

Frontelemente

2 LEDs Grün Channel Clear Kanal 1 / 2

2 LEDs Rot Alarme Kanal 1 / 2

2 SMB Steckbuchse für Sensorsignal Kanal 1 / 2

1 Mini−DIN Rundsteckbuchse für RS 232 zum Anschluss eines Laptops / Rechners


(zwecks Konfiguration und Parametrierung)

Gewicht ca. 320 g (ohne Verpackung)


ca. 450 g mit Standardverpackung
Product Information / Produktinformation A6125
Connection Diagrams and Figures / Anschlusspläne und Abbildungen Page/Seite 34

3 CONNECTION DIAGRAMS AND FIGURES /


ANSCHLUSSPLÄNE UND ABBILDUNGEN

Block diagram / Blockschaltbild A6125


Product Information / Produktinformation A6125
Connection Diagrams and Figures / Anschlusspläne und Abbildungen Page/Seite 35

Signal ground

PE
protective earth

Protective earth
Cabinet

to
LiYCY−CY

LiYCY−CY
cable

cable
Field

connection

connection
Harting

Harting

e.g. 3 m cable
e.g. 3 m cable
B

A
piezoelectric

piezoelectric
sensor

sensor

Connection diagram piezoelectric sensor /


Anschlussdiagramm piezoelektrischer Sensor
Field Cabinet
capacitive
sensor

Anschlussdiagramm kapazitiver Sensor


Connection diagram capacitive sensor /
Harting
connection

Signal

GND

+4 mA

cable
PR 9264 e.g. 4 m cablel LiYCY−CY
Product Information / Produktinformation A6125

to
protective earth

capacitive
sensor
Harting
connection

Signal

GND

+4 mA

cable
Connection Diagrams and Figures / Anschlusspläne und Abbildungen

PR 9264 e.g. 4 m cable LiYCY−CY

Signal ground
Protective earth

PE
Page/Seite 36
Product Information / Produktinformation A6125
Connection Diagrams and Figures / Anschlusspläne und Abbildungen Page/Seite 37

d b z d b

2 2 UB+ Supply + 24V U− 0V Common Supply UN+ Redu.Supply +24V

4 4 A RS 485 Interface Common B RS 485 Interface

6 6 SENS2+ Supply+ Sens 2 SENS1−Supply− Sens 1 SENS1+ Supply+ Sens1

8 8 SENS2−H Input Hi Sens2 SENS2−Supply− Sens 2 SENS1−H Input Hi Sens1

10 10 SENS2−L Input Lo Sens2 SENS−C Screen / Common SENS1−L Input Lo Sens1

12 12 NGL2 don’t use GND Common NGL1 don’t use

14 14 EO1 0...+10V outp Ch1 EI1 0...+10V inp Ch1 AC1/raw−signal 1*

16 16 EO2 0...+10V outp Ch2 EL2 0...+10V inp Ch2 AC2/raw−signal 1*

18 18 FX Limitmultipl. X I1− Iout1−/ Common I1+ Iout 0/4..20mA Ch1

20 20 F2 don’t use I2− Iout2−/ Common I2+ Iout 0/4..20mA Ch2

22 22 KEY (N) Key pulse input GND Common ES Alarm Stop

24 24 SC−A Current Mode Alert GND Common SC−D Current Mode Danger

26 26 D1−C Danger1 out Col A1−C Alert1 out Col C1−C Chan Clear1 out Col

28 28 D1−E Danger1 out Emit A1−E Alert1 out Emit C1−E Chan Clear1 out Em

30 30 D2−C Danger2 out Col A2−C Alert2 out Col C2−C Chan Clear2 out Col

32 32 D2−E Danger2 out Emit A2−E Alert2 out Emit C2−E Chan Clear2 out Em

*Only if Jumper J2 is closed. / Nur wenn Jumper J2 gesetzt ist.

Pin allocation / Steckerbelegung


Product Information / Produktinformation A6125
Connection Diagrams and Figures / Anschlusspläne und Abbildungen Page/Seite 38

100 27

173.5
160

2.5
2.5

17

Alle Abmessungen in mm
All dimensions in mm
6 TE
30.1

128.4
3 HE

Dimensions A6125
Abmessungen A6125
Product Information / Produktinformation A6125
PI Revision List Page/Seite 39

4 PI REVISION LIST

Version Date Changes Chapter

1.000 02.04.2011 Initial Version (PI MMS6125 Rev: 14.05.2009)

1.010 11.05.2011 Additional Information (CSA relevant) all

1.020 16.05.2011 Rename as A6125 all

1.030 16.05.2011 change of front cover design

1.031 23.05.2011 change of front cover subtitle

1.032 25.02.2013 Change of service address Europa


EG-Konformitätserklärung
EC-Declaration of Conformity

Wir (We): epro GmbH, Jöbkesweg 3, 48599 Gronau

erklären in alleiniger Verantwortung, dass das Produkt:


declare under the exclusive liability that the product:

Produktbezeichnung (Product designation): System A6000


Produktbeschreibung (Product description): Modul zur Auswertung von dynamischen und
statischen Messwerten.
Module for evaluation of dynamic and static
measuring values
Artikelnummer (Product codes): 9199−00XXX
CEKennzeichnung entsprechend der EU− Richtlinie/ CE identification corresponds to EU directive:
98/336 / EWG (EMV) geändert/ modified 97/236 ; EWG 92/31 / EWG; 93/68 / EWG.
auf das sich diese Erklärung bezieht, mit der/den folgenden Norm(en) oder normativen Doku-
menten übereinstimmt:
which is subject of this declaration, is in conformity with the following standards or normative
documents:
Bestimmungen der Richtlinie Titel und/oder Nr.

Terms of the directive Title and/or no.


Fachgrundnorm Störaussendung, Industriebereich DIN EN 55011 + A1 + A2
Engineering standard interference emission, industrial
DIN EN 61326 + A1 + A2 + A3
applications
einschliesslich / including:
DIN EN 61000−4−2 + A1 + A2
Fachgrundnorm Störfestigkeit, Industriebereich DIN EN 61000−4−3 + A1
Engineering standard interference immunity, industrial DIN EN 61000−4−4
applications DIN EN 61000−4−5 + A1
DIN EN 61000−4−6 + A1
Wir weisen darauf hin, dass
die Konformität und damit die Betriebserlaubnis erlischt, wenn dieses Erzeugnis ohne unsere
ausdrückliche Genehmigung geändert wird.
Nicht−Fachleute die Gegebenheiten des Einsatzgebietes und die daraus resultierenden
Anforderungen vor der Inbetriebnahme prüfen lassen sollen.
We point out that
the conformity and thus the approval for the operation lapses, if the product is modified without our
explicit permission (without consultation with us).
Non specialists should let check the conditions of the operational area and the requirements
resulting thereof before installation.

Gronau, 04.05.2011
Ort und Datum Geschäftsbereichsleiter Leiter Qualitätsmanagement
Place and date Divisional director Head of quality management

Certif_MMS_06_Rev_02