CSI 6500 Machinery Health™Monitor: A6125, Dual Channel Bearing Vibration Monitor
CSI 6500 Machinery Health™Monitor: A6125, Dual Channel Bearing Vibration Monitor
CSI 6500 Machinery Health™Monitor: A6125, Dual Channel Bearing Vibration Monitor
MHM-97444
NC: 6540-90069
Rev.: 1.032
If this symbol is printed on a device, according to IEC 61010 it means that the
documentation of the device must be completely read and understood before
If this symbol is printed on a device, according to IEC 61010 it means that this
device must be operated with DC voltage.
i
This symbol identifies text that contains important information.
!
Not following instructions identified with this symbol can result in functional
issues and incorrect measurements without damaging the machine.
D
Symbolerklärung
Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010
aus, das es zur Installation und Inbetriebnahme des Gerätes zwingend
!
erforderlich ist, die Dokumentation des Gerätes vollständig gelesen und
verstanden zu haben. Sicherheitsrelevante Hinweise in dieser
Dokumentation sind unweigerlich zu beachten und im weiteren Verlauf dieser
Dokumentation durch das “STOP” Symbol (siehe unten) gekennzeichnet.
Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010
aus, dass es mit Gleichspannung betrieben wird.
!
Hinweise, die bei Nichtbeachtung zu Funktionsstörungen und
Fehlmessungen führen, ohne das Gerät zu beschädigen, sind mit diesem
Symbol gekennzeichnet.
i
Slowakia The additional PCB (controller board)
Tel: +421/32/7700 538 is calibrated with the main board and
Fax: +421/32/7700 884 must not be replaced.
Listen to the options for receiving an RMA. You Out of warranty? Need to get under
will be routed to support personnel who will support? Get a customized quote for
document your concern and give you an RMA bringing all your CSI technologies under a
number if you are under support or warranty. If support agreement:
your hardware is not under support or warranty, Phone: 865.675.2400*, ext. 2130
you must have a Purchase Order for the amount Fax: 865.218.1478*
of the repair service before you can receive an Email:
RMA number. Pricing for your repair can be mhm.supportagreement@emersonproces
obtained from support personnel or by calling s.com
your local sales representative. Once you have
your purchase order, call 865.675.4274* for an
*Customers outside the Americas and
RMA.
Canada: please refer to the list of service
2. Once you have received your RMA, send your centers and contact the service center near
hardware to the appropriate product service you.
center. Your hardware package should include:
All rights are strictly reserved
G RMA Number (plus Purchase Order if
Reproduction or divulgation in any form
applicable)
whatsoever is not permitted without written
authority from the copyright owner.
RMA Required Information
Company Name:
Contact Phone:
Contact Fax:
Contact Email:
Yes No
GB
1 Bearing Vibration Monitor . . . . . . . . . . . . . . . . . . . . . . 8
1.1 Scope of Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 CSA Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 CSA − Conditions of acceptability . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Advice for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Installation and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6.1 Signal conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.6.2 Channel monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.6.3 Limit value formation and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.6.4 Communication interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.6.5 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.6.6 Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.6.7 Mechanical structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
D
2 Lagerschwingungsmonitor . . . . . . . . . . . . . . . . . . . . . 21
2.1 Lieferumfang . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2 CSA Zertifizierung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.3 CSA − Akzeptanzkriterien . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.4 Hinweis zur Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.5 Installation und Montage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.6 Technische Daten . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.6.1 Signalkonditionierung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.6.2 Kanalüberwachung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.6.3 Grenzwertbildung und Alarme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.6.4 Kommunikationsschnittstellen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.6.5 Spannungsversorgung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.6.6 Umgebungsbedingungen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.6.7 Mechanischer Aufbau . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4 PI Revision List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 8
GB
1 BEARING VIBRATION MONITOR
The two−channel Bearing Vibration Monitor for piezoelectric sensors A6125 is part of the A6000
machine monitoring system. The micro−processor controlled monitor is used in conjunction with
two piezoelectric sensors or capacitive sensors (e. g.: epro PR 9264) to measure and monitor
the absolute bearing vibrations at all kind of turbines, compressors, fans and gear boxes, etc.
The monitor A6125 permit the use of piezoelectric sensors, which provide signals proportional
to the vibration acceleration or vibration velocity.
The two channels of the monitor operate independently from each other. Each channel may be
configured for one of the following signal processing:
• Vibration acceleration
• Vibration velocity
The characteristic values can be output via a 0/4...20mA current output per channel.
i
the configuration software CD as pdf−data file. Amongst others, it contains
useful informations for configuration and use of the A6125.
To ensure the safe operation of the monitor and to permit setting of all
functions, it is indispensable to use only the latest version of configuration
software (version 2.08 or newer) and operating manual.
The use of old operating manuals or configuration programs out of date may
lead to malfunctions or limitations of the measuring functions.
If the contents are incomplete or if is there any damage, so directly complain at the bearer. The
competent epro−sales agency must be also informed, to enable repair or replacement for the
monitor. Repair or calibration of this instrument may only be done at epro.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 9
For valid CSA certification, all devices (IMR 6000/xx and A6000 modules)
must be marked with the respective CSA lable.
STOP If no CSA lable is available on the respective device, this device is not CSA
certified!
Adequate ventilation space has to be provided so that heat does not build up. The ventilation
space must be at least 1 RU (13/4 inch) in all directions. If the ambient temperature of the rack
rises above 45 °C, cool this instrument with a forced air fan, cooler, or similar.
When mounting several IMR units above each other in one cabinet, install cooling fan racks in
between instead of the ventilation space. The necessary specifications for cooling fan racks
result from the environmental and sitting criterions of the cabinet and thus cannot be defined
generally.
d b z
2 UN+ (+ 24V) U− (0V/Common) UB+ (+24V, redundant) 2
4 A (RS 485) GND (BP, Common, RS 485) B (RS 485) 4
6 Supply2+ (sensor) Supply1− (sensor) Supply1+ (sensor) 6
8 AIN2− (Input) Supply2− (sensor) AIN1− (Input) 8
10 AIN2+ (Input) GND AIN1+ (Input) 10
12 NGL2 (scaled dc−output) GND NGL1 (scaled dc−output) 12
14 EO1 (voltage output1) EI1 (voltage input1) AC1 (sensor raw signal1) 14
16 EO2 (voltage output2) EI2 (voltage input2) AC2 (sensor raw signal2) 16
18 GWM (limit value) I1− (current output common) I1+ (current output CH1) 18
20 NC I2− (current output common) I2+ (current output CH2) 20
22 KEY−N (key signal input) GND ES (external lock) 22
24 SC−A (oper. principle alert) GND SC−D (oper. principle danger) 24
26 D1−C (danger1 collector) A1−C (alert1 collector) CC1−C (ch. clear1 collector) 26
28 D1−E (danger1 emitter) A1−E (alert1 emitter) CC1−E (ch. clear1 emitter) 28
30 D2−C (danger2 collector) A2−C (alert2 collector) CC2−C (ch. clear2 collector) 30
32 D2−E (danger2 emitter) A2−E (alert2 emitter) CC2−E (ch. clear2 emitter) 32
Jumper RS 485
RS 485 bus operation requires an electrical terminator on the first and last bus device.
This is done with plug−in jumpers, that are on the controller board. The figure shows the position
of the jumpers.
To activate the bus terminator and to place lines “A” and “B” on the references, plug the jumpers
as shown in Fig. b). Fig. a) shows the jumper position for deactivated bus termination and open
references (delivery status).
• Plug−in jumper 1−2 closed: Bus line “B” via pull−down resistor on ground
• Plug−in jumper 3−4 closed: 120 Ω Resistor between “A” and “B”
• Plug−in jumper 5−6 closed: Bus line “A” via pull−up resistor on +5 V
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 11
2 4 6 2 4 6
1 3 5 1 3 5
a) b)
i
For trouble−free operation of the RS 485 bus, the lines “A” and “B” in one
monitor must be connected on their references (+5 V, ground), this is only
possible if the bus terminator jumper is also set in this monitor.
Sensor raw−signal
The raw sensor signal (in−phase output signal of the converter without Bias−voltage) applied
to the front panel SMB sockets, can be switched over with the J2 jumpers on terminals z14:
channel 1 and z16: channel 2 of the connection strip. The controller board must be removed in
order to switch the signal on the connection strip. The following points describe the procedure:
i
The reference point for the raw sensor signal from channel 1 is the connection
strip terminal b22: GND, and for the raw sensor from channel 2 the terminal
b24: GND.
When working at the monitor, ensure that there is adequate protection against
STOP electrostatic discharge. For examle, wear an ESD bracelet to prevent
electrostatic discharge via the monitor electronics.
3. Use a cross−head screwdriver to remove the four cross−headed screws, identified with the
arrows, in the following figure.
4. Carefully pull the controller board off the main board without tilting it. The position of the J2
jumpers on the main bard is identified with a white frame in the following figure.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 12
5. To switch the raw sensor signal to terminals z14 and z16 place the jumpers as shown in b).
If the jumpers are set as shown in a) then the dynamic portion of the sensor signal is applied
on terminals z14 and z16.
z14: z14:
J2 J2
z16: z16:
6. Place the controller board back on the main board and secure it with the four screws. Now,
the raw sensor signal is on the connection strip.
Installation
2. Push the A6125 monitor into the prepared slot and press it with light pressure into the plug
connector.
3. Hand tighten the two anchoring screws on the front panel to secure the monitor.
Any other information, e. g. shielding and grounding, configuration of the monitor, etc., can be
found in the direction for use “Bearing Vibration Monitor A6125”, order number: 6110−90069.
All of the following information applies uniformly for channel 1 and channel 2, if not otherwise
specified.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 13
Two separate signal inputs for channel 1 and channel 2 with uncoupled signal conditioning.
Signal conditioning
Sensor signal outputs Front sockets SMB and/or z14 / z16*, decoupled,
open circuit and short circuit proof, non reactive.
Precision ±1 % of f.s.d.
Internal resistance 1 kΩ
Dynamic outputs
The outputs are physically present however they do not supply a usable dynamic signal.
With the J2 jumpers the raw sensor signal (in−phase sensor signal) that is applied to the SMB
sockets on the front panel can be switched over to these terminals.
Channel 1 / channel 2 z14 / z16* open circuit and short circuit proof, non
reactive
The input signals are conditioned by adjusting amplifier, range−dependent amplifier, high
pass, and low pass prior to digitalization.
Frequency range
− Tolerance ±20 %
Digital filter
Operating Evaluation Dig. Filter High Dig. Filter Med Dig. Filter Low
mode
Velocity −−−−−−−−
Amplitude
Characteristic value formation and evaluation depends on the functions specified in the
configuration.
−Life zero operation in 4 ... 20 mA operation you can specify via the
configuration that the output is set to 0 mA if a fault is
detected.
Signal outputs EO 1 / EO 2
d14 / d16
Voltage outputs 0...10V proportional to the bearing vibration, measuring range and signal
evaluation according to the characteristical variables channel 1 (EO 1) andchannel 2 (EO 2).
Open circuit and short circuit proof, non reactive.
Resolution 8−bit
Inputs for single−channel measurement values 0 ... +10 V for connection with EO outputs
(not relevant for MMS 6125).
Resolution 10−bit
The key pulse is required for internal RPM determination for checking the measurements in
the measured value analysis.
Supervision function
permanent supervision
of the measuring chains (sensors) by supervising the input signal levels on short−circuit
and cable breaks
μP function (watchdog) WD − OK
Channel status = enable delayed an enable delay of 15 s (±2 s) will get active in the
moment of switching from the error to the OK status or
after power on of the monitor.
Visualization
Not ext. disabled and status = OK and C−E conducting, max. perm. current: 100 mA
not release delayed
z22 − for disabling the limit value alarms; e.g. for service work etc.
Disable function Input LOW = disable the channel monitoring and limit
value formation
Two alarm channels, each with an alarm output ALERT and DANGER, and separate limit value
adjustment. Alarming if the characteristic value exceeds the limit value parameters. (Actual
value > limit value)
Alarm delay
Alarm blocking
* In the configuration it is specified whether the alarm outputs will be blocked through channel
monitoring.
Alarm visualization
Alarm outputs
Maximum value for alarm outputs C−E disabled: max. perm. UCE: 48 V
C−E conductive: max. perm. UCE: 100 mA
Alarm status of the alarm outputs Conducting in open circuit mode, disabled in closed−
circuit mode
The digital inputs SC−A and SC−D can be selected with external signals.
Interface RS 232
Front socket for connecting a laptop / computer for configuration and visualization purposes
Round plug connector on the front Mini DIN socket type TM 0508A/6 for parameterization
side cable (included in the operating kit)
Interface RS 485
d4, z4 bus interface for communication with an MMS 68xx epro analysis and diagnostic
system and the configuration software.
Product Information / Produktinformation A6125
Bearing Vibration Monitor Page 19
The monitor system voltages, and thus the 0 V / common connections for the measurement
and monitoring inputs and outputs, are galvanically separated.
Supply voltage inputs Two redundant, diode decoupled inputs for nominal
+24 V with common 0 V reference
Common reference 0 V U− b2
The system voltages required for the internal supply are constantly monitored on overvoltage.
If undervoltage is detected an error message is generated.
Sensor supply
Ambient temperature
Nominal use range 0 ... +45°C (CSA requirement and recommended range)
max. range −10°C ... +65°C (not CSA conform)
Enclosure protection class IP 00, open design in accordance with DIN 40050
Front element
1 mini DIN round socket connector RS 232 for connecting a laptop / computer
(for configuration and visualization purposes)
D
2 LAGERSCHWINGUNGSMONITOR
Der zweikanalige Lagerschwingungsmonitor für piezoelektrische Sensoren A6125 ist eine
Baugruppe des A6000 Maschinenüberwachungssystems. Der mikrocontrollergesteuerte
Monitor dient in Verbindung mit zwei piezoelektrischen Sensoren (Sensorelement: PZT
Keramik) oder kapazitiven Sensoren der epro−Typenreihe PR 9264 der Messung und
Überwachung von absoluten Lagerschwingungen an Turbinen aller Art, Kompressoren, Lüftern,
Getrieben usw.
Der Monitor A6125 erlaubt den Einsatz von piezoelektrischen Aufnehmern, die ein beschleuni-
gungs− oder geschwindigkeitsproportionales Signal liefern.
Die beiden Kanäle des Monitors arbeiten unabhängig voneinander. Mittels Konfiguration
können für den Monitor folgende Betriebsarten eingestellt werden:
• Schwingbeschleunigung
• Schwinggeschwindigkeit
Die Kenngrößen können je Kanal über einen Stromausgang 0/4 ... 20 mA ausgegeben werden.
2.1 Lieferumfang
Folgende Teile gehören zum Lieferumfang und müssen in der Sendung enthalten sein:
• Lagerschwingungsmonitor A6125
• diese Produktinformation
Sollte der Inhalt unvollständig sein oder irgend welche Defekte vorliegen, so muss beim
Überbringer sofort reklamiert werden. Außerdem muss die zuständige epro Verkaufsstelle ver-
ständigt werden, um Reparatur oder Ersatz des Gerätes zu ermöglichen. Eventuell erforderliche
Reparaturen oder Kalibrierung von A6000 Monitoren sind nur im epro−Werk möglich.
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 22
Zur gültigen CSA Zertifizierung müssen alle Geräte (IMR 6000/xx und A6000)
mit einem entsprechenden CSA Label versehen worden sein.
STOP Für den Fall das kein CSA Lable auf dem Gerät angebracht wurde ist dieses
Gerät nicht CSA zugelassen!
Das IMR− System ist bewertet für einen Umgebungstemperaturbereich von 0°C bis 45°C.
Gemäß der IEC 61010 Richtlinie müssen fest installierte Systeme mit einer
Trenneinrichtung (ggf. einem Schalter und/ oder einem Leitungsschutz−
schalter nach IEC60947−1 und IEC60947−3) zum unterbrechen der
Spannungsversorgung ausgestattet sein. Bei Verwendung eines IMR
Systems kann dies, unter Beachtung dieser Richtlinie, durch einen Schalter
oder Leistungsschalter erfolgen.
STOP
Dazu muss sich dieser in der Gebäude− bzw. Schaltschrankinstallation
befinden, in unmittelbarer Nähe zum System implementiert sein und für den
Anwender leicht zugänglich sein.
Des weiteren muss jede derartige Trenneinrichtung entsprechend dem
zugehörigen System gekennzeichnet bzw. beschriftet sein.
d b z
2 UN+ (+ 24V) U− (0V/Common) UB+ (+24V, redundant) 2
4 A (RS 485) GND (BP, Common, RS 485) B (RS 485) 4
6 Supply2+ (sensor) Supply1− (sensor) Supply1+ (sensor) 6
8 AIN2− (Input) Supply2− (sensor) AIN1− (Input) 8
10 AIN2+ (Input) GND AIN1+ (Input) 10
12 NGL2 (scaled dc−output) GND NGL1 (scaled dc−output) 12
14 EO1 (voltage output1) EI1 (voltage input1) AC1 (sensor raw signal1) 14
16 EO2 (voltage output2) EI2 (voltage input2) AC2 (sensor raw signal2) 16
18 GWM (limit value) I1− (current output common) I1+ (current output CH1) 18
20 NC I2− (current output common) I2+ (current output CH2) 20
22 KEY−N (key signal input) GND ES (external lock) 22
24 SC−A (oper. principle alert) GND SC−D (oper. principle danger) 24
26 D1−C (danger1 collector) A1−C (alert1 collector) CC1−C (ch. clear1 collector) 26
28 D1−E (danger1 emitter) A1−E (alert1 emitter) CC1−E (ch. clear1 emitter) 28
30 D2−C (danger2 collector) A2−C (alert2 collector) CC2−C (ch. clear2 collector) 30
32 D2−E (danger2 emitter) A2−E (alert2 emitter) CC2−E (ch. clear2 emitter) 32
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 24
Der Betrieb des RS 485 Busses erfordert einen elektrischen Abschluss jeweils am ersten und
letzten Gerät des Busses.
Dies geschieht mit Steckbrücken, die sich auf dem Kontrollerboard befinden. Das Bild zeigt die
Position der Jumper.
Um den Bus−Abschluss zu aktivieren und die Leitungen “A” und “B” auf die Bezüge zu legen,
stecken Sie die Jumper wie in Bild b) gezeigt. Das Bild a) zeigt die Jumperposition für einen
deaktivierten Bus−Abschluss und offene Bezüge (Auslieferungszustand).
2 4 6 2 4 6
1 3 5 1 3 5
a) b)
Für einen störungsfreien Betrieb des RS 485 Busses müssen die Leitungen
i “A” und “B” in einem Monitor auf ihre Bezüge (+5 V; Masse) gelegt werden,
dies ist nur möglich wenn in diesem Monitor auch der Busabschluss−Jumper
gesetzt ist.
Sensorrohsignal
i
Der Bezugspunkt für das Sensorrohsignal von Kanal 1 ist die Steckleisten-
klemme b22: GND und für das Sensorrohsignal von Kanal 2 die Klemme b24:
GND.
Achten Sie bei Arbeiten an dem Monitor auf ausreichenden Schutz vor
STOP elektrostatischen Entladungen. Tragen Sie z.B., um elektrostatische
Entladungen über die Monitorelektronik zu verhindern, ein ESD−Armband.
1. Lösen Sie mit einem Kreuzschraubendreher die vier, im folgenden Bild mit den Pfeilen
gekennzeichneten Kreuzschrauben.
2. Ziehen Sie das Kontrollerboard vorsichtig, ohne zu verkanten von dem Mainboard ab. Die
Position der Jumper J2 auf dem Mainboard sind im folgenden Bild mit einem weißen
Rahmen gekennzeichnet.
3. Um das Sensorrohsignal auf die Klemmen z14 und z16 zu schalten, stecken Sie die Jumper
wie in b) dargestellt. Sind die Jumper wie in a) gesetzt, liegt an den Klemmen z14 und z16
ein nicht verwertbares Signal.
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 26
z14: z14:
J2 J2
z16: z16:
4. Stecken Sie das Kontrollerboard wieder auf das Mainboard und sichern Sie es mit den vier
Schrauben. Das Sensorrohsignal liegt nun auf der Steckleiste.
Monitor−Einbau
1. Überprüfen Sie vor Einbau des Monitors die Steckplatzverdrahtung.
2. Schieben Sie den A6125 Monitor in den vorbereiteten Steckplatz und drücken Sie ihn mit
leichtem Druck in den Steckverbinder.
3. Zur Sicherung des Monitors ziehen Sie die beiden Befestigungsschrauben auf der Front-
platte leicht handfest an.
Alle weiteren Informationen, wie z. B. Schirmung und Erdung, Konfiguration des Monitors, usw.,
finden Sie in der Gebrauchsanleitung “Lagerschwingungsmonitor A6125”, Bestellnr.
6100−90069.
Alle folgenden Angaben gelten, sofern nicht anders angeben, für Kanal 1 und Kanal 2
gleichermaßen.
2.6.1 Signalkonditionierung
Zwei separate Signaleingänge für Kanal 1 und Kanal 2 mit voneinander entkoppelter Signal-
konditionierung.
Messwerteingänge
Grenzbereich ±30 V DC
Signalkonditionierung
Innenwiderstand 1 kΩ
Dynamische Ausgänge
Die Ausgänge sind physikalisch vorhanden liefern jedoch kein verwendbares dynamisches
Signal.
Mit den Jumpern J2 kann das Sensorrohsignal (phasenrichtiges Sensorsignal), das an den
SMB−Buchsen auf der Frontplatte anliegt auf diese Klemmen umgeschaltet werden.
Frequenzbereich Hardwarefilter
− Toleranz ±20 %
Betriebsart Bewertung Dig. Filter High Dig. Filter Med Dig. Filter Low
Geschwindigkeit −−−−−−−−
Amplitude
Stromausgänge−Kenngröße
Die Kenngrößenbildung und Bewertung ist abhängig von den bei der Konfiguration
bestimmten Funktionen.
Stromausgang 1 − I1+ / I1− z18 / b18 (0 V / common)
Stromausgang 2 − I2+ / I2− z20 / b20 (0 V / common)
Nennbereich 0 ... 20 mA oder 4 ... 20 mA, abhängig von der
Konfiguration
− Life zero−Betrieb im 4 ... 20 mA Betrieb kann mittels der Konfiguration
bestimmt werden, dass der Ausgang bei Erkennung
einer Störung auf 0 mA gesetzt wird.
Genauigkeit / Auflösung ±1 % vom Messbereichsendwert / 16 Bit
Zul. Belastungswiderstand 500 Ω
d14 / d16
Spannungsausgänge 0 ... 10 V proportional der Lagerschwingung, Messbereich und Be-
wertung entsprechend der Kenngrößen Kanal 1 (EO 1) und Kanal 2 (EO 2).
leerlauf− und kurzschlussfest, rückwirkungsfrei.
Auflösung 8 Bit
Innenwiderstand ca. 50 Ω
Auflösung 10 Bit
Eingangswiderstand >100 kΩ
Product Information / Produktinformation A6125
Lagerschwingungsmonitor Seite 29
Signaleingang KEY
Eingangswiderstand >10 kΩ
2.6.2 Kanalüberwachung
Überwachungsfunktion
ständige Überwachung
Systemspannungen Spannung − OK
μP Funktion (watchdog) WD − OK
externes Sperrsignal ES
Status Kanalüberwachung
Visualisierung
Ext. gesperrt oder Status = Fehler C−E gesperrt, max. zul. Spannung: 48 V
oder Freigabe verzögert
nicht ext. gesperrt und Status = OK C−E leitend, max. zul. Strom: 100 mA
und nicht Freigabe verzögert
Zwei Alarmkanäle mit je einem Alarmausgang ALERT und DANGER und separater
Grenzwerteinstellung. Alarmierung, wenn die Kenngröße den parametrierten Grenzwert
überschreitet. (Istwert > Grenzwert)
Grenzwerteinstellung
Ansprechverzögerung
Alarmblockierung
Alarmvisualisierung
Alarmausgänge
Arbeitsstrom− / Ruhestrombetrieb
2.6.4 Kommunikationsschnittstellen
Schnittstelle RS 232
Schnittstelle RS 485
2.6.5 Spannungsversorgung
Die Monitorsystemspannungen und somit auch die 0 V / common−Anschlüsse für die Mess−
und Überwachungsein− und −ausgänge sind voneinander galvanisch getrennt.
Versorgungsspannungseingänge zwei redundante, diodenentkoppelte Eingänge für
nominal +24 V mit gemeinsamen 0 V Bezug
Spannungseingang UB+ / UN+ d2 / z2
Gemeinsamer Bezug, 0 V U− b2
Zul. Spannungsbereich 19 ... 31,2 Vdc (IEC 654−2 Klasse DC 4)
CSA: 24Vdc; SELV LPS
Leistungsaufnahme max. 6 W, bei 24 V max. 250 mA
Monitorsystemspannung
Die für die interne Versorgung benötigten Monitor−Systemspannungen werden ständig auf
Unterspannung überwacht. Bei Erkennung einer Unterspannung wird eine Fehlermeldung
generiert.
Sensorspeisung
2.6.6 Umgebungsbedingungen
Umgebungstemperatur
Bezugstemperatur +25°C
Frontelemente
Signal ground
PE
protective earth
Protective earth
Cabinet
to
LiYCY−CY
LiYCY−CY
cable
cable
Field
connection
connection
Harting
Harting
e.g. 3 m cable
e.g. 3 m cable
B
A
piezoelectric
piezoelectric
sensor
sensor
Signal
GND
+4 mA
cable
PR 9264 e.g. 4 m cablel LiYCY−CY
Product Information / Produktinformation A6125
to
protective earth
capacitive
sensor
Harting
connection
Signal
GND
+4 mA
cable
Connection Diagrams and Figures / Anschlusspläne und Abbildungen
Signal ground
Protective earth
PE
Page/Seite 36
Product Information / Produktinformation A6125
Connection Diagrams and Figures / Anschlusspläne und Abbildungen Page/Seite 37
d b z d b
24 24 SC−A Current Mode Alert GND Common SC−D Current Mode Danger
26 26 D1−C Danger1 out Col A1−C Alert1 out Col C1−C Chan Clear1 out Col
28 28 D1−E Danger1 out Emit A1−E Alert1 out Emit C1−E Chan Clear1 out Em
30 30 D2−C Danger2 out Col A2−C Alert2 out Col C2−C Chan Clear2 out Col
32 32 D2−E Danger2 out Emit A2−E Alert2 out Emit C2−E Chan Clear2 out Em
100 27
173.5
160
2.5
2.5
17
Alle Abmessungen in mm
All dimensions in mm
6 TE
30.1
128.4
3 HE
Dimensions A6125
Abmessungen A6125
Product Information / Produktinformation A6125
PI Revision List Page/Seite 39
4 PI REVISION LIST
Gronau, 04.05.2011
Ort und Datum Geschäftsbereichsleiter Leiter Qualitätsmanagement
Place and date Divisional director Head of quality management