Component Cladding WInd Load

This document contains a wind load analysis for wall components and cladding according to the ASCE 7-02 code. It provides input data for a building such as dimensions, wind speed, and exposure category. It then calculates resulting wind pressure coefficients and design net external wind pressures in pounds per square foot for various wall zones, including positive and negative pressures. Net pressures are listed for a sample girt component at various heights up to the roof height. Diagrams illustrate the wall zones for buildings below and above 60 feet in height.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
284 views

Component Cladding WInd Load

This document contains a wind load analysis for wall components and cladding according to the ASCE 7-02 code. It provides input data for a building such as dimensions, wind speed, and exposure category. It then calculates resulting wind pressure coefficients and design net external wind pressures in pounds per square foot for various wall zones, including positive and negative pressures. Net pressures are listed for a sample girt component at various heights up to the roof height. Diagrams illustrate the wall zones for buildings below and above 60 feet in height.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

"ASCE702W.

xls" Program
Version 1.7

WIND LOADING ANALYSIS - Wall Components and Cladding


Per ASCE 7-02 Code for Buildings of Any Height
Using Method 2: Analytical Procedure (Section 6.5)
Job Name: Subject:
Job Number: Originator: Checker:

Input Data:

Wind Speed, V = 90 mph (Wind Map, Figure 6-1)


Bldg. Classification = II (Table 1-1)
Exposure Category = C (Sect. 6.5.6) B
Ridge Height, hr = 53.33 ft. (hr >= he)
Eave Height, he = 20.00 ft. (he <= hr)
Building Width = 200.00 ft. (Normal to Building Ridge)
Building Length = 250.00 ft. (Parallel to Building Ridge) L
Roof Type = Gable (Gable or Monoslope)
Plan
Topo. Factor, Kzt = 1.00 (Sect. 6.5.7 & Figure 6-4)
Direct. Factor, Kd = 0.85 (Table 6-4)
Enclosed? (Y/N) Y (Sect. 6.2 & Figure 6-5)
Component Name = Girt (Girt, Siding, Wall, or Fastener) qo
Effective Area, Ae = 208 ft.^2 (Area Tributary to C&C) hr
h
he

Resulting Parameters and Coefficients: L


Elevation
Roof Angle, q = 18.43 deg.
Mean Roof Ht., h = 36.67 ft. (h = (hr+he)/2, for roof angle >10 deg.)

Wall External Pressure Coefficients, GCp:


GCp Zone 4 Pos. = 0.77 (Fig. 6-11A)
GCp Zone 5 Pos. = 0.77 (Fig. 6-11A)
GCp Zone 4 Neg. = -0.87 (Fig. 6-11A)
GCp Zone 5 Neg. = -0.93 (Fig. 6-11A)
Positive & Negative Internal Pressure Coefficients, GCpi (Figure 6-5):
+GCpi Coef. = 0.18 (positive internal pressure)
-GCpi Coef. = -0.18 (negative internal pressure)

If z <= 15 then: Kz = 2.01*(15/zg)^(2/a) , If z > 15 then: Kz = 2.01*(z/zg)^(2/a) (Table 6-3, Case 1a)
a= 9.50 (Table 6-2)
zg = 900 (Table 6-2)
Kh = 1.02 (Kh = Kz evaluated at z = h)
I= 1.00 (Table 6-1) (Importance factor)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15)
qh = 18.06 psf qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h)

Design Net External Wind Pressures (Sect. 6.5.12.4):


For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf)
For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf)
where: q = qz for windward walls, q = qh for leeward walls and side walls
qi = qh for all walls (conservatively assumed per Sect. 6.5.12.4.2)

1 of 3 08/04/2021 11:48 am
"ASCE702W.xls" Program
Version 1.7

Wind Load Tabulation for Wall Components & Cladding


Component z Kh qh p = Net Design Pressures (psf)
(ft.) (psf) Zone 4 (+) Zone 4 (-) Zone 5 (+) Zone 5 (-)
Girt 0 1.02 18.06 17.11 -18.91 17.11 -20.13
15.00 1.02 18.06 17.11 -18.91 17.11 -20.13
20.00 1.02 18.06 17.11 -18.91 17.11 -20.13
25.00 1.02 18.06 17.11 -18.91 17.11 -20.13
30.00 1.02 18.06 17.11 -18.91 17.11 -20.13
35.00 1.02 18.06 17.11 -18.91 17.11 -20.13
40.00 1.02 18.06 17.11 -18.91 17.11 -20.13
45.00 1.02 18.06 17.11 -18.91 17.11 -20.13
50.00 1.02 18.06 17.11 -18.91 17.11 -20.13
For z = hr: 53.33 1.02 18.06 17.11 -18.91 17.11 -20.13

For z = he: 20.00 1.02 18.06 17.11 -18.91 17.11 -20.13


For z = h: 36.67 1.02 18.06 17.11 -18.91 17.11 -20.13

Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 5 (end zones), 'a' = 14.67 ft.
3. Per Code Section 6.1.4.2, the minimum wind load for C&C shall not be less than 10 psf.
4. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures".
b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02"
by: Kishor C. Mehta and James M. Delahay (2004).

2 of 3 08/04/2021 11:48 am
"ASCE702W.xls" Program
Version 1.7

Wall Components and Cladding:

Wall Zones for Buildings with h <= 60 ft.

Wall Zones for Buildings with h > 60 ft.