Tutorial 6 EMII

The document contains 5 questions about electrical machines and synchronous generators. It provides details on open circuit and short circuit tests of an alternator to determine voltage regulation. It also includes questions about calculating synchronous reactance, excitation EMF, no load voltage and regulation of synchronous generators operating at lagging and leading power factors.

Uploaded by

Thangam Mahesh
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views

Tutorial 6 EMII

The document contains 5 questions about electrical machines and synchronous generators. It provides details on open circuit and short circuit tests of an alternator to determine voltage regulation. It also includes questions about calculating synchronous reactance, excitation EMF, no load voltage and regulation of synchronous generators operating at lagging and leading power factors.

Uploaded by

Thangam Mahesh
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

RAMCO INSTITUTE OF TECHNOLOGY

Department of Electrical and Electronics Engineering


Academic Year: 2019-2020 (Even Semester)
TUTORIAL SHEET
Degree, Semester& Branch : IV Semester B.E EEE
Course Code & Title : EE8401 Electrical Machines-II
Name of the Faculty member : Mr. E. Thangam, AP(SG) / EEE
Tutorial No.: 6 Date:

Questions:

1. A 3 phase star connected, 1000 kVA, 11000 V alternator has rated current if 52.5 A.
the ac resistance of the winding per phase is 0.45Ω. The test results are given below:
OC test: field current – 12.5 A, voltage between lines = 422 V.
SC test: field current – 12.5 A, line current = 52.5 A
Determine the full load voltage regulation of the alternator (i) 0.8 p.f. lagging (ii) 0.8
p.f. leading. [CO1,L3]

2. A 3 phase star-connected salient pole synchronous generator is driven at a speed near


synchronous with the field circuit open and the stator is supplied from a balanced
3-phase supply. Voltmeter connected across the line gave minimum and maximum
readings of 2800 volts and 2820 volts. The line current fluctuated between 360 A and
275 A. Calculate the Xd and Xq per phase. Neglect armature resistance. [CO1,L3]

3. A 50 Hz, 3 phase, 480 V , delta connected salient pole synchronous generator has
Xd =0.1ῼ and Xd =0.075ῼ. The generator is supplying 1200 A at 0.8 p.f. lagging.
Find the excitation EMF. Neglect armature resistance. [CO1,L1]

4. A 3 phase, 2000 kVA, 2.3 kV,star connected synchronous generator has direct axis
synchronous reactance of 2Ω/ phase and a quadrature axis synchronous reactance of
1.2Ω/ phase. It is suppling full load at 0.8 p.f lagging. Calculate (i) no load voltage
and (ii) percentage regulation. The resistance is negligible. [CO1,L3]

5. A 30 MVA, 15 kV, 60 Hz AC generator has a synchronous reactance of 1.2 pu and a


resistance of 0.02 pu. Calculate.
(i) the base voltage, base power and base impedance of the generator,
(ii) the actual values of the synchronous reactance,
(iii) the actual winding resistance, per phase
(iv) the total full-load copper losses.
[CO1,L3]

CO1: After completion of the course, the students will be able to explain the concept,
principle and performance of salient and non salient type synchronous generator.
L1: Remember; L2: Understand; L3: Apply

Signature of the Faculty member HOD

Form No. AC 09a Rev.No. 00 Effective Date: 18.01.2016