Cooling Components
• Electronic Controls
• Expansion Valves
• Hot Gas Bypass Valves
• Liquid Injection Valves
• Solenoid Valves
• Check Valves
• Sight Glasses
• Filter Driers
• Vibration Absorbers
Product Catalogue Cooling Components
Content Overview
Designation Page
Electronic Controls
Electronic Expansion Valves
EEV 9
Electronic Superheat Controllers
SHC 15
Accessories for SHC
PSR, TS 19
Electronic Suction Pressure Regulation Valves
ESDR 25
Electronic Thermostats and Cold Store Controls
PCR-100/110 29
PCR-300/310/410/300RC 31
Electronic Temperature Displays
PTI-610 35
Automatic Expansion Valves
Valves with interchangeable orifice
AMV (AMV, AMVX) 37
Valves with fixed orifice
AEL, AEL with Bypass 41
Thermostatic Expansion Valves
Valves with interchangeable orifice
TMV (TMV, TMVX, TMVBL, TMVXBL) 43
TMVL (TMVL, TMVLX) 47
TMX (TMXB, TMXL) 51
Valves with fixed orifice
TLK 55
TLE 0.5 – 3.0 59
TLEX 0.5 – 4.5 59
TBEX 0.5 – 4.5 63
TOEX 0.5 – 4.5 67
TLESX 4.75 – 6 71
TLEX 4.75 – 7 75
TLEX 8 – 11 79
Hot Gas Bypass Valves
CVC, HLE 83
HLEX 4.75 – 7, HLEX 8 – 11 85
Liquid Injection Valves
NMVL 89
NMX 89
Solenoid Valves
M (MA, MD, MS) 95
Check Valves
RV 103
Sight Glasses
SBI, SBIA, SLI 105
Filter Driers
FF 109
Vibration Absorbers
SA 113
Nomenclature 119
Honeywell Product Portfolio 121
VLS - D Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
internal pressure equalisation, solder connections, two-way construction
VLSX - D Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
external pressure equalisation, solder connections, two-way construction
VLS - W Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
internal pressure equalisation, solder connections, angle construction
VLSX - W Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
external pressure equalisation, solder connections, angle construction
XLS Solder Base for Thermostatic Expansion Valves TMX and NMX 51
solder connections, two-way or angle construction
XBS Flare Base for Thermostatic Expansion Valves TMX and NMX 51
flare connections, two-way construction
MA Solenoid Valves 95
normally closed, direct operated, angle construction, solder connections,
kv-value = 0.17 m3/h
MD Solenoid Valves 95
normally closed, direct operated, two-way construction, solder or flare
connections, kv-value = 0.17 – 0.23 m3/h, valve complete with coil for 230V AC
or as part programme valve without coil
MS Solenoid Valves 95
normally closed, pilot operated, two-way construction, solder or flare
connections, kv-value = 0.9 – 4 m3/h, valve complete with coil for 230V AC or as
part programme valve without coil
PRODUCT-DATA
Features
Proportional Electronic Expansion Valve for usage in
refrigeration circuits
Refrigerants:
HCFC, HFC (R410A, R32, R407C, R134a, R404A, ...)
HFOs (R1234yf, R1234ze) and blends
Hydrocarbons (R600a, R290, ...)
Further refrigerants on request
2-pole stepper motor with inside protected coil
Hermetical construction
Specification
The application-oriented valve calculation can take place in individual cases with the help of the selection tables.
Electrical Connections
Stepper Motor
Controller
24 V
White
Blue
Black
Brown
Step
1 + - - +
2 - - + +
3 - + + -
4 + + - -
Port Connections
Typ Weight (kg)
A-B
EEV 5 10 mm - 12 mm ODF 0,33
3/8“ – 1/2" ODF 0,33
EEV 10 10 mm - 12 mm ODF 0,33
3/8“ – 1/2" ODF 0,33
EEV 20 12 mm - 16 mm ODF 0,33
1/2“ – 5/8" ODF 0,33
Type description
EEV 20 12 x 16
Valve type
Valve size
5
10
20
Port Connection
10 x 12 = 10 x 12 mm ODF
12 x 16 = 12 x 16 mm ODF
PRODUCT DATA
Features
Automatic adaptation to the evaporator’s MSS
Balancing of the lowest possible superheat
Learning behavior with regards to the history of the
operating points
Automatic tracking of controller parameters
Independent recognition of defrost requirements
Termination of the defrost cycle commensurate with
energy efficiency needs
No external setpoint necessary!
Specification
Analog outputs
Temperature 2X (PT1000, NTC10K, NTC20K)
Temperature/voltage 2X (PT1000, NTC10K, NTC20K,
0.5 … 4.5 V, 0 … 10 V)
Voltage/current 2X (0.5 … 4.5 V, 0 … 10 V,
4 … 20 mA)
Analog output
Voltage 1X (0 … 10 V)
Power Supply
SHC COMPRESSOR Current 24 VAC ± 20% or
KOMPRESSOR
24 VDC ± 10%
EEV Max. power consumption 50 VA (when motor active)
Mounting
Mounting DIN rail or wall mounting
Dimensions 181 mm X 110 mm X 45 mm
EVAPORATOR / VERDAMPFER
Weight 220 g
PI TI
39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
GND D1 D2 D3 GND GND AO R1 GND V5/15 GND R2 U2 V5/15 GND U1 T2 GND T1
digital inputs 0...10 V output inputs: 4...20 mA / ratiometric / 0...10 V inputs: Pt1000, NTC10k, NTC20k / ratiometric / 0...10 V
24 Vac/dc 24 Vbat bipolar stepper motor RS485 (isolated) relay 4 (SPDT) relay 1 (NO) relay 2 (NO) relay 3 (NO)
G G0 BAT EARTH OUT2B OUT2A OUT1B OUT1A A B GNDX C4 NO4 NC4 C1 NO1 C2 NO2 C3 NO3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
9 A RS485, A + conductor
10 B RS485, B – conductor
11 GNDX RS485, isolated ground
Dimensions (mm)
40 181
110
Accessories
accessories models corresponding technical literature
Transformer CRT / ETR EN0B-0568GE51
Temperature Sensor TS-NFN, TS-NFR, TS-RFH EN0H-1950GE23
Pressure Sensor PSR EN0H-1949GE23
DPTM50-5000 EN0B-0466GE51
Differential Pressure Sensors
DPTM50D-5000D EN0B-0616GE51
Electronic Expansion Valve EEV EN0H-1945GE23
PRODUCT-DATA
Features
Pressure Sensor Transmitter for usage in
refrigeration and HVAC applications
For installation in liquid line, injection line, hot gas
line and suction line
For usage of refrigerants R22, R134a, R404A, R407C,
R410A, R502, R507; not for Ammonia
Condensation-tight
Type PSR - ** MS UB MP150:
Wetted parts of brass, CR70 (Chloroprene) and
ceramic
Integrated ceramic thick-layer sensor
Type PSR - ** VA UB MP150:
Wetted parts of stainless steel
Monolithic structure
Hermetically welded metallic, dry thin-film sensor
element
Specification
Pressure Range see table on page 20
Maximum Pressure PS see table on page 20
Application Electrical Output Signal 0.5…4.5 V ratiometric
Pressure Sensor Transmitter Type PSR is used in refrigeration
Power Supply 5 ± 0.5 VDC
circuits to measure the refrigerant’s pressure.
The Pressure Sensor Transmitter PSR can be used according Supply Current ≤ 10 mA
to its measuring range in the liquid line, in the injection line,
Maximum Load > 4.5 kΩ
in the hot gas line and in the suction line of refrigeration
circuits. Response Time (10…90%) ≤ 5 ms
Insulation Voltage 500 VDC
Materials Medium Temperature -40 °C … 80 °C
Housing Brass, Stainless Steel Ambient Temperature -25 °C … 80 °C
Sealing CR70 (Chloroprene) Storage Temperature -25 °C … 80 °C
Port Connection 7/16-20 UNF-2B Max. rel. Humidity 95 %
Electr. Protection degree IP67
Other appplications on request.
In plugged condition with connector of corresponding
protection class
Technical Specification
Typ PSR – 9 MS PSR – 16 MS PSR – 45 MS PSR – 9 VA UB PSR – 16 VA PSR – 45 VA UB
Type UB MP150 UB MP150 UB MP150 MP150 UB MP150 MP150
Messbereich -1…9 bar(ü) 0…16 bar(ü) 0…45 bar(ü) -1…9 bar(ü) 0…16 bar(ü) 0…45 bar(ü)
Pressure range -1…9 bar(g) 0…16 bar(g) 0…45 bar(g) -1…9 bar(g) 0…16 bar(g) 0…45 bar(g)
Überlastgrenze
20 bar 40 bar 100 bar 20 bar 32 bar 100 bar
Over pressure range
Berstdruck
25 bar 50 bar 120 bar 100 bar 160 bar 400 bar
Burst pressure
Genauigkeit -40 °C … -20 °C ≤ 1,5 %* -40 °C … -20 °C ≤ 1,5 %*
Accuracy -20 °C … +20 °C ≤ 1 %* -20 °C … +20 °C ≤ 1 %*
* bezogen auf Taulinie von R410A * bezogen auf Taulinie von R410A
* related to dewpoint of R410A * related to dewpoint of R410A
Stabilität pro Jahr ≤ 0,3 % der Spanne (bei Referenzbedingungen)
1-year stability ≤ 0.3 % of span (at reference conditions)
Elektrische Schutzart
IP67 in gestecktem Zustand mit Leitungsstecker entsprechender Schutzart
Protection degree
Kurzschlussfestigkeit
S+ gegen 0V S+ gegen UB-
Short-circuit protection
S+ towards 0V S+ towards UB-
Verpolschutz
UB gegen 0V UB+ gegen UB-
Reverse polarity
UB towards 0V UB+ towards UB-
protection
Überspannungsschutz
Overvoltage protection 36 VDC
EMV-Richtlinie 2004/108/EEC, EN 61 326 Emission (Group 1, 2004/108/EEC, EN 61 326 Emission (Group 1, Class B)
EMC directive Class B) and Immunity (industrial locations) and Immunity (industrial locations)
2004/108/EEC, EN 61 326 Emission (Group 1, 2004/108/EEC, EN 61 326 Emission (Group 1, Class B)
Class B) and Immunity (industrial locations) and Immunity (industrial locations)
Gewicht Ca. 0,08 kg Ca. 0,08 kg
Weight Appr. 0.08 kg Appr. 0.08 kg
PSR -9 MS UB MP150
Pressure Sensor Type
Type:
-9 = -1 … 9 bar(g)
16 = 0 … 16 bar(g)
45 = 0 … 45 bar(g)
Material:
MS – Brass
VA – Steinless Steel
Port Connection
7/16-20 UNF-2B, Schrader
Internal Thread
MetriPack 150
Function Assembly
The pressure prevailing within the application is transformed Required tools: wrench (flats 24), screw driver
into a standardised electrical signal through the deflection of Use the pressure transmitter only if it is in a faultless
the diaphragm, which acts on the sensor element with the condition as far as the safety-relevant features are
power supply fed to the transmitter. This electric signal concerned.
changes in proportion to the pressure and can be evaluated
correspondingly. When mounting the instrument, ensure that the
sealing faces of the instrument and the measuring
point are clean and undamaged.
Remarks:
Screw in or unscrew the instrument only via the flats
Select the appropriate pressure transmitter with using a suitable tool and the prescribed torque. The
regard to scale range, performance and specific appropriate torque depends on the dimension of the
measurement conditions prior to installing and starting pressure connection. Do not use the case as working
the instrument. surface for screwing in or unscrewing the instrument.
Observe the relevant national regulations (e.g.: EN
When screwing the transmitter in, ensure that the
50178) and observe the applicable standards and
threads are not jammed.
directives for special applications (e.g. with
dangerous media such as acetylene, flammable Connect the instrument to earth via the pressure
gases or liquids and toxic gases or liquids and with connection.
refrigeration plants or compressors). If you do not Use power supplies which guarantee reliable electrical
observe the appropriate regulations, serious isolation of the operating voltage as per IEC/DIN EN
injuries and/or damage can occur! 60204-1. Consider also the general requirements for
Open pressure connections only after the system PELV circuits in accordance with IEC/DIN EN 60204-1.
is without pressure! Ingress protection per IEC 60529 (The ingress
Please make sure that the pressure transmitter is protection classes specified only apply while the
only used within the overload threshold limit all the pressure transmitter is connected with female
time! connectors that provide the corresponding ingress
Observe the ambient and working conditions protection).
outlined in section „Technical data”. Please make sure that the ends of cables with flying
Ensure that the pressure transmitter is only operated leads do not allow any ingress of moisture.
in accordance with the provisions i.e. as described in
the installation instructions.
Do not interfere with or change the pressure
transmitter in any other way than described in the Spare Parts
operating instructions.
Remove the pressure transmitter from service and Cable
mark it to prevent it from being used again Description:
accidentally, if it becomes damaged or unsafe for
operation. Stecker mit Kabel für Drucksensor 3 m (IP67)
PSR-CAB300 MP150
Take precautions with regard to remaining Plug with cable for pressure sensor 3 m (IP67)
media in removed pressure transmitter.
Stecker mit Kabel für Drucksensor 6 m (IP67)
Remaining media in the pressure port may be PSR-CAB600 MP150
hazardous or toxic! Plug with cable for pressure sensor 6 m (IP67)
PRODUCT-DATA
Features
Pressure Sensor Transmitter for usage in
refrigeration and HVAC applications
For installation in liquid line, injection line, hot gas
line and suction line
For usage of refrigerants R22, R134a, R404A,
R407C, R410A, R502, R507; not for Ammonia
Condensation-tight body IP67
Type TS – NFN & TS – NFR: NTC 10K
Type TS – RFH: PT1000
Specification (1)
Application
Resistance Value:
Temperature Sensor Type TS is used in refrigeration circuits
TS – NFN; TS – NFR 10 kΩ at 25 °C
to measure the refrigerant’s temperature.
The Temperature Sensor TS can be used according to its TS – RFH 1 kΩ at 0 °C
measuring range in the liquid line, in the injection line, in the Accuracy:
hot gas line and in the suction line of refrigeration circuits.
Due to fast temperature capture in refrigeration circuits the TS – NFN 1 % Full scale
signal can be communicated very fast. TS – NFR ± 0.2 °C
TS – RFH Class A
Materials Response Time: K = 5 sec in liquid V = 2 m/s
Body Stainless Steel, AISI 304 Sensitivity:
Cable Thermical rubber poly. TS – NFN; TS – NFR NTC 10K fast
Electrical Connection Pins TS – RFH PT1000
Specification (2)
Type TS – NFN TS – NFR TS – RFH
Element Type NTC 10K 1% BETA 3435 NTC 10K BETA 3977 tolerance ± 0.2 °C PT 1000 Class A
Cable Type Thermical rubber poly Thermical rubber poly Thermical rubber poly
Cable colour Black Yellow Green
Cable diameter 2x0.25 mm² Ø 3.3 mm 2x0.25 mm² Ø 3.3 mm 2x0.25 mm² Ø 3.3 mm
Connection Pins Pins Pins
Filling Polyuretanic resin Polyuretanic resin Polyuretanic resin
Function
Due to temperature changes the resistance of temperature sensor will be changed. This change of resistance is changing
proportional to the temperature and can be evaluated accordingly.
Remarks:
Select the appropriate temperature sensor with regard to scale range, performance and specific measurement conditions
prior to installing and starting the refrigeration system.
Please make sure that the temperature sensor is only used within the valid measuring range.
Assembly
Position the temperature sensor on the refrigerant pipe in the position between 10 and 14 o'clock (at horizontal pipe installation).
Pay attention to install sensor to clean and intact surfaces at the measuring point.
Provide sufficient thermal compound at the measuring point between temperature sensor and measuring surface.
Fasten the temperature sensor by means of aluminum tape and/or fastening clips to the refrigerant pipe.
Insulate the fastened temperature sensor with heat insulation material.
Connect the temperature sensor according to the instructions of the evaluating equipment.
Ensure that no humidity may enter at cable-ends.
PRODUCT DATA
Features
Stepper motor operated
Continuous control behaviour
High pressure compensation (Balanced port)
Low pressure drop
High cooling capacity
Copper solder connections
Refrigerant: R134a, R404A, R407C, R410A, R422D
Technical Data
Nominal capacity see table on page 26
Maximum pressure PS 35 bar
Maximum test pressure PF 38.5 bar
Min. operating temperature -50 °C
ESDR 22 Max. operating temperature +65 °C
Max. ambient temperature +100 °C
Electronic Data
Stepper motor type 2 phase bipolar
Application Nominal voltage 12 V chopper controlled
Electronic suction pressure regulation valves series ESDR Nominal phase current 0,7 A
are used to control the refrigerant mass flow in the suction
line of a refrigerating plant. Max. phase current 1A
A stepper motor driven piston opens / closes the valve seat. Holding current max. 0,7 A
With this continuous control behaviour it is possible to hold a Step rate 300 Hz
defined temperature level in a cold store also with changing Phase resistance 6 Ohm
compressor working conditions.
It is also possible to handle different temperature levels in Phase inductance 14 mH
several cold stores with a common compressor pack by use Step angel 1.8 °
of suction pressure regulation valves.
Furthermore an overload protection of the compressor or a
capacity controller can be realised with ESDR valves. Material
Valve housing, internals brass
Motor housing stainless steel
Connections copper
Valve sealing PTFE
Motor electrical sheet, copper
Nominal Capacity
kv – value Nominal capacity (kW)*
Type Valve size (m³/h)
R134a R404A R407C R410A R422D
ESDR 22 17 34.9 37.8 42.7 55.5 34.5
* Capacities are based on evaporating temperature to = +4 °C, condensing temperature tc = +38 °C und 1 K subcooled
refrigerant, pressure drop over the valve 0.15 bar
22 mm ODF
ESDR 22 185 mm 201.4 mm 113.6 mm approx. 1.05 kg
28 mm ODF
ESDR 22
Stepper Motor
Driver
White
Blue
Black
Brown
Application Sample
Controller
SM
Driver
T1
T2
Installation
Respect the installation instruction!
Position of the stepper motor in a suspended arrangement.
Flow direction must correspond with the arrow on the valve
body.
When soldering the valve, the valve body must not get
warmer than 100 °C.
Do not direct connect the stepper motor to power supply.
Use a stepper motor driver to operate the stepper motor.
The technical data of the stepper motor driver must
correspond with the electrical and technical data of the
valve.
To open / close the valve via a stepper motor driver
respect the sequence of polarity at the coils shown in the
wiring schematic.
Constructive modifications at the valve are not allowed.
Features
User friendly programming
Thermostat for refrigeration and heating
Relay output
Defrost option for plus cold stores with continuous
operation of evaporator fan
Alarm output relay
Red digital display, good visibility
PCR-100: Module housing for 35 mm standard DIN rail
PCR-110: Snap-in installation housing for aperture
28.5 x 70.5 mm
PCR-100
PTC sensors with stainless steel sleeves
Mains transformer integrated
Specification
Power supply 230 V, ±10 %, 50/60 Hz
Power consumption 2.1 Watt
Control performance on-off
PCR-110 Display 3-digit, 7-segment, LED red,
height 14.2 mm
Resolution 1K
Display accuracy ±0.5 K internally, ±1 digit at 25 °C
Application
Measuring range -55 °C to +50 °C
PCR-100 and PCR-110 are microprocessor-controlled
Input 1 PTC sensor
thermostats for refrigeration, deep freeze systems and for
general purpose use. Outputs compressor or heater: 1 relay
The electronic thermostats can be used for cooling and with changeover contact, 8 A,
heating application in a temperature range of -55 °C to +50 °C. 230 V AC resistive load
alarm: 1 relay with N. O. contact,
Material 5 A, 230 V AC, resistive load
Housing ABS-plastic, self-extinguishing Sensor PTC sensor, cable length 2.5 m,
accuracy ±2 %
range of use:
-30 °C to +80 °C cable not fixed
-40 °C to +80 °C cable fixed
Ambient in operation:
temperature/humidity 0° to + 50 °C,
30 to 85 % R.H. excluding dew
in storage:
-20 °C to +80 °C
Data back up Non-volatile memory EEPROM
Connectors 250V / 10 A screw-type terminal
strips, max. 1.5 mm²
Protective rating Housing: IP 20, front panel: IP 52,
protection class 2
Installation
Operate only in dry places
Snap-in installation housing:
Fit unit in a recess 28.5 x 70.5 mm
maximum wall thickness: 22 mm
Secure housing with the mounting frame
4 DIN standard modular housing:
Open out the side mounting tabs
Clip the unit on to 35 mm rail
press tabs in again
Respect the wiring diagram
Tighten screws of connectors carefully
PCR-110 PCR-100
Features
User friendly programming
Compressor control with delayed start-up
Evaporator fan control; fan in combination with
compressor, operating continuously or switched via
the evaporator temperature.
Defrost control for electrical heating or hot-gas
defrosting; initiated via programmable time intervals,
at PCR-300RC by real-time clock
Alarm output (not for PCR-310)
Red digital display, good visibility
PCR-300 Module housing for 35 mm standard DIN rail at
PCR-300 and PCR-300RC
Snap-in installation housing at PCR-310 and PCR-410
for aperture 28.5 x 70.5 mm
Mains transformer integrated at PCR-300, PCR-300RC
External transformer at PCR-310, PCR-410
2 PTC sensors with stainless steel sleeves for room
temperature and defrost termination
PCR-310
Specification (1)
Power supply PCR-300, PCR-300RC
mains transformer installed:
Application 230 V, ±10 %, 50/60 Hz
PCR-300, PCR-310, PCR-410 and PCR-300RC are PCR-310, PCR-410
microprocessor-controlled cold store controls for refrigeration 12 V AC ±10%, 50/60 Hz or
and deep freeze systems. 12 V DC ±10%
The control switch the compressor, evaporator fan and the external Transformer TR-310:
defrost heating depending on the cold store temperature Prim.: 230 V AC ±10%, 50/60 Hz
and the adjusted parameters. Sec.: 12 V AC
Power consumption 2.5 Watt
Material
Control performance on/off
Housing ABS-plastic, self-extinguishing
Display 3-digit, 7-segment, LED red,
height 14.2 mm
Resolution 1K
Display accuracy ±0.5 K internally, ±1 digit at 25 °C
Measuring range -55 °C to +50 °C
Inputs 2 PTC sensors
Continued on page 32
Specification (2)
Outputs compressor: Sensor PTC sensor, cable length 2.5 m,
1 relay with changeover contact, 8 A, accuracy ±2 %
230 V AC, resistive load range of use:
evaporator fan: -30 °C to +80 °C cable not fixed
1 relay with N.O. contact, 8 A -40 °C to +80 °C cable fixed
(5 A PCR-300RC), 230 V AC, Ambient in operation:
resistive load temperature/humidity 0° to 50 °C,
defrost heating: 30 to 85 % R.H. excluding dew
1 relay with N.O. contact, 8 A in storage:
(5 A PCR-300RC), 230 V AC, -20 °C to +80 °C
resistive load
Data back up Non-volatile memory EEPROM,
alarm: Real time clock with back up
PCR-300, PCR-300RC battery (PCR-300RC)
Opto-bidirectional triode thyristor,
250 VAC, min. load 40 mA, Connectors 250V / 10 A screw-type terminal
max. load 80 mA strips, max. 1.5 mm²
PCR-410: 1 relay with N.O. Protective rating Housing: IP 20
contact, 8 A, 230 V AC, front panel: IP 52,
resistive load protection class 2
Installation
Operate only in dry places
Snap-in installation housing:
Fit unit in a recess 28.5 x 70.5 mm
maximum wall thickness: 22 mm
Secure housing with the mounting frame
4 DIN standard modular housing:
Open out the side mounting tabs
Clip the unit on to 35 mm rail
press tabs in again
Respect the wiring diagram
Tighten screws of connectors carefully
PCR-310
PCR-410
Features
Red digital display, good visibility
Display for °C and °F selectable
Snap-in installation for aperture 28.5 x 70.5 mm
Retaining frame for wall thickness up to 22 mm
PTC sensors with stainless steel sleeves
Electronic sensor-line up, if required
Mains transformer integrated
Specification
Power supply 230 V, ±10 %, 50/60 Hz
Power consumption 1.3 Watt
Display 3-digit, 7-segment, LED red,
height 14.2 mm
Resolution 1K
Display accuracy ±0.5 K internally, ±1 digit at 25 °C
Measuring range -55 °C to +99 °C
-67 °F to +99 °F
Input analogue input for PTC sensor
Sensor PTC sensor, cable length 2.5 m,
accuracy ±2 %
Application range of use:
PTI-610 is an electronic temperature display for general -30 °C to +80 °C cable not fixed
purpose use. -40 °C to +80 °C cable fixed
The display does have snap-in housing for installation in a Ambient in operation:
control panel. temperature/humidity 0° to + 50 °C,
30 to 85 % R.H. excluding dew
Material in storage:
Housing ABS-plastic, self-extinguishing -20 °C to +80 °C
Connectors 10 A screw-type terminal strips,
max. 1.5 mm
Protective rating Housing: IP 20
front panel: IP 52,
protection class 2
Installation
Operate only in dry places
Snap-in installation housing:
Fit unit in a recess 28.5 x 70.5 mm
maximum wall thickness: 22 mm
Secure housing with the mounting frame
Respect the wiring diagram
Tighten screws of connectors carefully
PRODUCT DATA
Features
AMV : with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits
AMVX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors
Adjustable evaporating pressure setting ± 0.5 bar
within the evaporating pressure range
Flare connections
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
AMV Interchangeable orifice cartridges
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Specification
Nominal capacity range 0.52 to 22.4 kW R22
(small orifice graduation for
AMVX optimal control behaviour,
interchangeable orifice
cartridges)
Evaporating pressure range see table on page 38
Application Maximum pressure PS 29.0 bar(a)
Automatic expansion valves (constant pressure valves) series Maximum test pressure PF 31.9 bar(a)
AMV are used in general refrigeration and for original Max. ambient temperature 100 °C
equipment.
For plants like dehumidifiers, air driers, water coolers,
ice-making machines or air conditioners.
Materials
Body brass
Thermal head stainless steel
Connection brass
Evaporating pressure
1. Automatic expansion valves with internal pressure equalisation 2. Automatic expansion valves with external pressure equalisation
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A R410A
0.3 0.36 0.52 0.50 0.36 0.36 0.36 0.62
0.5 0.69 0.99 0.95 0.67 0.68 0.69 1.2
0.7 1.0 1.4 1.3 0.92 0.97 0.98 1.6
1.0 1.4 2.0 1.9 1.3 1.4 1.4 2.4
1.5 2.2 3.2 3.1 2.2 2.2 2.3 3.8
AMV
2.0 2.9 4.0 3.9 2.7 2.8 2.9 4.8
AMVX
2.5 4.0 5.8 5.6 3.9 4.1 4.1 6.9
3.0 6.6 9.3 8.9 6.3 6.5 6.6 11.1
3.5 8.7 12.2 11.7 8.3 8.6 8.7 14.6
4.5 11.8 17.0 16.4 11.3 12.0 12.1 20.3
4.75 15.9 22.4 21.6 15.3 15.8 15.9 26.8
* Capacities are based on to= +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
2. Orifice cartridge
VD 0.5
Series
Orifice size
PRODUCT DATA
Features
Smallest dimensions
High performance
Hermetic construction
Wide evaporating pressure range
Adjustable evaporating pressure setting
Solder connections
Internal pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Fixed orifice
Bypass on request
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Specification
Nominal capacity range 1.4 to 29.1 kW R22
Evaporating pressure range 1 - 7 bar(a)
Factory setting for
evaporating pressure 2.2 bar(a)
Application Maximum pressure PS 25.5 bar(a)
Automatic expansion valves (constant pressure valves) series Maximum test pressure PF 28 bar(a)
AEL are used in general refrigeration and for original Max. ambient temperature 100 °C
equipment.
For plants with single injected evaporators and without a Installation
distributor, such as air conditioners, dehumidifiers, air driers,
water coolers or ice-making machines. The valves may be installed in any position.
When soldering the valve, the valve body must not get
Materials warmer than 100 °C.
Body brass Remove plastic cap during soldering
Head stainless steel, brass Constructive modifications at the valve are not allowed.
Capacities
Type Valve size Orifice Nominal capacity (kW)*
size R22 R134a R404A R507A
0.5 0.7 1.4 1.0 0.97 0.98
1.0 1.0 2.0 1.4 1.4 1.4
2.0 2.0 4.0 2.9 2.8 2.9
AEL 3.0 3.0 9.3 6.6 6.5 6.6
4.0 3.5 12.2 8.7 8.6 8.7
5 4.75 22.4 15.9 15.8 15.9
6 5 29.1 20.0 20.5 20.7
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
PRODUCT DATA
Features
TMV / TMVBL: with internal pressure equalisation; for
single injection in installations with one or more
cooling circuits
TMVX / TMVXBL: with external pressure equalisation;
for optimal evaporation effectiveness in all
applications. Obligatory for multiple injection by liquid
distributors
Combi adsorber charge
The same valve can be used for different
refrigerants (see table on page 44)
Controller charge is high sensitive and responsive
TMVX thus lowest possible level of superheat can be
achieved
Charge is not sensitive to effects of temperature on
the capillary tube and valve head
Damping characteristic results in stable control
behaviour
Suitable for systems with hot gas defrosting
Adjustable superheat setting
Flare connections: TMV, TMVX
TMVXBL
Flare / solder connections: TMVBL, TMVXBL
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Application
Interchangeable orifice cartridges
Thermostatic expansion valves series TMV are used in
general refrigeration and for original equipment. Refrigerants: R134a, R401A
R22, R407C, R407A, R422D
Plants with one or more circuits such as refrigerated cabinets
R404A, R507A, R402A, R407B
even with cramped mounting conditions, ice and cream
R410A. R407F
machines, milk cooling units, water chillers, vehicle air
HFO (e.g. R1234yf) and future Blends
conditioning systems, cold stores, and air conditioning
Further refrigerants on request.
systems.
Specification
Materials Nominal capacity range 0.52 to 22.4 kW R22
(small orifice graduation for
Body brass optimal control behaviour,
Thermal head stainless steel interchangeable orifice
cartridges)
Connection solder: copper
flare: brass Evaporating temperature see table on page 44
range
Maximum pressure PS see table on page 44
Maximum test pressure PF see table on page 44
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R407F R404A R507A R410A
0.3 0.36 0.52 0.50 0.56 0.36 0.36 0.62
0.5 0.69 0.99 0.95 1.1 0.68 0.69 1.2
0.7 1.0 1.4 1.3 1.5 0.97 0.98 1.6
1.0 1.4 2.0 1.9 2.2 1.4 1.4 2.4
TMV
1.5 2.2 3.2 3.1 3.5 2.2 2.3 3.8
TMVX
2.0 2.9 4.0 3.9 4.3 2.8 2.9 4.8
TMVBL
2.5 4.0 5.8 5.6 6.3 4.1 4.1 6.9
TMVXBL
3.0 6.6 9.3 8.9 10.1 6.5 6.6 11.1
3.5 8.7 12.2 11.7 13.2 8.6 8.7 14.6
4.5 11.8 17.0 16.4 18.5 12.0 12.1 20.3
4.75 15.9 22.4 21.6 24.3 15.8 15.9 26.8
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
TMVBL / TMVXBL VD
2. Orifice cartridge
VD 0.5
Series
Orifice size
Special Accessory:
Adapter series LA for solder connection at the inlet for 6 mm,
10 mm, 1/4”, 3/8”.
PRODUCT DATA
Features
Only one valve body necessary for internal and
external pressure equalisation. Connection for
pressure coupler is integrated in the solder base.
TMVL: Valve body and solder base with internal
pressure equalisation; for single injection in
installations with one or more cooling circuits.
TMVLX: Valve body and solder base with external
pressure equalisation; for optimal evaporation
effectiveness in all applications. Obligatory for
multiple injection by liquid distributors.
Combi adsorber charge
The same valve can be used for different
refrigerants (see table on page 48)
Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
TMVLX-W
Charge is not sensitive to effects of temperature on
the capillary tube and valve head
Damping characteristic results in stable control
behaviour
Suitable for systems with hot gas defrosting
TMVLX-D Adjustable superheat setting
Solder connections
Solder base available in two-way construction and in
Application angle construction
Thermostatic expansion valves series TMVL are used in Extreme durable due to stainless steel head and
general refrigeration and for original equipment. stainless steel diaphragm welded using protective gas
Plants with one or more refrigerant circuits such as Interchangeable orifice cartridges
refrigerated cabinets even with cramped mounting conditions,
ice and cream machines, milk cooling systems, cold stores, Refrigerants: R134a, R401A
air conditioning systems and heat pumps. R22, R407C, R407A, R422D
R404A, R507A, R402A, R407B
R124, R227, R410A, R236fa, R407F
HFO (e.g. R1234yf) and future Blends
Materials Further refrigerants on request.
Body brass
Specification
Thermal head stainless steel
Nominal capacity range 0.52 to 22.4 kW R22
Connection tubes copper
(small orifice graduation for
optimal control behaviour, inter-
changeable orifice cartridges)
Evaporating temp. range see table on page 48
Maximum pressure PS see table on page 48
Maximum test pressure PF see table on page 48
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R407F R404A R507A R410A
0.3 0.36 0.52 0.50 0.56 0.36 0.36 0.62
0.5 0.69 0.99 0.95 1.1 0.68 0.69 1.2
0.7 1.0 1.4 1.3 1.5 0.97 0.98 1.6
1.0 1.4 2.0 1.9 2.2 1.4 1.4 2.4
1.5 2.2 3.2 3.1 3.5 2.2 2.3 3.8
TMVL 2.0 2.9 4.0 3.9 4.3 2.8 2.9 4.8
2.5 4.0 5.8 5.6 6.3 4.1 4.1 6.9
3.0 6.6 9.3 8.9 10.1 6.5 6.6 11.1
3.5 8.7 12.2 11.7 13.2 8.6 8.7 14.6
4.5 11.8 17.0 16.4 18.5 12.0 12.1 20.3
4.75 15.9 22.4 21.6 24.3 15.8 15.9 26.8
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
TMVL
10 mm x VD 0.5
VLS X W
12 mm Series
Series Orifice size
Pressure equalisation:
X = external
() = internal
Solder connection ODF
(inlet x outlet)
D = two-way construction
W = angle construction
PRODUCT DATA
Features
TMXL: TMX and solder base, two-way construction or
angle construction
TMXB: TMX and flare base, two way construction
Damped gas charge with pressure limiting MOP
Liquid charge
Adjustable superheat setting
Solder connections or flare connections
External pressure equalisation is integrated in the
valve body
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Balanced port construction
TMXB Interchangeable orifice cartridges
Refrigerants: R22, R23, R134a, R227, R236fa,
R401A, R404A, R407C, R410A, R422D,
R507A, R508B, ISC89, R407F
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
TMXL
Specification
Nominal capacity range 17.0 to 75.1 kW R22
Application
Evaporating temperature
Thermostatic expansion valves series TMX are used in range see table on page 52
general refrigeration and for original equipment.
Maximum pressure PS see table on page 52
Plants with one or more refrigerant circuits such as
refrigerated cabinets, deep freezing plants, milk cooling units, Maximum test pressure PF see table on page 52
water chillers, air conditioning systems, cold stores and heat Max. ambient temperature 100 °C
pumps. For plants with single and multiple injections, with Max. bulb temperature gas charge: 140 °C
high or low flow resistance, for all kind of distributors. liquid charge: 70 °C
Static superheat approx. 3.5 K
Length of capillary tube 2m
Materials Bulb diameter 16 mm
Body brass
Thermal head stainless steel
Base brass
Capacities
Nominal capacitiy (kW)*
Type Orifice size
R22 R134a R404A R407C R407F R410A R507A R124 R227 R236fa
4.5 17.0 11.8 12.0 16.4 18.5 20.3 12.1 9.4 6.6 6.0
TMXL 4.75 22.4 15.9 15.8 21.6 24.3 26.8 15.9 12.4 8.7 8.0
5 29.1 20.0 20.5 28.0 31.6 34.8 20.7 16.1 11.3 10.3
and 6 42.4 27.6 29.8 40.8 46.0 50.8 30.1 23.5 16.4 15.1
7 54.5 35.3 38.3 52.5 59.1 65.3 38.7 30.2 21.1 19.4
TMXB 8 64.1 43.3 45.1 61.8 69.6 76.9 45.6 35.6 24.9 22.8
10 75.1 51.0 52.8 72.3 81.5 90.0 53.3 41.7 29.1 26.7
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For refrigerant R124, R227 and 236fa: Capacities are based on to = +10 °C, tc = +50 °C and 1 K subcooled liquid
refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
TMX
XD XBS – two-way
16 mm x XD 10
XLS W
22 mm Series
Series Orifice size
XLS = solder connection
XBS = flare connection
Connection size
D = two-way construction
W = angle construction
PRODUCT DATA
Features
Gas charge with MOP for quick response time adapted
to small evaporators
Wide evaporating temperature range
Smallest dimensions
Fixed superheat setting
Warm thermal head provides best reliability
Solder connections
Internal pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Fixed orifice
Bypass on request
Refrigerants: R134a, R22, R404A, R407C, R507A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Specification
Nominal capacity range 0.52 to 4.0 kW R22
Evaporating temperature
range see table on page 56
Maximum pressure PS see table on page 56
Application Maximum test pressure PF see table on page 56
Thermostatic expansion valves series TLK are used for serial Max. ambient temperature 100 °C
produced systems such as drink dispensers, beer coolers, ice Max. bulb temperature 140 °C
cream machines, milk cooling units, water chillers and vehicle Static superheat approx. 4 K
air conditioning systems. For single injected evaporators.
Length of capillary tube 1m
Bulb diameter 12 mm
Materials
Body brass
Thermal head stainless steel
Connection tubes copper
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R404A R407C R507A
0.3 0.36 0.52 0.36 0.50 0.36
0.5 0.69 0.99 0.68 0.95 0.69
0.7 1.0 1.4 0.97 1.3 0.98
TLK
1.0 1.4 2.0 1.4 1.9 1.4
1.5 2.2 3.2 2.2 3.1 2.3
2.0 2.9 4.0 2.8 3.9 2.9
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
Installation
The valves may be installed in any position. Information for original equipment manufacturers:
The bulb should preferably be positioned on the upper half The valve series TLK can be customised to the
of a horizontal suction line but never after a liquid trap. As requirements of your series device in an optimum way.
a general rule, bulbs of expansion valves should be Contact us!
insulated to prevent them being affected by the ambient
temperature.
In case of ice formation at the mounting site of the bulb,
we advise to use a bulb clamp instead of clips.
When soldering the valve, the valve body must not get
warmer than 100 °C.
Do not bend or squeeze the bulb!
Constructive modifications at the valve are not allowed.
PRODUCT DATA
Features
TLE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
TLEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
Combi adsorber charge as standard
The same valve can be used for different
refrigerants (see table on page 60)
Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
TLE Charge is not sensitive to effects of temperature on
the capillary tube and valve head
damping characteristic results in stable control
behaviour
Gas charge for deep freeze applications
Adjustable superheat setting
Warm thermal head provides best reliability
Solder connections
TLEX
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Application Fixed orifice
Thermostatic expansion valves series TLE and TLEX are Refrigerants: R134a, R401A
used in plants with one or more refrigerant circuits, in R22, R407C, R407A, R422D
particular for series systems such as heat pumps, refrigerated R404A, R507A, R402A, R407B
cabinets, deep freeze chests, freezers, fermentation R410A
interrupters, ice and cream machines, compact systems in R23, ISC 89, R508A, R508B
refrigeration and air conditioning. HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Materials
Specification
Body brass
Thermal head Nominal capacity range 0.99 to 17.0 kW R22
stainless steel
(small orifice graduation for
Connection tubes copper optimal control behaviour)
Evaporating temperature
range see table on page 60
Maximum pressure PS see table on page 60
Maximum test pressure PF see table on page 60
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R410A R404A R507A
0.5 0.69 0.99 0.95 1.2 0.68 0.69
0.7 1.0 1.4 1.3 1.6 0.97 0.98
1.0 1.4 2.0 1.9 2.4 1.4 1.4
1.5 2.2 3.2 3.1 3.8 2.2 2.3
TLE
2.0 2.9 4.0 3.9 4.8 2.8 2.9
TLEX
2.5 4.0 5.8 5.6 6.9 4.1 4.1
3.0 6.6 9.3 8.9 11.1 6.5 6.6
3.5 8.7 12.2 11.7 14.6 8.6 8.7
4.5 11.8 17.0 16.4 20.3 12.0 12.1
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
1.5
2.0 10 mm ODF 12 mm ODF 6 mm ODF
TLE 2.5
approx. 0.32
TLEX 3.0
3/8" ODF 1/2" ODF 1/4" ODF
3.5
10 mm ODF 16 mm ODF 6 mm ODF
3/8" ODF 5/8" ODF 1/4" ODF
4.5
12 mm ODF 16 mm ODF 6 mm ODF
1/2" ODF 5/8" ODF 1/4" ODF
Information for original equipment manufacturers: One turn of adjusting spindle alters superheat setting by
approx. 0.25 bar. Increase of superheat setting results in a
The valve series TLE can be customised to the
lower MOP-value and vice versa.
requirements of your series device in an optimum way.
Contact us!
PRODUCT DATA
Features
TBE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
TBEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
Combi adsorber charge as standard
The same valve can be used for different
refrigerants (see table on page 64)
Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
Charge is not sensitive to effects of temperature on
TBEX 0.5 - 4.5 two-way the capillary tube and valve head
damping characteristic results in stable control
behaviour
Optional available with gas charge and MOP
Adjustable superheat for two-way construction
Fixed superheat setting for angle construction
Warm thermal head provides best reliability
TBEX 0.5 - 4.5 angle
Flare connections
Extreme durable due to stainless steel head and
Application stainless steel diaphragm welded using protective gas
Thermostatic expansion valves series TBE are used in plants Fixed orifice
with one or more refrigerant circuits, especially for series Refrigerants: R134a, R401A
installations mobile air-conditioning and cooling units with R22, R407C, R407A, R422D
flare connection, e. g. bus AC, train AC, transport cooling. R404A, R507A, R402A, R407B
HFO (e.g. R1234yf) and future Blends
Materials Further refrigerants on request.
Body brass
Specification
Thermal head stainless steel
Nominal capacity range 0.99 to 17.0 kW R22
Connections brass
(small orifice graduation for
optimal control behaviour)
Evaporating temperature
range see table on page 64
Maximum pressure PS see table on page 64
Maximum test pressure PF see table on page 64
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A
0.5 0.69 0.99 0.95 0.67 0.68 0.69
0.7 1.0 1.4 1.3 0.92 0.97 0.98
1.0 1.4 2.0 1.9 1.3 1.4 1.4
1.5 2.2 3.2 3.1 2.2 2.2 2.3
TBE
2.0 2.9 4.0 3.9 2.7 2.8 2.9
TBEX
2.5 4.0 5.8 5.6 3.9 4.1 4.1
3.0 6.6 9.3 8.9 6.3 6.5 6.6
3.5 8.7 12.2 11.7 8.3 8.6 8.7
4.5 11.8 17.0 16.4 11.3 12.0 12.1
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
PRODUCT DATA
Features
TOE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
TOEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
Combi adsorber charge as standard
The same valve can be used for different
refrigerants (see table on page 68)
Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A
0.5 0.69 0.99 0.95 0.67 0.68 0.69
0.7 1.0 1.4 1.3 0.92 0.97 0.98
1.0 1.4 2.0 1.9 1.3 1.4 1.4
1.5 2.2 3.2 3.1 2.2 2.2 2.3
TOE
2.0 2.9 4.0 3.9 2.7 2.8 2.9
TOEX
2.5 4.0 5.8 5.6 3.9 4.1 4.1
3.0 6.6 9.3 8.9 6.3 6.5 6.6
3.5 8.7 12.2 11.7 8.3 8.6 8.7
4.5 11.8 17.0 16.4 11.3 12.0 12.1
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
PRODUCT DATA
Features
Damped gas charge with MOP as standard
Optional available with liquid charge
Adjustable superheat setting
Warm thermal head provides best reliability
Solder connections
External pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Single port construction, without high pressure
compensation
Fixed orifice
Refrigerants: R22, R134a, R404A, R407C, R410A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Specification
Nominal capacity range 22.4 to 42.4 kW R22
Evaporating temperature range see table on page 72
Maximum pressure PS see table on page 72
Maximum test pressure PF see table on page 72
Max. ambient temperature 100 °C
Application
Max. bulb temperature gas charge: 140 °C
Thermostatic expansion valves series TLESX are used in liquid charge: 70 °C
plants with one or more refrigerant circuits, in particular for
series installations such as bus and train air-conditioning Static superheat approx. 3 K
units, mobile air-conditioning and cooling units, chiller units Length of capillary tube 2m
and heat pumps. Bulb diameter 16 mm
Materials
Body brass
Thermal head stainless steel
Connection tubes copper
Capacities
Nominal capacity (kW)*
Type Orifice size
R22 R134a R404A R407C R410A
4.75 22.4 15.9 15.8 21.6 26.8
TLESX 5 29.1 20.0 20.5 28.0 34.8
6 42.4 27.6 29.8 40.8 50.8
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
3
Variation of static superheat setting [K]
-1
-2
T L E S X 4 ,7 5
-3
T LESX 5 + 6
-4
-5
7 9 11 13 15 17 19 21 23 25
c o n d e n s a tio n p re s s u re [b a r]
PRODUCT DATA
Features
Damped gas charge with MOP as standard
Optional available with liquid charge
Adjustable superheat setting
Warm thermal head provides best reliability
Solder connections
External pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Balanced port construction
Fixed orifice
Refrigerants: R22, R134a, R404A, R407C, R410A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Specification
Nominal capacity range 22.4 to 54.5 kW R22
Evaporating temperature
range see table on page 76
Maximum pressure PS see table on page 76
Maximum test pressure PF see table on page 76
(simultaneous on all
Application connections)
Thermostatic expansion valves series TLEX are used in Max. ambient temperature 100 °C
plants with one or more refrigerant circuits, in particular for
series installations such as chiller units, heat pumps, and Max. bulb temperature gas charge: 140 °C
transport cooling. liquid charge: 70 °C
Static superheat approx. 3.5 K
Materials Length of capillary tube 2m
Body brass Bulb diameter 16 mm
Thermal head stainless steel
Connection tubes copper
Capacities
Nominal capacity (kW)*
Type Orifice size
R22 R134a R404A R407C R410A
4.75 22.4 15.9 15.8 21.6 26.8
5 29.1 20.0 20.5 28.0 34.8
TLEX
6 42.4 27.6 29.8 40.8 50.8
7 54.5 35.3 38.3 52.5 65.3
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
PRODUCT DATA
Features
Damped gas charge with MOP as standard
Optional available with liquid charge
Adjustable superheat setting
Warm thermal head provides best reliability
Solder connections
External pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Balanced port construction
Fixed orifice
Refrigerants: R22, R134a, R404A, R407C, R410A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Specification
Nominal capacity range 64.1 to 95.8 kW R22
Evaporating temperature
range see table on page 80
Maximum pressure PS see table on page 80
Maximum test pressure PF see table on page 80
(simultaneous on all
Application connections)
Thermostatic expansion valves series TLEX are used in Max. ambient temperature 100 °C
plants with one or more refrigerant circuits, in particular for
series installations such as air conditioning units, chiller units Max. bulb temperature gas charge: 140 °C
and heat pumps. liquid charge: 70 °C
Static superheat approx. 3.5 K
Materials Length of capillary tube 2m
Body brass Bulb diameter 16 mm
Thermal head stainless steel
Connection tubes copper
Capacities
Nominal capacity (kW)*
Type Orifice size
R22 R134a R404A R407C R410A
8 64.1 43.3 45.1 61.8 76.9
TLEX 10 75.1 51.0 52.8 72.3 90.0
11 95.8 65.0 67.4 92.3 115
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
PRODUCT DATA
Features
CVC: Orifice size 4.0,
equivalent to 1 kW bypass capacity R134a
HLE: Orifice size 4.5S,
equivalent to 1.5 kW bypass capacity R134a
Smallest dimensions
High performance
Hermetic construction
Adjustable suction pressure limitation
Solder connections
Internal pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Fixed orifice
Refrigerants: all CFC, HCFC, HFC
CVC HFO (e.g. R1234yf) and future Blends
not for ammonia
HLE
Specification
Nominal capacity see table on page 84
Adjusting range for 1 - 6 bar(a) (CVC)
suction pressure limitation 1 - 9 bar(a) (HLE)
Application Factory setting 3.2 bar(a) (CVC)
Hot gas bypass valves series CVC and HLE are used to 3.5 bar(a) (HLE)
adjust the compressor capacity to the actual evaporator Maximum pressure PS 25.5 bar(a)
capacity in a refrigerating plant.
Maximum test pressure PF 28 bar(a)
The hot gas bypass valve can be installed in a bypass tube
between the hot gas line and suction line. The suction Max. ambient temperature 100 °C
pressure is downward limited by flowing hot gas from the high
pressure to the low pressure side. Installation
For plants in general refrigeration and for original equipment
such as dehumidifiers, air driers, water coolers or ice-making The valves may be installed in any position.
machines. When soldering the valve, the valve body must not get
warmer than 100 °C.
Materials Remove plastic cap during soldering
Body brass Constructive modifications at the valve are not allowed.
Head stainless steel, brass
Connection tubes copper
Adjustment
One complete revolution of the adjusting screw effects an
alternation of the suction pressure limitation by approx.
0.5 bar (CVC) resp. 0.4 bar (HLE).
Capacities
Condensing pOffset Bypass-capacity QN
Valve temperature tc (bar) (kW)
Type
size (°C) R134a R407C R404A
0.5 0.62 1.05 0.88
35
0.7 0.85 1.45 1.20
CVC 4.0
0.5 0.71 1.16 0.88
50
0.7 1.00 1.60 1.20
0.5 0.98 1.67 1.40
35
0.7 1.37 2.33 1.95
HLE 4.5S
0.5 1.13 1.86 1.41
50
0.7 1.57 2.60 1.97
Evaporating temperature to: 0 °C; Hot gas superheat tV2oh: 25 K
CVC HLE
PRODUCT DATA
Features
Compact design
High performance
Hermetic construction
Adjustable suction pressure limitation
Solder connections
External pressure equalisation
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Balanced port construction
Fixed orifice
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Materials Adjustment
Body brass One complete revolution of the adjusting screw effects an
Head stainless steel, brass alternation of the suction pressure limitation by approx.
0.5 bar.
Connection tubes copper
Turning clockwise = Higher suction pressure
Turning
= Lower suction pressure
counterclockwise
Capacities
Condensing pOffset Bypass-capacity QN (kW)
Type Orifice size temperature tc
R134a R407C R404A
(°C) (bar)
0.5 0.98 1.67 1.40
35
0.7 1.37 2.33 1.95
4.75
0.5 1.13 1.86 1.41
50
0.7 1.57 2.60 1.97
0.5 1.29 2.18 1.83
35
0.7 1.79 3.04 2.55
5
0.5 1.47 2.43 1.84
50
0.7 2.05 3.39 2.57
0.5 1.92 3.26 2.73
35
0.7 2.68 4.54 3.81
6
0.5 2.20 3.64 2.75
50
0.7 3.07 5.07 3.83
0.5 2.35 3.98 3.34
35
0.7 3.27 5.55 4.65
HLEX 7
0.5 2.69 4.44 3.36
50
0.7 3.75 6.19 4.68
0.5 2.66 4.52 3.79
35
0.7 3.72 6.31 5.29
8
0.5 3.05 5.04 3.81
50
0.7 4.26 7.04 5.32
0.5 3.29 5.57 4.67
35
0.7 4.58 7.77 6.52
10
0.5 3.76 6.22 4.70
50
0.7 5.25 8.67 6.56
0.5 4.50 7.63 6.40
35
0.7 6.29 10.66 8.94
11
0.5 5.16 8.52 6.45
50
0.7 7.20 11.90 9.00
Evaporating temperature to: 0 °C; hot gas superheat tV2oh: 25 K
Application Samples
PRODUCT DATA
Features
Suction gas controlled liquid injection valves
Part programme containing:
Valve body head, orifice cartridge, connection base
Honeywell NMVL:
- Only one valve body head needed both for internal
and external pressure equalisation
- Connection for pressure coupler integrated
in the solder base
- solder base two-way or angle construction
Honeywell NMX:
- Balanced port
- External pressure equalisation integrated in the
valve body head
- solder base two-way or angle construction
- flare base two way construction
Adjustable superheat setting
NMVL
Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Interchangeable orifice cartridges
Liquid charge
Refrigerants: R134a, R22, R404A, R407C, R507A
NMX HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Application Specification
Nominal capacity range 0.52 to 75.1 kW R22
Honeywell thermostatic liquid injection valves series NMVL
and NMX are used in refrigeration applications to reduce the (small orifice graduation for
temperature of the suction gas. optimal control behaviour)
Depending on the superheat of the compressor suction gas, Temperature range -50 °C to +65 °C
liquid refrigerant is injected into the suction line. The Maximum pressure PS See table on page 90
refrigerant is evaporating and thereby the suction gas is
Maximum test pressure PF See table on page 90
cooled down.
Suitable for plants in general refrigeration and for serial Max. ambient temperature 70 °C
products such as air driers, dehumidifiers, chiller units or Max. bulb temperature 70 °C
ice-making machines with hot gas bypass control valves, for Static superheat See table on page 90
temperature reduction in multiple stage units and for suction Length of capillary tube NMVL: 1.5 m
gas cooled compressors.
NMX: 3.0 m
Bulb diameter NMVL: 12 mm
NMX: 16 mm
Materials
Body, base brass
Thermal head stainless steel
Connections copper or brass
Capacities
Type Orifice size Nominal capacity (kW)*
R134a R22 R404A R407C R507A
0.3 0.36 0.52 0.36 0.50 0.36
0.5 0.69 0.99 0.68 0.95 0.69
0.7 0.96 1.4 0.97 1.3 0.98
1.0 1.4 2.0 1.4 1.9 1.4
1.5 2.2 3.2 2.2 3.1 2.3
NMVL 2.0 2.9 4.0 2.8 3.9 2.9
2.5 4.0 5.8 4.1 5.6 4.1
3.0 6.6 9.3 6.5 8.9 6.6
3.5 8.7 12.2 8.6 11.7 8.7
4.5 11.8 17.0 12.0 16.4 12.1
4.75 15.9 22.4 15.8 21.6 15.9
4.5 11.8 17.0 12.0 16.4 12.1
4.75 15.9 22.4 15.8 21.6 15.9
5 20.0 29.1 20.5 28.0 20.7
NMX 6 27.6 42.4 29.8 40.8 30.1
7 35.3 54.5 38.3 52.5 38.7
8 43.3 64.1 45.1 61.8 45.6
10 51.0 75.1 52.8 72.3 53.3
* Capacities are based on to = +4 °C. tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
NMVL
NMX
XD XBS – two-way
NMVL DA VD 0.5
Series (NMVL, NMX) Series (VD, XD)
Code for thermal charge Orifice size
3. Connection base
Application Sample
4 1 2 5
Power control with hot gas bypass valve and temperature reduction
of suction gas with liquid injection valve
PRODUCT DATA
Features
MA: direct operated, angle construction
MD: direct operated, two way construction
MS: pilot operated, two way construction
Normally closed
Hermetic construction
Low pressure drop
MA High performance
MD Direct operated: no minimum pressure differential
required to open the valve
Pilot operated: minimum pressure differential of
0.05 bar required to open the valve
Solder and flare connections
Coils for AC and DC
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Specification
MS
Nominal capacity see tables on page 96
Maximum pressure PS 35 bar(a)
Application Maximum test pressure PF 50 bar(a)
Min. pressure differential MA, MD: 0 bar
Solenoid valves series M are used in general refrigeration
and for original equipment to cut off/activate the refrigerant MS: 0.05 bar
flow in a refrigerating plant. Max. pressure differential MS: 2 bar
The solenoid valves can be installed in the liquid line, hot gas Max. opening pressure AC-coil: MA, MD: 25 bar
line and suction line of a refrigerating unit. differential MOPD MS: 30 bar
DC-coil: MA, MD: 21bar
Materials MS: 21 bar
Body brass, stainless steel Max. medium temperature 125 °C
Seal material PTFE Min. medium temperature -45 °C
Connection tubes solder: copper Max. ambient temperature 80 °C
flare: brass Min. ambient temperature -40 °C
Coil copper, steel, Crastin Number of operating cycles > 1,5 million
Standard coil voltages AC: 230V, 110V, 24V
DC: 230V, 24V
further voltages on request
Voltage tolerance AC: ±10%
DC: +10%, -5%
QN = Qo x fTF x fPF
QN nominal capacity (according to table on page 96)
Qo refrigeration capacity
fTF correcting factor for evaporating and liquid
temperature
fPF correcting factor for pressure loss across the valve
Correcting factor fTF for the change of capacity according to the operating temperatures
Correcting factor fPF for the change of capacity according to the chosen pressure loss across the valve
Pressure loss across valve p (bar) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70
Correcting factor fPF 2.83 2.00 1.63 1.41 1.26 1.15 1.07 1.00 0.94 0.89 0.85 0.82 0.78 0.76
If the hot gas temperature is changed by ±10 °C the valve capacity changes (inversely proportional) by ±2,5 %.
With other evaporating temperatures to the capacities above should be multiplied by the following correcting factors:
QN = Qo x fTS x fPS
QN nominal capacity (according to table on page 96)
Qo refrigeration capacity
fTS correcting factor for evaporating and liquid
temperature
fPS correcting factor for pressure loss across the valve
Correcting factor fTS for the change of capacity according to the operating temperatures
Correcting factor fPS for the change of capacity according to the chosen pressure loss across the valve
Pressure loss across valve p (bar) 0.05 0.075 0.10 0.15 0.20 0.30 0.40 0.50 0.60
Correcting factor fPS 1.73 1.41 1.22 1.00 0.87 0.71 0.61 0.55 0.50
2. Solenoid Coil
Type of coil, capacity For Solenoid Valve Voltage, frequency Voltage tolerance
MC 062, 8 W MA 062(S)(MMS) 230 V, 50/60 Hz
MD 062(S)(MMS) 110 V, 50/60 Hz ±10 %
24 V, 50/60 Hz
MC 102-227, 13 W MD 103(S)(MMS) 230 V, 50/60 Hz
MS 103-227(S)(MMS) 110 V, 50/60 Hz ±10 %
24 V, 50/60 Hz
MC 102-227, 20 W MD 103(S)(MMS)
24 V DC +10 %
MS 103-227(S)(MMS)
230 V DC -5 %
International protection rating IP65, coil incl. e.l.c.b.-protected plug to DIN 43650 with cable gland; conduit thread PG11.
MA MD MS
Installation
Position of plunger tube should be from upright to Voltage of coil and network must correspond.
horizontal position. The flat spade terminals is the earth connection. The
Arrow on valve body must correspond with flow direction. protective conductor must also be connected at the plant.
Keep 45 mm distance clear above the valve for Do not energize the coil before assembling on the valve
assembly/disassembly of coil. body.
Fit solenoid valve so that it is drip proof. All gaskets must be fitted carefully in order to achieve
Solder valves: protection to IP65.
Remove cap nut, coil and gaskets before soldering. Tighten fixing screw of connector.
Max. temperature of valve body: 125 °C. Constructive modifications at the valve are not allowed.
PRODUCT DATA
Features
Hermetically welded type
Low pressure drop
Copper plated solder connections
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Specification
Nominal capacity range see table on page 104
Maximum pressure PS 43 bar(a)
32.5 bar(a) (RV-07S)
11 bar(a) at t < -20 °C
Maximum test pressure PF 61.5 bar(a)
46.5 bar(a) (RV-07S)
15.7 bar(a) at t < -20 °C
Maximum temperature 120 °C
Minimum temperature -40 °C
Application
Check valves series RV are installed in the liquid line, hot gas
line or suction line of a refrigerated plant to permit the flow of
the refrigerant only in one direction. This is realised by a
spring-loaded piston which opens the valve only in one
direction.
Materials
Housing, piston brass
Sealing material Teflon
Connection tubes copper plated brass
Capacities
Type P* kv- QN (kW)
(bar) value
Liquid line Suction gas line Hot gas line
(m3/h)
R22 R134a R404A R407C R22 R134a R404A R407C R22 R134a R404A R407C
R507A R410A R507A R410A R507A R410A
RV-02 MMS
0.06 0.37 6.7 6.2 4.4 6.2 1.0 0.8 0.8 1.0 4.4 3.2 3.7 4.7
RV-02 S
RV-03 MMS
0.06 1.75 31.7 29.3 20.8 29.2 4.7 3.8 3.8 4.5 20.8 15.1 17.5 22.2
RV-03 S
RV-04 MMS
0.05 3.27 59.2 54.8 38.9 54.6 8.8 7.1 7.1 8.4 38.0 28.3 32.7 40.6
RV-04 S
RV-05 S 0.05 3.64 65.9 61.0 43.3 60.7 9.8 7.9 7.9 9.3 43.3 31.5 36.4 46.3
RV-07 S 0.03 7.50 136.4 126.4 89.5 125.7 20.5 16.3 17.0 19.5 87.5 63.8 75.0 93.5
* P = min. pressure drop at which the valve is completely open
The nominal capacity QN as mentioned in table above refers to the following conditions:
Liquid and suction gas:
evaporating temperature to: +4 °C
condensing temperature tc: +38 °C
pressure drop: 0.15 bar
Hot gas:
temperature of hot gas: +85 °C
pressure drop: 1.0 bar
PRODUCT DATA
Features
Large display area
Moisture indicator
Low pressure loss
SLI with solder connections on both sides
SBI with flare connections on both sides
SLI
SBIA with flare connections,
female thread x male thread
Refrigerants: all CFC, HCFC, HFC,
HFO (e.g. R1234yf) and future Blends
not for R12, R502 and ammonia
Specifications
SBI Moisture indicator range see table on page 106
Max. ambient temperature TS 80 °C
Diameter display area 22.5 mm
Maximum Maximum
Type
SBIA pressure PS test pressure PF
SLI 6; SLI 1/4
SLI 10; SLI 3/8
SLI 12; SLI 1/2 44 bar(a) 63 bar(a)
Application SLI 15
Sight glasses series SLI/SBI/SBIA show the condition of the SLI 16 (5/8)
refrigerant flowing through the lines in the refrigerating plant,
SLI 18; SLI 3/4
for example it is possible to see if the refrigerant in the liquid
line is free of bubbles. SLI 22 (7/8)
36 bar(a) 51.5 bar(a)
The moisture indicator shows the moisture content in the SBI
refrigerant. SBIA
SLI 28; SLI 1 1/8 35 bar(a) 50 bar(a)
Materials
Housing brass
Display area pressure resistant glass,
indicator paper
Connection tubes Solder: copper
Flare: brass
Moisture Indicator
The colour of the indicator is a measure for the moisture load Green colour: Moisture free.
of the refrigerant inside the plant. Only a moisture-free refrigerant assures no trouble with the
The range of indication depends on the refrigerant: expansion valve coming from humidity.
SBI SBIA
Features
Liquid line filter drier
Drying agent in bulk
Low pressure drop
High performance
Hermetic construction
Solder or flare connections
FF ...MMS: solder connection in mm
FF ...S: solder connection in inch
FF ...: flare connection
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Specification
Nominal capacity see tables on page 110
Water adsorption see table on page 111
Maximum pressure PS 43 bar(a)
40 bar(a) (for FF 410)
11 bar(a) at t < -20 °C
Maximum test pressure PF 61.5 bar(a)
57.2 bar(a) (for FF 410)
Application 15.7 bar(a) at t < -20 °C
Filter driers series FF are used for filtration of impurities by Max. operating temperature 80 °C
microscopic filters and to take away moisture from the
refrigerant. Min. operating temperature -40 °C
The filter driers are placed in the liquid line of airconditioning,
refrigeration and deep freeze systems. Installation
Any mounting position in the liquid line.
Materials Flow in direction of arrow!
Housing steel When soldering the filter drier, the housing must not get
Internals steel warmer than 160 °C.
Drier molekularsieve, activated alumina Constructive modifications at the filter drier are not
allowed.
Connections solder: copper, copper plated steel or
steel**
flare: nickel plated steel
PRDUCT DATA
Features
Short connection fittings
Compact construction
Flexible pipe, braid and shoulder made of stainless
steel
Frost resistant construction - no collecting of
condensation water within the corrugated area
Suitable for vertical installation
Laser welded
Connection fittings made of copper
No preventive measures from overheating necessary
when soldering
Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia
Specification
Maximum pressure PS 35 bar(a)
Maximum test pressure PF 1.5 x PS
Maximum temperature 250 °C
Minimum temperature -100 °C
Application
Vibration absorbers series SA are installed in refrigerated
plants to minimize vibrations on the pipes caused by the
compressor. Furthermore they decrease noise and
compensate small thermal displacements.
Materials
Flexible pipe stainless steel
Braid stainless steel
Shoulder stainless steel
Connection fittings copper
Solenoid valves
M A 06 2 MMS
M D 10 3 S MA MD MS
M S 16 5
Valve size
S B I 10 SBIA
SLI
S B I A 12
Indicator
Filter driers
FF 05 2
FF
FF 08 3 S
FF 16 4 MMS
Filter size
Electronic Controls
P TI 6 10
P CR 1 10
PCR-110
P CR 3 00 RC PCR-100 PTI-610
P CR 4 10
A E L
A MV X
AMVX AMV
A MV AEL
Series of valve E MV
Series of valve MV M
Solder bases for series TMVL and NMVL Löt/Bördelsockel für Typenreihe TMX und NMX
two-way angle Two-way angle
XLS
VLS
T L E
T O E X
T L ES X TOEX
TLE TLEX 8-11 TLESX
Pressure equaliser () = internal, eXternal
Series of valve K E ES
• Link Products
Technical information, data
sheets, mounting guidelines
and certificates to download
• Link Selection Software
Selection software „Valve Tool“