Product Catalogue

Cooling Components
• Electronic Controls
• Expansion Valves
• Hot Gas Bypass Valves
• Liquid Injection Valves
• Solenoid Valves
• Check Valves
• Sight Glasses
• Filter Driers
• Vibration Absorbers
Product Catalogue Cooling Components
Content Overview
Designation Page

Electronic Controls
Electronic Expansion Valves
EEV 9
Electronic Superheat Controllers
SHC 15
Accessories for SHC
PSR, TS 19
Electronic Suction Pressure Regulation Valves
ESDR 25
Electronic Thermostats and Cold Store Controls
PCR-100/110 29
PCR-300/310/410/300RC 31
Electronic Temperature Displays
PTI-610 35
Automatic Expansion Valves
Valves with interchangeable orifice
AMV (AMV, AMVX) 37
Valves with fixed orifice
AEL, AEL with Bypass 41
Thermostatic Expansion Valves
Valves with interchangeable orifice
TMV (TMV, TMVX, TMVBL, TMVXBL) 43
TMVL (TMVL, TMVLX) 47
TMX (TMXB, TMXL) 51
Valves with fixed orifice
TLK 55
TLE 0.5 – 3.0 59
TLEX 0.5 – 4.5 59
TBEX 0.5 – 4.5 63
TOEX 0.5 – 4.5 67
TLESX 4.75 – 6 71
TLEX 4.75 – 7 75
TLEX 8 – 11 79
Hot Gas Bypass Valves
CVC, HLE 83
HLEX 4.75 – 7, HLEX 8 – 11 85
Liquid Injection Valves
NMVL 89
NMX 89
Solenoid Valves
M (MA, MD, MS) 95
Check Valves
RV 103
Sight Glasses
SBI, SBIA, SLI 105
Filter Driers
FF 109
Vibration Absorbers
SA 113
Nomenclature 119
Honeywell Product Portfolio 121

EN0H-0376GE23 R1014 · Subject to change without notice 3


Product Overview

Series Description Page

EEV Electronic Expansion Valves 9


bipolar stepper motor and bidirectional flow direction

SHC Electronic Superheat Controllers 15


Automatic adaptation to the evaporator’s MSS
Balancing of the lowest possible superheat
Learning behavior with regards to the history of the operating points
Automatic tracking of controller parameters

ESDR Electronic Suction Pressure Regulation Valves 25


stepper motor operated, continuous control behaviour, Balanced Port, copper
solder connections, low pressure drop, kv – value = 17 m³/h, equivalent to 38
kW cooling capacity R404A

PCR Electronic Thermostats and Cold Store Controls 29


temperature- and cold store controls for snap-in installation and standard
DIN-rail

PTI Electronic Temperature Display 35


temperature display for snap-in installation

AMV Automatic Expansion Valves 37


adjustable evaporating pressure, flare connections, internal pressure
equalisation, interchangeable orifice cartridges

AMVX Automatic Expansion Valves 37


adjustable evaporating pressure, flare connections, external pressure
equalisation, interchangeable orifice cartridges

AEL Automatic Expansion Valves 41


adjustable evaporating pressure, solder connections, internal pressure
equalisation, fixed orifice, bypass optional

TMV Thermostatic Expansion Valves 43


internal pressure equalisation, combi adsorber charge for several refrigerants,
adjustable superheat set, flare connections, interchangeable orifice cartridges

4 EN0H-0376GE23 R1014 · Subject to change without notice


Series Description Page

TMVX Thermostatic Expansion Valves 43


external pressure equalisation, combi adsorber charge for several refrigerants,
adjustable superheat set, flare connections, interchangeable orifice cartridges

TMVBL Thermostatic Expansion Valves 43


internal pressure equalisation, combi adsorber charge for several refrigerants,
adjustable superheat setting, inlet flare connection, outlet solder connection,
interchangeable orifice cartridges

TMVXBL Thermostatic Expansion Valves 43


external pressure equalisation, combi adsorber charge for several refrigerants,
adjustable superheat setting, inlet flare connection, outlet solder connection,
interchangeable orifice cartridges

TMVL Thermostatic Expansion Valves 47


part programme valve, one valve body head for solder base with internal (VLS)
or external (VLSX) pressure equalisation, combi adsorber charge for several
refrigerants, adjustable superheat setting, interchangeable orifice cartridges

VLS - D Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
internal pressure equalisation, solder connections, two-way construction

VLSX - D Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
external pressure equalisation, solder connections, two-way construction

VLS - W Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
internal pressure equalisation, solder connections, angle construction

VLSX - W Solder Base for Thermostatic Expansion Valves TMVL and NMVL 47
external pressure equalisation, solder connections, angle construction

VD Orifice Cartridge for Thermostatic Expansion Valves TMV, TMVL and 43


NMVL 47
for all expansion valves of series TMV, TMVX, TMVBL, TMVXBL, TMVL and
NMVL, orifice size 0.3 to 4.75, equivalent to 0.5 - 21.5 kW cooling capacity R22

EN0H-0376GE23 R1014 · Subject to change without notice 5


Übersicht

Series Description Page

TMX Thermostatic Expansion Valves 51


part programme valve, valve body head can be combined with various bases
and orifice cartridges, MOP – or liquid charge, warm thermal head, external
pressure equaliser in the valve body, adjustable superheat setting, with
Balanced-Port, interchangeable orifice cartridges

XLS Solder Base for Thermostatic Expansion Valves TMX and NMX 51
solder connections, two-way or angle construction

XBS Flare Base for Thermostatic Expansion Valves TMX and NMX 51
flare connections, two-way construction

XD Orifice Cartridge for Thermostatic Expansion Valves TMX and NMX 51


for expansion valves of series TMX and NMX
orifice size 4.5 to 10, equivalent to 16.3 - 72.1 kW cooling capacity R22

TLK Thermostatic Expansion Valves 55


internal pressure equalisation, MOP charge, warm thermal head, fixed
superheat setting, solder connections, fixed orifice, orifice size 0.3 to 2.0,
equivalent to 0.5 - 3.9 kW cooling capacity R22, bypass optional

TLE 0.5 - 3.0 Thermostatic Expansion Valves 59


internal pressure equalisation, combi adsorber charge for several refrigerants,
MOP charge at deep freeze applications, warm thermal head, adjustable
superheat setting, solder connections, fixed orifice, orifice size 0.5 to 3.0,
equivalent to 1 - 8.9 kW cooling capacity R22

TLEX 0.5 - 4.5 Thermostatic Expansion Valves 59


external pressure equalisation, combi adsorber charge for several refrigerants,
MOP charge at deep freeze applications, warm thermal head, adjustable
superheat setting, solder connections, fixed orifice, orifice size 0.5 to 4.5,
equivalent to 1 - 16.3 kW cooling capacity R22

TBEX 0.5 - 4.5 D Thermostatic Expansion Valves 63


TBEX 0.5 - 4.5 W on request, external pressure equalisation, combi adsorber charge or MOP
charge, warm thermal head, two-way or angle construction, adjustable
superheat setting at two-way construction, flare connections, fixed orifice, orifice
size 0.5 to 4.5, equivalent to 1 - 16.3 kW cooling capacity R22

6 EN0H-0376GE23 R1014 · Subject to change without notice


Series Description Page

TOEX 0.5 -4.5 D Thermostatic Expansion Valves 67


TOEX 0.5 - 4.5 W on request, external pressure equalisation, combi adsorber charge or MOP
charge, warm thermal head, two-way or angle construction, adjustable
superheat setting at two-way construction, o-ring connections, fixed orifice,
orifice size 0.5 to 4.5, equivalent to 1 - 16.3 kW cooling capacity R22

TLESX 4.75 - 6 Thermostatic Expansion Valves 71


external pressure equalisation, MOP charge, warm thermal head, adjustable
superheat setting, Single Port, solder connections, fixed orifice, orifice size 4.75
to 6, equivalent to 21.5 – 40.7 kW cooling capacity R22

TLEX 4.75 - 7 Thermostatic Expansion Valves 75


TLEX 8 - 11 external pressure equalisation, MOP charge, warm thermal head, adjustable 79
superheat setting, Balanced Port, solder connections, fixed orifice, orifice size
4.75 to 11, equivalent to 21.5 - 92 kW cooling capacity R22

CVC Hot Gas Bypass Valves 83


capacity regulator, internal pressure equalisation, adjustable suction pressure
limitation 1 – 6 bar, solder connections, fixed orifice, orifice size 4, equivalent to
1 kW bypass capacity R134a

HLE Hot Gas Bypass Valves 83


capacity regulator, internal pressure equalisation, adjustable suction pressure
limitation 1 – 9 bar, solder connections, fixed orifice, orifice size 4.5S,
equivalent to 1.5 kW bypass capacity R134a

HLEX 4.75 - 7 Hot Gas Bypass Valves 85


HLEX 8 - 11 capacity regulator, external pressure equalisation, adjustable suction pressure
limitation 1 - 9 bar, Balanced Port, solder connections, fixed orifice, orifice size
4.75 - 11, equivalent to 1 - 7.2 kW bypass capacity R134a

NMVL Liquid Injection Valves 89


suction pressure controlled valve, part programme valve, only one valve body
head is needed for solder base with internal (VLS) or external (VLSX) pressure
equalisation, liquid charge, adjustable superheat setting, interchangeable orifice
cartridges

NMX Liquid Injection Valves 89


suction pressure controlled valve, part programme valve, valve body can be
combined with various bases and orifice cartridges, liquid charge, warm thermal
head, external pressure equalisation in the valve body head, adjustable
superheat setting, with high pressure compensation (Balanced-Port),
interchangeable orifice cartridges

EN0H-0376GE23 R1014 · Subject to change without notice 7


Series Description Page

MA Solenoid Valves 95
normally closed, direct operated, angle construction, solder connections,
kv-value = 0.17 m3/h

MD Solenoid Valves 95
normally closed, direct operated, two-way construction, solder or flare
connections, kv-value = 0.17 – 0.23 m3/h, valve complete with coil for 230V AC
or as part programme valve without coil

MS Solenoid Valves 95
normally closed, pilot operated, two-way construction, solder or flare
connections, kv-value = 0.9 – 4 m3/h, valve complete with coil for 230V AC or as
part programme valve without coil

MC Coil for Solenoid Valves MA, MD, MS 95


as spare part or for part programme

RV Check Valves 103


brass housing, copper-plated solder connections, for installation in the liquid,
hot gas or suction line

SBI Sight Glasses 105


with moisture indicator, flare connections on both sides

SBIA Sight Glasses 105


with moisture indicator, flare connections female / male thread

SLI Sight Glasses 105


with moisture indicator, solder connections on both sides

FF Filter Driers 109


for installation in liquid line, solder or flare connections, drier size 030 to 410

SA Vibration Absorber 113


laser welded, stainless steel hose, copper fittings, frost resistant construction,
suitable for vertical installation

8 EN0H-0376GE23 R1014 · Subject to change without notice


Series EEV
ELECTRONIC EXPANSION VALVE
WITH STEPPER MOTOR

PRODUCT-DATA

Features
 Proportional Electronic Expansion Valve for usage in
refrigeration circuits
Refrigerants:
HCFC, HFC (R410A, R32, R407C, R134a, R404A, ...)
HFOs (R1234yf, R1234ze) and blends
Hydrocarbons (R600a, R290, ...)
Further refrigerants on request
 2-pole stepper motor with inside protected coil
 Hermetical construction

Specification

Operating Temperature Medium: -40 ... +75 °C


(90 °C in reverse mode)
Ambient: -50 ... +70 °C
Biflow 100 % cooling capacity in
both directions
MOP (= PS) 47 bar (abs)
MOPD 42 bar
Application
Total steps 473
The electronic expansion valves EEV are designed to be
installed in refrigeration circuits as expansion devices to ex- Rangeability 1:15
pand the refrigerant. The electronic expansion valve will be Stator / Actuator 2 Phasen Bipolar
driven by a controller which gets a pressure and temperature
Nominal voltage 24 V DC +/- 10 %
signal from the outlet of the evaporator to control the super-
heat of refrigerant. Nominal phase current 0,2 A
To drive the EEV a Honeywell-Controller or a common stepper Maximum phase current 0,75 A (short term)
motor driver is recommended to be used.
short term = 10 steps
Holding current max 0,04 A
Nominal power 4,08 W
Materials Stepper motor drive frequen- 60 Hz (full step/sec)
Body Brass, Stainless steel cy
Valve sealing PTFE Reliability 250.000 full strokes
Port Connections Copper 120.000.000 steps
Motor Copper, electrical sheet

EN0H-1952GE23 R1014 · Subject to change without notice 9


Series EEV

Cooling Capacity QN (kW)


Operation Conditions:
Condensing temperature tc: 38 °C;
Evaporating temperature to: 4 °C;
Subcooling: 1 K

Cooling Capacity QN (kW)


Valve Type
R134a R450A R1234yf R407C R407F R290 R410A
EEV 5 3.3 2.9 2.4 4.4 4.6 4.4 5.0
EEV 10 6.6 5.8 4.8 8.7 9.2 8.9 10.0
EEV 20 14.0 12.2 10.1 18.3 19.4 18.65 21.0

The application-oriented valve calculation can take place in individual cases with the help of the selection tables.

Electrical Connections

Stepper Motor
Controller

 
24 V

 White
 Blue
 Black

 Brown

Step    
1 + - - +
2 - - + +
3 - + + -
4 + + - -

10 EN0H-1952GE23 R1014 · Subject to change without notice


Dimensions and Weights

Port Connections
Typ Weight (kg)
A-B
EEV 5 10 mm - 12 mm ODF 0,33
3/8“ – 1/2" ODF 0,33
EEV 10 10 mm - 12 mm ODF 0,33
3/8“ – 1/2" ODF 0,33
EEV 20 12 mm - 16 mm ODF 0,33
1/2“ – 5/8" ODF 0,33

EN0H-1952GE23 R1014 · Subject to change without notice 11


Series EEV

Type description

EEV 20 12 x 16
Valve type

Valve size
5
10
20
Port Connection

10 x 12 = 10 x 12 mm ODF
12 x 16 = 12 x 16 mm ODF

3/8 x 1/2 = 3/8” x 1/2” ODF


1/2 x 5/8 = 1/2” x 5/8” ODF

12 EN0H-1952GE23 R1014 · Subject to change without notice


Assembly
 Respect the installation instruction!
 Main direction s. Valve body.
 Horizontal to vertical (connection on top)
 Protect EEV from humidity and dripping water.
 Wrap a wet rag around on the valve and perform the
welding without overheating the valve.
 Aim the flame towards the ends of the fittings.
 Let EEV cool down.
 Connect pre-wired connector to the socket on
the stepper motor and tighten the screw to a
maximum torque of 0,6 Nm
 Connect four-pin end of the cable to the corres-
ponding terminals on the Honeywell controller
according the wiring diagram of the controller.

EN0H-1952GE23 R1014 · Subject to change without notice 13


14 EN0H-1952GE23 R1014 · Subject to change without notice
Series SHC
SUPERHEAT CONTROLLER – OEM VERSION

PRODUCT DATA

Features
 Automatic adaptation to the evaporator’s MSS
 Balancing of the lowest possible superheat
 Learning behavior with regards to the history of the
operating points
 Automatic tracking of controller parameters
 Independent recognition of defrost requirements
 Termination of the defrost cycle commensurate with
energy efficiency needs
 No external setpoint necessary!

Specification
Analog outputs
Temperature 2X (PT1000, NTC10K, NTC20K)
Temperature/voltage 2X (PT1000, NTC10K, NTC20K,
0.5 … 4.5 V, 0 … 10 V)
Voltage/current 2X (0.5 … 4.5 V, 0 … 10 V,
4 … 20 mA)
Analog output
Voltage 1X (0 … 10 V)

Stepper motor outputs


For bipolar stepper motor 4X (12 V or 24 V, max. 800 mA
General per phase, max. 500 steps / sec)
SHC Electronic Superheat Controllers are suitable for use in Digital outputs
compression refrigeration plants and heat pumps for the Relays 4X (230 VAC, 5 [2] A)
control of electronic expansion valves of the type EEV.
Battery input
Generally, the suction line pressure and the temperature of
the superheated refrigerant are the critical measurement Buffer 24 V, min. 1 Ah
values. The superheat of the refrigerant is regulated at the
evaporator’s outlet. Ambient Storage and Operating Conditions
Storage temperature -25...+70 °C
Operating temperature -25…+60 °C
Relative humidity 10…90% (non-condensing)
Protection Class IP00 (no housing)
CONDENSER / VERFLÜSSIGER

Power Supply
SHC COMPRESSOR Current 24 VAC ± 20% or
KOMPRESSOR
24 VDC ± 10%
EEV Max. power consumption 50 VA (when motor active)

Mounting
Mounting DIN rail or wall mounting
Dimensions 181 mm X 110 mm X 45 mm
EVAPORATOR / VERDAMPFER
Weight 220 g
PI TI

MU0B-0639GE51 R0410 · Subject to change without notice 15


Series SHC

Function Valve Control


The Honeywell SHC Controller operates with a 24 VAC/DC The Honeywell SHC Controller is capable of driving EEV
power supply. The controller uses the signals from the electronic expansion valves with stepped motors from various
temperature sensor and the pressure sensor located at the different manufacturers. However, the use of Honeywell EEV
evaporator outlet (alternatively: temperature sensors at the valves of the type EV2, EV3, and EV4 is to be preferred.
evaporator inlet and outlet) to determine the actual superheat of Alternatively, electronic control valves can be driven with
the refrigerant at the evaporator outlet and controls the EEV standard 0…10 V signals via the controller’s analog output.
electronic expansion valve so as to ensure that the lowest The control parameters of the given valve are to be adjusted
possible superheat at the operating point is achieved. at the controller.
To do this, the SHC Controller requires no external setpoint
provided by operating personnel or another controller. The
controller, itself, determines the optimal setpoint for the (given)
operating point. By altering the operating point, the Valve Parameters
corresponding optimal setpoint for superheat of the refrigerant is Type of Drive
determined and controlled. The SHC Controller always operates
Type Bipolar stepped motor,
along the evaporator’s Minimal Stable Signal (MSS).
modulating actuator with 0…10 V
For every operating point, the PID parameters of the controller analog output
are automatically tracked and the control behavior optimized.
Because of the ability of the Honeywell SHC Controller to store
historical operating data, it “learns,” over the course of time, the Stepped Motor Parameters
refrigeration circuit’s evaporator characteristics (MSS). In the Motor voltage 12 V or 24 V
event of a change in load in the refrigeration circuit, the SHC Step frequency 10…500 steps/sec
Controller is capable of immediately achieving the optimal Motor current 80…800 mA
operating point. This yields very dynamic control and resultant Holding current 0…100% of the motor current, in
high energy efficiency. approx. 10% steps
Max. no. of steps 1…10,000 steps
No. of opening steps 1…1,000 steps

Terminal Connection Diagram

39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
GND D1 D2 D3 GND GND AO R1 GND V5/15 GND R2 U2 V5/15 GND U1 T2 GND T1
digital inputs 0...10 V output inputs: 4...20 mA / ratiometric / 0...10 V inputs: Pt1000, NTC10k, NTC20k / ratiometric / 0...10 V

24 Vac/dc 24 Vbat bipolar stepper motor RS485 (isolated) relay 4 (SPDT) relay 1 (NO) relay 2 (NO) relay 3 (NO)
G G0 BAT EARTH OUT2B OUT2A OUT1B OUT1A A B GNDX C4 NO4 NC4 C1 NO1 C2 NO2 C3 NO3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CONNECTION OF THE RELEASE/ENABLER SIGNAL (DI1, FACTORY DEFAULT)


The SHC Controller is active when the contact is closed.
39 38 37
GND D1 D2

16 MU0B-0639GE51 R0410 · Subject to change without notice


Terminal Assignment
term. # name description
1 G voltage supply 24 VAC/DC (+)
2 G0 voltage supply 24 VAC/DC (-)
3 BAT buffer battery module 24 V (+) with power level indicator

4 EARTH earth / shielding


5 OUT2B output 2B of stepped motor
6 OUT2A output 2A of stepped motor
7 OUT1B output 1B of stepped motor
8 OUT1A output 1A of stepped motor

9 A RS485, A + conductor
10 B RS485, B – conductor
11 GNDX RS485, isolated ground

12 C4 relay 4, change-over contact


13 NO4 relay 4, normally-open contact NOC
14 NC4 relay 4, normally-closed contact NCC
15 C1 relay 1, change-over contact
16 NO1 relay 1, normally-open contact NOC
17 C2 relay 2, change-over contact
18 NO2 relay 2, normally-open contact NOC
19 C3 relay 3, change-over contact
20 NO3 relay 3, normally-open contact NOC

21 T1 AIN1: temperature input 1 (NTC10K, NTC20K, Pt1000)


22 GND AIN1/2: ground for temperature inputs 1 + 2
23 T2 AIN2: temperature input 2 (NTC10K, NTC20K, Pt1000)
24 U1 AIN3: universal input 1 (NTC10K, NTC20K, Pt1000, 0.5…4.5 V ratiometric, 0…10 V)
25 GND AIN3/4: ground for universal inputs 1 + 2
26 V5/15 AIN3/4: sensor voltage supply for universal inputs 1 + 2
27 U2 AIN3: universal input 2 (NTC10K, NTC20K, Pt1000, 0.5…4.5 V ratiometric, 0…10 V)

28 R2 AIN6: current/voltage input 2 (0.5…4.5 V, 0…10 V, 4…20 mA)


29 GND AIN6: ground for current/voltage input 2
30 V5/15 AIN5/6: sensor voltage supply for current/voltage inputs 1 + 2
31 GND AIN5: ground for current/voltage input 1
32 R1 AIN5: current/voltage input 1 (0.5…4.5 V, 0…10 V, 4…20 mA)

33 AO AO1: analog output 1 (0…10V)


34 GND AO1: ground for analog output 1
35 GND DI1/2/3: ground for digital inputs 1 + 2 + 3
36 D3 DI3: digital input 3 (log.1 = contact open or 24 VAC/DC, log.0 = short-circuit or < 2 VAC/DC)
37 D2 DI2: digital input 2 (log.1 = contact open or 24 VAC/DC, log.0 = short-circuit or < 2 VAC/DC)
38 D1 DI1: digital input 1 (log.1 = contact open or 24 VAC/DC, log.0 = short-circuit or < 2 VAC/DC)
39 GND DI1/2/3: ground for digital inputs 1 + 2 + 3

LED Blink Coding


status LED (yellow) alarm LED (red)
ON plant is switched OFF (safety position) 1 x battery supply
1x switch ON phase or EEV active (opening/closing) 2 x superheat too low
2x switch relay active, switch delay running 3 x superheat too high
3x start-up function active (ramp, incl. holding time) 4 x sensor failure
4x pump down active or compressor restart block 5 x LOP active
5x MOP active 6 x configuration failure
6x HIT active 7 x communication failure
7x waiting for release conditions 8 x Hardware self-test failure
8x EEV in manual mode

MU0B-0639GE51 R0410 · Subject to change without notice 17


Series SHC

Dimensions (mm)

40 181

110

Accessories
accessories models corresponding technical literature
Transformer CRT / ETR EN0B-0568GE51
Temperature Sensor TS-NFN, TS-NFR, TS-RFH EN0H-1950GE23
Pressure Sensor PSR EN0H-1949GE23
DPTM50-5000 EN0B-0466GE51
Differential Pressure Sensors
DPTM50D-5000D EN0B-0616GE51
Electronic Expansion Valve EEV EN0H-1945GE23

18 MU0B-0639GE51 R0410 · Subject to change without notice


Series PSR
PRESSURE SENSOR TRANSMITTER
FOR REFRIGERATION AND HVAC APPLICATIONS

PRODUCT-DATA

Features
 Pressure Sensor Transmitter for usage in
refrigeration and HVAC applications
 For installation in liquid line, injection line, hot gas
line and suction line
 For usage of refrigerants R22, R134a, R404A, R407C,
R410A, R502, R507; not for Ammonia
 Condensation-tight
 Type PSR - ** MS UB MP150:
 Wetted parts of brass, CR70 (Chloroprene) and
ceramic
 Integrated ceramic thick-layer sensor
 Type PSR - ** VA UB MP150:
 Wetted parts of stainless steel
 Monolithic structure
 Hermetically welded metallic, dry thin-film sensor
element

Specification
Pressure Range see table on page 20
Maximum Pressure PS see table on page 20
Application Electrical Output Signal 0.5…4.5 V ratiometric
Pressure Sensor Transmitter Type PSR is used in refrigeration
Power Supply 5 ± 0.5 VDC
circuits to measure the refrigerant’s pressure.
The Pressure Sensor Transmitter PSR can be used according Supply Current ≤ 10 mA
to its measuring range in the liquid line, in the injection line,
Maximum Load > 4.5 kΩ
in the hot gas line and in the suction line of refrigeration
circuits. Response Time (10…90%) ≤ 5 ms
Insulation Voltage 500 VDC
Materials Medium Temperature -40 °C … 80 °C
Housing Brass, Stainless Steel Ambient Temperature -25 °C … 80 °C
Sealing CR70 (Chloroprene) Storage Temperature -25 °C … 80 °C
Port Connection 7/16-20 UNF-2B Max. rel. Humidity 95 %
Electr. Protection degree IP67
Other appplications on request.
In plugged condition with connector of corresponding
protection class

EN0H-1949GE23 R0310 · Subject to change without notice 19


Series PSR

Technical Specification
Typ PSR – 9 MS PSR – 16 MS PSR – 45 MS PSR – 9 VA UB PSR – 16 VA PSR – 45 VA UB
Type UB MP150 UB MP150 UB MP150 MP150 UB MP150 MP150
Messbereich -1…9 bar(ü) 0…16 bar(ü) 0…45 bar(ü) -1…9 bar(ü) 0…16 bar(ü) 0…45 bar(ü)
Pressure range -1…9 bar(g) 0…16 bar(g) 0…45 bar(g) -1…9 bar(g) 0…16 bar(g) 0…45 bar(g)
Überlastgrenze
20 bar 40 bar 100 bar 20 bar 32 bar 100 bar
Over pressure range
Berstdruck
25 bar 50 bar 120 bar 100 bar 160 bar 400 bar
Burst pressure
Genauigkeit -40 °C … -20 °C ≤ 1,5 %* -40 °C … -20 °C ≤ 1,5 %*
Accuracy -20 °C … +20 °C ≤ 1 %* -20 °C … +20 °C ≤ 1 %*
* bezogen auf Taulinie von R410A * bezogen auf Taulinie von R410A
* related to dewpoint of R410A * related to dewpoint of R410A
Stabilität pro Jahr ≤ 0,3 % der Spanne (bei Referenzbedingungen)
1-year stability ≤ 0.3 % of span (at reference conditions)
Elektrische Schutzart
IP67 in gestecktem Zustand mit Leitungsstecker entsprechender Schutzart
Protection degree
Kurzschlussfestigkeit
S+ gegen 0V S+ gegen UB-
Short-circuit protection
S+ towards 0V S+ towards UB-
Verpolschutz
UB gegen 0V UB+ gegen UB-
Reverse polarity
UB towards 0V UB+ towards UB-
protection
Überspannungsschutz
Overvoltage protection 36 VDC

Material Messing, Keramik AI203 96 %


Material O-Ring: CR70 (Chloropren) Edelstahl (316L)
Brass, Ceramic AI203 96 % Stainless steel (316L)
O-Ring: CR70 (chloroprene)
Gehäuse Messing Edelstahl (316L)
Body Brass Stainless steel (316L)

EMV-Richtlinie 2004/108/EEC, EN 61 326 Emission (Group 1, 2004/108/EEC, EN 61 326 Emission (Group 1, Class B)
EMC directive Class B) and Immunity (industrial locations) and Immunity (industrial locations)
2004/108/EEC, EN 61 326 Emission (Group 1, 2004/108/EEC, EN 61 326 Emission (Group 1, Class B)
Class B) and Immunity (industrial locations) and Immunity (industrial locations)
Gewicht Ca. 0,08 kg Ca. 0,08 kg
Weight Appr. 0.08 kg Appr. 0.08 kg

20 EN0H-1949GE23 R0310 · Subject to change without notice


Type Description
Pressure Sensor Transmitter

PSR -9 MS UB MP150
Pressure Sensor Type
Type:
-9 = -1 … 9 bar(g)
16 = 0 … 16 bar(g)
45 = 0 … 45 bar(g)
Material:
MS – Brass
VA – Steinless Steel
Port Connection
7/16-20 UNF-2B, Schrader
Internal Thread
MetriPack 150

Port Connections Electrical Connections


Type Port Connection 3-pole Connector Metri Pack Series 150
PSR – 9 MS UB MP150 7/16’’ UNF UB = B
PSR – 16 MS UB MP150 7/16’’ UNF 0V = A
PSR – 45 MS UB MP150 7/16’’ UNF S+ = C
PSR – 9 VA UB MP150 7/16’’ UNF
PSR – 16 VA UB MP150 7/16’’ UNF
PSR – 45 VA UB MP150 7/16’’ UNF

EN0H-1949GE23 R0310 · Subject to change without notice 21


Series PSR

Function Assembly
The pressure prevailing within the application is transformed  Required tools: wrench (flats 24), screw driver
into a standardised electrical signal through the deflection of  Use the pressure transmitter only if it is in a faultless
the diaphragm, which acts on the sensor element with the condition as far as the safety-relevant features are
power supply fed to the transmitter. This electric signal concerned.
changes in proportion to the pressure and can be evaluated
correspondingly.  When mounting the instrument, ensure that the
sealing faces of the instrument and the measuring
point are clean and undamaged.
Remarks:
 Screw in or unscrew the instrument only via the flats
 Select the appropriate pressure transmitter with using a suitable tool and the prescribed torque. The
regard to scale range, performance and specific appropriate torque depends on the dimension of the
measurement conditions prior to installing and starting pressure connection. Do not use the case as working
the instrument. surface for screwing in or unscrewing the instrument.
 Observe the relevant national regulations (e.g.: EN
 When screwing the transmitter in, ensure that the
50178) and observe the applicable standards and
threads are not jammed.
directives for special applications (e.g. with
dangerous media such as acetylene, flammable  Connect the instrument to earth via the pressure
gases or liquids and toxic gases or liquids and with connection.
refrigeration plants or compressors). If you do not  Use power supplies which guarantee reliable electrical
observe the appropriate regulations, serious isolation of the operating voltage as per IEC/DIN EN
injuries and/or damage can occur! 60204-1. Consider also the general requirements for
 Open pressure connections only after the system PELV circuits in accordance with IEC/DIN EN 60204-1.
is without pressure!  Ingress protection per IEC 60529 (The ingress
 Please make sure that the pressure transmitter is protection classes specified only apply while the
only used within the overload threshold limit all the pressure transmitter is connected with female
time! connectors that provide the corresponding ingress
 Observe the ambient and working conditions protection).
outlined in section „Technical data”.  Please make sure that the ends of cables with flying
 Ensure that the pressure transmitter is only operated leads do not allow any ingress of moisture.
in accordance with the provisions i.e. as described in
the installation instructions.
 Do not interfere with or change the pressure
transmitter in any other way than described in the Spare Parts
operating instructions.
 Remove the pressure transmitter from service and Cable
mark it to prevent it from being used again Description:
accidentally, if it becomes damaged or unsafe for
operation. Stecker mit Kabel für Drucksensor 3 m (IP67)
PSR-CAB300 MP150
 Take precautions with regard to remaining Plug with cable for pressure sensor 3 m (IP67)
media in removed pressure transmitter.
Stecker mit Kabel für Drucksensor 6 m (IP67)
Remaining media in the pressure port may be PSR-CAB600 MP150
hazardous or toxic! Plug with cable for pressure sensor 6 m (IP67)

 Have repairs performed by the manufacturer only.


Colour of single wire:
A Green Earth Connection
B Brown Power Supply
C White Output Signal

Temperature Range: -40 °C … 85 °C

22 EN0H-1949GE23 R0310 · Subject to change without notice


Series TS
TEMPERATURE SENSOR
FOR REFRIGERATION AND HVAC APPLICATIONS

PRODUCT-DATA

Features
 Pressure Sensor Transmitter for usage in
refrigeration and HVAC applications
 For installation in liquid line, injection line, hot gas
line and suction line
 For usage of refrigerants R22, R134a, R404A,
R407C, R410A, R502, R507; not for Ammonia
 Condensation-tight body IP67
 Type TS – NFN & TS – NFR: NTC 10K
 Type TS – RFH: PT1000

Specification (1)
Application
Resistance Value:
Temperature Sensor Type TS is used in refrigeration circuits
TS – NFN; TS – NFR 10 kΩ at 25 °C
to measure the refrigerant’s temperature.
The Temperature Sensor TS can be used according to its TS – RFH 1 kΩ at 0 °C
measuring range in the liquid line, in the injection line, in the Accuracy:
hot gas line and in the suction line of refrigeration circuits.
Due to fast temperature capture in refrigeration circuits the TS – NFN 1 % Full scale
signal can be communicated very fast. TS – NFR ± 0.2 °C
TS – RFH Class A
Materials Response Time: K = 5 sec in liquid V = 2 m/s
Body Stainless Steel, AISI 304 Sensitivity:
Cable Thermical rubber poly. TS – NFN; TS – NFR NTC 10K fast
Electrical Connection Pins TS – RFH PT1000

Measuring Range: -50 °C … +110 °C

Types Storage Temperature -25 °C … 80 °C


Ambient Temperature -25 °C … 80 °C
Description Sensor Type Temperature Range
Electrical Connection 2-wire
TS - NFN NTC 10K Fast -50 °C … 110 °C
Dimension Ø 4 mm; l = 40 mm
TS - NFR NTC 10K Fast -50 °C … 110 °C
Connecting Cable 3m
TS - RFH PT1000 -50 °C … 110 °C
Insulation Voltage 250 VAC
Electr. Protection
degree: IP67

EN0H-1950GE23 R0410 · Subject to change without notice 23


Series TS

Specification (2)
Type TS – NFN TS – NFR TS – RFH
Element Type NTC 10K 1% BETA 3435 NTC 10K BETA 3977 tolerance ± 0.2 °C PT 1000 Class A
Cable Type Thermical rubber poly Thermical rubber poly Thermical rubber poly
Cable colour Black Yellow Green
Cable diameter 2x0.25 mm² Ø 3.3 mm 2x0.25 mm² Ø 3.3 mm 2x0.25 mm² Ø 3.3 mm
Connection Pins Pins Pins
Filling Polyuretanic resin Polyuretanic resin Polyuretanic resin

Type Description Electrical Connections


Temperature Sensor

TS NFN Connection of Temperature Sensors according below


picture. Temperature Sensor is insensible against
Type reverse polarity. TS Sensors have a 2-wire structure. To
Type: minimize electromagnetic perturbation the cable should
NFN = NTC 10K 1% Beta 3435 be as short as possible.
NFR = NTC 10K Beta 3977 ±0.2°C
RFH = Pt 1000 class A

Function
Due to temperature changes the resistance of temperature sensor will be changed. This change of resistance is changing
proportional to the temperature and can be evaluated accordingly.
Remarks:
 Select the appropriate temperature sensor with regard to scale range, performance and specific measurement conditions
prior to installing and starting the refrigeration system.
 Please make sure that the temperature sensor is only used within the valid measuring range.

Assembly
 Position the temperature sensor on the refrigerant pipe in the position between 10 and 14 o'clock (at horizontal pipe installation).
 Pay attention to install sensor to clean and intact surfaces at the measuring point.
 Provide sufficient thermal compound at the measuring point between temperature sensor and measuring surface.
 Fasten the temperature sensor by means of aluminum tape and/or fastening clips to the refrigerant pipe.
 Insulate the fastened temperature sensor with heat insulation material.
 Connect the temperature sensor according to the instructions of the evaluating equipment.
 Ensure that no humidity may enter at cable-ends.

24 EN0H-1950GE23 R0410 · Subject to change without notice


Series ESDR
ELECTRONIC SUCTION PRESSURE REGULATION VALVE
STEPPER MOTOR OPERATED

PRODUCT DATA

Features
 Stepper motor operated
 Continuous control behaviour
 High pressure compensation (Balanced port)
 Low pressure drop
 High cooling capacity
 Copper solder connections
 Refrigerant: R134a, R404A, R407C, R410A, R422D

Technical Data
Nominal capacity see table on page 26
Maximum pressure PS 35 bar
Maximum test pressure PF 38.5 bar
Min. operating temperature -50 °C
ESDR 22 Max. operating temperature +65 °C
Max. ambient temperature +100 °C

Electronic Data
Stepper motor type 2 phase bipolar
Application Nominal voltage 12 V chopper controlled
Electronic suction pressure regulation valves series ESDR Nominal phase current 0,7 A
are used to control the refrigerant mass flow in the suction
line of a refrigerating plant. Max. phase current 1A
A stepper motor driven piston opens / closes the valve seat. Holding current max. 0,7 A
With this continuous control behaviour it is possible to hold a Step rate 300 Hz
defined temperature level in a cold store also with changing Phase resistance 6 Ohm
compressor working conditions.
It is also possible to handle different temperature levels in Phase inductance 14 mH
several cold stores with a common compressor pack by use Step angel 1.8 °
of suction pressure regulation valves.
Furthermore an overload protection of the compressor or a
capacity controller can be realised with ESDR valves. Material
Valve housing, internals brass
Motor housing stainless steel
Connections copper
Valve sealing PTFE
Motor electrical sheet, copper

EN0H-1943GE23 R0810 · Subject to change without notice 25


Series ESDR

Nominal Capacity
kv – value Nominal capacity (kW)*
Type Valve size (m³/h)
R134a R404A R407C R410A R422D
ESDR 22 17 34.9 37.8 42.7 55.5 34.5
* Capacities are based on evaporating temperature to = +4 °C, condensing temperature tc = +38 °C und 1 K subcooled
refrigerant, pressure drop over the valve 0.15 bar

Dimensions and Weights


Type Valve size Dimensions Weight
ØA B C D

22 mm ODF
ESDR 22 185 mm 201.4 mm 113.6 mm approx. 1.05 kg
28 mm ODF

ESDR 22

Type Code / Order Information


ESDR 22 22 x 22mm
Series
Valve seat diameter / Valve size
Solder connections ODF
(Inlet x Outlet)

26 EN0H-1943GE23 R0810 · Subject to change without notice


Wiring Schematic for Stepper Motor

Stepper Motor
Driver

 White
 Blue
 Black
 Brown

Step     open close


1 + - - +  
2 - - + +
3 - + + -
4 + + - -

Application Sample

Controller

SM
Driver

T1

T2

EN0H-1943GE23 R0810 · Subject to change without notice 27


Series ESDR

Installation
 Respect the installation instruction!
 Position of the stepper motor in a suspended arrangement.
 Flow direction must correspond with the arrow on the valve
body.
 When soldering the valve, the valve body must not get
warmer than 100 °C.
 Do not direct connect the stepper motor to power supply.
Use a stepper motor driver to operate the stepper motor.
 The technical data of the stepper motor driver must
correspond with the electrical and technical data of the
valve.
 To open / close the valve via a stepper motor driver
respect the sequence of polarity at the coils shown in the
wiring schematic.
 Constructive modifications at the valve are not allowed.

Information for original equipment manufacturers:


The valve series ESDR can be customised to the
requirements of our series device in an optimum way.
Contact us!

28 EN0H-1943GE23 R0810 · Subject to change without notice


Series PCR-100 / PCR-110
ELECTRONIC THERMOSTATS
PRODUCT DATA

Features
 User friendly programming
 Thermostat for refrigeration and heating
 Relay output
 Defrost option for plus cold stores with continuous
operation of evaporator fan
 Alarm output relay
 Red digital display, good visibility
 PCR-100: Module housing for 35 mm standard DIN rail
 PCR-110: Snap-in installation housing for aperture
28.5 x 70.5 mm
PCR-100
 PTC sensors with stainless steel sleeves
 Mains transformer integrated

Specification
Power supply 230 V, ±10 %, 50/60 Hz
Power consumption 2.1 Watt
Control performance on-off
PCR-110 Display 3-digit, 7-segment, LED red,
height 14.2 mm
Resolution 1K
Display accuracy ±0.5 K internally, ±1 digit at 25 °C
Application
Measuring range -55 °C to +50 °C
PCR-100 and PCR-110 are microprocessor-controlled
Input 1 PTC sensor
thermostats for refrigeration, deep freeze systems and for
general purpose use. Outputs compressor or heater: 1 relay
The electronic thermostats can be used for cooling and with changeover contact, 8 A,
heating application in a temperature range of -55 °C to +50 °C. 230 V AC resistive load
alarm: 1 relay with N. O. contact,
Material 5 A, 230 V AC, resistive load
Housing ABS-plastic, self-extinguishing Sensor PTC sensor, cable length 2.5 m,
accuracy ±2 %
range of use:
-30 °C to +80 °C cable not fixed
-40 °C to +80 °C cable fixed
Ambient in operation:
temperature/humidity 0° to + 50 °C,
30 to 85 % R.H. excluding dew
in storage:
-20 °C to +80 °C
Data back up Non-volatile memory EEPROM
Connectors 250V / 10 A screw-type terminal
strips, max. 1.5 mm²
Protective rating Housing: IP 20, front panel: IP 52,
protection class 2

EN0H-1925GE23 R0709 · Subject to change without notice 29


Series PCR-100 / PCR-110

Dimensions and Weight


Type Dimensions of housing (mm) Weight
(kg)
W H D
PCR-100 70 85 61 approx. 0.33
PCR-110 70 32 74 approx. 0.24

Installation
 Operate only in dry places
 Snap-in installation housing:
 Fit unit in a recess 28.5 x 70.5 mm
 maximum wall thickness: 22 mm
 Secure housing with the mounting frame
 4 DIN standard modular housing:
 Open out the side mounting tabs
 Clip the unit on to 35 mm rail
 press tabs in again
 Respect the wiring diagram
 Tighten screws of connectors carefully

PCR-110 PCR-100

30 EN0H-1925GE23 R0709 · Subject to change without notice


Series PCR-300/-310/-410/-300RC
ELECTRONIC COLD STORE CONTROLS
PRODUCT DATA

Features
 User friendly programming
 Compressor control with delayed start-up
 Evaporator fan control; fan in combination with
compressor, operating continuously or switched via
the evaporator temperature.
 Defrost control for electrical heating or hot-gas
defrosting; initiated via programmable time intervals,
at PCR-300RC by real-time clock
 Alarm output (not for PCR-310)
 Red digital display, good visibility
PCR-300  Module housing for 35 mm standard DIN rail at
PCR-300 and PCR-300RC
 Snap-in installation housing at PCR-310 and PCR-410
for aperture 28.5 x 70.5 mm
 Mains transformer integrated at PCR-300, PCR-300RC
 External transformer at PCR-310, PCR-410
 2 PTC sensors with stainless steel sleeves for room
temperature and defrost termination
PCR-310
Specification (1)
Power supply PCR-300, PCR-300RC
mains transformer installed:
Application 230 V, ±10 %, 50/60 Hz
PCR-300, PCR-310, PCR-410 and PCR-300RC are PCR-310, PCR-410
microprocessor-controlled cold store controls for refrigeration 12 V AC ±10%, 50/60 Hz or
and deep freeze systems. 12 V DC ±10%
The control switch the compressor, evaporator fan and the external Transformer TR-310:
defrost heating depending on the cold store temperature Prim.: 230 V AC ±10%, 50/60 Hz
and the adjusted parameters. Sec.: 12 V AC
Power consumption 2.5 Watt
Material
Control performance on/off
Housing ABS-plastic, self-extinguishing
Display 3-digit, 7-segment, LED red,
height 14.2 mm
Resolution 1K
Display accuracy ±0.5 K internally, ±1 digit at 25 °C
Measuring range -55 °C to +50 °C
Inputs 2 PTC sensors

Continued on page 32

EN0H-1923GE23 R0709 · Subject to change without notice 31


Series PCR-300/-310/-410/-300RC

Specification (2)
Outputs compressor: Sensor PTC sensor, cable length 2.5 m,
1 relay with changeover contact, 8 A, accuracy ±2 %
230 V AC, resistive load range of use:
evaporator fan: -30 °C to +80 °C cable not fixed
1 relay with N.O. contact, 8 A -40 °C to +80 °C cable fixed
(5 A PCR-300RC), 230 V AC, Ambient in operation:
resistive load temperature/humidity 0° to 50 °C,
defrost heating: 30 to 85 % R.H. excluding dew
1 relay with N.O. contact, 8 A in storage:
(5 A PCR-300RC), 230 V AC, -20 °C to +80 °C
resistive load
Data back up Non-volatile memory EEPROM,
alarm: Real time clock with back up
PCR-300, PCR-300RC battery (PCR-300RC)
Opto-bidirectional triode thyristor,
250 VAC, min. load 40 mA, Connectors 250V / 10 A screw-type terminal
max. load 80 mA strips, max. 1.5 mm²
PCR-410: 1 relay with N.O. Protective rating Housing: IP 20
contact, 8 A, 230 V AC, front panel: IP 52,
resistive load protection class 2

Dimensions and Weight


Type Dimensions of housing (mm) Weight
(kg)
W H D
PCR-300 70 85 61 approx. 0.42
PCR-310 70 32 74
approx. 0.52
Transformer 52 47 34
PCR-410 70 32 74
approx. 0.52
Transformer 52 47 34
PCR-300RC 70 85 61 approx. 0.42

Installation
 Operate only in dry places
 Snap-in installation housing:
 Fit unit in a recess 28.5 x 70.5 mm
 maximum wall thickness: 22 mm
 Secure housing with the mounting frame
 4 DIN standard modular housing:
 Open out the side mounting tabs
 Clip the unit on to 35 mm rail
 press tabs in again
 Respect the wiring diagram
 Tighten screws of connectors carefully

32 EN0H-1923GE23 R0709 · Subject to change without notice


PCR-300
PCR-300RC

Alarm only PCR-410

PCR-310
PCR-410

EN0H-1923GE23 R0709 · Subject to change without notice 33


34 EN0H-1923GE23 R0709 · Subject to change without notice
Series PTI-610
ELECTRONIC TEMPERATURE DISPLAY
PRODUCT DATA

Features
 Red digital display, good visibility
 Display for °C and °F selectable
 Snap-in installation for aperture 28.5 x 70.5 mm
 Retaining frame for wall thickness up to 22 mm
 PTC sensors with stainless steel sleeves
 Electronic sensor-line up, if required
 Mains transformer integrated

Specification
Power supply 230 V, ±10 %, 50/60 Hz
Power consumption 1.3 Watt
Display 3-digit, 7-segment, LED red,
height 14.2 mm
Resolution 1K
Display accuracy ±0.5 K internally, ±1 digit at 25 °C
Measuring range -55 °C to +99 °C
-67 °F to +99 °F
Input analogue input for PTC sensor
Sensor PTC sensor, cable length 2.5 m,
accuracy ±2 %
Application range of use:
PTI-610 is an electronic temperature display for general -30 °C to +80 °C cable not fixed
purpose use. -40 °C to +80 °C cable fixed
The display does have snap-in housing for installation in a Ambient in operation:
control panel. temperature/humidity 0° to + 50 °C,
30 to 85 % R.H. excluding dew
Material in storage:
Housing ABS-plastic, self-extinguishing -20 °C to +80 °C
Connectors 10 A screw-type terminal strips,
max. 1.5 mm
Protective rating Housing: IP 20
front panel: IP 52,
protection class 2

EN0H-1928GE23 R0709 · Subject to change without notice 35


Series PTI-610

Dimensions and Weight


Type Dimensions of housing (mm) Weight
(kg)
W H D
PTI-610 70 32 74 approx. 0.27

Installation
 Operate only in dry places
 Snap-in installation housing:
 Fit unit in a recess 28.5 x 70.5 mm
 maximum wall thickness: 22 mm
 Secure housing with the mounting frame
 Respect the wiring diagram
 Tighten screws of connectors carefully

36 EN0H-1928GE23 R0709 · Subject to change without notice


Series AMV
AUTOMATIC EXPANSION VALVES
INTERCHANGEABLE ORIFICE CARTRIDGE, ADJUSTABLE EVAPORATING PRESSURE

PRODUCT DATA

Features
 AMV : with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits
 AMVX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors
 Adjustable evaporating pressure setting ± 0.5 bar
within the evaporating pressure range
 Flare connections
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
AMV  Interchangeable orifice cartridges
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

Specification
Nominal capacity range 0.52 to 22.4 kW R22
(small orifice graduation for
AMVX optimal control behaviour,
interchangeable orifice
cartridges)
Evaporating pressure range see table on page 38
Application Maximum pressure PS 29.0 bar(a)
Automatic expansion valves (constant pressure valves) series Maximum test pressure PF 31.9 bar(a)
AMV are used in general refrigeration and for original Max. ambient temperature 100 °C
equipment.
For plants like dehumidifiers, air driers, water coolers,
ice-making machines or air conditioners.

Materials
Body brass
Thermal head stainless steel
Connection brass

EN0H-1946GE23 R0809 · Subject to change without notice 37


Series AMV

Evaporating pressure
1. Automatic expansion valves with internal pressure equalisation 2. Automatic expansion valves with external pressure equalisation

Type OS number Evaporating Type OS number Evaporating


pressure range pressure range
AMV-00001 1.5 – 2.5 bar AMVX-00001 1.5 – 2.5 bar
AMV-00002 2.5 – 3.5 bar AMVX-00002 2.5 – 3.5 bar
AMV AMVX
AMV-00003 3.5 – 4.5 bar AMVX-00003 3.5 – 4.5 bar
AMV-00004 4.5 – 5.5 bar AMVX-00004 4.5 – 5.5 bar

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A R410A
0.3 0.36 0.52 0.50 0.36 0.36 0.36 0.62
0.5 0.69 0.99 0.95 0.67 0.68 0.69 1.2
0.7 1.0 1.4 1.3 0.92 0.97 0.98 1.6
1.0 1.4 2.0 1.9 1.3 1.4 1.4 2.4
1.5 2.2 3.2 3.1 2.2 2.2 2.3 3.8
AMV
2.0 2.9 4.0 3.9 2.7 2.8 2.9 4.8
AMVX
2.5 4.0 5.8 5.6 3.9 4.1 4.1 6.9
3.0 6.6 9.3 8.9 6.3 6.5 6.6 11.1
3.5 8.7 12.2 11.7 8.3 8.6 8.7 14.6
4.5 11.8 17.0 16.4 11.3 12.0 12.1 20.3
4.75 15.9 22.4 21.6 15.3 15.8 15.9 26.8
* Capacities are based on to= +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Type Connections Weight
Inlet Outlet Pressure (kg)
(B) (A) equaliser (C)
AMV 5/8" UNF 3/4" UNF - approx. 0.35
AMVX 5/8" UNF 3/4" UNF 7/16" UNF approx. 0.36

38 EN0H-1946GE23 R0809 · Subject to change without notice


AMV / AMVX VD

Type Code / Order Information (Part Programme)


1. Valve body

AMV X BM 3.0 5/8" UNF x 3/4" UNF


Series
Pressure equalisation:
X = external
() = internal
Range middle
evaporating pressure range (bar)
Connection size
(inlet x outlet)

2. Orifice cartridge

VD 0.5
Series
Orifice size

EN0H-1946GE23 R0809 · Subject to change without notice 39


Series AMV

Installation Evaporating pressure Adjustment


 The valves may be installed in any position. The evaporating pressure setting can be adjusted by
 The external pressure equaliser line should be 6 mm or 1/4” ± 0.5 bar around the range middle of the evaporating
in diameter. An overbow is recommended in order to prevent pressure range.
the ingress of oil into the equaliser line.
Turning clockwise = reduced evaporating pressure
 When soldering the valve, the valve body must not get
warmer than 100 °C. Turning
= increased evaporating pressure
counterclockwise
 When tightening flare nuts of the flare connections grip at
wrench flats on the valve body.
Special Accessory:
 Constructive modifications at the valve are not allowed.
Adapter series LA for solder connection at the inlet for 6 mm,
10 mm, 1/4” and 3/8”.

40 EN0H-1946GE23 R0809 · Subject to change without notice


Series AEL
AUTOMATIC EXPANSION VALVES
FIXED ORIFICE, ADJUSTABLE EVAPORATING PRESSURE

PRODUCT DATA

Features
 Smallest dimensions
 High performance
 Hermetic construction
 Wide evaporating pressure range
 Adjustable evaporating pressure setting
 Solder connections
 Internal pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Fixed orifice
 Bypass on request
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

Specification
Nominal capacity range 1.4 to 29.1 kW R22
Evaporating pressure range 1 - 7 bar(a)
Factory setting for
evaporating pressure 2.2 bar(a)
Application Maximum pressure PS 25.5 bar(a)

Automatic expansion valves (constant pressure valves) series Maximum test pressure PF 28 bar(a)
AEL are used in general refrigeration and for original Max. ambient temperature 100 °C
equipment.
For plants with single injected evaporators and without a Installation
distributor, such as air conditioners, dehumidifiers, air driers,
water coolers or ice-making machines.  The valves may be installed in any position.
 When soldering the valve, the valve body must not get
Materials warmer than 100 °C.
Body brass  Remove plastic cap during soldering
Head stainless steel, brass  Constructive modifications at the valve are not allowed.

Connection tubes copper


Adjustment
One complete revolution of the adjusting screw effects an
alternation of the evaporating pressure by approx. 0.8 bar.

Turning clockwise = Higher evaporation pressure


Turning
= Lower evaporation pressure
counterclockwise

EN0H-1912GE12 R0709 · Subject to change without notice 41


Series AEL

Capacities
Type Valve size Orifice Nominal capacity (kW)*
size R22 R134a R404A R507A
0.5 0.7 1.4 1.0 0.97 0.98
1.0 1.0 2.0 1.4 1.4 1.4
2.0 2.0 4.0 2.9 2.8 2.9
AEL 3.0 3.0 9.3 6.6 6.5 6.6
4.0 3.5 12.2 8.7 8.6 8.7
5 4.75 22.4 15.9 15.8 15.9
6 5 29.1 20.0 20.5 20.7
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Type Valve Connections Dimensions (mm) Weight (kg)
size
Inlet (A) Outlet (B) C D E F
0.5
1.0 6 mm ODF 10 mm ODF
2.0 58 36 106 54 approx. 0.16
3.0
AEL 1/4" ODF 3/8" ODF
4.0
5 3/8" ODF 5/8" ODF
10 mm ODF 16 mm ODF 64 47 122 69 approx. 0.28
6
3/8" ODF 5/8" ODF

42 EN0H-1912GE12 R0709 · Subject to change without notice


Series TMV
THERMOSTATIC EXPANSION VALVES
INTERCHANGEABLE ORIFICE CARTRIDGE

PRODUCT DATA

Features
 TMV / TMVBL: with internal pressure equalisation; for
single injection in installations with one or more
cooling circuits
 TMVX / TMVXBL: with external pressure equalisation;
for optimal evaporation effectiveness in all
applications. Obligatory for multiple injection by liquid
distributors
 Combi adsorber charge
 The same valve can be used for different
refrigerants (see table on page 44)
  Controller charge is high sensitive and responsive
TMVX thus lowest possible level of superheat can be
achieved
 Charge is not sensitive to effects of temperature on
the capillary tube and valve head
 Damping characteristic results in stable control
behaviour
 Suitable for systems with hot gas defrosting
 Adjustable superheat setting
 Flare connections: TMV, TMVX
TMVXBL
 Flare / solder connections: TMVBL, TMVXBL
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Application
 Interchangeable orifice cartridges
Thermostatic expansion valves series TMV are used in
general refrigeration and for original equipment.  Refrigerants: R134a, R401A
R22, R407C, R407A, R422D
Plants with one or more circuits such as refrigerated cabinets
   R404A, R507A, R402A, R407B
even with cramped mounting conditions, ice and cream
R410A. R407F
machines, milk cooling units, water chillers, vehicle air
HFO (e.g. R1234yf) and future Blends
conditioning systems, cold stores, and air conditioning
Further refrigerants on request.
systems.

Specification
Materials Nominal capacity range 0.52 to 22.4 kW R22
(small orifice graduation for
Body brass optimal control behaviour,
Thermal head stainless steel interchangeable orifice
cartridges)
Connection solder: copper
flare: brass Evaporating temperature see table on page 44
range
Maximum pressure PS see table on page 44
Maximum test pressure PF see table on page 44
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm

EN0H-1900GE23 R0709 · Subject to change without notice 43


Series TMV

Thermal Charges and Temperature Ranges


1. Adsorber charge 2. Adsorber charge with pressure limiting performance MOP

Refrigerant Evaporation PS PF Refri- Evaporation MOP PS PF


temperature (bar(a)) (bar(a)) gerant temperature (bar(a)) (bar(a))
range range
R134a, R401A +15 °C to -30 °C 34 37.4 R134a, +5 °C to -30 °C MOP A +15 °C 34 37.4
R401A
R22, R407C, +15 °C to -45 °C 36 39.6 -10 °C to -30 °C MOP A ±0 °C 29 31.9
R407A, R422D R22, +5 °C to –45 °C MOP A +15 °C 36 39.6
R404A, R507A, ±0 °C to -50 °C 36 39.6 R407C,
-10 °C to -45 °C MOP A ±0 °C 29 31.9
R402A, R407B R407A,
+15 °C to -30 °C 36 39.6 R422D -27 °C to -45 °C MOP A -18 °C 29 31.9
R407C +15 °C to -30 °C 36 39.6 R404A, -10 °C to -50 °C MOP A ±0 °C 36 39.6
R407F ±0 °C to -45 °C 36 39.6 R507A,
-20 °C to -50 °C MOP A -10 °C 34 37.4
R402A,
R410A +15 °C to -20 °C 40 44 R407B -27 °C to -50 °C MOP A -18 °C 34 37.4
Further refrigerants on request. R407F 27 °C to -45 °C MOP A -18 °C 29 31.9
Thermal systems with adsorber charge are completely
Further refrigerants and MOP on request.
insensitive to effects of temperature on the capillary tube and
valve head. It reacts only according to the temperature of the
bulb.
Thus, Honeywell TMV valves with combi adsorber charge
work absolutely reliable, even in icy condition or while
defrosting using hot gas.

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R407F R404A R507A R410A
0.3 0.36 0.52 0.50 0.56 0.36 0.36 0.62
0.5 0.69 0.99 0.95 1.1 0.68 0.69 1.2
0.7 1.0 1.4 1.3 1.5 0.97 0.98 1.6
1.0 1.4 2.0 1.9 2.2 1.4 1.4 2.4
TMV
1.5 2.2 3.2 3.1 3.5 2.2 2.3 3.8
TMVX
2.0 2.9 4.0 3.9 4.3 2.8 2.9 4.8
TMVBL
2.5 4.0 5.8 5.6 6.3 4.1 4.1 6.9
TMVXBL
3.0 6.6 9.3 8.9 10.1 6.5 6.6 11.1
3.5 8.7 12.2 11.7 13.2 8.6 8.7 14.6
4.5 11.8 17.0 16.4 18.5 12.0 12.1 20.3
4.75 15.9 22.4 21.6 24.3 15.8 15.9 26.8
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Type Connections Weight
(kg)
Inlet Outlet Pressure
(B) (A) equaliser (C)
TMV 5/8" UNF 3/4" UNF - approx. 0.35
TMVX 5/8" UNF 3/4" UNF 7/16" UNF approx. 0.36
5/8" UNF 12 mm ODF -
TMVBL approx. 0.33
5/8" UNF 1/2" ODF -
5/8" UNF 12 mm ODF 6 mm ODF
TMVXBL approx. 0.34
5/8" UNF 1/2" ODF 1/4" ODF

44 EN0H-1900GE23 R0709 · Subject to change without notice


TMV / TMVX

TMVBL / TMVXBL VD

Type Code / Order Information (Part Programme)


1. Valve body

TMV X BL R134a MOP A +15 °C 5/8" UNF x 1/2" ODF


Series
Pressure equalisation:
X = external
() = internal
BL = flare x solder connection
() = flare connection
Refrigerant
Adsorber charge with MOP
() = without MOP
Connection size
(inlet x outlet)

2. Orifice cartridge

VD 0.5
Series
Orifice size

EN0H-1900GE23 R0709 · Subject to change without notice 45


Series TMV

Installation Superheat Adjustment


 The valves may be installed in any position. In general the Honeywell valves should be installed with the
 The external pressure equaliser line should be 6 mm or factory setting for the used refrigerant unaltered.
1/4” in diameter and is to be connected downstream of the At combi adsorber valves the label on the capillary tube
remote bulb. An overbow is recommended in order to indicates how to adjust the adjusting spindle (with arrow for
prevent the ingress of oil into the equaliser line. direction), depending on the refrigerant used. This correction
of the adjustment is essential to ensure that the control
 The bulb should preferably be positioned on the upper half performance of the valve is correct. The refrigerant used must
of a horizontal suction line but never after a liquid trap. be marked on the label.
As a general rule, bulbs of expansion valves should be
insulated to prevent them being affected by the ambient This superheat adjustment is calibrated for lowest
temperature. superheating and optimum evaporator utilisation. However,
should it be necessary to adjust the superheat, turn the
 Do not bend or squeeze the bulb when tightening the bulb adjusting spindle as follows:
clamp!
 When soldering the valve, the valve body must not get Turning clockwise reduced refrigerant mass flow,
=
warmer than 100 °C. increase of superheat
 When tightening flare nuts of the flare connections grip at Turning increased refrigerant mass
=
wrench flats on the valve body. counterclockwise flow, decrease of superheat
 Constructive modifications at the valve are not allowed. One turn of adjusting spindle alters superheat setting by
approx. 0.55 bar. Increase of superheat setting results in a
lower MOP-value and vice versa.

Special Accessory:
Adapter series LA for solder connection at the inlet for 6 mm,
10 mm, 1/4”, 3/8”.

46 EN0H-1900GE23 R0709 · Subject to change without notice


Series TMVL
THERMOSTATIC EXPANSION VALVES
INTERCHANGEABLE ORIFICE CARTRIDGE, SEPARATE SOLDER BASE

PRODUCT DATA

Features
 Only one valve body necessary for internal and
external pressure equalisation. Connection for
pressure coupler is integrated in the solder base.
 TMVL: Valve body and solder base with internal
pressure equalisation; for single injection in
installations with one or more cooling circuits.
 TMVLX: Valve body and solder base with external
pressure equalisation; for optimal evaporation
effectiveness in all applications. Obligatory for
multiple injection by liquid distributors.
 Combi adsorber charge
 The same valve can be used for different
refrigerants (see table on page 48)
 Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
TMVLX-W
 Charge is not sensitive to effects of temperature on
the capillary tube and valve head
 Damping characteristic results in stable control
behaviour
 Suitable for systems with hot gas defrosting
TMVLX-D  Adjustable superheat setting
 Solder connections
 Solder base available in two-way construction and in
Application angle construction
Thermostatic expansion valves series TMVL are used in  Extreme durable due to stainless steel head and
general refrigeration and for original equipment. stainless steel diaphragm welded using protective gas
Plants with one or more refrigerant circuits such as  Interchangeable orifice cartridges
refrigerated cabinets even with cramped mounting conditions,
ice and cream machines, milk cooling systems, cold stores,  Refrigerants: R134a, R401A
air conditioning systems and heat pumps. R22, R407C, R407A, R422D
R404A, R507A, R402A, R407B
  R124, R227, R410A, R236fa, R407F
HFO (e.g. R1234yf) and future Blends
Materials   Further refrigerants on request.

Body brass
Specification
Thermal head stainless steel
Nominal capacity range 0.52 to 22.4 kW R22
Connection tubes copper
(small orifice graduation for
optimal control behaviour, inter-
changeable orifice cartridges)
Evaporating temp. range see table on page 48
Maximum pressure PS see table on page 48
Maximum test pressure PF see table on page 48
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm

EN0H-1902GE23 R0312 · Subject to change without notice 47


Series TMVL

Thermal Charges and Temperature Ranges


1. Adsorber charge 2. Adsorber charge with pressure limiting performance MOP

Refrigerant Evaporation PS PF Refri- Evaporation MOP PS PF


temperature range (bar(a)) (bar(a)) gerant temperature (bar(a)) (bar(a))
range
R134a, R401A +15 °C to -30 °C 34 37.4
R134a, +5 °C to -30 °C MOP A +15 °C 34 37.4
R22, R407C, +15 °C to -45 °C 36 39.6
R401A
R407A, R422D -10 °C to -30 °C MOP A ±0 °C 29 31.9
R404A, R507A, ±0 °C to -50 °C 36 39.6 R22, +5 °C to -45 °C MOP A +15 °C 36 39.6
R402A, R407B R407C,
+15 °C to -30 °C 36 39.6 -10 °C to -45 °C MOP A ±0 °C 29 31.9
R407A,
R124 +20 °C to -30 °C 29 31.9 R422D -27 °C to -45 °C MOP A -18 °C 29 31.9
R227 +20 °C to -30 °C 29 31.9 R404A, -10 °C to -50 °C MOP A ±0 °C 36 39.6
R236fa +30 °C to -10 °C 29 31.9 R507A,
-20 °C to -50 °C MOP A -10 °C 34 37.4
R402A,
R407C +15 °C to -30 °C 36 39.6 R407B -27 °C to -50 °C MOP A -18 °C 34 37.4
R410A +15 °C to -20 °C 40 44 R407F -27 °C to -45 °C MOP A -18 °C 29 31.9
R407F ±0 °C to -45 °C 36 39.6 Further refrigerants and MOP on request.
Further refrigerants on request.
Thermal systems with adsorber charge are completely
insensitive to effects of temperature on the capillary tube and
valve head. It reacts only according to the temperature of the
bulb.
Thus, Honeywell TMVL valves with combi adsorber charge
work absolutely reliable, even in icy condition or while
defrosting using hot gas.

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R407F R404A R507A R410A
0.3 0.36 0.52 0.50 0.56 0.36 0.36 0.62
0.5 0.69 0.99 0.95 1.1 0.68 0.69 1.2
0.7 1.0 1.4 1.3 1.5 0.97 0.98 1.6
1.0 1.4 2.0 1.9 2.2 1.4 1.4 2.4
1.5 2.2 3.2 3.1 3.5 2.2 2.3 3.8
TMVL 2.0 2.9 4.0 3.9 4.3 2.8 2.9 4.8
2.5 4.0 5.8 5.6 6.3 4.1 4.1 6.9
3.0 6.6 9.3 8.9 10.1 6.5 6.6 11.1
3.5 8.7 12.2 11.7 13.2 8.6 8.7 14.6
4.5 11.8 17.0 16.4 18.5 12.0 12.1 20.3
4.75 15.9 22.4 21.6 24.3 15.8 15.9 26.8
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

48 EN0H-1902GE23 R0312 · Subject to change without notice


Dimensions and Weights
Type Connections Weight
(kg)
Inlet Outlet Pressure
(A) (B) equaliser (C)
TMVL - - - approx. 0.43
6 mm ODF 10 mm ODF -
1/4" ODF 3/8" ODF -
VLS 10 mm ODF 12 mm ODF -
approx. 0.16
angle construction 3/8" ODF 1/2" ODF -
12 mm ODF 16 mm ODF -
1/2" ODF 5/8" ODF -
6 mm ODF 10 mm ODF 6 mm ODF
1/4" ODF 3/8" ODF 1/4" ODF
VLSX 10 mm ODF 12 mm ODF 6 mm ODF
approx. 0.17
angle construction 3/8" ODF 1/2" ODF 1/4" ODF
12 mm ODF 16 mm ODF 6 mm ODF
1/2" ODF 5/8" ODF 1/4" ODF
10 mm ODF 12 mm ODF -
VLS 3/8" ODF 1/2" ODF -
approx. 0.16
two-way construction 12 mm ODF 16 mm ODF -
1/2" ODF 5/8" ODF -
10 mm ODF 12 mm ODF 6 mm ODF
VLSX 3/8" ODF 1/2" ODF 1/4" ODF
approx. 0.17
two-way construction 12 mm ODF 16 mm ODF 6 mm ODF
1/2" ODF 5/8" ODF 1/4" ODF

TMVL

VD VLS(X) – two-way VLS(X) - angle

EN0H-1902GE23 R0312 · Subject to change without notice 49


Series TMVL

Type Code / Order Information (Part Programme)


1. Valve body

TMVL R22 MOP A -18 °C


Series
Refrigerant
Adsorber charge with MOP
() = without MOP

2. Solder base 3. Orifice cartridge

10 mm x VD 0.5
VLS X W
12 mm Series
Series Orifice size
Pressure equalisation:
X = external
() = internal
Solder connection ODF
(inlet x outlet)
D = two-way construction
W = angle construction

Installation Superheat Adjustment


 The valves may be installed in any position. In general the Honeywell valves should be installed with the
 The external pressure equaliser line should be 6 mm or factory setting for the used refrigerant unaltered.
1/4" in diameter and is to be connected downstream of the At combi adsorber valves the label on the capillary tube
remote bulb. An overbow is recommended in order to indicates how to adjust the adjusting spindle (with arrow for
prevent the ingress of oil into the equaliser line. direction), depending on the refrigerant used. This correction
of the adjustment is essential to ensure that the control
 The bulb should preferably be positioned on the upper performance of the valve is correct. The refrigerant used must
half of a horizontal suction line but never after a liquid be marked on the label.
trap. As a general rule, bulbs of expansion valves should
be insulated to prevent them being affected by the This superheat adjustment is calibrated for lowest
ambient temperature. superheating and optimum evaporator utilisation. However,
should it be necessary to adjust the superheat, turn the
 Do not bend or squeeze the bulb when tightening the bulb adjusting spindle as follows:
clamp!
 The screws fixing the valve body to the solder base must Turning clockwise reduced refrigerant mass flow,
=
be tightened in diagonal sequence (torque 12+1 Nm). increase of superheat
 Constructive modifications at the valve are not allowed. Turning increased refrigerant mass
=
counterclockwise flow, decrease of superheat
 Never quench the solder base with water after soldering,
this may cause cracks and distort the sealing surfaces. One turn of adjusting spindle alters superheat setting by
approx. 0.55 bar. Increase of superheat setting results in a
lower MOP-value and vice versa.

50 EN0H-1902GE23 R0312 · Subject to change without notice


Series TMX
THERMOSTATIC EXPANSION VALVES
INTERCHANGEABLE ORIFICE CARTRIDGE, BALANCED PORT

PRODUCT DATA

Features
 TMXL: TMX and solder base, two-way construction or
angle construction
 TMXB: TMX and flare base, two way construction
 Damped gas charge with pressure limiting MOP
 Liquid charge
 Adjustable superheat setting
 Solder connections or flare connections
 External pressure equalisation is integrated in the
valve body
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Balanced port construction
TMXB  Interchangeable orifice cartridges
 Refrigerants: R22, R23, R134a, R227, R236fa,
R401A, R404A, R407C, R410A, R422D,
R507A, R508B, ISC89, R407F
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.

TMXL
Specification
Nominal capacity range 17.0 to 75.1 kW R22
Application
Evaporating temperature
Thermostatic expansion valves series TMX are used in range see table on page 52
general refrigeration and for original equipment.
Maximum pressure PS see table on page 52
Plants with one or more refrigerant circuits such as
refrigerated cabinets, deep freezing plants, milk cooling units, Maximum test pressure PF see table on page 52
water chillers, air conditioning systems, cold stores and heat Max. ambient temperature 100 °C
pumps. For plants with single and multiple injections, with Max. bulb temperature gas charge: 140 °C
high or low flow resistance, for all kind of distributors. liquid charge: 70 °C
Static superheat approx. 3.5 K
Length of capillary tube 2m
Materials Bulb diameter 16 mm
Body brass
Thermal head stainless steel
Base brass

EN0H-1904GE23 R0312 · Subject to change without notice 51


Series TMX

Thermal Charges and Temperature Ranges


1. Gas charge with pressure limiting MOP

Refri- Evaporation MOP PS PF Refri- Evaporation MOP PS PF


gerant temperature (bar(a)) (bar(a)) gerant temperature (bar(a)) (bar(a))
range range
Commercial refrigerants Deep freeze refrigerants
R22 +15 °C to -45 °C MOP +15 °C 36 39.6 R23 -40 °C to -80 °C MOP -40 °C 29 31.9
+10 °C to -45 °C MOP +10 °C 36 39.6 -55 °C to -80 °C MOP -55 °C 29 31.9
±0 °C to -45 °C MOP ±0 °C 29 31.9 R410A -40 °C to -70 °C MOP -40 °C 29 31.9
-10 °C to -45 °C MOP -10 °C 29 31.9 R508B -55 °C to -100 °C MOP -55 °C 29 31.9
-18 °C to -45 °C MOP -18 °C 29 31.9 Isceon 89 -40 °C to -70 °C MOP -40 °C 29 31.9
R134a +25 °C to -40 °C MOP +25 °C 34 37.4 Further refrigerants and MOP on request.
+20 °C to -40 °C MOP +20 °C 34 37.4 MOP valves protect the compressor by limiting the increase
+15 °C to -40 °C MOP +15 °C 34 37.4 of suction pressure.
The MOP value should be chosen for the max. permissible
+10 °C to -40 °C MOP +10 °C 34 37.4
suction pressure of the compressor or min. 5 K higher than
±0 °C to -40 °C MOP ±0 °C 29 31.9 the required evaporating temperature of the system.
R401A +10 °C to -40 °C MOP +10 °C 34 37.4 For orders without any MOP indication a valve with MOP
R404A +10 °C to -50 °C MOP +10 °C 36 39.6 + 10 C will be delivered.
±0 °C to -50 °C MOP ±0 °C 36 39.6 With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
-10 °C to -50 °C MOP -10 °C 34 37.4
capillary tube and the thermal head!
-18 °C to -50 °C MOP -18 °C 34 37.4 With the Honeywell TMX series the thermal head is heated
-30 °C to -50 °C MOP -30 °C 29 31.9 advantageously by the liquid refrigerant. The warm thermal
R407C +15 °C to -30 °C MOP +15 °C 36 39.6 head is on the safe side at any time.
+10 °C to -30 °C MOP +10 °C 36 39.6 2. Flüssigfüllung
±0 °C to -30 °C MOP ±0 °C 29 31.9 Refrigerant Evaporation PS PF
R410A +15 °C to -50 °C MOP +15 °C 40 44.0 temperature range (bar(a)) (bar(a))
-10 °C to -50 °C MOP -10 °C 29 31.9 R22 +30 °C to -45 °C 36 39.6
-15 °C to -50 °C MOP -15 °C 29 31.9
R134a +20 °C to -40 °C 34 37.4
-20 °C to -50 °C MOP -20 °C 29 31.9
R227 +40 °C to -10 °C 29 31.9
R422D +15 °C to -45 °C MOP +15 °C 36 39.6
-18 °C to -45 °C MOP -18 °C 29 31.9 R236fa +30 °C to -10 °C 29 31.9
R507A +10 °C to -50 °C MOP +10 °C 36 39.6 R404A +10 °C to -50 °C 36 39.6
±0 °C to -50 °C MOP ±0 °C 36 39.6 R407C +30 °C to -30 °C 36 39.6
-18 °C to -50 °C MOP -18 °C 34 37.4 Further refrigerants on request.
R407F +10 °C to -45 °C MOP +10 °C 36 39.6
-18 °C to -45 °C MOP -18 °C 29 31.9
Further refrigerants and MOP on request.

Capacities
Nominal capacitiy (kW)*
Type Orifice size
R22 R134a R404A R407C R407F R410A R507A R124 R227 R236fa

4.5 17.0 11.8 12.0 16.4 18.5 20.3 12.1 9.4 6.6 6.0
TMXL 4.75 22.4 15.9 15.8 21.6 24.3 26.8 15.9 12.4 8.7 8.0
5 29.1 20.0 20.5 28.0 31.6 34.8 20.7 16.1 11.3 10.3
and 6 42.4 27.6 29.8 40.8 46.0 50.8 30.1 23.5 16.4 15.1
7 54.5 35.3 38.3 52.5 59.1 65.3 38.7 30.2 21.1 19.4
TMXB 8 64.1 43.3 45.1 61.8 69.6 76.9 45.6 35.6 24.9 22.8
10 75.1 51.0 52.8 72.3 81.5 90.0 53.3 41.7 29.1 26.7
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For refrigerant R124, R227 and 236fa: Capacities are based on to = +10 °C, tc = +50 °C and 1 K subcooled liquid
refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

52 EN0H-1904GE23 R0312 · Subject to change without notice


Dimensions and Weights
Type Connections Weight
(kg)
Inlet Outlet Pressure
(A) + (B) (C) + (D) equaliser
TMX - - 7/16" UNF approx. 0.60
XD - - - approx. 0.14
XLS 12 + 16 mm ODF 16 + 22 mm ODF -
approx. 0.41
two-way construction 1/2" + 5/8" ODF 5/8" + 7/8" ODF -
XLS 12 + 16 mm ODF 16 + 22 mm ODF -
approx. 0.32
angle construction 1/2" + 5/8" ODF 5/8" + 7/8" ODF -
XBS
7/8" UNF 7/8" UNF - approx. 0.49
two-way construction

TMX

XD XBS – two-way

XLS - angle XLS – two-way

EN0H-1904GE23 R0312 · Subject to change without notice 53


Series TMX

Type Code / Order Information (Part Programme)


1. Valve body

TMX R134a MOP +10 °C


Series
Refrigerant
Pressure limiting MOP
() = without MOP

2. Solder / Flare base 3. Orifice cartridge

16 mm x XD 10
XLS W
22 mm Series
Series Orifice size
XLS = solder connection
XBS = flare connection
Connection size
D = two-way construction
W = angle construction

Installation Superheat Adjustment


 The valves may be installed in any position. In general the Honeywell valves should be installed with the
 The external pressure equaliser line should be 6 mm or factory setting for the used refrigerant unaltered.
1/4” in diameter and is to be connected downstream of the This superheat adjustment is calibrated for lowest
remote bulb. An overbow is recommended in order to superheating and optimum evaporator utilisation. However,
prevent the ingress of oil into the equaliser line. should it be necessary to adjust the superheat, turn the
adjusting spindle as follows:
 The bulb should preferably be positioned on the upper
half of a horizontal suction line but never after a liquid Turning clockwise reduced refrigerant mass flow,
trap. As a general rule, bulbs of expansion valves should =
increase of superheat
be insulated to prevent them being affected by the
ambient temperature. Turning increased refrigerant mass
=
counterclockwise flow, decrease of superheat
 Do not bend or squeeze the bulb when tightening the bulb
clamp! One turn of adjusting spindle alters superheat setting by
 Never quench the base with water after soldering, approx. 0.3 bar. Increase of superheat setting results in a
this may cause cracks and distort the sealing surfaces. lower MOP-value and vice versa.
 The screws fixing the valve body to the solder base must
+1
be tightened in diagonal sequence (torque 16 Nm).
 Constructive modifications at the valve are not allowed.

54 EN0H-1904GE23 R0312 · Subject to change without notice


Series TLK
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, FIXED SUPERHEAT SETTING

PRODUCT DATA

Features
 Gas charge with MOP for quick response time adapted
to small evaporators
 Wide evaporating temperature range
 Smallest dimensions
 Fixed superheat setting
 Warm thermal head provides best reliability
 Solder connections
 Internal pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Fixed orifice
 Bypass on request
 Refrigerants: R134a, R22, R404A, R407C, R507A
HFO (e.g. R1234yf) and future Blends
  Further refrigerants on request.

Specification
Nominal capacity range 0.52 to 4.0 kW R22
Evaporating temperature
range see table on page 56
Maximum pressure PS see table on page 56
Application Maximum test pressure PF see table on page 56
Thermostatic expansion valves series TLK are used for serial Max. ambient temperature 100 °C
produced systems such as drink dispensers, beer coolers, ice Max. bulb temperature 140 °C
cream machines, milk cooling units, water chillers and vehicle Static superheat approx. 4 K
air conditioning systems. For single injected evaporators.
Length of capillary tube 1m
Bulb diameter 12 mm
Materials
Body brass
Thermal head stainless steel
Connection tubes copper

EN0H-1911GE23 R0709 · Subject to change without notice 55


Series TLK

Thermal Charges and Temperature Ranges


1. Gas charge with pressure limiting MOP
MOP valves protect the compressor by limiting the increase
Refri- Evaporation MOP PS PF
of suction pressure.
gerant temperature (bar(a)) (bar(a))
range The MOP value should be chosen for the max. permissible
suction pressure of the compressor or min. 5 K higher than
R134a +15 °C to -40 °C MOP +15 °C 34 37.4 the required evaporating temperature of the system.
+10 °C to -40 °C MOP +10 °C 34 37.4 For orders without any MOP indication a valve with MOP
+ 10°C will be delivered.
±0 °C to -40 °C MOP ±0 °C 29 31.9
With gas charged valves and MOP it is under all operating
R22 +15 °C to -45 °C MOP +15 °C 36 39.6 conditions necessary that the bulb is always colder than the
+10 °C to -45 °C MOP +10 °C 36 39.6 capillary tube and the thermal head!
With the Honeywell TLK series the thermal head is heated
± 0 °C to -45 °C MOP ±0 °C 29 31.9 advantageously by the liquid refrigerant. The warm thermal
-18 °C to -45 °C MOP -18 °C 29 31.9 head is on the safe side at any time.
R404A +10 °C to -50 °C MOP +10 °C 36 39.6
±0 °C to -50 °C MOP ±0 °C 36 39.6
-18 °C to -50 °C MOP -18 °C 34 37.4
R407C +15 °C to -30 °C MOP +15 °C 36 39.6
+10 °C to -30 °C MOP +10 °C 36 39.6
R507A +10 °C bis -50 °C MOP +10 °C 36 39.6
Further refrigerants and MOP on request.

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R404A R407C R507A
0.3 0.36 0.52 0.36 0.50 0.36
0.5 0.69 0.99 0.68 0.95 0.69
0.7 1.0 1.4 0.97 1.3 0.98
TLK
1.0 1.4 2.0 1.4 1.9 1.4
1.5 2.2 3.2 2.2 3.1 2.3
2.0 2.9 4.0 2.8 3.9 2.9
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Type Orifice Connections Weight
size (kg)
Inlet Outlet
(A) (B)
0.3
0.5 6 mm ODF 10 mm ODF

0.7 approx. 0.18


TLK 1.0 1/4" ODF 3/8" ODF
1.5
10 mm ODF 12 mm ODF
2.0 approx. 0.19
3/8" ODF 1/2" ODF

56 EN0H-1911GE23 R0709 · Subject to change without notice


TLK

Type Code / Order Information


TLK 0.5 R22 MOP +10 °C 6 mm x 10 mm
Series
Orifice size
Refrigerant
Gas charge with MOP
Solder connection ODF
(inlet x outlet)

Installation
 The valves may be installed in any position. Information for original equipment manufacturers:
 The bulb should preferably be positioned on the upper half The valve series TLK can be customised to the
of a horizontal suction line but never after a liquid trap. As requirements of your series device in an optimum way.
a general rule, bulbs of expansion valves should be Contact us!
insulated to prevent them being affected by the ambient
temperature.
 In case of ice formation at the mounting site of the bulb,
we advise to use a bulb clamp instead of clips.
 When soldering the valve, the valve body must not get
warmer than 100 °C.
 Do not bend or squeeze the bulb!
 Constructive modifications at the valve are not allowed.

EN0H-1911GE23 R0709 · Subject to change without notice 57


58 EN0H-1911GE23 R0709 · Subject to change without notice
Series TLE
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, ADJUSTABLE SUPERHEAT SETTING

PRODUCT DATA

Features
 TLE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
 TLEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
 Combi adsorber charge as standard
 The same valve can be used for different
refrigerants (see table on page 60)
 Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
TLE  Charge is not sensitive to effects of temperature on
the capillary tube and valve head
 damping characteristic results in stable control
behaviour
 Gas charge for deep freeze applications
 Adjustable superheat setting
 Warm thermal head provides best reliability
 Solder connections
TLEX
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
Application  Fixed orifice
Thermostatic expansion valves series TLE and TLEX are  Refrigerants: R134a, R401A
used in plants with one or more refrigerant circuits, in R22, R407C, R407A, R422D
particular for series systems such as heat pumps, refrigerated R404A, R507A, R402A, R407B
cabinets, deep freeze chests, freezers, fermentation R410A
interrupters, ice and cream machines, compact systems in R23, ISC 89, R508A, R508B
refrigeration and air conditioning. HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Materials
Specification
Body brass
Thermal head Nominal capacity range 0.99 to 17.0 kW R22
stainless steel
(small orifice graduation for
Connection tubes copper optimal control behaviour)
Evaporating temperature
range see table on page 60
Maximum pressure PS see table on page 60
Maximum test pressure PF see table on page 60
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm

EN0H-1905GE23 R0312 · Subject to change without notice 59


Series TLE

Thermal Charges and Temperature Ranges


1. Adsorber charge 3. Gas charge

Refrigerant Evaporation PS PF Refrige Evaporation MOP PS PF


temperature range (bar(a)) (bar(a)) rant temperature (bar(a)) (bar(a))
range
R134a, R401A +15 °C to -30 °C 34 37.4
ISC 89 -40 °C to -70 °C MOP -40 °C 29 31.9
R22, R407C, +15 °C to -45 °C 36 39.6
R407A, R422D -55 °C to -70 °C MOP -55 °C 29 31.9
R404A, R507A, ±0 °C to -50 °C 36 39.6 R23 -40 °C to -80 °C MOP -40 °C 29 31.9
R402A, R407B -55 °C to -80 °C MOP -55 °C 29 31.9
R410A +15 °C to -20 °C 40 44.0 R407C +10 °C to -30 °C MOP +10 °C 36 39.6
Further refrigerants on request. R410A +15 °C to -50 °C MOP +15 °C 40 44.0
Thermal systems with adsorber charge are completely
R508A -40 °C to -90 °C MOP -40 °C 29 31.9
insensitive to effects of temperature on the capillary tube and
valve head. It reacts only according to the temperature of the -55 °C to -90 °C MOP -55 °C 29 31.9
bulb.
R508B -40 °C to -100 °C MOP -40 °C 29 31.9
Thus, Honeywell TLE and TLEX valves with combi adsorber
charge work absolutely reliable, even in icy condition or while -55 °C to -100 °C MOP -55 °C 29 31.9
defrosting using hot gas. Further refrigerants and MOP on request.
With gas charged valves and MOP it is under all operating
2. Adsorber charge with pressure limiting performance (MOP) conditions necessary that the bulb is always colder than the
capillary tube and the thermal head!
Refri- Evaporation MOP PS PF With the Honeywell TLE and TLEX series the thermal head is
gerant temperature (bar(a)) (bar(a)) heated advantageously by the liquid refrigerant. The warm
range thermal head is on the safe side at any time.
R134a, +5 °C to -30 °C MOP A +15 °C 34 37.4
R401A
-10 °C to -30 °C MOP A ±0 °C 29 31.9
R22, +5 °C to -45 °C MOP A +15 °C 36 39.6
R407C,
-10 °C to -45 °C MOP A ±0 °C 29 31.9
R407A,
R422D -27 °C to -45 °C MOP A -18 °C 29 31.9
R404A, -10 °C to -50 °C MOP A ±0 °C 36 39.6
R507A,
-20 °C to -50 °C MOP A -10 °C 34 37.4
R402A,
R407B, -27 °C to -50 °C MOP A -18 °C 34 37.4
Further refrigerants and MOP on request.

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R410A R404A R507A
0.5 0.69 0.99 0.95 1.2 0.68 0.69
0.7 1.0 1.4 1.3 1.6 0.97 0.98
1.0 1.4 2.0 1.9 2.4 1.4 1.4
1.5 2.2 3.2 3.1 3.8 2.2 2.3
TLE
2.0 2.9 4.0 3.9 4.8 2.8 2.9
TLEX
2.5 4.0 5.8 5.6 6.9 4.1 4.1
3.0 6.6 9.3 8.9 11.1 6.5 6.6
3.5 8.7 12.2 11.7 14.6 8.6 8.7
4.5 11.8 17.0 16.4 20.3 12.0 12.1
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

60 EN0H-1905GE23 R0312 · Subject to change without notice


Dimensions and Weights
Type Orifice Connections Weight
size (kg)
Inlet Outlet Pressure
(A) (B) equaliser (C)
0.5 6 mm ODF 12 mm ODF 6 mm ODF
0.7
1.0 1/4" ODF 1/2" ODF 1/4" ODF

1.5
2.0 10 mm ODF 12 mm ODF 6 mm ODF

TLE 2.5
approx. 0.32
TLEX 3.0
3/8" ODF 1/2" ODF 1/4" ODF
3.5
10 mm ODF 16 mm ODF 6 mm ODF
3/8" ODF 5/8" ODF 1/4" ODF
4.5
12 mm ODF 16 mm ODF 6 mm ODF
1/2" ODF 5/8" ODF 1/4" ODF

TLE 0.5 – 4.5 TLEX 0.5 – 4.5

Type Code / Order Information


TLE X 0.7 R22 MOP A -18 °C 3/8“ x 1/2“
Series
Pressure equalisation:
X = external
() = internal
Orifice size
Refrigerant
Charge type, MOP,
evaporation temperature range
Solder connection ODF
(inlet x outlet)

EN0H-1905GE23 R0312 · Subject to change without notice 61


Series TLE

Installation Superheat Adjustment


 The valves may be installed in any position. In general the Honeywell valves should be installed with the
 The external pressure equaliser line (TLEX) should be factory setting for the used refrigerant unaltered.
6 mm or 1/4" in diameter and is to be connected down- At combi adsorber valves the label on the capillary tube
stream of the remote bulb. An overbow is recommended indicates how to adjust the adjusting spindle (with arrow for
in order to prevent the ingress of oil into the equaliser line. direction), depending on the refrigerant used. This correction
of the adjustment is essential to ensure that the control
 The bulb should preferably be positioned on the upper half performance of the valve is correct. The refrigerant used must
of a horizontal suction line but never after a liquid trap. As be marked on the label.
a general rule, bulbs of expansion valves should be
insulated to prevent them being affected by the ambient This superheat adjustment is calibrated for lowest
temperature. superheating and optimum evaporator utilisation. However,
should it be necessary to adjust the superheat, turn the
 When soldering the valve, the valve body must not get adjusting spindle as follows:
warmer than 100 °C.
 Do not bend or squeeze the bulb when tightening the bulb Turning clockwise reduced refrigerant mass flow,
=
clamp! increase of superheat
 Constructive modifications at the valve are not allowed. Turning increased refrigerant mass
=
counterclockwise flow, decrease of superheat

Information for original equipment manufacturers: One turn of adjusting spindle alters superheat setting by
approx. 0.25 bar. Increase of superheat setting results in a
The valve series TLE can be customised to the
lower MOP-value and vice versa.
requirements of your series device in an optimum way.
Contact us!

62 EN0H-1905GE23 R0312 · Subject to change without notice


Series TBE
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, FLARE CONNECTIONS

PRODUCT DATA

Features
 TBE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
 TBEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
 Combi adsorber charge as standard
 The same valve can be used for different
refrigerants (see table on page 64)
 Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
 Charge is not sensitive to effects of temperature on
TBEX 0.5 - 4.5 two-way the capillary tube and valve head
 damping characteristic results in stable control
behaviour
 Optional available with gas charge and MOP
 Adjustable superheat for two-way construction
 Fixed superheat setting for angle construction
 Warm thermal head provides best reliability
TBEX 0.5 - 4.5 angle
 Flare connections
 Extreme durable due to stainless steel head and
Application stainless steel diaphragm welded using protective gas
Thermostatic expansion valves series TBE are used in plants  Fixed orifice
with one or more refrigerant circuits, especially for series  Refrigerants: R134a, R401A
installations mobile air-conditioning and cooling units with R22, R407C, R407A, R422D
flare connection, e. g. bus AC, train AC, transport cooling. R404A, R507A, R402A, R407B
HFO (e.g. R1234yf) and future Blends
Materials Further refrigerants on request.

Body brass
Specification
Thermal head stainless steel
Nominal capacity range 0.99 to 17.0 kW R22
Connections brass
(small orifice graduation for
optimal control behaviour)
Evaporating temperature
range see table on page 64
Maximum pressure PS see table on page 64
Maximum test pressure PF see table on page 64
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm

EN0H-1906GE23 R0709 · Subject to change without notice 63


Series TBE

Thermal Charges and Temperature Ranges


1. Adsorber charge 3. Gas charge

Refrigerant Evaporation PS PF Refrigerants and MOP on request.


temperature range (bar(a)) (bar(a)) With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
R134a, R401A +15 °C to -30 °C 34 37.4 capillary tube and the thermal head!
R22, R407C, +15 °C to -45 °C 36 39.6 With the Honeywell TBE series the thermal head is heated
R407A, R422D advantageously by the liquid refrigerant. The warm thermal
head is on the safe side at any time.
R404A, R507A, ±0 °C to -50 °C 36 39.6
R402A, R407B
Further refrigerants on request.
Thermal systems with adsorber charge are completely
insensitive to effects of temperature on the capillary tube and
valve head. It reacts only according to the temperature of the
bulb.
Thus, Honeywell TBE(X) valves with combi adsorber charge
work absolutely reliable, even in icy condition or while
defrosting using hot gas.

2. Adsorber charge with pressure limiting performance (MOP)

Refri- Evaporation MOP PS PF


gerant temperature (bar(a)) (bar(a))
range
R134a, +5 °C to -30 °C MOP A +15 °C 34 37.4
R401A
-10 °C to -30 °C MOP A ±0 °C 29 31.9
R22, +5 °C to -45 °C MOP A +15 °C 36 39.6
R407C,
-10 °C to -45 °C MOP A ±0 °C 29 31.9
R407A,
R422D -27 °C to -45 °C MOP A -18 °C 29 31.9
R404A, -10 °C to -50 °C MOP A ±0 °C 36 39.6
R507A,
-20 °C to -50 °C MOP A -10 °C 34 37.4
R402A,
R407B -27 °C to -50 °C MOP A -18 °C 34 37.4
Further refrigerants and MOP on request.

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A
0.5 0.69 0.99 0.95 0.67 0.68 0.69
0.7 1.0 1.4 1.3 0.92 0.97 0.98
1.0 1.4 2.0 1.9 1.3 1.4 1.4
1.5 2.2 3.2 3.1 2.2 2.2 2.3
TBE
2.0 2.9 4.0 3.9 2.7 2.8 2.9
TBEX
2.5 4.0 5.8 5.6 3.9 4.1 4.1
3.0 6.6 9.3 8.9 6.3 6.5 6.6
3.5 8.7 12.2 11.7 8.3 8.6 8.7
4.5 11.8 17.0 16.4 11.3 12.0 12.1
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

64 EN0H-1906GE23 R0709 · Subject to change without notice


Dimensions and Weights
Connections Dimensions (mm)
Weight
Type Inlet Outlet Pressure D E F G H I (kg)
(A) (B) equalisation (C)
Two-way
5/8" UNF 3/4" UNF 7/16" UNF 47.5 40 51.5 38 43 29 approx. 0.34
construction
Angle
3/4" UNF 7/8" UNF 7/16" UNF 42.5 - 46.5 40 - 29 approx. 0.34
construction
Connection = size of UNF thread

TBE(X) 0.5 - 4.5 two-way TBEX 0.5 - 4.5 angle

Type Code / Order Information


TBE X 4.5 R134a MOP A +15 °C 5/8“ x 3/4“ D
Series
Pressure equalisation:
X = external
() = internal
Orifice size
Refrigerant
Charge type, MOP,
evaporation temperature range
Flare connection UNF
(inlet x outlet)
D = two-way construction
W = angle construction

EN0H-1906GE23 R0709 · Subject to change without notice 65


Series TBE

Installation Superheat Adjustment (Two-way Valve)


 The valves may be installed in any position. In general the Honeywell valves should be installed with the
 The external pressure equaliser line (TBEX) should be factory setting for the used refrigerant unaltered.
6 mm or 1/4" in diameter and is to be connected down- This superheat adjustment is calibrated for lowest
stream of the remote bulb. An overbow is superheating and optimum evaporator utilisation. However,
recommended in order to prevent the ingress of oil into should it be necessary to adjust the superheat, turn the
the equaliser line. adjusting spindle as follows:
 The bulb should preferably be positioned on the upper Turning clockwise reduced refrigerant mass flow,
half of a horizontal suction line but never after a liquid =
increase of superheat
trap. As a general rule, bulbs of expansion valves should
be insulated to prevent them being affected by the Turning increased refrigerant mass
=
ambient temperature. counterclockwise flow, decrease of superheat
 When tightening flare nuts of the flare connections grip at One turn of adjusting spindle alters superheat setting by
wrench flats on the valve body. approx. 0.25 bar. Increase of superheat setting results in a
 Do not bend or squeeze the bulb when tightening the bulb lower MOP-value and vice versa.
clamp! With TBEX angle construction there is no superheat
 Constructive modifications at the valve are not allowed. setting in built-in condition possible, use factory setting.

Information for original equipment manufacturers:


The valve series TBE can be customised to the
requirements of your series device in an optimum way.
Contact us!

66 EN0H-1906GE23 R0709 · Subject to change without notice


Series TOE
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, O-RING CONNECTIONS

PRODUCT DATA

Features
 TOE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
 TOEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
 Combi adsorber charge as standard
 The same valve can be used for different
refrigerants (see table on page 68)
 Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved

TOEX 0.5 - 4.5 two-way  Charge is not sensitive to effects of temperature on


the capillary tube and valve head
 damping characteristic results in stable control
behaviour
 Optional available with gas charge and MOP
 Adjustable superheat for two-way construction
 Fixed superheat setting for angle construction
 Warm thermal head provides best reliability
TOEX 0.5 - 4.5 angle
 O-ring connections
 Extreme durable due to stainless steel head and
Application stainless steel diaphragm welded using protective gas
Thermostatic expansion valves series TOE(X) are used in  Fixed orifice
plants with one or more refrigerant circuits, especially for  Refrigerants: R134a
series installations, mobile air-conditioning and cooling units R22, R407C, R422D
with O-ring connection, e. g. bus AC, train AC, transport R404A, R507A
cooling. HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.
Materials
Body brass
Specification
Thermal head stainless steel Nominal capacity range 0.99 to 17.0 kW R22
(small orifice graduation for
Connections brass
optimal control behaviour)
Evaporating temperature
range see table on page 68
Maximum pressure PS see table on page 68
Maximum test pressure PF see table on page 68
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm

EN0H-1907GE23 R0709 · Subject to change without notice 67


Series TOE

Thermal Charges and Temperature Ranges


1. Adsorber charge 3. Gas charge

Refrigerant Evaporation PS PF Refrigerants and MOP on request.


temperature range (bar(a)) (bar(a)) With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
R134a +15 °C to -30 °C 34 37.4 capillary tube and the thermal head!
R22, R407C, R422D +15 °C to -30 °C 36 39.6 With the Honeywell TOE series the thermal head is heated
R404A, R507A ±0 °C to -30 °C 36 39.6 advantageously by the liquid refrigerant. The warm thermal
head is on the safe side at any time.
Further refrigerants on request.
Thermal systems with adsorber charge are completely
insensitive to effects of temperature on the capillary tube and
valve head. It reacts only according to the temperature of the
bulb.
Thus, Honeywell TOE(X) valves with combi adsorber charge
work absolutely reliable, even in icy condition or while
defrosting using hot gas.

2. Adsorber charge with pressure limiting performance (MOP)

Refri- Evaporation MOP PS PF


gerant temperature (bar(a)) (bar(a))
range
R134a +5 °C to -30 °C MOP A +15 °C 34 37.4
-10 °C to -30 °C MOP A ±0 °C 29 31.9
R22, +5 °C to -30 °C MOP A +15 °C 36 39.6
R407C,
-10 °C to -30 °C MOP A ±0 °C 29 31.9
R422D
R404A, -10 °C to -30 °C MOP A ±0 °C 36 39.6
R507A
-20 °C to -30 °C MOP A -10 °C 34 37.4
Further refrigerants and MOP on request.

Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A
0.5 0.69 0.99 0.95 0.67 0.68 0.69
0.7 1.0 1.4 1.3 0.92 0.97 0.98
1.0 1.4 2.0 1.9 1.3 1.4 1.4
1.5 2.2 3.2 3.1 2.2 2.2 2.3
TOE
2.0 2.9 4.0 3.9 2.7 2.8 2.9
TOEX
2.5 4.0 5.8 5.6 3.9 4.1 4.1
3.0 6.6 9.3 8.9 6.3 6.5 6.6
3.5 8.7 12.2 11.7 8.3 8.6 8.7
4.5 11.8 17.0 16.4 11.3 12.0 12.1
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

68 EN0H-1907GE23 R0709 · Subject to change without notice


Dimensions and Weights
Connections Dimensions (mm)
Weight
Type Inlet Outlet Pressure D E F G H I (kg)
(A) (B) equalisation (C)
Two-way
5/8" UNF 3/4" UNF 7/16" UNF 47.5 40 51.5 38 43 29 approx. 0.34
construction
Angle
3/4" UNF 7/8" UNF 7/16" UNF 42.5 - 46.5 40 - 29 approx. 0.34
construction
Connection = size of UNF thread

TOE(X) 0.5 - 4.5 two-way TOEX 0.5 - 4.5 angle

Type Code / Order Information


TOE X 4.5 R134a MOP A +15 °C 5/8“ x 3/4“ D
Series
Pressure equalisation:
X = external
() = internal
Orifice size
Refrigerant
Charge type, MOP,
evaporation temperature range
O-ring connection UNF
(inlet x outlet)
D = two-way construction
W = angle construction

EN0H-1907GE23 R0709 · Subject to change without notice 69


Series TOE

Installation Superheat Adjustment (Two-way Valve)


 The valves may be installed in any position. In general the Honeywell valves should be installed with the
 The external pressure equaliser line (TOEX) should be factory setting for the used refrigerant unaltered.
6 mm or 1/4" in diameter and is to be connected down- This superheat adjustment is calibrated for lowest
stream of the remote bulb. An overbow is recommended superheating and optimum evaporator utilisation. However,
in order to prevent the ingress of oil into the equaliser line. should it be necessary to adjust the superheat, turn the
adjusting spindle as follows:
 The bulb should preferably be positioned on the upper
half of a horizontal suction line but never after a liquid Turning clockwise reduced refrigerant mass flow,
trap. As a general rule, bulbs of expansion valves should =
increase of superheat
be insulated to prevent them being affected by the
ambient temperature. Turning increased refrigerant mass
=
counterclockwise flow, decrease of superheat
 When tightening flare nuts of the flare connections grip at
wrench flats on the valve body. One turn of adjusting spindle alters superheat setting by
 Do not bend or squeeze the bulb when tightening the bulb approx. 0.25 bar. Increase of superheat setting results in a
clamp! lower MOP-value and vice versa.
 Constructive modifications at the valve are not allowed. With TOEX angle construction there is no superheat
setting in built-in condition possible, use factory setting.

Information for original equipment manufacturers:


The valve series TOE can be customised to the
requirements of your series device in an optimum way.
Contact us!

70 EN0H-1907GE23 R0709 · Subject to change without notice


Series TLESX
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, ADJUSTABLE SUPERHEAT SETTING, SINGLE PORT

PRODUCT DATA

Features
 Damped gas charge with MOP as standard
 Optional available with liquid charge
 Adjustable superheat setting
 Warm thermal head provides best reliability
 Solder connections
 External pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Single port construction, without high pressure
compensation
 Fixed orifice
 Refrigerants: R22, R134a, R404A, R407C, R410A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.

Specification
Nominal capacity range 22.4 to 42.4 kW R22
Evaporating temperature range see table on page 72
Maximum pressure PS see table on page 72
Maximum test pressure PF see table on page 72
Max. ambient temperature 100 °C
Application
Max. bulb temperature gas charge: 140 °C
Thermostatic expansion valves series TLESX are used in liquid charge: 70 °C
plants with one or more refrigerant circuits, in particular for
series installations such as bus and train air-conditioning Static superheat approx. 3 K
units, mobile air-conditioning and cooling units, chiller units Length of capillary tube 2m
and heat pumps. Bulb diameter 16 mm

Materials
Body brass
Thermal head stainless steel
Connection tubes copper

EN0H-1929GE23 R0312 · Subject to change without notice 71


Series TLESX

Thermal Charges and Temperature Ranges


1. Gas charge with pressure limiting MOP 2. Liquid charge

Refri- Evaporation MOP PS PF Refrigerants on request.


gerant temperature (bar(a)) (bar(a))
range
R22 +15 °C to -45 °C MOP +15 °C 36 39.6
R134a +15 °C to -40 °C MOP +15 °C 34 37.4
R404A +10 °C to -50 °C MOP +10 °C 36 39.6
R407C +10 °C to -30 °C MOP +10 °C 36 39.6
+15 °C to -30 °C MOP +15 °C 36 39.6
R410A +15 °C to -30 °C MOP +15 °C 40 44
Further refrigerants and MOP on request.
MOP valves protect the compressor by limiting the increase of
suction pressure.
The MOP value should be chosen for the max. permissible
suction pressure of the compressor or min. 5 K higher than the
required evaporating temperature of the system.
With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
capillary tube and the thermal head!
With the Honeywell TLESX series the thermal head is heated
advantageously by the liquid refrigerant. The warm thermal
head is on the safe side at any time.

Capacities
Nominal capacity (kW)*
Type Orifice size
R22 R134a R404A R407C R410A
4.75 22.4 15.9 15.8 21.6 26.8
TLESX 5 29.1 20.0 20.5 28.0 34.8
6 42.4 27.6 29.8 40.8 50.8
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Connections Dimensions
(mm) Weight
Type Inlet Outlet Pressure equalizer F G (kg)
(E) (A) (DA)
12 mm ODF 16 mm ODF 6 mm ODF
54
1/2‘‘ ODF 5/8‘‘ ODF 1/4‘‘ ODF
TLESX 54 approx. 0.8
16 mm ODF 22 mm ODF 6 mm ODF
61
5/8‘‘ ODF 7/8‘‘ ODF 1/4‘‘ ODF

72 EN0H-1929GE23 R0312 · Subject to change without notice


TLESX

Type Code / Order Information


TLESX 5 R134a MOP +15 °C 12 mm x 16 mm
Series
Orifice size
Refrigerant
MOP,
evaporation temperature range
Solder connection ODF
(inlet x outlet)

EN0H-1929GE23 R0312 · Subject to change without notice 73


Series TLESX

Influence of Condensation Pressure to the Static Superheat Setting

3
Variation of static superheat setting [K]

-1

-2

T L E S X 4 ,7 5
-3
T LESX 5 + 6

-4

-5
7 9 11 13 15 17 19 21 23 25
c o n d e n s a tio n p re s s u re [b a r]

Installation Superheat Adjustment


 The valves may be installed in any position. In general the valves should be installed with the factory
 The external pressure equaliser line should be 6 mm or setting for the used refrigerant unaltered. This setting is
1/4" in diameter and is to be connected downstream of calibrated for lowest superheating and optimum evaporator
the remote bulb. An overbow is recommended in order to utilization. However, should it be necessary to adjust the
prevent the ingress of oil into the equaliser line. superheat, turn the adjusting spindle as follows:
 The bulb should preferably be positioned on the upper Turning clockwise reduced refrigerant mass flow,
half of a horizontal suction line but never after a liquid =
increase of superheat
trap. As a general rule, bulbs of expansion valves should
be insulated to prevent them being affected by the Turning increased refrigerant mass
=
ambient temperature. counterclockwise flow, decrease of superheat
 When soldering the valve, the valve body must not get One turn of the adjusting spindle alters superheat setting by
warmer than 100 °C. approx. 0.3 bar. Increase of superheat setting results in a
 Do not bend or squeeze the bulb when thightening the lower MOP value and vice versa.
bulb clamp!
 Constructive modifications at the valve are not allowed.

Information for original equipment manufacturers:


The valve series TLESX can be customised to the
requirements of your series device in an optimum way.
Contact us!

74 EN0H-1929GE23 R0312 · Subject to change without notice


Series TLEX
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, ADJUSTABLE SUPERHEAT SETTING, BALANCED PORT

PRODUCT DATA

Features
 Damped gas charge with MOP as standard
 Optional available with liquid charge
 Adjustable superheat setting
 Warm thermal head provides best reliability
 Solder connections
 External pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Balanced port construction
 Fixed orifice
 Refrigerants: R22, R134a, R404A, R407C, R410A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.

Specification
Nominal capacity range 22.4 to 54.5 kW R22
Evaporating temperature
range see table on page 76
Maximum pressure PS see table on page 76
Maximum test pressure PF see table on page 76
(simultaneous on all
Application connections)
Thermostatic expansion valves series TLEX are used in Max. ambient temperature 100 °C
plants with one or more refrigerant circuits, in particular for
series installations such as chiller units, heat pumps, and Max. bulb temperature gas charge: 140 °C
transport cooling. liquid charge: 70 °C
Static superheat approx. 3.5 K
Materials Length of capillary tube 2m
Body brass Bulb diameter 16 mm
Thermal head stainless steel
Connection tubes copper

EN0H-1909GE23 R0312 · Subject to change without notice 75


Series TLEX

Thermal Charges and Temperature Ranges


1. Gas charges with pressure limiting MOP 2. Liquid charge

Refri- Evaporation MOP PS PF Refrigerants on request.


gerant temperature (bar(a)) (bar(a))
range
R22 +15 °C to -45 °C MOP +15 °C 36 39.6
+10 °C to -45 °C MOP +10 °C 36 39.6
R134a +20 °C to -40 °C MOP +20 °C 34 37.4
+15 °C to -40 °C MOP +15 °C 34 37.4
+10 °C to -40 °C MOP +10 °C 34 37.4
R404A +10 °C to -45 °C MOP +10 °C 36 39.6
±0 °C to -45 °C MOP ±0 °C 36 39.6
R407C +15 °C to -30 °C MOP +15 °C 36 39.6
+15 °C to -45 °C MOP +15 °C 36 39.6
R410A +15 °C to -30 °C MOP +15 °C 40 44
Further refrigerants and MOP on request.
MOP valves protect the compressor by limiting the increase of
suction pressure.
The MOP value should be chosen for the max. permissible
suction pressure of the compressor or min. 5 K higher than the
required evaporating temperature of the system.
With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
capillary tube and the thermal head!

Capacities
Nominal capacity (kW)*
Type Orifice size
R22 R134a R404A R407C R410A
4.75 22.4 15.9 15.8 21.6 26.8
5 29.1 20.0 20.5 28.0 34.8
TLEX
6 42.4 27.6 29.8 40.8 50.8
7 54.5 35.3 38.3 52.5 65.3
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Type Orifice Connections Dimensions (mm)
Weight
size Inlet Outlet Pressure equalizer F G
(kg)
(E) (A) (DA)
4.75 12 mm ODF 16 mm ODF 6 mm ODF 54±2
5 1/2" ODF 5/8" ODF 1/4" ODF 54±2
TLEX 54±2 Approx. 0.86
6 16 mm ODF 22 mm ODF 6 mm ODF 61±2
7 5/8" ODF 7/8" ODF 1/4" ODF 61±2

76 EN0H-1909GE23 R0312 · Subject to change without notice


TLEX 4.75 - 7

Type Code / Order Information


TLEX 6 R22 MOP +15 °C 16 mm x 22 mm
Series
Orifice size
Refrigerant
MOP,
evaporation temperature range
Solder connection ODF
(inlet x outlet)

EN0H-1909GE23 R0312 · Subject to change without notice 77


Series TLEX

Installation Superheat Adjustment


 The valves may be installed in any position. In general the valves should be installed with the factory
 The external pressure equaliser line should be 6 mm or setting for the used refrigerant unaltered. This setting is
1/4" in diameter and is to be connected downstream of the calibrated for lowest superheating and optimum evaporator
remote bulb. An overbow is recommended in order to utilization. However, should it be necessary to adjust the
prevent the ingress of oil into the equaliser line. superheat, turn the adjusting spindle as follows:
 The bulb should preferably be positioned on the upper Turning clockwise reduced refrigerant mass flow,
half of a horizontal suction line but never after a liquid =
increase of superheat
trap. As a general rule, bulbs of expansion valves should
be insulated to prevent them being affected by the Turning increased refrigerant mass
=
ambient temperature. counterclockwise flow, decrease of superheat
 When soldering the valve, the valve body must not get One turn of the adjusting spindle alters superheat setting by
warmer than 100 °C. approx. 0.3 bar. Increase of superheat setting results in a
 Do not bend or squeeze the bulb when thightening the lower MOP value and vice versa.
bulb clamp!
 Constructive modifications at the valve are not allowed.

Information for original equipment manufacturers:


The valve series TLEX can be customised to the
requirements of your series device in an optimum way.
Contact us!

78 EN0H-1909GE23 R0312 · Subject to change without notice


Series TLEX 8 - 11
THERMOSTATIC EXPANSION VALVES
FIXED ORIFICE, ADJUSTABLE SUPERHEAT SETTING, BALANCED PORT

PRODUCT DATA

Features
 Damped gas charge with MOP as standard
 Optional available with liquid charge
 Adjustable superheat setting
 Warm thermal head provides best reliability
 Solder connections
 External pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Balanced port construction
 Fixed orifice
 Refrigerants: R22, R134a, R404A, R407C, R410A
HFO (e.g. R1234yf) and future Blends
Further refrigerants on request.

Specification
Nominal capacity range 64.1 to 95.8 kW R22
Evaporating temperature
range see table on page 80
Maximum pressure PS see table on page 80
Maximum test pressure PF see table on page 80
(simultaneous on all
Application connections)
Thermostatic expansion valves series TLEX are used in Max. ambient temperature 100 °C
plants with one or more refrigerant circuits, in particular for
series installations such as air conditioning units, chiller units Max. bulb temperature gas charge: 140 °C
and heat pumps. liquid charge: 70 °C
Static superheat approx. 3.5 K
Materials Length of capillary tube 2m
Body brass Bulb diameter 16 mm
Thermal head stainless steel
Connection tubes copper

EN0H-1910GE23 R0312 · Subject to change without notice 79


Series TLEX 8 - 11

Thermal Charges and Temperature Ranges


1. Gas charge with pressure limiting MOP 2. Liquid charge

Refri- Evaporation MOP PS PF Refrigerants on request.


gerant temperature (bar(a)) (bar(a))
range
R22 +15 °C to -45 °C MOP +15 °C 36 39.6
R134a +15 °C to -40 °C MOP +15 °C 34 37.4
R404A +10 °C to -50 °C MOP +10 °C 36 39.6
R407C +15 °C to -30 °C MOP +15 °C 36 39.6
R410A +15 °C to -30 °C MOP +15 °C 40 44
Further refrigerants and MOP on request.
MOP valves protect the compressor by limiting the increase of
suction pressure.
The MOP value should be chosen for the max. permissible
suction pressure of the compressor or min. 5 K higher than the
required evaporating temperature of the system.
With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
capillary tube and the thermal head!
With the Honeywell TLEX series the thermal head is heated
advantageously by the liquid refrigerant. The warm thermal
head is on the safe side at any time.

Capacities
Nominal capacity (kW)*
Type Orifice size
R22 R134a R404A R407C R410A
8 64.1 43.3 45.1 61.8 76.9
TLEX 10 75.1 51.0 52.8 72.3 90.0
11 95.8 65.0 67.4 92.3 115
* Capacities are based on to = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

Dimensions and Weights


Type Orifice Anschlüsse Weight
size Inlet Outlet Pressure equalizer (kg)
(E) (A) (DA)
22 mm ODF 28 mm ODF 6 mm ODF
8
22 mm ODF 35 mm ODF 6 mm ODF
TLEX 10 approx. 1.3
7/8" ODF 1 1/8" ODF 1/4" ODF
11
7/8" ODF 1 3/8" ODF 1/4" ODF

80 EN0H-1910GE23 R0312 · Subject to change without notice


TLEX 8 - 11

Type Code / Order Information


TLEX 8 R134a MOP +15 °C 22 mm x 28 mm
Series
Orifice size
Refrigerant
MOP, evaporation temperature range
Solder connection ODF
(inlet x outlet)

EN0H-1910GE23 R0312 · Subject to change without notice 81


Series TLEX 8 - 11

Installation Superheat Adjustment


 The valves may be installed in any position. In general the valves should be installed with the factory
 The external pressure equaliser line should be 6 mm or setting for the used refrigerant unaltered. This setting is
1/4" in diameter and is to be connected downstream of the calibrated for lowest superheating and optimum evaporator
remote bulb. An overbow is recommended in order to utilization. However, should it be necessary to adjust the
prevent the ingress of oil into the equaliser line. superheat, turn the adjusting spindle as follows:
 The bulb should preferably be positioned on the upper Turning clockwise reduced refrigerant mass flow,
half of a horizontal suction line but never after a liquid =
increase of superheat
trap. As a general rule, bulbs of expansion valves should
be insulated to prevent them being affected by the Turning increased refrigerant mass
=
ambient temperature. counterclockwise flow, decrease of superheat
 When soldering the valve, the valve body must not get One turn of adjusting spindle alters superheat setting by
warmer than 100 °C. approx. 0.3 bar. Increase of superheat setting results in a
 Do not bend or squeeze the bulb when thightening the lower MOP value and vice versa.
bulb clamp!
 Constructive modifications at the valve are not allowed.

Information for original equipment manufacturers:


The valve series TLEX can be customised to the
requirements of your series device in an optimum way.
Contact us!

82 EN0H-1910GE23 R0312 · Subject to change without notice


Series CVC and HLE
HOT GAS BYPASS VALVES
FIXED ORIFICE, ADJUSTABLE SUCTION PRESSURE LIMITATION

PRODUCT DATA

Features
 CVC: Orifice size 4.0,
equivalent to 1 kW bypass capacity R134a
 HLE: Orifice size 4.5S,
equivalent to 1.5 kW bypass capacity R134a
 Smallest dimensions
 High performance
 Hermetic construction
 Adjustable suction pressure limitation
 Solder connections
 Internal pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Fixed orifice
 Refrigerants: all CFC, HCFC, HFC
CVC HFO (e.g. R1234yf) and future Blends
not for ammonia

HLE
Specification
Nominal capacity see table on page 84
Adjusting range for 1 - 6 bar(a) (CVC)
suction pressure limitation 1 - 9 bar(a) (HLE)
Application Factory setting 3.2 bar(a) (CVC)
Hot gas bypass valves series CVC and HLE are used to 3.5 bar(a) (HLE)
adjust the compressor capacity to the actual evaporator Maximum pressure PS 25.5 bar(a)
capacity in a refrigerating plant.
Maximum test pressure PF 28 bar(a)
The hot gas bypass valve can be installed in a bypass tube
between the hot gas line and suction line. The suction Max. ambient temperature 100 °C
pressure is downward limited by flowing hot gas from the high
pressure to the low pressure side. Installation
For plants in general refrigeration and for original equipment
such as dehumidifiers, air driers, water coolers or ice-making  The valves may be installed in any position.
machines.  When soldering the valve, the valve body must not get
warmer than 100 °C.
Materials  Remove plastic cap during soldering
Body brass  Constructive modifications at the valve are not allowed.
Head stainless steel, brass
Connection tubes copper
Adjustment
One complete revolution of the adjusting screw effects an
alternation of the suction pressure limitation by approx.
0.5 bar (CVC) resp. 0.4 bar (HLE).

Turning clockwise = Higher suction pressure


Turning
= Lower suction pressure
counterclockwise

EN0H-1913GE23 R0709 · Subject to change without notice 83


Series CVC and HLE

Capacities
Condensing pOffset Bypass-capacity QN
Valve temperature tc (bar) (kW)
Type
size (°C) R134a R407C R404A
0.5 0.62 1.05 0.88
35
0.7 0.85 1.45 1.20
CVC 4.0
0.5 0.71 1.16 0.88
50
0.7 1.00 1.60 1.20
0.5 0.98 1.67 1.40
35
0.7 1.37 2.33 1.95
HLE 4.5S
0.5 1.13 1.86 1.41
50
0.7 1.57 2.60 1.97
Evaporating temperature to: 0 °C; Hot gas superheat tV2oh: 25 K

Dimensions and Weights


Type Valve Connections Dimensions (mm) Weight
size (kg)
Inlet (A) Outlet (B) C D E F
6 mm ODF 12 mm ODF
CVC 4.0 64 43 113 61 approx. 0.16
1/4" ODF 1/2" ODF
10 mm ODF 12 mm ODF
HLE 4.5S 71 46 142 65 approx. 0.3
3/8" ODF 1/2" ODF

CVC HLE

84 EN0H-1913GE23 R0709 · Subject to change without notice


Series HLEX 4.75 - 7 and HLEX 8 - 11
HOT GAS BYPASS VALVES
FIXED ORIFICE, ADJUSTABLE SUCTION PRESSURE LIMITATION

PRODUCT DATA

Features
 Compact design
 High performance
 Hermetic construction
 Adjustable suction pressure limitation
 Solder connections
 External pressure equalisation
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Balanced port construction
 Fixed orifice
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

HLEX 4,75 - 7 Specification


Nominal capacity see table on page 86
Adjusting range for
suction pressure limitation 1 - 9 bar(a)
HLEX 8 - 11
Factory setting 3.7 bar(a)
Maximum pressure PS 29 bar(a)
Application Maximum test pressure PF 32 bar(a) (simultanous on
all connections)
Hot gas bypass valves series HLEX are used to adjust the
compressor capacity to the actual evaporator capacity in a Max. ambient temperature 100 °C
refrigerating plant.
The hot gas bypass valve can be installed in a bypass tube Installation
between the hot gas line and suction line. The suction  The valves may be installed in any position.
pressure is downward limited by flowing hot gas from the high
pressure to the low pressure side.  When soldering the valve, the valve body must not get
For plants in general refrigeration and for original equipment warmer than 100 °C.
such as dehumidifiers, air driers, water coolers or ice-making  Remove plastic cap during soldering
machines.  Constructive modifications at the valve are not allowed.

Materials Adjustment
Body brass One complete revolution of the adjusting screw effects an
Head stainless steel, brass alternation of the suction pressure limitation by approx.
0.5 bar.
Connection tubes copper
Turning clockwise = Higher suction pressure
Turning
= Lower suction pressure
counterclockwise

EN0H-1914GE23 R0312 · Subject to change without notice 85


Series HLEX 4.75 - 7 and HLEX 8 - 11

Capacities
Condensing pOffset Bypass-capacity QN (kW)
Type Orifice size temperature tc
R134a R407C R404A
(°C) (bar)
0.5 0.98 1.67 1.40
35
0.7 1.37 2.33 1.95
4.75
0.5 1.13 1.86 1.41
50
0.7 1.57 2.60 1.97
0.5 1.29 2.18 1.83
35
0.7 1.79 3.04 2.55
5
0.5 1.47 2.43 1.84
50
0.7 2.05 3.39 2.57
0.5 1.92 3.26 2.73
35
0.7 2.68 4.54 3.81
6
0.5 2.20 3.64 2.75
50
0.7 3.07 5.07 3.83
0.5 2.35 3.98 3.34
35
0.7 3.27 5.55 4.65
HLEX 7
0.5 2.69 4.44 3.36
50
0.7 3.75 6.19 4.68
0.5 2.66 4.52 3.79
35
0.7 3.72 6.31 5.29
8
0.5 3.05 5.04 3.81
50
0.7 4.26 7.04 5.32
0.5 3.29 5.57 4.67
35
0.7 4.58 7.77 6.52
10
0.5 3.76 6.22 4.70
50
0.7 5.25 8.67 6.56
0.5 4.50 7.63 6.40
35
0.7 6.29 10.66 8.94
11
0.5 5.16 8.52 6.45
50
0.7 7.20 11.90 9.00
Evaporating temperature to: 0 °C; hot gas superheat tV2oh: 25 K

Type Code / Order Information


HLEX 5 12 mm x 16 mm
Series
Orifice size
Solder connections ODF
(inlet x outlet)

86 EN0H-1914GE23 R0312 · Subject to change without notice


Dimensions and Weights
Connections
Weight
Type Orifice size Inlet Outle Pressure equalizer (kg)
(E) (A) (DA)
4,75
12 mm ODF 16 mm ODF 6 mm ODF
5
approx. 0.9
6
1/2‘‘ ODF 5/8‘‘ ODF 1/4‘‘ ODF
HLEX 7
8 16 mm ODF 22 mm ODF 6 mm ODF
10 approx. 1.3
11 5/8‘‘ ODF 7/8‘‘ ODF 1/4‘‘ ODF

HLEX 4.75 - 7 HLEX 8 - 11

EN0H-1914GE23 R0312 · Subject to change without notice 87


Series HLEX 4.75 - 7 and HLEX 8 - 11

Application Samples

Hot gas bypass in the suction line

Hot gas bypass in the evaporator inlet

88 EN0H-1914GE23 R0312 · Subject to change without notice


Series NMVL and NMX
LIQUID INJECTION VALVES
SUCTION PRESSURE CONTROLLED, INTERCHANGEABLE ORIFICE CARTRIDGES

PRODUCT DATA

Features
 Suction gas controlled liquid injection valves
 Part programme containing:
Valve body head, orifice cartridge, connection base
 Honeywell NMVL:
- Only one valve body head needed both for internal
and external pressure equalisation
- Connection for pressure coupler integrated
in the solder base
- solder base two-way or angle construction
 Honeywell NMX:
- Balanced port
- External pressure equalisation integrated in the
valve body head
- solder base two-way or angle construction
- flare base two way construction
 Adjustable superheat setting
NMVL
 Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
 Interchangeable orifice cartridges
 Liquid charge
 Refrigerants: R134a, R22, R404A, R407C, R507A
NMX HFO (e.g. R1234yf) and future Blends
 Further refrigerants on request.

Application Specification
Nominal capacity range 0.52 to 75.1 kW R22
Honeywell thermostatic liquid injection valves series NMVL
and NMX are used in refrigeration applications to reduce the (small orifice graduation for
temperature of the suction gas. optimal control behaviour)
Depending on the superheat of the compressor suction gas, Temperature range -50 °C to +65 °C
liquid refrigerant is injected into the suction line. The Maximum pressure PS See table on page 90
refrigerant is evaporating and thereby the suction gas is
Maximum test pressure PF See table on page 90
cooled down.
Suitable for plants in general refrigeration and for serial Max. ambient temperature 70 °C
products such as air driers, dehumidifiers, chiller units or Max. bulb temperature 70 °C
ice-making machines with hot gas bypass control valves, for Static superheat See table on page 90
temperature reduction in multiple stage units and for suction Length of capillary tube NMVL: 1.5 m
gas cooled compressors.
NMX: 3.0 m
Bulb diameter NMVL: 12 mm
NMX: 16 mm
Materials
Body, base brass
Thermal head stainless steel
Connections copper or brass

EN0H-1930GE23 R0709 · Subject to change without notice 89


Series NMVL and NMX

Thermal Charges and Static Superheat


Code for Superheat PS PF
thermal charge R134a R22 R404A R407C R507A (bar(a)) (bar(a))
DA - 15 K 21 K 12 K 21 K 34 37.4
TA 15 K 30 K 35 K 26 K 35 K 29 31.9
LB 30 K 45 K - 40 K - 29 31.9
Further refrigerants on request.
The superheat is based on to = +0 °C.

Capacities
Type Orifice size Nominal capacity (kW)*
R134a R22 R404A R407C R507A
0.3 0.36 0.52 0.36 0.50 0.36
0.5 0.69 0.99 0.68 0.95 0.69
0.7 0.96 1.4 0.97 1.3 0.98
1.0 1.4 2.0 1.4 1.9 1.4
1.5 2.2 3.2 2.2 3.1 2.3
NMVL 2.0 2.9 4.0 2.8 3.9 2.9
2.5 4.0 5.8 4.1 5.6 4.1
3.0 6.6 9.3 6.5 8.9 6.6
3.5 8.7 12.2 8.6 11.7 8.7
4.5 11.8 17.0 12.0 16.4 12.1
4.75 15.9 22.4 15.8 21.6 15.9
4.5 11.8 17.0 12.0 16.4 12.1
4.75 15.9 22.4 15.8 21.6 15.9
5 20.0 29.1 20.5 28.0 20.7
NMX 6 27.6 42.4 29.8 40.8 30.1
7 35.3 54.5 38.3 52.5 38.7
8 43.3 64.1 45.1 61.8 45.6
10 51.0 75.1 52.8 72.3 53.3
* Capacities are based on to = +4 °C. tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.

90 EN0H-1930GE23 R0709 · Subject to change without notice


Dimensions and Weights
Type Connections Weight
(kg)
Inlet Outlet Pressure equalizer
(A) (B) (C)
NMVL - - - approx. 0.43
VD - - - approx. 0.02
6 mm ODF 10 mm ODF -
1/4" ODF 3/8" ODF -
VLS 10 mm ODF 12 mm ODF -
approx. 0.16
angle 3/8" ODF 1/2" ODF -
12 mm ODF 16 mm ODF -
1/2" ODF 5/8" ODF -
6 mm ODF 10 mm ODF 6 mm ODF
1/4" ODF 3/8" ODF 1/4" ODF
VLSX 10 mm ODF 12 mm ODF 6 mm ODF
approx. 0.17
angle 3/8" ODF 1/2" ODF 1/4" ODF
12 mm ODF 16 mm ODF 6 mm ODF
1/2" ODF 5/8" ODF 1/4" ODF
10 mm ODF 12 mm ODF -
VLS 3/8" ODF 1/2" ODF -
approx. 0.16
two-way 12 mm ODF 16 mm ODF -
1/2" ODF 5/8" ODF -
10 mm ODF 12 mm ODF 6 mm ODF
VLSX 3/8" ODF 1/2" ODF 1/4" ODF
approx. 0.17
two-way 12 mm ODF 16 mm ODF 6 mm ODF
1/2" ODF 5/8" ODF 1/4" ODF

NMVL

VD VLS(X) – two-way VLS(X) - angle

EN0H-1930GE23 R0709 · Subject to change without notice 91


Series NMVL and NMX

Type Connections Weight


(kg)
Inlet Outlet Pressure equalizer
(A) + (B) (C) + (D)
NMX - - 7/16" UNF approx. 0.6
XD - - - approx. 0.14
XLS 12 + 16 mm ODF 16 + 22 mm ODF -
approx. 0.41
two-way 1/2" + 5/8" ODF 5/8" + 7/8" ODF -
XLS 12 + 15 mm ODF 16 + 22 mm ODF -
approx. 0.32
angle 1/2" + 5/8" ODF 5/8" + 7/8" ODF -
XBS
7/8" UNF 7/8" UNF - approx. 0.49
two-way

NMX

XD XBS – two-way

XLS - angle XLS - two-way

92 EN0H-1930GE23 R0709 · Subject to change without notice


Type Code / Order Information
(Part Programme)
1. Valve body head 2. Orifice cartridge

NMVL DA VD 0.5
Series (NMVL, NMX) Series (VD, XD)
Code for thermal charge Orifice size

3. Connection base

VLS X 10 mm ODF x 12 mm ODF W


Series (VLS, XLS, XBS)
Pressure equalizer VLS:
X = external
() = internal
Connection size
(Inlet x Outlet)
D = two-way construction
W = angle construction

Installation Superheat Adjustment


 The valves may be installed in any position. In general the Honeywell liquid injection valves should be
 The external pressure equaliser line (VLSX and NMX) installed with the factory setting for the used refrigerant
should be 6 mm or 1/4" in diameter. It is connected to the unaltered.
suction line downstream of the remote bulb. An overbow is This superheat adjustment is calibrated for the above
recommended in order to prevent the ingress of oil into the mentioned superheat and optimal control behaviour.
equaliser line. However, should it be necessary to adjust the superheat,
turn the adjusting spindle as follows:
 The bulb should preferably be positioned on the upper half
of a horizontal suction line but never after a liquid trap. As Turning clockwise reduced refrigerant mass flow,
a general rule, bulbs of liquid injection valves should be =
increase of superheat
insulated to prevent them being affected by the ambient
temperature. Turning increased refrigerant mass
=
counterclockwise flow, decrease of superheat
 Do not bend or squeeze the bulb when tightening the bulb
clamp. One turn of the adjusting spindle alters superheat setting by
 Never quench the solder base with water after soldering, approx. 0.55 bar for NMVL and 0.3 bar for NMX.
this may cause cracks and distort the sealing surfaces.
 When tightening flare nuts of the flare connections grip at
wrench flats on the valve body.
 The screws fixing the valve body head to the base must be
tightened in diagonal sequence. Torque 12+1 Nm for NMVL
and 16+1 Nm for NMX.
 Constructive modifications at the valve are not allowed.

EN0H-1930GE23 R0709 · Subject to change without notice 93


Series NMVL and NMX

Application Sample

4 1 2 5

Power control with hot gas bypass valve and temperature reduction
of suction gas with liquid injection valve

1 Liquid Injection Valve


2 Hot gas bypass Valve
3 Thermostatic Expansion Valve
4 Liquid - Solenoid Valve
5 Hot gas - Solenoid Valve

94 EN0H-1930GE23 R0709 · Subject to change without notice


Series M
SOLENOID VALVES
NORMALLY CLOSED

PRODUCT DATA

Features
 MA: direct operated, angle construction
 MD: direct operated, two way construction
 MS: pilot operated, two way construction
 Normally closed
 Hermetic construction
 Low pressure drop
MA  High performance
MD  Direct operated: no minimum pressure differential
required to open the valve
 Pilot operated: minimum pressure differential of
0.05 bar required to open the valve
 Solder and flare connections
 Coils for AC and DC
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

Specification
MS
Nominal capacity see tables on page 96
Maximum pressure PS 35 bar(a)
Application Maximum test pressure PF 50 bar(a)
Min. pressure differential MA, MD: 0 bar
Solenoid valves series M are used in general refrigeration
and for original equipment to cut off/activate the refrigerant MS: 0.05 bar
flow in a refrigerating plant. Max. pressure differential MS: 2 bar
The solenoid valves can be installed in the liquid line, hot gas Max. opening pressure AC-coil: MA, MD: 25 bar
line and suction line of a refrigerating unit. differential MOPD MS: 30 bar
DC-coil: MA, MD: 21bar
Materials MS: 21 bar
Body brass, stainless steel Max. medium temperature 125 °C
Seal material PTFE Min. medium temperature -45 °C
Connection tubes solder: copper Max. ambient temperature 80 °C
flare: brass Min. ambient temperature -40 °C
Coil copper, steel, Crastin Number of operating cycles > 1,5 million
Standard coil voltages AC: 230V, 110V, 24V
DC: 230V, 24V
further voltages on request
Voltage tolerance AC: ±10%
DC: +10%, -5%

EN0H-1917GE23 R0312 · Subject to change without notice 95


Series M

Nominal Capacity QN (kW)


Liquid Hot gas Suction gas
kv-value
Typ R134a R22 R407C R404A R134a R22 R407C R404A R134a R22 R407C R404A
(m3/h)
R507A R507A R507A
Direct operated
MA 062 0.17 5.21 5.62 5.39 3.87 1.14 1.47 1.45 1.29 - - - -
MD 062 0.17 5.21 5.62 5.39 3.87 1.14 1.47 1.45 1.29 - - - -
MD 103 0.23 7.05 7.61 7.29 5.24 1.54 1.99 1.96 1.75 - - - -
Pilot operated
MS 103 0.9 27.6 29.8 28.5 20.5 6.04 7.78 7.67 6.83 1.54 2.06 1.92 1.80
MS 104 0.9 27.6 29.8 28.5 20.5 6.04 7.78 7.67 6.83 1.54 2.06 1.92 1.80
MS 124 1.6 49.0 52.9 50.7 36.4 10.7 13.8 13.6 12.1 2.74 3.66 3.42 3.19
MS 125 1.6 49.0 52.9 50.7 36.4 10.7 13.8 13.6 12.1 2.74 3.66 3.42 3.19
MS 165 2 61.3 66.1 63.4 45.5 13.4 17.3 17.1 15.2 3.42 4.57 4.27 3.99
MS 167 2 61.3 66.1 63.4 45.5 13.4 17.3 17.1 15.2 3.42 4.57 4.27 3.99
MS 227 4 123 132 127 91.1 26.8 34.6 34.1 30.4 6.85 9.14 8.54 7.98

The nominal capacity QN is based on the following conditions

Medium Evaporating Condensing Subcooling Hot gas Pressure loss


temperature temperature temperature across valve
to (°C) tc (°C) tc2u (K) tH (°C) p (bar)
Liquid -10 25 1 - 0.4
Hot gas -10 25 1 50 °C 1
Suction gas -10 25 1 - 0.15
Valve selection for other operating conditions see the following tables or consult the Honeywell software

96 EN0H-1917GE23 R0312 · Subject to change without notice


Valve size calculation for the liquid line
Refrigeration capacity Q0, multiplied with correcting factor fTF,
multiplied with correcting factor fPF results in the required
nominal capacity QN.

QN = Qo x fTF x fPF
QN nominal capacity (according to table on page 96)
Qo refrigeration capacity
fTF correcting factor for evaporating and liquid
temperature
fPF correcting factor for pressure loss across the valve

Correcting factor fTF for the change of capacity according to the operating temperatures

Evaporating temperature to (°C)


tL*
R134a R22 R407C R404A, R507A
(°C)
+10 ±0 -10 -20 -30 -40 +10 ±0 -10 -20 -30 -40 +10 ±0 -10 -20 -30 +10 ±0 -10 -20 -30 -40
0 - - 0.80 0.83 0.85 0.88 - - 0.82 0.83 0.85 0.88 - - 0.80 0.80 0.80 - - 0.73 0.76 0.79 0.83
+5 - - 0.83 0.86 0.89 0.93 - - 0.85 0.87 0.89 0.91 - 0.80 0.80 0.80 0.90 - - 0.77 0.8 0.84 0.88
+10 - 0.84 0.87 0.91 0.94 0.97 - 0.86 0.88 0.90 0.92 0.95 - 0.80 0.90 0.90 0.90 - 0.79 0.82 0.85 0.89 0.94
+15 - 0.88 0.91 0.94 0.98 1.02 - 0.90 0.92 0.94 0.96 0.99 0.90 0.90 0.90 0.90 1.00 - 0.84 0.87 0.91 0.95 1.00
+20 0.89 0.92 0.95 0.99 1.03 1.08 0.92 0.94 0.96 0.98 1.00 1.03 0.90 0.90 0.90 1.00 1.00 0.86 0.89 0.93 0.97 1.02 1.08
+25 0.94 0.96 1.00 1.05 1.09 1.14 0.96 0.98 1.00 1.03 1.05 1.09 0.90 1.00 1.00 1.00 1.10 0.92 0.96 1.05 1.05 1.11 1.18
+30 0.99 1.02 1.06 1.12 1.16 1.22 1.01 1.02 1.05 1.08 1.10 1.14 1.00 1.00 1.00 1.10 1.20 0.99 1.03 1.08 1.14 1.21 1.29
+35 1.04 1.08 1.12 1.18 1.24 1.30 1.05 1.07 1.10 1.13 1.16 1.20 1.10 1.10 1.10 1.20 1.20 1.08 1.13 1.19 1.26 1.34 1.44
+40 1.10 1.14 1.19 1.26 1.32 1.39 1.10 1.12 1.15 1.19 1.22 1.26 1.10 1.20 1.20 1.30 1.30 1.18 1.24 1.32 1.40 1.50 1.63
+45 1.18 1.22 1.28 1.35 1.42 1.50 1.17 1.19 1.22 1.26 1.29 1.34 1.20 1.30 1.30 1.40 1.40 1.32 1.39 1.48 1.59 1.72 1.88
+50 1.25 1.24 1.37 1.45 1.53 1.62 1.23 1.26 1.29 1.33 1.37 1.42 1.30 1.40 1.40 1.50 1.60 1.50 1.59 1.7 1.85 2.02 2.23
+55 1.35 1.41 1.48 1.58 1.67 1.78 1.30 1.33 1.37 1.42 1.46 1.52 1.40 1.50 1.60 1.70 1.80 1.74 1.87 2.02 2.22 2.47 2.79
+60 1.46 1.55 1.61 1.73 1.84 1.97 1.38 1.41 1.46 1.51 1.56 1.63 - - - - - - - - - - -
* Temperature of liquid refrigerant at valve inlet.

Correcting factor fPF for the change of capacity according to the chosen pressure loss across the valve

Pressure loss across valve p (bar) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70
Correcting factor fPF 2.83 2.00 1.63 1.41 1.26 1.15 1.07 1.00 0.94 0.89 0.85 0.82 0.78 0.76

EN0H-1917GE23 R0312 · Subject to change without notice 97


Series M

Valve capacity for the hot gas line


Type Pressure Capacity (kW)*
loss
Condensing temperature tc (°C)
across
valve R134a R22 R407C R404A, R507A
p (bar) +25 +30 +40 +50 +60 +25 +30 +40 +50 +60 +25 +30 +40 +50 +25 +30 +40 +50
Direct operated
0.2 0.54 0.55 0.57 0.58 0.57
0.68 0.70 0.74 0.76 0.78 0.62 0.65 0.68 0.70 0.60 0.60 0.58 0.53
MA 062 0.5 0.83 0.86 0.89 0.90 0.89
1.06 1.10 1.15 1.19 1.22 0.98 1.02 1.08 1.11 0.93 0.93 0.90 0.83
1.0 1.12 1.17 1.23 1.25 1.24
1.46 1.51 1.60 1.67 1.70 1.39 1.44 1.52 1.57 1.29 1.29 1.26 1.16
MD 062
1.5 1.31 1.38 1.47 1.50 1.50
1.74 1.81 1.93 2.01 2.06 1.71 1.77 1.87 1.93 1.54 1.55 1.52 1.41
2.0 1.44 1.52 1.64 1.70 1.70
1.94 2.04 2.19 2.29 2.34 1.96 2.04 2.15 2.22 - - - -
0.2 0.72 0.75 0.78 0.78 0.77
0.80 0.95 1.00 1.03 1.05 0.84 0.87 0.92 0.95 0.80 0.80 0.78 0.71
0.5 1.12 1.16 1.21 1.22 1.21
1.43 1.48 1.56 1.62 1.65 1.33 1.38 1.46 1.50 1.26 1.26 1.22 1.12
MD 103 1.0 1.51 1.58 1.67 1.69 1.68
1.98 2.05 2.17 2.25 2.30 1.88 1.95 2.06 2.13 1.74 1.74 1.70 1.57
1.5 1.77 1.86 1.98 2.03 2.02
2.35 2.45 2.61 2.72 2.78 2.31 2.39 2.52 2.61 2.08 2.09 2.05 1.90
2.0 1.94 2.06 2.22 2.30 2.30
2.64 2.76 2.96 3.10 3.17 2.66 2.76 2.91 3.01 - - - -
Pilot operated
0.2 2.83 2.93 3.04 3.06 3.02 4.20 4.33 4.55 4.70 4.79 3.60 3.71 3.90 4.03 3.09 3.09 3.00 2.74
MS 103 0.5 4.37 4.53 4.73 4.78 4.72 6.55 6.76 7.13 7.38 7.52 5.61 5.79 6.11 6.33 4.89 4.89 4.80 4.37
1.0 5.93 6.19 6.52 6.63 6.57 9.02 9.35 9.91 10.3 10.5 7.73 8.01 8.49 8.83 6.77 6.86 6.69 6.09
MS 104
1.5 6.93 7.29 7.77 7.95 7.92 10.8 11.2 11.9 12.4 12.7 9.26 9.60 10.2 10.6 8.14 8.14 8.06 7.37
2.0 7.60 8.07 8.66 9.00 9.00 12.1 12.6 13.5 14.2 14.5 10.4 10.8 11.6 12.2 - - - -
0.2 5.04 5.21 5.40 5.44 5.36 6.40 6.60 6.94 7.17 7.30 5.86 6.07 6.41 6.62 5.60 5.60 5.44 4.96
MS 124 0.5 7.77 8.07 8.40 8.50 8.39 9.97 10.3 10.9 11.2 11.5 9.27 9.6 10.1 10.5 8.76 8.76 8.52 7.80
1.0 10.5 11.0 11.6 11.8 11.7 13.7 14.3 15.1 15.7 16.0 13.1 13.6 14.3 14.8 12.1 12.1 11.8 10.9
MS 125
1.5 12.3 13.0 13.8 14.1 14.1 16.4 17.1 18.2 19.0 19.4 16.1 16.6 17.6 18.1 14.5 14.6 14.3 13.2
2.0 13.5 14.3 15.5 16.0 16.0 18.4 19.2 20.6 21.6 22.1 18.5 19.2 20.3 20.9 - - - -
0.2 6.29 6.51 6.76 6.80 6.70 8.00 8.25 8.68 8.96 9.12 7.33 7.59 8.01 8.28 7.00 7.00 6.80 6.20
MS 165 0.5 9.72 10.1 10.5 10.6 10.5 12.5 12.9 13.6 14.1 14.3 11.6 12.0 12.7 13.1 10.9 10.9 10.6 9.70
1.0 13.2 13.7 14.5 14.7 14.6 17.2 17.8 18.9 19.6 20.0 16.4 17.0 17.9 18.5 15.1 15.2 14.8 13.6
MS 167
1.5 15.4 16.2 17.2 17.7 17.6 20.5 21.3 22.7 23.7 24.2 20.1 20.8 22.0 22.7 18.1 18.2 17.9 16.5
2.0 16.9 17.9 19.3 20.0 20.0 23.0 24.0 25.7 27.0 27.6 23.2 24.0 25.3 26.2 - - - -
0.2 12.6 13.0 13.5 13.6 13.4 16.0 16.5 17.4 17.9 18.2 14.7 15.2 16.0 16.6 14.0 14.0 13.6 12.4
0.5 19.4 20.1 21.0 21.2 21.0 24.9 25.8 27.1 28.1 28.6 23.2 24.0 25.3 26.2 21.9 21.9 21.3 19.5
MS 227 1.0 26.3 27.5 29.0 29.5 29.2 34.4 35.6 37.8 39.2 40.0 32.8 33.9 35.8 37.0 30.3 30.4 29.7 27.3
1.5 30.8 32.4 34.5 35.3 35.2 41.0 42.6 45.4 47.4 48.4 40.1 41.6 43.9 45.3 36.3 36.5 35.8 33.1
2.0 33.8 35.9 38.7 39.9 40.0 45.9 48.0 51.5 53.9 55.2 46.3 48.0 50.7 52.4 - - - -
* Capacities are based on evaporating temperature to = -10 °C, hot gas temperature tH = +25 °C and 1 K subcooled refrigerant.

If the hot gas temperature is changed by ±10 °C the valve capacity changes (inversely proportional) by ±2,5 %.
With other evaporating temperatures to the capacities above should be multiplied by the following correcting factors:

to (°C) -50 -40 -30 -20 -10 ±0 +10


R134a - 0.85 0.90 0.95 1.00 1.05 1.09
R22 0.88 0.91 0.95 0.97 1.00 1.03 1.05
R407C 0.83 0.88 0.92 0.95 1.00 1.01 1.06
R404A, R507 0.75 0.81 0.88 0.13 1.00 1.05 -

98 EN0H-1917GE23 R0312 · Subject to change without notice


Valve size calculation for the suction line
Refrigeration capacity Qo, multiplied with correcting factor fTS,
multiplied with correcting factor fPS results in the required
nominal capacity QN.

QN = Qo x fTS x fPS
QN nominal capacity (according to table on page 96)
Qo refrigeration capacity
fTS correcting factor for evaporating and liquid
temperature
fPS correcting factor for pressure loss across the valve

Correcting factor fTS for the change of capacity according to the operating temperatures

Evaporating Condensating temperature tc (°C)


temperature +60 +50 +40 +30 +20
to (°C)
For refrigerant R134a, R22, R407C
+10 0.98 0.86 0.78 0.71 0.66
±0 1.19 1.05 0.95 0.86 0.79
-10 1.48 1.29 1.16 1.05 0.96
-20 1.88 1.62 1.44 1.31 1.19
-30 2.42 2.08 1.83 1.65 1.59
-40 3.20 2.71 2.37 2.13 1.92
For refrigerant R404A, R507A
+10 - 1.14 0.82 0.71 0.63
±0 - 1.24 1.01 0.87 0.77
-10 - 1.57 1.26 1.07 0.94
-20 - 2.02 1.60 1.35 1.17
-30 - 2.67 2.07 1.72 1.49
-40 - 3.62 2.74 2.25 1.93

Correcting factor fPS for the change of capacity according to the chosen pressure loss across the valve

Pressure loss across valve p (bar) 0.05 0.075 0.10 0.15 0.20 0.30 0.40 0.50 0.60
Correcting factor fPS 1.73 1.41 1.22 1.00 0.87 0.71 0.61 0.55 0.50

EN0H-1917GE23 R0312 · Subject to change without notice 99


Series M

Type Code / Order Information


1. Solenoid Valve
M S 16 5 S 230 V AC
Series
Type:
A = direct operated, angle
D = direct operated
S = pilot operated
Valve size
Connection size in 1/8”
() = flare connection
MMS = solder, metric
S = solder, inch
Voltage
() = without coil

2. Solenoid Coil
Type of coil, capacity For Solenoid Valve Voltage, frequency Voltage tolerance
MC 062, 8 W MA 062(S)(MMS) 230 V, 50/60 Hz
MD 062(S)(MMS) 110 V, 50/60 Hz ±10 %
24 V, 50/60 Hz
MC 102-227, 13 W MD 103(S)(MMS) 230 V, 50/60 Hz
MS 103-227(S)(MMS) 110 V, 50/60 Hz ±10 %
24 V, 50/60 Hz
MC 102-227, 20 W MD 103(S)(MMS)
24 V DC +10 %
MS 103-227(S)(MMS)
230 V DC -5 %

International protection rating IP65, coil incl. e.l.c.b.-protected plug to DIN 43650 with cable gland; conduit thread PG11.

100 EN0H-1917GE23 R0312 · Subject to change without notice


Dimensions and Weights
Type Connections For tube Dimensions (mm) Weight (kg)
(E) diameter
A B C D without coil with coil
230 V AC 230 V AC
Direct operated
MA 062MMS 6 mm ODF 6 mm 88 88 142 47 0.15 0.30
MA 062S 1/4" ODF 1/4" 88 88 142 47 0.15 0.30
MD 062 7/16" UNF 6 mm, 1/4" 65 17 57 47 0.19 0.33
MD 062MMS 6 mm ODF 6 mm 112 17 57 47 0.17 0.31
MD 062S 1/4" ODF 1/4" 112 17 57 47 0.17 0.31
MD 103 5/8" UNF 10 mm, 3/8" 71 19 64 54 0.28 0.52
MD 103MMS 10 mm ODF 10 mm 118 19 64 54 0.25 0.49
MD 103S 3/8" ODF 3/8" 118 19 64 54 0.25 0.49
Pilot operated
MS 103 5/8" UNF 10 mm, 3/8" 84 12 79 54 0.51 0.75
MS 103MMS 10 mm ODF 10 mm 159 12 79 54 0.55 0.79
MS 103S 3/8" ODF 3/8" 159 12 79 54 0.55 0.79
MS 104 MMS 12 mm ODF 12 mm 159 12 79 54 0.56 -
MS 104S 1/2" ODF 1/2" 159 12 79 54 0.56 -
MS 124 3/4" UNF 12 mm, 1/2" 91 12 79 54 0.54 0.77
MS 124MMS 12 mm ODF 12 mm 159 12 79 54 0.56 0.79
MS 124S 1/2" ODF 1/2" 159 12 79 54 0.56 0.79
16 mm,
MS 125S 16 mm, 5/8" 159 12 79 54 0.56 -
5/8" ODF
MS 165 7/8" UNF 16 mm, 5/8" 97 12 79 54 0.57 0.80
16 mm,
MS 165S 16 mm, 5/8" 159 12 79 54 0.59 0.82
5/8" ODF
22 mm,
MS 167S 22 mm, 7/8" 173 12 79 54 0.59 -
7/8" ODF
22 mm,
MS 227S 22 mm, 7/8" 262 22 88 54 1.45 1.65
7/8" ODF

MA MD MS

EN0H-1917GE23 R0312 · Subject to change without notice 101


Series M

Installation
 Position of plunger tube should be from upright to  Voltage of coil and network must correspond.
horizontal position.  The flat spade terminals is the earth connection. The
 Arrow on valve body must correspond with flow direction. protective conductor must also be connected at the plant.
 Keep 45 mm distance clear above the valve for  Do not energize the coil before assembling on the valve
assembly/disassembly of coil. body.
 Fit solenoid valve so that it is drip proof.  All gaskets must be fitted carefully in order to achieve
 Solder valves: protection to IP65.

 Remove cap nut, coil and gaskets before soldering.  Tighten fixing screw of connector.

 Max. temperature of valve body: 125 °C.  Constructive modifications at the valve are not allowed.

 When soldering, always point flame away from valve


body.
 When assembling after soldering, fit the coil’s top and
bottom seal rings.
 Flare valves:
 When tightening flare nuts grip at wrench flats on the
valve body provided for this purposes.
 Do not use coil and plunger tube as lever (thin-walled
plunger tube).
 When installing direct operated valves with 20 W DC
coil, the flare nut must be tightened in that way that one
flat of the nut is in parallel with the lower surface of the
coil.

102 EN0H-1917GE23 R0312 · Subject to change without notice


Series RV
CHECK VALVES
FOR ALL FLUORINATED REFRIGERANTS

PRODUCT DATA

Features
 Hermetically welded type
 Low pressure drop
 Copper plated solder connections
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

Specification
Nominal capacity range see table on page 104
Maximum pressure PS 43 bar(a)
32.5 bar(a) (RV-07S)
11 bar(a) at t < -20 °C
Maximum test pressure PF 61.5 bar(a)
46.5 bar(a) (RV-07S)
15.7 bar(a) at t < -20 °C
Maximum temperature 120 °C
Minimum temperature -40 °C

Application
Check valves series RV are installed in the liquid line, hot gas
line or suction line of a refrigerated plant to permit the flow of
the refrigerant only in one direction. This is realised by a
spring-loaded piston which opens the valve only in one
direction.

Materials
Housing, piston brass
Sealing material Teflon
Connection tubes copper plated brass

EN0H-1916GE23 R0709 · Subject to change without notice 103


Series RV

Capacities
Type P* kv- QN (kW)
(bar) value
Liquid line Suction gas line Hot gas line
(m3/h)
R22 R134a R404A R407C R22 R134a R404A R407C R22 R134a R404A R407C
R507A R410A R507A R410A R507A R410A

RV-02 MMS
0.06 0.37 6.7 6.2 4.4 6.2 1.0 0.8 0.8 1.0 4.4 3.2 3.7 4.7
RV-02 S
RV-03 MMS
0.06 1.75 31.7 29.3 20.8 29.2 4.7 3.8 3.8 4.5 20.8 15.1 17.5 22.2
RV-03 S
RV-04 MMS
0.05 3.27 59.2 54.8 38.9 54.6 8.8 7.1 7.1 8.4 38.0 28.3 32.7 40.6
RV-04 S
RV-05 S 0.05 3.64 65.9 61.0 43.3 60.7 9.8 7.9 7.9 9.3 43.3 31.5 36.4 46.3
RV-07 S 0.03 7.50 136.4 126.4 89.5 125.7 20.5 16.3 17.0 19.5 87.5 63.8 75.0 93.5
* P = min. pressure drop at which the valve is completely open
The nominal capacity QN as mentioned in table above refers to the following conditions:
Liquid and suction gas:
evaporating temperature to: +4 °C
condensing temperature tc: +38 °C
pressure drop: 0.15 bar

Hot gas:
temperature of hot gas: +85 °C
pressure drop: 1.0 bar

Dimensions and Weights


Type Connection Dimensions (mm) Weight
(A) B C D L (kg)
RV-02 MMS 6 mm ODF 42 22 18 95
approx. 0.05
RV-02 S 1/4" ODF 42 22 18 95
RV-03 MMS 10 mm ODF 42 22 18 95
approx. 0.05
RV-03 S 3/8" ODF 42 22 18 95
RV-04 MMS 12 mm ODF 48 28 27 117
approx. 0.15
RV-04 S 1/2" ODF 48 28 27 117
16 mm ODF
RV-05 S 48 28 27 117 approx. 0.20
5/8" ODF
22 mm ODF
RV-07 S 72 72 35.5 186 approx. 0.25
7/8" ODF

104 EN0H-1916GE23 R0709 · Subject to change without notice


Series SLI/SBI
SIGHT GLASSES
WITH MOISTURE INDICATOR

PRODUCT DATA

Features
 Large display area
 Moisture indicator
 Low pressure loss
 SLI with solder connections on both sides
 SBI with flare connections on both sides
SLI
 SBIA with flare connections,
female thread x male thread
 Refrigerants: all CFC, HCFC, HFC,
HFO (e.g. R1234yf) and future Blends
not for R12, R502 and ammonia

Specifications
SBI Moisture indicator range see table on page 106
Max. ambient temperature TS 80 °C
Diameter display area 22.5 mm

Maximum Maximum
Type
SBIA pressure PS test pressure PF
SLI 6; SLI 1/4
SLI 10; SLI 3/8
SLI 12; SLI 1/2 44 bar(a) 63 bar(a)
Application SLI 15
Sight glasses series SLI/SBI/SBIA show the condition of the SLI 16 (5/8)
refrigerant flowing through the lines in the refrigerating plant,
SLI 18; SLI 3/4
for example it is possible to see if the refrigerant in the liquid
line is free of bubbles. SLI 22 (7/8)
36 bar(a) 51.5 bar(a)
The moisture indicator shows the moisture content in the SBI
refrigerant. SBIA
SLI 28; SLI 1 1/8 35 bar(a) 50 bar(a)
Materials
Housing brass
Display area pressure resistant glass,
indicator paper
Connection tubes Solder: copper
Flare: brass

EN0H-1922GE23 R1110 · Subject to change without notice 105


Series SLI/SBI

Moisture Indicator
The colour of the indicator is a measure for the moisture load Green colour: Moisture free.
of the refrigerant inside the plant. Only a moisture-free refrigerant assures no trouble with the
The range of indication depends on the refrigerant: expansion valve coming from humidity.

Refrigerant Indication Range Transition range:


dry (green) Transition wet (yellow) When the green colour begins to fade, it is an indication that
R22 < 30 ppm 30 – 150 ppm > 150 ppm small quantities of moisture are present. It is recommended to
change the filter drier.
R134a < 60 ppm 60 – 100 ppm > 100 ppm
R404A < 20 ppm 20 – 100 ppm > 100 ppm Yellow colour: Wet.
R407C < 20 ppm 20 – 130 ppm > 130 ppm The refrigerant is loaded with moisture higher than the stated
R410A < 40 ppm 40 – 150 ppm > 150 ppm values. A change of the filter drier is required.
R507A < 20 ppm 20 – 100 ppm > 100 ppm
Due to the humidity in the air, the indicator is yellow on
Indication temperature: 30 °C
delivery. After the installation inside the plant, the indicator
will change to green when filling the system with dry
refrigerant.

Dimensions and Weights


Dimensions
Weight
Type Connection Pipe diameter Length approx. (kg)
(A) (B) (L)
SLI 6 6 mm ODF 6 mm 106 mm 0.15
SLI 10 10 mm ODF 10 mm 119 mm 0.15
SLI 12 12 mm ODF 12 mm 144 mm 0.20
SLI 15 15 mm ODF 15 mm 146 mm 0.17
SLI 16 16 mm; 5/8" ODF 16 mm; 5/8" ODF 146 mm 0,17
SLI 18 18 mm ODF 18 mm 183 mm 0.22
SLI 22 22 mm; 7/8" ODF 22 mm; 7/8" ODF 183 mm 0,24
SLI 1/4 1/4" ODF 1/4" 106 mm 0.15
SLI 3/8 3/8" ODF 3/8" 119 mm 0.15
SLI 1/2 1/2" ODF 1/2" 144 mm 0.19
SLI 3/4 3/4" ODF 3/4" 183 mm 0.22
SLI 1 1/8 1 1/8" ODF 1 1/8" 188 mm 0.48
SBI 6 7/16" UNF 6 mm 1/4" 70 mm 0.15
SBI 10 5/8" UNF 10 mm 3/8" 76 mm 0.15
SBI 12 3/4" UNF 12 mm 1/2" 88 mm 0.17
SBI 16 7/8" UNF 16 mm 5/8" 98 mm 0.29
SBIA 6 7/16" UNF 6 mm 1/4" 60 mm 0.30
SBIA 10 5/8" UNF 10 mm 3/8" 76 mm 0.15
SBIA 12 3/4" UNF 12 mm 1/2" 74 mm 0.19
SBIA 16 7/8" UNF 16 mm 5/8" 78 mm 0.31

106 EN0H-1922GE23 R1110 · Subject to change without notice


SLI

SBI SBIA

EN0H-1922GE23 R1110 · Subject to change without notice 107


Series SLI/SBI

Type Code / Order Information


S B I A 12
Series
Connection type:
B = flare
L = solder
Indicator
A = Inner and outer connection
()
Tube connection size (mm, inch)

108 EN0H-1922GE23 R1110 · Subject to change without notice


Series FF
FILTER DRIERS
PRODUCT DATA

Features
 Liquid line filter drier
 Drying agent in bulk
 Low pressure drop
 High performance
 Hermetic construction
 Solder or flare connections
 FF ...MMS: solder connection in mm
 FF ...S: solder connection in inch
 FF ...: flare connection
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

Specification
Nominal capacity see tables on page 110
Water adsorption see table on page 111
Maximum pressure PS 43 bar(a)
40 bar(a) (for FF 410)
11 bar(a) at t < -20 °C
Maximum test pressure PF 61.5 bar(a)
57.2 bar(a) (for FF 410)
Application 15.7 bar(a) at t < -20 °C
Filter driers series FF are used for filtration of impurities by Max. operating temperature 80 °C
microscopic filters and to take away moisture from the
refrigerant. Min. operating temperature -40 °C
The filter driers are placed in the liquid line of airconditioning,
refrigeration and deep freeze systems. Installation
 Any mounting position in the liquid line.
Materials  Flow in direction of arrow!
Housing steel  When soldering the filter drier, the housing must not get
Internals steel warmer than 160 °C.
Drier molekularsieve, activated alumina  Constructive modifications at the filter drier are not
allowed.
Connections solder: copper, copper plated steel or
steel**
flare: nickel plated steel

EN0H-1920GE23 R0709 · Subject to change without notice 109


Series FF

Capacities, Dimensions and Weights


Filter drier with solder connections
Type Nominal cooling capacity Connections Dimensions Weight
(kW)* ODF D L VF (kg)
(d)
R134a R22 R404A R407C R410A (mm) (mm) (dm3)
R507A
FF 032MMS 9.8 10.7 7.0 10.1 10.6 6 mm 52 98.5 0.1 0.26
FF 032S 9.8 10.7 7.0 10.1 10.6 1/4" 52 98.5 0.1 0.26
FF 052MMS 9.6 10.5 6.8 9.9 10.4 6 mm 52 111.5 0.1 0.295
FF 052S 9.6 10.5 6.8 9.9 10.4 1/4" 52 111.5 0.1 0.295
FF 053MMS 23.3 25.4 16.6 23.9 25.0 10 mm 52 111.5 0.1 0.325
FF 053S 23.3 25.4 16.6 23.9 25.0 3/8" 52 111.5 0.1 0.325
FF 082MMS 9.1 9.9 6.5 9.3 9.7 6 mm 52 139.5 0.2 0.37
FF 082S 9.1 9.9 6.5 9.3 9.7 1/4" 52 139.5 0.2 0.37
FF 083MMS 22.7 24.8 16.1 23.3 24.4 10 mm 52 139.5 0.2 0.405
FF 083S 22.7 24.8 16.1 23.3 24.4 3/8" 52 139.5 0.2 0.405
FF 084MMS 30.2 33.0 21.5 31.1 32.6 12 mm 52 139.5 0.2 0.465
FF 084S 30.2 33.0 21.5 31.1 32.6 1/2" 52 139.5 0.2 0.465
FF 162MMS 8.8 9.6 6.2 9.0 9.4 6 mm 74 159 0.4 0.825
FF 162S 8.8 9.6 6.2 9.0 9.4 1/4" 74 159 0.4 0.825
FF 163MMS 22.7 24.8 16.1 23.3 24.4 10 mm 74 159 0.4 0.875
FF 163S 22.7 24.8 16.1 23.3 24.4 3/8" 74 159 0.4 0.875
FF 164MMS 33.6 36.6 23.9 34.5 36.1 12 mm 74 159 0.4 0.93
FF 164S 33.6 36.6 23.9 34.5 36.1 1/2" 74 159 0.4 0.93
FF 165S 47.8 52.1 34.0 49.1 51.4 16 mm - 5/8" 74 163 0.4 0.96
FF 303MMS 22.7 24.8 16.1 23.3 24.4 10 mm 74 235.5 0.6 1.305
FF 303S 22.7 24.8 16.1 23.3 24.4 3/8" 74 235.5 0.6 1.305
FF 304MMS 33.6 36.6 23.9 34.5 36.1 12 mm 74 235.5 0.7 1.35
FF 304S 33.6 36.6 23.9 34.5 36.1 1/2" 74 235.5 0.7 1.35
FF 305S 47.8 52.1 34.0 49.1 51.4 16 mm - 5/8" 74 239.5 0.7 1.41
FF 307S** 64.7 70.6 46.0 66.5 69.7 22 mm - 7/8" 74 259.5 0.6 1.45
FF 414MMS 38.8 42.4 27.6 39.9 41.8 12 mm 93 232.5 1.1 2.035
FF 414S 38.8 42.4 27.6 39.9 41.8 1/2" 93 232.5 1.1 2.035
FF 415S 60.5 66.0 43.0 62.2 65.1 16 mm - 5/8" 93 245.5 1.1 2.105
FF 417S** 84.1 91.7 59.8 86.4 90.5 22 mm - 7/8" 93 278.5 1.2 2.110

Filter drier with flare connections


Type Nominal cooling capacity Connectios Dimensions Weight
(kW)* UNF D L VF (kg)
(d)
R134a R22 R404A R407C R410A (mm) (mm) (dm3)
R507A
FF 032 5.7 6.3 4.1 5.9 6.2 7/16" 52 108.5 0.1 0.26
FF 052 5.6 6.1 4.0 5.8 6.1 7/16" 52 121.5 0.1 0.295
FF 053 18.6 20.3 13.3 19.2 20.1 5/8" 52 127.5 0.1 0.325
FF 082 5.3 5.8 3.8 5.5 5.8 7/16" 52 149.5 0.2 0.37
FF 083 18.1 19.8 12.9 18.7 19.6 5/8" 52 155.5 0.2 0.405
FF 084 28.7 31.4 20.4 29.5 30.9 3/4" 52 159.5 0.2 0.465
FF 162 5.2 5.7 3.7 5.3 5.6 7/16" 74 169 0.4 0.825
FF 163 17.7 19.3 12.6 18.2 19.1 5/8" 74 175 0.4 0.875
FF 164 31.1 33.9 22.1 32.0 33.5 3/4" 74 179.5 0.4 0.93
FF 165 44.4 48.4 31.6 45.6 47.8 7/8" 74 183.5 0.4 0.96
FF 303 17.7 19.3 12.6 18.2 19.1 5/8" 74 251.5 0.6 1.305
FF 304 31.1 33.9 22.1 32.0 33.5 3/4" 74 255.5 0.7 1.35
FF 305 44.4 48.4 31.6 45.6 47.8 7/8" 74 259.5 0.7 1.41
FF 414 36.3 39.7 25.9 37.4 39.2 3/4" 93 252.5 1.1 2.035
FF 415 56.6 61.8 40.3 58.2 61.0 7/8" 93 265.5 1.1 2.105
* Capacities are based on to = -15 °C, tc = +30 °C and pressure drop p = 0.07 bar.
** Steel connections

110 EN0H-1920GE23 R0709 · Subject to change without notice


Filter drier with solder connections

Filter drier with flare connections

Water adsorption rate


Water adsorption rate (g)
Refrigerant R134a R22 R404A R407C R410A
R507A
Final moisture 50 ppm 60 ppm 50 ppm 50 ppm 50 ppm
Liquid tempera-
24 °C 52 °C 24 °C 52 °C 24 °C 52 °C 24 °C 52 °C 24 °C 52 °C
ture
030 4.0 3.7 3.9 3.6 4.3 4.0 3.6 3.1 2.5 2.3
050 7.8 7.2 7.5 6.9 8.3 7.7 7.0 5.9 4.8 4.4
080 12.6 11.6 12.1 11.1 13.4 12.4 11.2 9.6 7.7 7.0
Type
160 25.1 23.2 24.1 22.2 26.7 24.8 22.4 19.1 15.3 14.1
300 48.5 44.8 46.7 42.9 51.7 47.9 43.2 37.0 29.7 27.2
410 67.2 62.0 64.6 59.4 71.6 66.4 59.9 51.2 41.0 37.7

EN0H-1920GE23 R0709 · Subject to change without notice 111


Series FF

Type Code / Order Information


FF 16 4 MMS
Series
Filter size
Tube connection size in 1/8‘‘
Connection type:
() = flare
S = solder in inch
MMS = solder in mm

112 EN0H-1920GE23 R0709 · Subject to change without notice


Series SA
VIBRATION ABSORBERS
FROST RESISTANT CONSTRUCTION, LASER WELDED

PRDUCT DATA

Features
 Short connection fittings
 Compact construction
 Flexible pipe, braid and shoulder made of stainless
steel
 Frost resistant construction - no collecting of
condensation water within the corrugated area
 Suitable for vertical installation
 Laser welded
 Connection fittings made of copper
 No preventive measures from overheating necessary
when soldering
 Refrigerants: all CFC, HCFC, HFC
HFO (e.g. R1234yf) and future Blends
not for ammonia

Specification
Maximum pressure PS 35 bar(a)
Maximum test pressure PF 1.5 x PS
Maximum temperature 250 °C
Minimum temperature -100 °C

Application
Vibration absorbers series SA are installed in refrigerated
plants to minimize vibrations on the pipes caused by the
compressor. Furthermore they decrease noise and
compensate small thermal displacements.

Materials
Flexible pipe stainless steel
Braid stainless steel
Shoulder stainless steel
Connection fittings copper

EN0H-1942GE23 R0709 · Subject to change without notice 113


Series SA

Dimensions and Weight


Type Connection Dimensions (mm) Weight
(A) B C D L (kg)
6 mm ODF 230
SA06-1/4 1.0 20 19 approx. 0.11
1/4" ODF
SA08 8 mm ODF 1.0 20 19 230 approx. 0.11
SA3/8 3/8" ODF 1.0 20 19 230 approx. 0.11
SA10 10 mm ODF 1.0 20 19 230 approx. 0.12
SA12 12 mm ODF 1.0 20 21 230 approx. 0.13
SA1/2 1/2" ODF 1.0 20 21 230 approx. 0.13
SA15 15 mm ODF 1.0 25 27 255 approx. 0.17
16 mm ODF 255 approx. 0.17
SA16-5/8 1.0 25 27
5/8" ODF
SA18 18 mm ODF 1.0 25 27 255 approx. 0.17
SA3/4 3/4" ODF 1.0 25 27 255 approx. 0.17
22 mm ODF 290 approx. 0.28
SA22-7/8 1.5 25 32
7/8" ODF
28 mm ODF 330 approx. 0.44
SA28-1 1/8 1.5 25 39
1 1/8" ODF
35 mm ODF 375 approx. 0.72
SA35-1 3/8 2.0 30 48
1 3/8" ODF
42 mm ODF 430 approx. 1.35
SA42-1 5/8 2.0 35 58
1 5/8" ODF
54 mm ODF
SA54-2 1/8 2.5 45 70 510 approx. 1.68
2 1/8" ODF

114 EN0H-1942GE23 R0709 · Subject to change without notice


Notes

EN0H-0376GE23 R1014 · Subject to change without notice 115


Notes

116 EN0H-0376GE23 R1014 · Subject to change without notice


Notes

EN0H-0376GE23 R1014 · Subject to change without notice 117


Notes

118 EN0H-0376GE23 R1014 · Subject to change without notice


Nomenclature

Solenoid valves
M A 06 2 MMS

M D 10 3 S MA MD MS
M S 16 5

() = Flare, MMS = solder in mm, S = solder in inch

Connections Connection size in 1/8‘‘

Valve size

Type A = angle – direct operated, D = direct operated, S = pilot operated

Product Solenoid valve

Sight glasses SBI


S L I 1/2

S B I 10 SBIA
SLI
S B I A 12

Connection size (mm, inch)

A = inner and outer

Indicator

Connections L = solder, B = flare

Product Sight glass

Filter driers
FF 05 2
FF
FF 08 3 S

FF 16 4 MMS

() = Flare, MMS = solder in mm, S = solder in inch

Connection Connection size in 1/8‘‘

Filter size

Product Filter drier

Electronic Controls
P TI 6 10

P CR 1 10
PCR-110
P CR 3 00 RC PCR-100 PTI-610
P CR 4 10

Real time Clock


installation
00 = DIN rail, 10 = snap-in
type
no. of outputs (not for PTI)

Temperature Indicator, ContRoller

Product P = electronic controller series

EN3H-0395GE23 R0712 · Subject to change without notice 119


Automatic Expansion Valves

A E L

A MV X
AMVX AMV
A MV AEL

Connections L = solder AMV(X) only flare connections

Pressure equaliser () = internal, eXternal

Series of valve E MV

Product Automatic Expansion Valve

Thermostatic Expansion Valves Orifice cartridges


with interchangeable orifice AMV(X)
T MV TMV(X)
TMV(X)BL
T MV X TMVL
TMVBL NMVL VD
T MV BL TMV

T MV X BL TMVL Orifice cartridges


TMX
T MV L NMX
TMVX
T M X TMVXBL TMX
Connections L = solder, B = flare XD

Pressure equaliser () = internal, eXternal

Series of valve MV M

Product Thermostatic Expansion Valve

Solder bases for series TMVL and NMVL Löt/Bördelsockel für Typenreihe TMX und NMX
two-way angle Two-way angle
XLS
VLS

VLSX VLS XBS XLS


VLSX
Thermostatic Expansion Valves
with fixed orifice
T L K

T L E

T L E X TBEX TLEX 4.75-7


TLEX 0.5-4.5
TLK
T B E X

T O E X

T L ES X TOEX
TLE TLEX 8-11 TLESX
Pressure equaliser () = internal, eXternal

Series of valve K E ES

Connections L = solder, B = flare, O =O-Ring

Product Thermostatic Expansion Valve

EN3H-0395GE23 R0712 · Subject to change without notice 120


Honeywell Product Portfolio

EN0H-0376GE23 R0912 · Subject to change without notice


121
Our online service

On the internet you can find


detailed information about the
cooling components of
Honeywell.
www.honeywell-cooling.com

• Link Products
Technical information, data
sheets, mounting guidelines
and certificates to download
• Link Selection Software
Selection software „Valve Tool“
to download and for free usage
• Link Contacts
Request of additional
information, world-wide
contacts

   Please note:
Do you prefer to have that
information on CD? Then please
order your personal copy by
sending an E-mail to (do not
forget to mention your address):
cooling.mosbach@honeywell.com

Automation and Control Solutions


Honeywell GmbH
Hardhofweg
74821 Mosbach/Germany
Phone: +49 (0) 62 61 / 81-212 and +49 (0) 6261 / 81-472
Fax: +49 (0) 62 61 / 81-520
cooling.mosbach@honeywell.com
EN0H-0376GE23 R1014
Subject to change without notice
www.honeywell-cooling.com © 2014 Honeywell GmbH