Abb HD4
Abb HD4
Abb HD4
2
CIRCUIT-BREAKER SELECTION AND ORDERING 8
3
SPECIFIC PRODUCT CHARACTERISTICS 22
4
OVERALL DIMENSIONS 24
5
ELECTRICAL CIRCUIT DIAGRAM 43
1 DESCRIPTION
2
1
7 3
6 4
1
Main contact separation
No electric arc strikes as the current flows through the arcing contacts.
During its run downwards, the moving part compresses the gas contained in the lower chamber.
The compressed gas flows out of the lower chamber into the upper chamber, taking them both to
8 the same pressure.
tions where the motor, cable, etc. insulating materials operating overvoltages.
may be particularly sensitive to dielectric stresses. The HD4 series brings to medium voltage the
advantages of the “autopuffer” breaking technique
Breaking technique already used in high voltage.
The breaking technique of HD4 circuit-breakers is
based on compression and self-blast techniques to
obtain top performances at all service current
values, with minimum arc times, gradual arc
extinction without chopping, and no restriking or
3
1 DESCRIPTION
Service safety
Thanks to the availability of a complete range of
mechanical and electrical locks (on request), safe
distribution switchboards can be constructed using
The terminals and isolating The withdrawable circuit- The nameplate, located on All the control and signalling devices are located on the
contacts are silver-plated. breakers feature a device the front panel, enables all front of the circuit-breaker.
enabling them to be racked the circuit-breaker Suitable locks prevent incorrect operations.
in/out with the door closed. characteristics to be The antipumping device is always provided on the actuator.
identified.
4
HD4 circuit-breakers. The locking devices have been designed to Technical documentation
prevent incorrect operations and to carry out inspection of the To obtain in-depth knowledge of technical and application
installation, ensuring maximum operator safety. aspects of the HD4 circuit-breakers please ask for the following
publications:
– PowerCube modules
Accessories
– UniGear ZS1 type switchboards
HD4 circuit-breakers have a complete range of accessories
– ZS3.2/PowerBloc switchboards
which fulfil all installation requirements.
The operating mechanism is the same type for the whole series – REF542plus unit
and has a standardized range of accessories and spare parts – PR512 protection device.
which are easy to identify and order.
Apparatus use, maintenance and service have been simplified
and require less use of resources. Quality System
Complies with ISO 9001 Standards,
certified by an independent
ESH operating mechanism organisation.
• Just one device for the whole series.
• The same set of accessories for all the types of HD4 circuit-
breaker.
• Fixed strikers to facilitate assembly or replacement of accesso- Test Laboratory
ries. Complies with UNI CEI EN ISO/IEC
• Accessory cabling with socket and plug. 17025 Standards, accredited by an
independent organisation.
Environmental Management
System
Complies with ISO 14001 Standards,
certified by an independent
organisation.
5
2 CIRCUIT-BREAKER SELECTION AND ORDERING
Circuit-breaker HD4/GT 12
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 10
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
(1)
Rated normal current Ir [A] 630 1250 630 1250 1250 1600 2000 2500 3150
Rated breaking capacity Isc [kA] – – – – – – – – –
20 20 20 20 – 20 – – –
25 25 25 25 – 25 25 25 25
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5
– – – – 40 40 40 40 40
– – – – 50 50 50 50 50
Rated short-time Ik [kA] – – – – – – – – –
withstand current (3 s) 20 20 20 20 – 20 – – –
25 25 25 25 – 25 25 25 25
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5
– – – – 40 40 40 40 40
– – – – 50 50 50 50 50
Making capacity Ip [kA] – – – – – – – – –
50 50 50 50 – 50 – – –
63 63 63 63 – 63 63 63 63
80 80 80 80 – 80 80 80 80
– – – – 100 100 100 100 100
– – – – 125 125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
[O-0,3s-CO-20s-CO]
[O-0,3s-CO-180s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
(1) Rated uninterrupted cur-
Closing time [ms] 80
rent defined in free air at
40 °C ambient tempera- Overall Dimension standardization table TN 7360 TN 7361 TN 7201 TN 7202
ture for HD4 17 and HD4 dimensions Pole distance [mm] 150 210 210 275
24; rated uninterrupted
currents in free air at 55 H [mm] 582 622 655 655
°C ambient temperature H L [mm] 493 618 618 730
for HD4/GT12.
L D D [mm] 459 456 493 493
(2) Rated service value.
(3) The minimum storage Weight [Kg] 114 114 145 165
and transportation tem- Absolute SF6 gas pressure (2)
[kPa] 380
perature is minus 35 °C.
Operating temperature (3) [°C] – 25 ... + 55
(4) Including insulating
shields (available on re- Tropicalization IEC: 60068-2-30, 60721-2-1
quest). Electromagnetic compatibility IEC 62271-1
6
HD4 17 HD4 24
17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 16 – – – – – 16 16 16 16 16 16 – – – – –
– – – – – – – – – – – 20 20 20 20 20 20 – – – – –
25 25 25 25 25 25 – 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5 – – – – – – 31.5 31.5 31.5 31.5 31.5
– – – – – – 40 40 40 40 40 – – – – – – 40 40 40 40 40
– – – – – – 50 50 50 50 50 – – – – – – – – – – –
16 16 16 16 16 16 – – – – – 16 16 16 16 16 16 – – – – –
– – – – – – – – – – – 20 20 20 20 20 20 – – – – –
25 25 25 25 25 25 – 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5 – – – – – – 31.5 31.5 31.5 31.5 31.5
– – – – – – 40 40 40 40 40 – – – – – – 40 40 40 40 40
– – – – – – 50 50 50 50 50 – – – – – – – – – – –
40 40 40 40 40 40 – – – – – 40 40 40 40 40 40 – – – – –
50 50 50 50 50 50 – – – – – 50 50 50 50 50 50 – – – – –
– – – – – – – 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 – 80 80 80 80 – – – – – – 80 80 80 80 80
– – – – – – 100 100 100 100 100 – – – – – – 100 100 100 100 100
– – – – – – 125 125 125 125 125 – – – – – – – – – – –
45 45
10-15 10-15
55-60 55-60
80 80
TN 7177 TN 7178 TN 7163 TN 7165 TN 7179 TN 7242 TN 7174 TN 7165
150 210 210 275 210 275 275 275
640 649 655 655 818 (4) 730 655 818 (4)
493 618 618 730 618 748 730 730
496 496 561 603 600 (4) 496 561 620 (4)
114 114 145 165 119 119 145 165
380 380
– 25 ... + 40 – 25 ... + 40
7
2 CIRCUIT-BREAKER SELECTION AND ORDERING
Circuit-breaker HD4/C 12
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
(1)
Rated normal current (40 °C) Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)
Rated breaking capacity Isc [kA] 16 16 – – – – –
– – – – – – –
25 25 – 25 25 25 –
31.5 31.5 – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40
– – 50 50 50 50 50
Rated short-time Ik [kA] 16 16 – – – – –
withstand current (3 s) – – – – – – –
25 25 – 25 25 25 –
31.5 31.5 – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40
– – 50 50 50 50 50
Making capacity Ip [kA] 40 40 – – – – –
50 50 – – – – –
– – – 63 63 63 –
80 80 – 80 80 80 80
– – 100 100 100 100 100
– – 125 125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
[O-0,3s-CO-20s-CO]
(1) Rated uninterrupted cur- [O-0,3s-CO-180s-CO]
rent guaranteed with Opening time [ms] 45
withdrawable circuit-
breaker installed in a Arcing time [ms] 10-15
switchboard at 40 °C Total breaking time [ms] 55-60
ambient temperature ex-
Closing time [ms] 80
ternally the panel.
(2) Rated service value. Overall Dimension standardization table TN 7184 TN 7151 TN 7153 TN 7155 1VCD000017
(3) The minimum storage dimensions Pole distance [mm] 150 210 275 275 275
and transportation tem-
perature is minus 35 °C. H [mm] 636 702 702 702 704
(4) Rated uninterrupted H L [mm] 532 682 882 882 882
current in switchboard D
L D [mm] 659 640 640 640 640
with forced ventilation
(forced ventilation at Weight [Kg] 120 177 210 220 230
customer care). Absolute SF6 gas pressure (2)
[kPa] 380
(5) For the replacement of
Operating temperature (3) [°C] – 25 ... + 40
already installed HD4/
C only, as CBE and Tropicalization IEC: 60068-2-30, 60721-2-1
CBF are phased-out Electromagnetic compatibility IEC 62271-1
product
8
HD4/C 17 HD4/C 24
17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1250 1600 2000 2500 630 1250 1250 1600 2000 2500
16 16 – – – – 16 16 – – – –
– – – – – – 20 20 – – – –
25 25 – 25 25 25 25 25 – – 25 25
31.5 31.5 – 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 – – 40 40 40 40
– – 50 50 50 50 – – – – – –
16 16 – – – – 16 16 – – – –
– – – – – – 20 20 – – – –
25 25 – 25 25 25 25 25 – – 25 25
31.5 31.5 – 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 – – 40 40 40 40
– – 50 50 50 50 – – – – – –
40 40 – – – – 40 40 – – – –
50 50 – – – – 50 50 – – – –
– – – 63 63 63 63 63 – – 63 63
80 80 – 80 80 80 – – 80 80 80 80
– – 100 100 100 100 – – 100 100 100 100
– – 125 125 125 125 – – – – – –
45 45
10-15 10-15
55-60 55-60
80 80
TN 7184 TN 7151 TN 7153 TN 7155 TN 7186 TN 7156 TN7157 TN 7158 TN7159
150 210 275 275 210 210 275 275 275
636 702 702 702 792 792 838 838 838
532 682 882 882 682 682 882 882 882
659 640 640 640 799 799 788 788 771
120 177 210 220 125 177 177 177 220
380 380
– 25 ... + 40 – 25 ... + 40
9
2 CIRCUIT-BREAKER SELECTION AND ORDERING
Circuit-breaker HD4/GT/P 12
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 10 10
Rated insulation voltage Us [kV] 12 12
(6)
Withstand voltage at 50 Hz Ud (1 min) [kV] 42 38 (6)
Impulse withstand voltage Up [kV] 75 75
Rated frequency fr [Hz] 50-60 50-60
Rated normal current (40 °C) (1)
Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)
Rated breaking capacity Isc [kA] – – – – – – –
20 20 – 20 – – –
25 25 – 25 25 25 25
31,5 31,5 – 31,5 31,5 31,5 31,5
– – 40 40 40 40 40
– – – 50 50 50 50
Rated short-time Ik [kA] – – – – – – –
withstand current (3 s) 20 20 – 20 – – –
25 25 – 25 25 25 25
31,5 31,5 – 31,5 31,5 31,5 31,5
– – 40 40 40 40 40
(1) Rated uninterrupted cur-
– – – 50 50 50 50
rent guaranteed with
withdrawable circuit- Making capacity Ip [kA] – – – – – – –
breaker installed in 50 50 – 50 – – –
UniGear type ZS1
switchboard at 40 °C 63 63 – 63 63 63 63
ambient temperature ex- 80 80 – 80 80 80 80
ternally the panel.
– – 100 100 100 100 100
(2) Rated service value.
(3) The minimum storage – – – 125 125 125 125
and transportation tem- Operation sequence [O-0,3s-CO-15s-CO]
perature is minus 35 °C.
(4) Rated uninterrupted cur- [O-0,3s-CO-20s-CO]
rent in switchboard with [O-0,3s-CO-180s-CO]
forced ventilation. Opening time [ms] 45
(5) The locking electromag-
net (-RL2) in the truck to Arcing time [ms] 10-15
prevent the circuit- Total breaking time [ms] 55-60
breaker being racked-in
Closing time [ms] 80
with the auxiliary circuits
disconnected (plug not Overall Dimension standardization table TN 7286 TN 7350 TN 7351 TN 7352 TN 7371
inserted in the socket) is dimensions Pole distance [mm] 150 210 210 275 275
included in the standard
equipment. H [mm] 628 702 702 702 746
(6) UniGear type ZS1 H L [mm] 532 682 682 882 882
switchboard with rated 659 640 640 643 643
L D D [mm]
insulation voltage 17.5
kV. Weight [Kg] 120 177 177 220 230
(7) Rated uninterrupted cur- Absolute SF6 gas pressure (2)
[kPa] 380
rent in switchboard with
Operating temperature (3) [°C] – 25 ... + 40
forced ventilation. In a
switchboard with natu- Tropicalization IEC: 60068-2-30, 60721-2-1
ral ventilation, the rated Electromagnetic compatibility IEC 62271-1
current is 2300 A.
10
HD4/P 17 HD4/P 24
17.5 24
17.5 24
38 50
95 125
50-60 50-60
(4) (7)
630 1250 1250 1600 2000 2500 3150 630 1250 1250 1600 2000 2500
16 16 – – – – – 16 – – 16 16 –
– – – – – – – 20 20 – 20 20 20
25 25 – 25 25 25 25 25 25 – 25 25 25
31.5 31.5 – 31.5 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40 – – – – – –
– – – 50 50 50 50 – – – – – –
16 16 – – – – – 16 – – 16 16 –
– – – – – – – 20 20 – 20 20 20
25 25 – 25 25 25 25 25 25 – 25 25 25
31.5 31.5 – 31.5 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40 – – – – – –
– – – 50 50 50 50 – – – – – –
40 40 – – – – – 40 – – 40 40 –
50 50 – – – – – 50 50 – 50 50 50
– – – 63 63 63 63 63 63 – 63 63 63
80 80 – 80 80 80 80 – – 80 80 80 80
– – 100 100 100 100 100 – – – – – –
– – – 125 125 125 125 – – – – – –
45 45
10-15 10-15
55-60 55-60
80 80
TN 7286 TN 7350 TN 7351 TN 7352 TN 7371 TN 7354 1VCD000099 TN 7355 TN7356
150 210 210 275 275 210 210 275 275
628 702 702 702 746 736 792 821 821
532 682 682 882 882 636 653 842 842
659 640 640 643 643 802 799 788 788
120 177 177 220 230 125 177 177 220
380 380
– 25 ... + 40 – 25 ... + 40
11
2 CIRCUIT-BREAKER SELECTION AND ORDERING
Circuit-breaker HD4/W 12
PowerCube enclosures PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C)(1) Ir [A] 630 1250 630 1250 1250 1600 2000 3150 (4)
Rated breaking capacity Isc [kA] 16 16 16 16 – 16 16 –
– – – – – – – –
25 25 25 25 – 25 25 –
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5
– – – – 40 – – 40
– – – – 50 – – 50
Rated short-time Ik [kA] 16 16 16 16 – 16 16 –
withstand current (3 s) – – – – – – – –
25 25 25 25 – 25 25 –
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5
– – – – 40 – – 40
– – – – 50 – – 50
Making capacity Ip [kA] 40 40 40 40 – 40 40 –
–- –- – – – – – –
63 63 63 63 –- 63 63 –
80 80 80 80 –- 80 80 80
(1) Rated uninterrupted cur- – – – – 100 – – 100
rent guaranteed with – – – – 125 – – 125
withdrawable circuit-
breaker installed in a Operation sequence [O-0,3s-CO-15s-CO]
switchboard at 40 °C [O-0,3s-CO-20s-CO]
ambient temperature
[O-0,3s-CO-180s-CO]
externally the panel.
(2) Rated service value. Opening time [ms] 45
(3) The minimum storage Arcing time [ms] 10-15
and transportation tem-
Total breaking time [ms] 55-60
perature is minus 35 °C.
(4) Rated uninterrupted cur- Closing time [ms] 80
rent in switchboard with Overall Dimension standardization table TN 7229 TN 7182 TN 7421 TN 7239 1VCD000053
natural ventilation; rated dimensions Pole distance [mm] 150 210 210 210 275
current 3600 A with one
fan pre-installed in PB3 H [mm] 636 702 702 702 742
cassette; rated current H
L [mm] 532 682 682 682 882
4000 A with one addi-
tional fan installed by L D D [mm] 659 640 640 640 643
customer in the back of Weight [Kg] 120 120 177 177 230
switchgear (see Absolute SF6 gas pressure (2) [kPa] 380
PowerCube Instruction
Manual). Operating temperature (3) [°C] - 25 ... + 40
(5) Rated uninterrupted cur- Tropicalization IEC: 60068-2-30, 60721-2-1
rent in switchboard with Electromagnetic compatibility IEC 62271-1
forced ventilation.
12
HD4/P 12 HD4/W 17 HD4/P 17 HD4/W 24 HD4/P 24
PB2 PB2 PB3 PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3 PB2 PB2 PB3 PB4 PB4 PB5 PB5
12 17.5 17.5 24 24
12 17.5 17.5 24 24
28 28 28 50 50
75 95 95 125 125
50-60 50-60 50-60 50-60 50-60
1600 2000 2500 630 1250 630 1250 1250 1600 2000 3150 (4) 1600 2000 2500 630 1250 1600 2000 2500(5)
– – – 16 16 16 16 – 16 16 – – – – 16 16 16 16 16
– – – – – – – – – – – – – – 20 20 20 20 20
– – 25 25 25 25 25 – 25 25 – – – 25 25 25 25 25 25
– – 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 – – 31.5 – – – – –
40 40 40 – – – – 40 – – 40 40 40 40 – – – – –
50 50 50 – – – – 50 – – 50 50 50 50 – – – – –
– – – 16 16 16 16 – 16 16 – – – – 16 16 16 16 16
– – – – – – – – – – – – – – 20 20 20 20 20
– – 25 25 25 25 25 – 25 25 – – – 25 25 25 25 25 25
– – 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 – – 31.5 – – – – –
40 40 40 – – – – 40 – – 40 40 40 40 – – – – –
50 50 50 – – – – 50 – – 50 50 50 50 – – – – –
– – – 40 40 40 40 – 40 40 – – – – 40 40 40 40 40
– – – – – – – – – – – – – – 50 50 50 50 50
– – 63 63 63 63 63 – 63 63 – – – 63 63 63 63 63 63
– – 80 80 80 80 80 – 80 80 80 – – 80 – – – – –
100 100 100 – – – – 100 – – 100 100 100 100 – – – – –
125 125 125 – – – – 125 – – 125 125 125 125 – – – – –
45 45 45 45 45
10-15 10-15 10-15 10-15 10-15
55-60 55-60 55-60 55-60 55-60
80 80 80 80 80
TN 7350 TN 7351 TN 7352 TN 7229 TN 7182 TN 7421 TN 7239 1VCD000053 TN 7350 TN 7351 TN 7352 TN 7183 TN 7355 TN 7356
210 210 275 150 210 210 210 275 210 210 275 210 275 275
702 702 702 636 702 702 702 742 702 702 702 792 821 821
682 682 882 532 682 682 682 882 682 682 882 682 842 842
640 640 643 659 640 640 640 643 640 640 643 799 788 788
177 177 220 120 120 177 177 230 177 177 220 125 177 220
380 380 380 380 380
- 25 ... + 40 - 25 ... + 40 - 25 ... + 40 - 25 ... + 40 - 25 ... + 40
13
2 CIRCUIT-BREAKER SELECTION AND ORDERING
(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS3.2. switchboard
at 40 °C ambient temperature externally the panel.
(2) Rated service value.
(3) The minimum storage and transportation temperature is minus 35 °C.
(5) The operating sequence is O-0.3sec-CO-3min-CO for the rated breaking capacity Isc = 31.5 kA.
14
Standard equipment Moreover:
The basic versions of the circuit-breakers are for fixed circuit-breaker
always three-pole and fitted with: – connection terminals (on request for
– manual operating mechanism HD4/GT 12)
– mechanical signalling device for closing springs – terminal board for auxiliary circuits;
charged/discharged
– mechanical signalling device for circuit-breaker for withdrawable circuit-breaker
open/closed – isolating contacts
– closing pushbutton – cord with connector (plug only) for auxiliary
– opening pushbutton circuits
– operation counter – earthing contact on truck (only for CBE, CBF)
– set of ten open/closed circuit-breaker auxiliary – lock to prevent racking-in of circuit-breaker with
contacts (four opening (NC) and three closing different rated current
(NO) available, according to the applications – racking-in/out lever (the quantity must be de-
requested) fined according to the number of pieces of ap-
– lever for manually charging the closing springs paratus ordered)
(the quantity must be defined according to the – locking electromagnet in the truck (/P and /W
number of pieces of apparatus ordered). versions).
Terminals for fixed circuit-breaker. Tulip isolating contacts for withdrawable Plier isolating contacts for withdrawable
circuit-breaker. circuit-breaker.
15
2 CIRCUIT-BREAKER SELECTION AND ORDERING
release trip.
energised).
release.
1 2A 2B 3 4A 4B 5 6
Fixed circuit-breakers
HD4/GT 12
HD4 17
HD4 24
Withdrawable circuit-breakers
for CBE enclosures and CBF fixed parts
HD4/C 12
HD4/C 17
HD4/C 24
Withdrawable circuit-breakers
for UniGear type ZS1 switchboards
16
Group of 15 auxiliary circuit-breaker
contacts: 4 make and 5 break (alterna-
tive to the 10 provided as standard, of
7
which a maximum of 3 make and 4 bre-
ak are available depending on the
accessories requested).
8
-BB4 transient contact.
–
–
–
–
9
truck). It is compulsory if the RL1
locking magnet is present.
–
–
–
(1)
ted contacts (installed in the circuit-
10
breaker truck).
11
-MS spring charging geared motor.
12
spring charging geared motor.
–
Opening pushbutton lock.
–
Closing pushbutton lock.
magnet.
–
–
–
(4)
(4)
(4)
(4)
(4)
(4)
–
–
–
–
Interlock for fixed circuit-breaker.
18 19
–
–
–
–
–
–
–
–
–
–
–
–
–
–
(3)
Two-level pressure switch (2).
–
–
–
–
–
–
–
–
–
–
–
–
23
Insulating partitions.
17
2 CIRCUIT-BREAKER SELECTION AND ORDERING
Optional accessories
The accessories identified with the same number are alternative to each other.
Undervoltage release
4A -MU undervoltage release (power supply branched on the supply side).
4B -MU undervoltage release with electronic delay device (0.5 – 1 – 1.5 –
2 – 3 s) (power supply branched on the supply side). This device is
delivered set to 0.5 s see the Electric Diagram chapter - note I on
page 82).
5 Mechanical override of undervoltage release trip with electrical signalling.
6 -BB5 undervoltage release electric signalling (energised or de-ener-
gised).
Shunt closing release.
Motor operator
11 -MS spring-charging geared motor.
12 -FB1 thermomagnetic protection of the spring-charging geared motor
(mounted as standard for 24 V d.c. geared motors) complete with
electrical signalling of thermomagnetic protection trip.
13A Electrical signalling of operating mechanism springs charged.
13B Electrical signalling of operating mechanism springs discharged.
Auxiliary contacts.
18
Locks and interlocks
Insulating partitions
23 Insulating partitions.
19
2 CIRCUIT-BREAKER SELECTION AND ORDERING
Shunt opening release (-MO1; -MO2) Ps = 125 W/VA (Instantaneous service < 45 ms)
Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
20
Identification of the circuit-breaker type
The identification code of a circuit-breaker is made up with the elements from
the table below.
For correct identification of a circuit-breaker, it is necessary to refer to the
characteristics tables on pages 12 to 16.
The selected circuit-breaker can then be completed with the optional accesso-
ries indicated on the following pages.
Examples of identification
• The code HD4/C 12.16.25 identifies a withdrawable circuit-breaker for CBE
enclosure or CBF fixed part with 12 kV rated voltage, 1600 A rated normal
current and 25 kA breaking capacity.
• The code HD4/W 24.20.25 identifies a withdrawable circuit-breaker for
PowerCube modules with 24 kV rated voltage, 2000 A rated normal current
and 25 kA breaking capacity.
Version Fixed –
CBE / CBF C
UniGear ZS1 type P
PowerCube W-P
ZS3.2 Z
Rated voltage 12 kV 12
17.5 kV 17
24 kV 24
40.5 kV 40
Rated normal
current (1)
630 A 06
1250 A 12
1600 A 16
2000 A 20
2500 A 25
3150 A 32
3600 A 36
Rated
breaking
16 kA 16
capacity 20 kA 20
25 kA 25
31.5 kA 32
40 kA 40
50 kA 50
(1) Rated uninterrupted current defined in free air for fixed circuit-breaker.
For the withdrawable version, see the previous pages.
21
3 SPECIFIC PRODUCT CHARACTERISTICS
Example
• Installation altitude 2000 m
• Operation at the rated voltage of 12 kV
• Withstand voltage at industrial frequency 28
Ka = e m (H – 1000)/8150
kV rms (IEC 60071-2)
• Impulse withstand voltage 75 kVp
• Factor Ka obtained from graph = 1.13.
22
Switching special loads
The table indicates the breaking capacities which can be guaranteed for switching special loads.
Circuit-breaker HD4
Rated normal current In [A] 630 1250 1600 2000 2500 3150 3600
for fixed circuit-breaker
Capacitive current breaking Isc [A] 400 630 1000 1250 1250 1250 1250
(C2 class)
Reactance compensation Isc [A] 630 630 1250 1250 1250 1250 1250
current breaking
Breaking of rated motor Isc [A] 630 630 1250 1250 1250 1250 1250
currents
23
4 OVERALL DIMENSIONS
Type HD4/GT
TN 7201
Ur 12 kV
Ir 1600 A
Isc 20 kA
25 kA
31.5 kA
40 kA
50 kA
24
Type HD4/GT Fixed circuit-breakers without terminals
TN 7360
Ur 12 kV
Ir 630 A
1250 A
Isc 20 kA
25 kA
31.5 kA
25
4 OVERALL DIMENSIONS
F 22
Isc 16 kA
F 22
50
25 kA
31.5 kA
317
317
28
10
F 22
10
640 F 22
YU
582
549.5
540
YU
8
297.5
297.5
257.5
Q60
21.5
43
347
F 10.5 F 13 120
473 1250A 270
37
493 1600A 335 630A
317
317
10
F 22
28 F 22
648.5
10
622
558.5
YU
468.5
YU
306.5
306.5
266.5
8
43
472 F 13 120
F 10.5
598 270
1250A 37
618
1600A 335 630A
26
Type HD4 Fixed circuit-breakers
TN 7163
Ur 17.5 kV 600
Ir 1600 A 578
210 210
Isc 40 kA
50 kA
Type HD4
TN 7163 2x F18
310
Ur 17.5 kV
310
Ir 2000 A 28
80
Isc 25 kA
15.5 32
655
31.5 kA
622
YU
40 kA
8
YU
50 kA
306.5
266.5
Q60
8
F 13
43
472
598 F 10.5 35
2.5
20
618 322
385
561
349.5
Isc 25 kA
31.5 kA
40 kA
670 min.
50 kA
15
310
Type HD4 28
62
TN 7165 20 40
655
20
622
Ur 24 kV YU
Ir 2500 A
468.5
40
YU
3150 A
20
20
8
3600 A
266.5
Isc 25 kA 4 x F 18
F 13
31.5 kA
43
40 kA
602 F10.5 115
2
20
728 322
35
748 385
603
27
4 OVERALL DIMENSIONS
F 22
25 kA
F 22
670 min.
362
362
F 22
F 22
10
729.5
28
712
639.5
622
YU
468.5
YU
342.5
342.5
302.5
10
Q60
8
F 13
43
472 120
598 F10.5 270
1250A 37
618 1600A 335 630A
25 kA
F 22
362
362
F 22
F 22
729.5
10
28
639.5
620
YU
468.5
YU
10
342.5
342.5
302.5
8
Q60
F 13
43
602 120
728 F 10.5 270
1250A 37
748 335
1600A 630A
28
Type HD4 Fixed circuit-breakers
TN 7174
Ur 24 kV 730
Ir 1600-2000 A 708
275 275
Isc 25 kA
31.5 kA
40 kA
2x Ø 18
310
310
80
28
15.5 32
622
655
YU
8
YU
306.5
266.5
Q60
Ø 13
43
20
728 322
35
385
748
561
29
4 OVERALL DIMENSIONS
Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7184
For CBE11
493
CBF11
150 150
Ur 12 kV
10
30 202 56 72 5.5
17.5 kV
Ir 630 A
1250 A
Isc 16 kA
25 kA
31.5 kA
F 35
28
205
636
627
630
588
547
8
264
78
158
20
340 4
F 19.5
25.5
458 416
503 437
532 36 570 53
659
Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7151
For CBE21 636
Ur 12 kV 578
210 210
17.5 kV
272 56 63
Ir 1250 A 44 15
Isc 40 kA
10
50 kA
Type HD4/C
TN 7151
For CBE21
310
Ur 12 kV
673
640
17.5 kV
Ir 1600 A
Isc 25 kA
F 79
8
31.5 kA
284
89
40 kA
169
25.5
50 kA
4
F19.5
550 359
606 416
40
36 551 53
653
640
682
30
HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7153
For CBE31
Ur 12 kV
842
17.5 kV 730
56 63
Ir 2000 A 275 275 15
144 232 10
Isc 25 kA
31.5 kA
40 kA
F 109
50 kA
310
28
695
673
702
640
8
284
89
169
708 4
F 19.5
25.5
750 359 30
792 416 53
853
552
882 36
HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7155
For CBE31
Ur 12 kV
17.5 kV 842
Ir 2500 A 730
(*)
310
28
695
673
702
640
YU
YU
8
284
Q60
89
169
708 4
25.5
Φ 19.5
359 30
750
416
792 53
33 554
(*) Only for 17.5 kV. 853
640
882
31
4 OVERALL DIMENSIONS
Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 1VCD000017
For CBF31
Ur 12 kV
Ir 3150 A
Isc 25 kA
31.5 kA
40 kA
50 kA
Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7186
For CBE41
CBF41 636
578
Ur 24 kV 210 210
799
Ir 630 A
20
272 23
1250 A 44
Isc 16 kA
F 35
20 kA
25 kA
310
28
776
767
740
792
649
8
329
12.5
125
202
25.5
550 4 53
F 23
25.5
452
610
460
653
682 710
36
32
HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7156
For CBE41 641
578
Ur 24 kV 799
210 210
Ir 1250 A 272 23
Isc 31.5 kA 44
40 kA
20
F 35
310
28
776
718
682
792
8
329
25.5
125
10
202
550 25.5
452 4 53
F 23
610
460
653
710
682 36
HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7157
For CBE51
Ur 24 kV
Ir 1600 A
Isc 31.5 kA
40 kA
33
4 OVERALL DIMENSIONS
144 232 20 23
Ir 2500 A
Isc 25 kA
31.5 kA
80
40 kA
380
28
821.5
838
704
8
349
125
202
750 4
452
F 23
25.5
805
457 30
853
882
34
HD4/GT/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7286
Ur 12 kV
Ir 630 A
493
1250 A
150 150
Isc 20 kA 56 72 5.5
202
10
30
25 kA
31.5 kA
67.5
HD4/P (*)
TN 7286
F 35
622 MAX
51
205
Ur 12 kV
621.5
624.5
543
17.5 kV
586
Ir 630 A
63
1250 A
28
Isc 16 kA
247.5
25 kA 260
Q60
78
31.5 kA
154
20
4
4
21.5
F 19
4
458 416
503 437
532 570 53
36
(*) HD4/P kV for 659
PowerCube.
HD4/GT/P
TN 7350
Ur 12 kV
Ir 1600 A
Isc 20 kA
25 kA
31.5 kA
40 kA
50 kA
HD4/GT/P
TN 7351
Ur 12 kV
Ir 2000 A
Isc 25 kA
31.5 kA
40 kA
50 kA
35
4 OVERALL DIMENSIONS
HD4/P
TN 7352
Ur 12 kV (*)
17.5 kV
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
50 kA
36
HD4/GT/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7371
Ur 12 kV
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA
HD4/P
TN 7371
Ur 17.5 kV
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA
37
4 OVERALL DIMENSIONS
HD4/P (*) HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7355
Ur 24 kV
Ir 1600 A
Isc 16 kA
20 kA
25 kA
31.5 kA (**)
HD4/P (**) HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7356
Ur 24 kV
Ir 2000 A
Isc 16 kA
20 kA
25 kA
31.5 kA (***)
HD4/P (**)
TN 7356
Ur 24 kV
Ir 2500 A (*)
Isc 20 kA
25 kA
31.5 kA (***)
38
HD4/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 1VCD000099
Ur 24 kV
Ir 1250 A
Isc 31.5 kA
10
1250 A 30 202 56
Isc 16 kA
25 kA
31.5 kA
48
F 35
205
625.5
628.5
590
547
636
28
264
Q60
78
158
340 416 4
21.5
F 19.5
458 437
20
503 570 53
36
532
659
39
4 OVERALL DIMENSIONS
10
44 228 56 63 15
1250 A
Isc 16 kA
F 35
25 kA
31.5 kA
310
28
695
692
702
640
284 8
89
169
606 4
359
653 40
551 53
682 36
640
40
HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules
TN 7239
636
Ur 12 kV 578
17.5 kV 210 210
Ir 1600 A 272
63
56 15
10
44
2000 A
Isc 16 kA
25 kA
31.5 kA
310
28
695
673
702
640
F 79
8
284
89
169
4
606 359 40
653 36 551 53
682 640
41
4 OVERALL DIMENSIONS
20
272
Isc 16 kA 44
20 kA
25 kA
F 35
310
776
28
767
740
792
649
8
329
125
12.5
202
25.5
610 4 53
460
653 710
682 36
HD4/Z 40.5 kV HD4/Z withdrawable circuit-breakers for UniGear type ZS3.2 - 40.5 kV switchboards
TN 7227
Ur 40.5 kV
Ir 1250 A
1600 A
2000 A
2500 A (*)
Isc 25 kA
31.5 kA
ØA
1250-1600 A 35 mm
2000-2500(*)A 79 mm
42
5 ELECTRICAL CIRCUIT DIAGRAM
Application diagrams
The following diagram (No. 400007) shows the circuits of the withdrawable circuit-breakers up to 24 kV
type HD4/C, HD4/P, HD4/W, delivered to the customer by means of connector “X”.
43
5 ELECTRICAL CIRCUIT DIAGRAM
44
45
5 ELECTRICAL CIRCUIT DIAGRAM
Represented operational state -BT2 = Contacts signalling circuit-breaker in the isolated position (see
note G)
The diagram indicates the following conditions:
-SC = Pushbutton or contact for the circuit-breaker closing
– circuit-breaker open and connected
-BK = Contact operated by the key lock preventing electrical opening
– circuits de-energized
with earthing truck connected (It is mandatory for earthing truck
– closing springs discharged
with making capacity)
– key lock with key inserted and trapped
-SL1 = Contact locking for circuit-breaker closing
– SF6 gas pressure at rated service value (380 kPa absolute).
-SO = Pushbutton or contact for the circuit-breaker opening
-TR1, -TR2 = Rectifiers for shunt opening releases -MO1 and -MO2
Caption -XB = Connector for the circuit-breaker circuits
-XB2…-XB62 = Connectors of accessories
= Reference number of diagram figure -XB1 = Switchboard terminal board (mounted externelly to the circuit-
* = See note indicated by the letter breaker)
-BM = Device for the supervision of shunt opening release coil continuity -MC = Shunt closing release
(see note E) -RL1 = Locking magnet on the operating mechanism. If de-energized it
-BP = Pressure-switches with two operating levels: prevents the circuit-breaker closing mechanically
– operating for low gas pressure. Contacts 11-12-14 change -RL2 = Locking magnet on the truck. If de-energized it prevents the cir-
position, as regard the position indicated on the diagram, when cuit-breaker racking-in and racking-out mechanically (It is pos-
the pressure from 380 kPa absolute gets to a value lower than sible to limit its consumption by connecting in series a delaying
310 kPa absolute. In case of rated pressure reset the same pushbutton enabling the operation)
contacts change again position when the pressure, from a -MO1 = First shunt opening release (see note E)
value lower than 310 kPa absolute, gets up to 340 kPa -MO2 = Second shunt opening release (see note E)
absolute. -MO3 = Opening solenoid for the PR512 microprocessor based release
– operating for insufficient gas pressure. Contacts 21-22-24 external the circuit-breaker (see note D)
change position when the pressure from 380 kPa absolute -MU = Instantaneous undervoltage release or undervoltage release with
absolute gets to a value lower than 280 kPa absolute. In case electronic time-delaying device (see note B)
of rated pressure reset the same contacts change again -VF = Filter (provided with voltage supply 220V d.c. or greater)
position when the pressure, from a value lower than 280 kPa
absolute, gets up to 310 kPa absolute.
-KT = Solid-state time-delaying device for the undervoltage release
Diagram figures description
(see note I)
-KI = Integrated gas pressure control circuit, including: Fig. 1 = Spring charging-motor circuit (see note C).
-PG = Green led indicating normal gas pressure Fig. 2 = Shunt closing release (antipumping is achieved mechanically).
-PR = Red led indicating insufficient gas pressure Fig. 3 = Locking magnet on the operating mechanism. If de-energized
-PY = Yellow led indicating low gas pressure it prevents the circuit-breaker closing mechanically.
-KA1 = Auxiliary relay to double the -BP pressure-switch con- Fig. 4 = Locking magnet on the truck. If de-energized it prevents the
tacts operating for low gas pressure circuit-breaker racking-in and racking-out mechanically (It is
-KA2 = Auxiliary relay to double the -BP pressure-switch con- possible to limit its consumption by connecting in series a de-
tacts operating for insufficient gas pressure laying pushbutton enabling the operation) (see note H).
-XB5 = Connector Fig. 5 = Instantaneous undervoltage release (see note B)
-BR51 = Microprocessor based overcurrent release type PR512 external Fig. 6 = Undervoltage release with solid-state time-delaying device (see
to the circuit-breaker (see note D) notes B and I)
-MS = Motor for the closing springs charging (see note C) Fig. 7 = First shunt opening release circuit with possibility of perma-
-QB = Main circuit-breaker nent supervision of coil continuity (see note E).
-BB1…-BB3 = Circuit-breaker auxiliary contacts (no. 3 packs of 5 contacts) Fig. 9 = Second shunt opening release circuit with possibility of perma-
-BB4 = Auxiliary passing contact (closing momentarily when circuit- nent supervision of coil continuity (see note E).
breaker opens) Fig. 10 = Opening solenoid for PR512 microprocessor based release
-BB5 = Contacts signalling undervoltage release energized/de-energized external to the circuit-breaker (see note D).
-FB1 = Miniature breaker with thermomagnetic O/C release for protec- Fig. 11 = Gas pressure control circuit including:
tion of the spring-charging motor (see note F) – contacts for remote indication of normal, low and insufficient
-BS1...2 = Limit switches of the spring-charging motor gas pressure.
-BD1 = Position contact of the enclosure door. Foreseen for HD4/C only. For -BP pressure-switches tripping values see the caption.
-BT3 = Circuit-breaker position contact. It is open during the isolating Fig. 12 = Integrated gas pressure control circuit, including:
travel of the breaker – circuit-breaker opening through the -MO2 release and clos-
-BT5 = Contacts signalling circuit-breaker in the removed position (they ing lock through a -KA2 relay auxiliary contact in case of
are those signalling circuit-breaker in the isolated position located insufficient gas pressure (provide the locking magnet given
on the enclosure, in the fixed part: see contacts -BT2 given on in fig. 3)
circuit diagram 1VCD 400036 figures 5-6) – 3 leds for local indication of normal, low and insufficient gas
-BT1 = Contacts signalling circuit-breaker in the connected position (see pressure
note G)
46
– contacts for remote indication of normal, low and insufficient Notes
gas pressure. A) The circuit-breaker is only fitted with the accessories listed in the order
For -BP pressure switches tripping values see the caption. confirmation. To make out the order, please consult the catalogue of the
Fig. 14 = Integrated gas pressure control circuit, including: apparatus.
– lock of circuit-breaker closing and opening through -KA2 relay B) The undervoltage release can be provided for power supply with volt-
auxiliary contacts in case of insufficient gas pressure (provide age branched on the supply side of the circuit-breaker or from an inde-
the locking magnet given in fig. 3) pendent source.
– 3 leds for local indication of normal, low and insufficient gas Either the instantaneous undervoltage release or the one with elec-
pressure tronic delay device can be used (delay can be selected between 0.5 …
– contacts for remote indication of normal, low and insufficient 3 s; see note I). Circuit-breaker closing is only possible with the release
gas pressure. energised (the closing lock is made mechanically).
For -BP pressure switches tripping values see the caption. The contact in fig. 24 or the one in fig. 25 is available on request.
Fig. 20 = Contact operated by the key lock, preventing electrical opening, A delay of 50 ms between the moment of consent of the undervoltage
with earthing truck with making capacity connected. (It is obliga- release and energisation of the shunt closing release must be inserted
tory for earthing truck with making capacity when is requested the when there is the same power supply for the shunt closing and
first shunt opening release -MO1). undervoltage releases and automatic circuit-breaker closing on return
Fig. 21 = Miniature breaker with thermomagnetic O/C release for protec- of the auxiliary power supply is required. This can be carried out by
tion of the spring-charging motor (see note F). means of a circuit outside the circuit-breaker, including a permanent
Fig. 22 = Contact signalling closing springs charged. closing contact, the contact indicated in fig. 24 and a time-delay relay.
Fig. 23 = Contact signalling closing springs discharged. C) Check the power available on the auxiliary circuit to verify the possibil-
Fig. 24 = Contact signalling undervoltage release energized (see note B). ity of starting several motors for charging the closing springs at the
Fig. 25 = Contact signalling undervoltage release de-energized (see note B). same time. To avoid excessive consumption, it is necessary to charge
Fig. 26 = Contact signalling miniature breaker for protection of the spring- the springs manually before supplying the auxiliary circuit with voltage.
charging motor on. D) Please see diagram 401530 for the connections between the circuit-
Fig. 27 = Contact signalling miniature breaker for protection of the spring- breaker auxiliary circuits and the PR512 type of microprocessor-based
charging motor off. overcurrent release located in the switchboard.
Fig. 30 = Passing auxiliary make contact closing momentarily when cir- E) The circuit for controlling continuity of the shunt opening release winding
cuit-breaker opens (-MO1, -MO2, -MO3 and -MU). must only be used for this function.
Fig. 31 = Circuit-breaker available auxiliary contacts. At a power supply lower than 220V, connect the “Control Coil Continu-
Fig. 32 = Circuit-breaker available auxiliary contacts. ity” device, or a relay or a signalling lamp which consumes a current
Fig. 51 = Contacts signalling circuit-breaker in the connected and isolated not exceeding 20 mA.
positions located on the circuit-breaker, they are provided on At a power supply equal to or higher than 220V, connect a delay or
request (see note G). signalling lamp which consumes a current not exceeding 10 mA.
Other uses might jeopardise release functionality.
F) The -FB1 circuit-breaker in fig. 21 must always be provided when there
Incompatibility is a 24 kV d.c. spring charging motor.
The combination of circuits given in the figures below are not possible on In case of opening caused by a fault in the motor, before carrying out
the same circuit-breaker: manual resetting, recharge the springs by means of the special handle.
G) The contacts (-BT1 and -BT2) shown in fig. 51 for signalling the circuit-
breaker status are located on the circuit-breaker (moving part) and are
5 - 6 - 14 9 - 10 - 12 - 20 24 - 25
available on request. However, application of these contacts on the
5 - 6 - 20 11 - 12 - 14 26 - 27 enclosure is usually foreseen (fixed part): see diagram 401693 for CBE
9 - 10 - 12 - 14 22 - 23 31 - 32 11 - 21 - 31 and diagram 401526 for CBE 41 - 51.
H) When fig. 9 is requested, the contact of pack -BB3 to terminals 29-30 in
fig. 32 is not available.
When figs. 26-27 are requested, the -BB2 contact to terminals 29-30 of
figs. 31-32 is not available.
When fig. 30 is requested, the contact of pack -BB3 to terminals 23-24
in fig. 32 is not available.
I) Make one of the following bridges to select the delay required:
0.5 s: terminals 6-7
1 s: terminals 6-8
1.5 s: terminals 6-9
2 s: terminals 6-10
3 s: no bridge.
J) When fig. 4 is requested, the contact of pack -BB1 to terminals 7-8 in
figs. 31-32 is not available.
47
5 ELECTRICAL CIRCUIT DIAGRAM
Graphical symbols for electrical diagrams (IEC 60617 and CEI 3-14 ... 3-26 Standards)
Power circuit-breaker
Earth (general symbol) M Motor (general symbol) with automatic opening
Conductors in shielded
cable (two conductors Make contact Lamp (general symbol)