Automatic Transfer Switch
Automatic Transfer Switch
Automatic Transfer Switch
TRANSFER SWITCH
AUTOMATIC
TRANSFER SWITCH
Electric Power Division December 2005
MX150 Microprocessor
Controller
IIntroduction
MX150 microprocessor panel controls the operation
and displays the status of the transfer switch’s
position, timers and available sources. As an
embedded digital controller, the MX series offers
high reliability and ease of unattended operation
across a range of applications.
LEHE4650-01
AUTOMATIC
TRANSFER SWITCH
MX150
Control Function Range Factory Setting
S1 Line Sensing – Under-voltage Fail 75-98% 80%
Restore 85-100% 90%
S2 Line Sensing – Under-voltage Fail 75-98% 80%
Restore 85-100% 90%
S2 Line Sensing – Under-frequency Fail 2 Hz below pickup Set
Restore 90-100% 95%
Time Delay – Engine Start 0-10 seconds 3 seconds
Time Delay – Engine Cool Down 0-60 minutes 5 minutes
Time Delay – Transfer to Emergency 0-5 minutes 1 second
Time Delay – Retransfer to Normal 0-60 minutes 30 minutes
Time Delay – Motor Disconnect 0-60 seconds 20 seconds
or Transfer Pre-signal
Delayed Transition
(when applicable) 0-10 minutes 5 seconds