Greenheck DOAS Start-Up Report June2019
Greenheck DOAS Start-Up Report June2019
Job Information:
Job Name:
Unit Sales Order Number:
Unit Serial Number:
Unit Tag:
Technician Information:
Start-Up Company:
Technician Name:
Start-Up Date:
This report consists of recorded data as observed by a Greenheck certified technician on the date
indicated. The data is generated by a series of tests of the individual sub-systems within the air
handler. The entire system (with all sub-systems functional) is tested to observe proper operation of
the standard sequences within the completed air system of the occupied space. The air handler itself
has been engineered to meet criteria specified by the owner but field conditions often vary from
design specifications. During the course of this start-up, the Greenheck technician will make needed
minor adjustments to operating parameters to produce the desired operating characteristics.
The testing of this unit is based upon completed installation of the unit. All associated ductwork is
to be intact and completed. A completed Pre Start-Up Checklist is to be furnished by the installer
prior to the unit start-up.
Because field conditions may change after the start-up testing of this unit, the recorded data points
are subject to change.
As each sub-system is isolated and tested, critical data is observed and recorded. This data should
be preserved as a benchmark, to be used by others for purposes of normal maintenance and for
possible trouble-shooting of the system. Due to seasonal ambient conditions, it may not be possible
to test full operational ranges of all subsystems.
All data is analyzed by the Greenheck technician and anomalies are recorded in the “Notes” portion
of each sub-system. The analysis on the final page of this report indicates whether the system
operates as intended and may make recommendations regarding potential areas of concern.
SUBMIT FORM
1
3
4
4
DAMPERS/VALVES AND ACTUATORS FUNCTIONAL TEST 5
SUPPLY AIR BLOWER AND MOTOR 6
EXHAUST / RELIEF / RETURN BLOWER AND MOTOR 7
8
9
10
11
INTEGRAL AC SYSTEM START-UP 12
INTEGRAL AC DATA RUNS 13
14
15
16
17
18
19
NOTES:
YES NO
NOTES:
NOTES:
Outside Air
Outside Air Heat Exchanger Face and Bypass Dampers
Recirculation Air
Exhaust or Relief Air
Heat Exchanger HX2 Face and Bypass Dampers
Coil Face and Bypass Dampers
NOTES:
Figure 1.) Enable Manual Override Mode Figure 2.) Manually Override Unit On
EC MOTORS
Digital input Start / Stop enable
NOTES:
VFD VFD
Modified parameters from default settings Modified parameters from default settings
VFD VFD
Modified parameters from default settings Modified parameters from default settings
VFD VFD
Modified parameters from default settings Modified parameters from default settings
Figure 5.) To enter the Furnace Commissioning Menu go into the Manual Overrides Menu and press
enter on the first screen below the title screen. In this mode, the controller will modulate valves and
power combustion blowers motors as appropriate and give you direction on which valves to set and
what pressure to set them to. Once you've completed the instructions on each page you will have to
change "No" to "Yes" to continue.
Gas Set Point Guidelines (all gas pressure readings must be taken from the gas manifold)
NOTES:
Heater Model:
Heater Serial #:
NOTE
Start-up of any compressorized
system is to be done only by a
EPA-608 certified technician.
To see Manual Overrides associated
with this startup see Pg.12
Unit Tag: Ambient Temp:
Voltage
Amps
Voltage
Amps
Complete data runs as shown on the following page. Acquired data is to become part of the
permanent unit records and function as a benchmark.
For water-cooled heat pumps:
• Both stages of any tandem circuit should be ON while testing.
• Record ambient conditions at time of test (dry bulb and RH or dew point)
• Circuit Enable should be set at 100% Cooling.
• Circuit Enable should be set at 100% Cooling with 100% Reheat.
• Circuit Enable should be set at 100% Cooling with 50% Reheat (as required).
• Circuit Enable should be set at 100% Heating.
• Digital Circuit should be set to enable at 50% to verify Unloading is operational.
Compressors Active
(Compressor # and Circuit)
Circuit
% Reheat
HGB Active (Y / N)
Discharge (psi)
(psi)
Liquid (°F)
Subcooling
(psi)
Suction (°F)
Superheat
Receiver (% full)
Time (duration of run
prior to measurement)
OA (°F)
SA (°F)
DX (°F)
Figure 6.) Start/Stop signal to each compressor. Figure 7.) Compressor Modulation signal. In order to
Run each compressor individually and then run run, digital scroll compressors require a start signal
compressors that share circuits together. Record as well as a modulation signal of at least 10%.
refrigeration numbers for each of these runs.
Notes:
Figure 10.) To manually override cooling/heating coil valve position set override to manual and demand to 100%
in cooling or heating ramp manual override pages, respectively.
Voltage
Amps
Inspection
Casette is securely mounted.
Rotor is centered within the casette frame.
Seals lightly contact the full perimeter of the
rotor.
Rotor turns freely.
Drive motor and pulley securely mounted.
Drive belt is aligned properly and has
sufficient tension.
Verify correct supply voltage to the drive
motor.
Start-Up
Rotor turns in proper direction.
Drive motor controller properly set up.
System controls operate properly.
Establish design airflow through Supply and
Exhaust Air streams.
Verify rotor is centered and has proper seal
contact.
NOTE
Recheck drive belt tension after 100 hours of
operation and adjust.
Yes No N/A
Does Heating mode operate as defined in the sequence?
(Set temperature sensor offset down to bring temperature below the set point.)
Does Cooling mode operate as defined in the sequence?
(Set temperature sensor offset up to bring temperature above the set point.)
Does Economizer mode operate as defined in the sequence?
(Set outside air temperature/humidity sensor offset down to bring T/H below set point.)
Does Defrost mode operate as defined in the sequence?
(Set the exhaust air sensor offset down to bring temperature below set point.)
Does dehumidification mode operate as defined in the sequence?
(Set the humidity sensor offset up to bring humidity above the set point.)
Does Reheat mode (dehumidification) operate as defined in the sequence?
(While Dehumidification mode is enabled, set the supply air sensor offset down to bring
the supply temperature below set point.)
Does Supply Fan Control mode operate as defined in the sequence?
Does Exhaust/Return Fan Control mode operate as defined in the sequence?
NOTES:
When the form is completed, please submit to DOAS@greenheck.com by clicking the "Submit Form" button below.