Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Service Manual Minisplits GOOD R410

Download as pdf or txt
Download as pdf or txt
You are on page 1of 37

WALL MOUNTED SPLIT-TYPE AIR CONDITIONER

SERVICE MANUAL No.20180928

Models
Indoor unit Outdoor unit
4MWW1512A9000AA 4TWK1512A9000AA
4MWW1512A1000AA 4TWK1512A1000AA
4MWW1518A1000AA 4TWK1518A1000AA
4MWW1524A1000AA 4TWK1524A1000AA
4MWW1530A1000AA 4TWK1530A1000AA

CONTENTS

1. IMPORTANT NOTICE
2. PRODUCT DIMENSIONS
3. REFRIGERATION CYCLE DIAGRAM
4. OPERATION DETAILS
5. WIRING DIAGRAM
6. EXPLOSION VIEW AND PART LISTS
7. PRECAUTION
8. NAMES OF PARTS
9. INSTALLATION
10. TROUBLE SHOOTING
 
Air Conditioner Service Manual

 
1. IMPORTANT NOTICE
 
 
This service manual is intended for use by individuals possessing adequate
backgrounds of electrical, electronic and mechanical experience. Any
attempt to repair the appliance may result in personal injury and property
damage. The manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any liability in
connection with its use.
The information, specifications and parameters are subject to change due to
technical modification or improvement without any prior notice. The
accurate specifications are presented on the nameplate label.
 
 
 
 
How to order spare parts
To have your order filled promptly and correctly, please finish the following
information:
6 Model No. with Indoor or Outdoor
7 Part No. in the Explosion View

8 Part Name
9 The quantity you needed

  1
Air Conditioner Service Manual

2. PRODUCT DIMENSIONS

Indoor Unit:

Model A B C

4MWW1512A9000AA 777 205 250

4MWW1512A1000AA 777 205 250

4MWW1518A1000AA 910 205 292

4MWW1524A1000AA 1010 220 315

4MWW1530A1000AA 1186 260 340

2
 
Air Conditioner Service Manual

Outdoor Unit:

Model D E F G H I J K

4TWK1512A9000AA 712 490.7 234 415 290.4 263 48 53.2

4TWK1512A1000AA 712 490.7 234 415 290.4 263 48 53.2

4TWK1518A1000AA 780 605 290 500 360 327.5 55 63

4TWK1524A1000AA 845 607 326 586 375 347.5 59 63

4TWK1530A1000AA 902 650 307 623 399 349 65 63

  3
 
Air Conditioner Service Manual

10 3. REFRIGERATION CYCLE DIAGRAM


Cooling only

Liquid side

2-way valve Capillary

Heat exchange Heat exchange


(Evaporator) (condenser)

Gas side

3-way valve
Accumulator

Compressor

Heat pump

Liquid side Check valve

2-way valve

Capillary Assembly

Heat exchange Heat exchange


(Evaporator) (condenser)

Gas side

3-way valve
4-way valve

Accumulator Heating
Compressor Cooling

  4
Air Conditioner Service Manual

4.Operation Details
Remote controller

The outlooking and some function of remote control may vary according
to the model.
The shape and position of buttons and indicators may vary according to
the model, but their function is the same.
The unit confirms the correct reception of each press button with a beep.
Functions of horizontal swing and health are optional.

5
Air Conditioner Service Manual

No. Button Function

1 ON/OFF Press it to start or stop operation.

2 MODE To select the mode of operation

3 FAN To select the fan speed of auto/low/mid/high

4 SLEEP To activate the function SLEEP

5 SWING To activate or deactivate of the movement of the deflectors.


To switch - on /off HEALTHY funtion.It is a button which controls the ionizer or
6 HEALTHY plasma genera for available model only.

7 (TEMP UP) Press it to increase temperature / time setting.

8 (TEMP DN) Press it to decrease temperature/ time setting.

9 TIMER Press it to set auto-off timer.

In cooling mode,press this button ,the temperature will increase 2 on the base of
setting temperature
10 ECO
In heating mode, press this button, the temperature will decrease 2 on the base of
setting temperature

11 DISPLAY To switch on/off the LED display

Press this button to activate / deactivate the Super function which enables the unit to
reach the preset temperature in the shortest time.
12 TURBO In COOL mode, the unit will give the maximum cooling temperature with 16 ,high fan
speed.
In HEAT ode, the unit will give the maximum heating temperature with 31 ,high fan
speed.

To switch active /deactive "I FEEL" function.The air conditioner will regulate the room
13 I FEEL temperature based on the temperature(0 ~50 ) around the remote controller.This
function will terminate 2 hours later once it's active.

When you press the buttons "MODE" and "TIMER" at the same time, the remote
14 LOCK/UNLOCK controller will be locked, all buttons of the remote controller will be deactive
and it displays "Lo" .You can operate again as the same way to unlock the remote
contoller.

15 Mute To activate the function of Mute.

6
 
  Air Conditioner Service Manual
 

Electronic controller
NOTES:
RT-------Room Temperature.
IPT------Indoor Pipe Temperature.
ST------indoor Setting Temperature.
OPT---Outdoor Pipe Temperature.
CRT---Compensated Room Temperature

1. Automatic mode
1) The initial RT determines A/C working mode and the setting temperature (ST), the mode is
determined effective only once unless A/C shut-down and then re-started. If from other mode
switches to automatic mode (including mode conversion after shutdown), it should be that the
compress stop more than 3 min then temperature judgment and automatic mode are conducted (it
can conduct immediately from fan mode switched to automatic, the indoor fan stops, three minutes
later the response is made and start up). Within 3 min, the output as: Showing the room
temperature, indoor fans starts (or anti-cold airflow), the outdoor fan stops;
With auto re‐start controller, once being turned off or in case of an accidently power cut, the A/C is able  to 
retain and restore the original mode when being turned on or the power supply is resumed, if the  auto 
restart  function  activated.  power‐off  after  power‐on;  while  if  the  auto  restart  function  isn’t  activated, 
the A/C enters standby state. 

Heat pump
Mode Initial RT Initial ST
Cooling RT≥26°C 23°C
Dry 26°C>RT≥20°C 7°C
Heating RT<20°C 23°C

Cooling-only
Mode Initial RT Initial ST
Cooling RT≥26°C 23°C
Dry 26°C>RT≥20°C 7°C
Ventilating RT<20°C -

Under automatic mode (including from automatic converted into Dry mode), when A/C received the
temperature UP or DOWN signals from the remote controller, the setting temperature (ST) adjusts
correspondingly to the current room temperature plus or minus 1°C, the automatic regulating
temperature range is ± 2°C.

2. Cooling mode
1) The control of the compressor
a. When RT-ST≥1°C,the compressor is running.
b. When RT-ST<-1°C,the compressor stops.
c. When-1°C≤RT-ST<1°C, the compressor keeps its original state.
2) Outdoor fan motor and the compressor run simultaneously (except for defrosting).
3) The control of indoor fan motor:
a. Indoor fan motor can operate by automatic, low, middle, or high airflow speed circularly.

7
 
 
 
  Air Conditioner Service Manual

b. Indoor fan motor automatic airflow speed control, it works as shown in Figure 1:

Hi
Mid
Lo
RT-ST
1°C 2°C 4°C
Figure 1 Cooling automatic airflow

When the temperature changing leads the fan speed variation, the switch can only be made orderly,
and in every grade of air flow speed should run 1 minute at least.

3. Dry mode
While select to this mode, the air conditioner operates for 3 minutes according to cooling mode firstly
(ST set at 7°C), and then takes the detected backflow air temperature minus 2°C as a new set
temperature (the lowest temperature: 5°C) and runs according to cooling mode, indoor fan operates at
low-speed, at this moment the setting operation of fan speed invalid but Swing adjustable.

4. Heating mode
On the Heating mode, the room temperature (RT) is compensated (CRT), a fter that, the room
temperature displayed on the LED is CRT=RT-3°C.
1) The control of the compressor
a. When ST-CRT≥1°C,the compressor is running.
b. When ST-CRT<-1°C,the compressor stops.
c. When -1°C≤ST-CRT<1°C, the compressor keeps its original state
2) Outdoor fan motor and the compressor run simultaneously (except for defrosting)
3) The control of indoor fan motor:
a. Indoor fan motor can operate by automatic, low, middle, or high airflow speed circularly.
b. Indoor fan motor automatic airflow speed control, it works as shown in Figure 2:

Hi
Mid
Lo
ST-CRT 1°C 2°C 4°C

Figure 2 Heat automatic airflow

When the temperature changing leads the fan speed variation, the switch can only be made orderly,
and every grade of air flow speed should run 1 minute at least.
4) Vane motor control: run as set state.
5) 4-way valve control:
a. Under heating mode, the four-way valve maintains well-connected status (including the
compressor stops on set condition, except for the defrosting process)
b. When the mode switches into the heating mode or A/C start-up, four-way valves will open 5
Seconds before the compressor starts; while the mode exits from the heating mode or A/C turn off,
the four-way valve will close 2min later after shut-down the compressor.

8
 
 
 
  Air Conditioner Service Manual

6) Defrosting function:
During defrosting, once mode changing, economic operation or temperature setting signals received, the
buzzer and display will make response immediately, but the other operations won’t implement until
defrosting finished;
During defrosting, the signals of On-Off, Timing, Sleep, Fan speed and/or Swing can respond, but the
Fan speed and/or Swing should be in accordance with operation for Cold Air Prevention.
Except the above signal processing during defrosting, no other signals will deal with, only a voice of
buzz for response.
During defrosting, electrical heating (optional function) stops compulsively.

Defrosting Enter and Exit program:


Option 1:with jumper JC
The condition of enter defrosting: run into defrosting once any of condition 1, 2, and/or 3 met.

Condition 1:As shown in figure 3


Definition:
The following conditions a, b and c all required to meet:
a. IPT1 settles for IPT1=IPTmax-ᇞIPT
b. t5≥50min(running time t5≥50min(the compressor runs cumulatively),t5 is removable,and could
be less than t1)
c. IPT<40°C,and lasts 2min。
Running into defrosting on condition 1, the first running time of set defrosting is F (8min); after running a
defrosting cycle, the defrosting time should be determined and adjusted.

Figure 3

Condition 2: When running time is more than or equal to 120 min (compressor is running
accumulatively), the indoor temperature is less than 35°C for 2 min sustained. Running into defrosting
under condition 2, defrosting time set is 8 min.

Condition 3: After the compressor is operating for 20min continuously, the indoor pipe temperature is
less than 23°C (cold air prevention wind temperature) when the fan stops running (including
temperature dropping when compressor operating, not including the compressor’s starting up course),
and the machine runs into defrosting according to any one condition as below.

9
 
 
 
  Air Conditioner Service Manual

Running into defrosting under condition 3, defrosting time set is 10 min.


a) Running into the first defrosting in 20 min after start-up.
b) The interval from last defrosting equivalent to or more than 50 min (stopping the compressor or the
machine in standby is allowed in the meantime).
Option 2: Without Jumper JC, and no OPT outdoor sensor
when the compressor runs for 45 min (accumulated), if the indoor coil temperature is less than 40°C for
2 min, the machine runs into defrosting, and lasts for 3min, otherwise when the compressor
runs for 120 min (accumulated), the machine runs into defrosting automatically and last for 10 min.
Option 3: Without jumper JC, but with OPT outdoor sensor
While heating, when the temperature of condenser is lower than E °C (-4°C), and the compressor runs
for 45 min (accumulated), then the machine runs into defrosting and lasts for 10 min.
Option 4. On heating, while the outdoor fan motor stopped but the compressor operated
accumulative totally 30min, then the machine runs into defrosting and last for 8 min. if the accumulative
totally less than 30min, but accord with one of the condition option 1-3 then the machine runs into
defrosting at the option 1-3 and the accumulative total time restarts from 0.
Conditions for quitting defrosting
(1) The quitting conditions for option 1, option 2 and 4, the machine quits from defrosting if any one
below condition met.
6a. Defrosting time is over.
7 b. When it runs in defrosting for three minutes, the IPT indoor coil temperature rises 15°C or above
from the bottom point.
(2) The quitting conditions for option 3.
When OPT ≥ 20°C or defrosting for more than 10 min, then quit from defrosting.
(3) Defrosting process shown in Figure 4
The indoor fan runs in anti-cold wind modle

Outdoor Fan
ON ON

OFF

4-way Valve
ON ON

OFF

Compressor Relay ON OFF ON OFF ON


t
Defrosting time MAX 12 Min
39S 19S 5S

Figure 4 Defrosting process

7) Auxiliary electric heating function (optional)


(1) The default condition is automatic on/off the electric heating function.
(2) The conditions of auxiliary electric heating works (all the following conditions must be met)
a. the compressor runs for more than 3min;
b. indoor fan runs normally;
c. not in defrosting state;

10
 
 
 
  Air Conditioner Service Manual

d. auxiliary electric heating is turned off for more than 30s。


e. ST-RT≥0°C;
f. RT﹤25°C;
g. IPT≤43°C;
(3) The conditions of stopping auxiliary electric heating(any one of the following conditions met, the
state stops)
a. the compressor stops
b. RT≥27°C;
c. IPT≥50°C
d. indoor fan stops。
e. running into sleeping function

5. Fan mode
1) Indoor fan motor is running at setting speed (the speed same as heating mode).
2) Vane motor control: running according to the setting condition.
3) The outdoor unit doesn’t work under fan mode.

6. Sleeping mode
1) Under sleep mode, the indoor fan motor running at low speed, except the power light and sleep light
are ON, timer lights ON/OFF according to the setting state, running light OFF. LED will be OFF after
displaying 30S.
2) Temperature control:
6 (1) While changing from Cool mode to Sleep mode, one hour later, the operation Temp.=ST+1°C,
another one hour later, the operation Temp.=ST+2°C,after then the temperature has no changed
anymore.
7(2) When changing from Heating mode to Sleep mode, one hour later, the operation Temp.= ST‐1°C,
another one hour  later, the operation Temp.=ST‐2°C,after then no changed anymore. 
3) The machine will automatically shut up after running 10 hours under sleep mode.
When Timer ON and Sleep mode are implemented at the same time, the Sleep mode can not be
functioned.

7. Timer function
The timer can preset between 10min to 24h, when the time set less than “10” hours, the displayed time
shown by 0.5 hour as the unit, when the time set more than or equal to “10” hours, the displayed time
shown by 1 hour as the unit.

8. Emergency switch (ON/OFF)


1) When stand-by, to operate by pressing the emergency switch as follows:
Press the emergency switch within 3 seconds, release emergency switch while the buzzer rings once,
the machine goes into Cooling mode. If the buzzer rings twice while release emergency switch,
Heating mode is selected. To press the Emergency switch while A/C is on, the buzzer rings once and
then A/C will shut down.
2) The machine runs mandatorily as selected mode within 30min when Emergency operated,
meanwhile indoor fan motor runs in high-speed, and stepping vane swinging as well. 30min later the
A/C goes into automatic mode under the same operation manner, the set temperature to be 23°C, and
the rotate speed of indoor fan motor automatic control, stepping vane swinging all the way.
3) To press the emergency button when the A/C goes on operation, then the machine runs into
stand-by.

11
 
 
 
  Air Conditioner Service Manual

4) Under emergency operation, the function of compressor’s time-delay protection, Anti-frosting


protection in cooling mode, Overheating protection in heating mode, sensor fault protection and defrost
operate are effective.
5) Under emergency operation, once effective signal from remote controller received, the A/C
exits form of emergency mode without delay, and operates according to the setting value from remote
controller immediately.

9. Auto-restart function
1) The PCB retains the setting parameters in case of power off. When the power supply is resumed,
the machine, which has been started up the power-off memory function, is able to restore into the
original running state automatically.
To press the emergency button and power on the unit, and hold on for10 seconds, The buzzer
2) will ring three times, after this operation, the auto restart function activated.
3) To close auto restart function while it is activated, repeat process as above 2), the buzzer will ring
four times.

10. Protection / Failure code

10.1 Protection

1) Compressor’s protection:
a. The PCB which with Auto-restart function, once it is activated, the compressor goes along 3min
delay protection when power on, otherwise the compressor without this protection even when the PCB
is power-on.
b . The compressor’s 3 min interval protection: the compressor can’t start-up until it stops 3 min later.
(except for the defrosting process).
c. .After the compressor started, it’s operation state remains the same within 3 min even when ST, RT variation.

2) Anti-frosting protection of indoor evaporator (Cooling mode):


If IPT≤0°C detected in consecutive 3 min, compressor and outdoor fan motor to be stopped operation,
indoor fan motor runs at high-speed forcibly; i f IPT≥5°C detected 3min later, then outdoor fan motor
and compressor will start up, and indoor fan motor restores to it’s original state.

3) Overheating protection (Heating mode):


If IPT≥55°C, the outdoor fan motor: OFF.
If IPT≥65°C, the compressor: OFF, and indoor fan motor runs at high-speed forcibly.
When IPT≤48°C, the outdoor fan motor and the compressor start up, indoor fan motor restores to it’s
original state.

4) Cold air prevention (Heating mode):


This function is intend to prevent cold air from being discharged when the heating operation starts or when
defrosting.
a. When running into the heating mode, once the compressor fails to comply with the start-up
conditions, the fan speed is regulated according to the coil temperature within 2 min, 2 min later the
indoor fan motor stops. If the compressor starts up within 2 min, then operating according to Figure 5.
Under heating process, while the compressor stop (including stopping for protection), the fan motor’s
operation (including stopping the indoor fan motor) is regulated according to the coil temperature within
1min, 1min later the fan will be stopped forcibly.

b. When the indoor fan motor running at a low-speed under cold air prevention operation, once

12
 
 
 
  Air Conditioner Service Manual

auxiliary electric heating works, the vane immediately withdraws from the cold air prevention location
and turn back to normal vane angle. While auxiliary electric heating stops, indoor fan motor goes on to
run at low-speed accordingly, the vane turns to cold air prevention location

Set fan speed Set fan speed

Temperature dropping
34°C 32°
Temperature rising

27°
 
25°C  

23°C
Stop the fan motor Stop the fan motor

Figure 5 Cold air prevention

10.2 Failure code


The following table shows the fault protections.
When failures happens, the PCB alarms and buzzer rings three times, Failure code shows on
display board, and the PCB operates protection procedures.
Failure code: For the machine with LED display (88), the code shows on LED, for machine without
LED, the code reflects by the running light.

Failure Running Light Flash LED Display (88)


RT Sensor Failure Once / cycle E1
IPT Sensor Failure Twice / cycle E2
Indoor Fan Motor Failure 6 times / cycle E6

While failure happens, the code displayed statically, if there are several failure codes reported at the
same time, then failure codes appears by turns every eight seconds correspondingly.
6 a. Sensor’s failure protection: when the sensor tested temperature out of the range ---
50°C≤T≤110°C, sensor failure is determined.
Once RT and/or IPT sensor failure appears, the compressor stops, and indoor and outdoor fan motors
shut off. Remote controller doesn’t response to any signal except for shutdown. During failure the
machine can run in fan mode. After the failure is settled, the PCB restores to standby status.
7 b. Failure protection of Indoor PG fan motor: If there is no feedback signal of rotated speed within 5s,
the indoor fan motor stops, meanwhile, the compressor, outdoor fan motor, four-way valve and/or
auxiliary electric heater etc. also cut down.
The indoor fan motor restarts again 10 seconds later, if still there is no feedback signal of rotated speed
within 5 seconds, the A/C stops and goes into indoor fan motor failure protection, buzzer rings three
times, and running light flashes at 6 times per 8 seconds. Once there is feedback signal while the failure
recovery, the failure will relieve automatically.

13
 
 
Air Conditioner Service Manual

5. WIRING DIAGRAM
INDOOR UNIT: 4MWW1512A9000AA 4MWW1512A1000AA
4MWW1518A1000AA

OUTDOOR UNIT: 4TWK1512A9000AA 4TWK1512A1000AA 4TWK1518A1000AA

14
Air Conditioner Service Manual
 

INDOOR UNIT: 4MWW1524A1000AA


 

 
 
OUTDOOR UNIT: 4TWK1524A1000AA
 

 
   

15
Air Conditioner Service Manual
 

INDOOR UNIT: 4MWW1530A1000AA


 

FM

MDC

FM

SM SM SM

 
 
 
OUTDOOR UNIT: 4TWK1530A1000AA

 
 
 

16
Air Conditioner Service Manual

6. EXPLOSION VIEW AND PARTS


INDOOR UNIT: 4MWW1512A9000AA 4MWW1512A1000AA
4MWW1518A1000AA 4MWW1524A1000AA 

17
Air Conditioner Service Manual

INDOOR UNIT: 4MWW1512A9000AA 4MWW1512A1000AA


4MWW1518A1000AA 4MWW1524A1000AA 

No. Part No. Part Name Q’ty Remark


1 Front Panel 1
2 Air Filter 2
3 Face Frame 1
4 Electrical Box Cover 1
5 Display PCB 1
6 Display PCB Box 1
7 Evaporator 1
8 Screw Cover 2
9 Cross Fan 1
10 Bearing Mount 1
11 Indoor Motor 1
12 In And Out Pipe Fixer 1
13 Indoor Motor Cover 1
14 Electrical Box 1
15 Main PCB 1
16 Transformer 1
17 Cable Clamp 1
18 Vane Motor 1
19 Base 1
20 Vertical Vane Assembly 2
21 Vane 1
22 Installation Plate 1
24 Indoor Sensor Assembly 1
25 Remote Controller 1
Not shown in Explosion
26 Indoor Carton 1
view
27 Left Foaming 1
28 Right Foaming 1

18
Air Conditioner Service Manual
 

INDOOR UNIT: 4MWW1530A1000AA

1
2

3 23
4
5 22
6 21
7
8 20
9
19
10
18
11
17
12
16

15
14
13

19
Air Conditioner Service Manual
 

INDOOR UNIT: 4MWW1530A1000AA

No. Part No. Part Name Q’ty Remark


1 Installation Plate 1
2 Base 1
3 Vertical Vane Assembly 3
4 Cross Fan 1
5 Bearing Mount 1
6 Evaporator 1
7 Face Frame 1
8 Screw Cover 4
9 Air Filter 2
10 Display PCB Box 1
11 Display PCB 1
12 Front Panel 1
13 Up Vane 1
14 Down Vane 1
15 Drainage Hose 1
16 Cable Clamp 1
17 Main PCB 1
18 Electrical Box 1
19 Vane Motor 2
20 Indoor Motor 1
21 Indoor Motor Cover 1
22 Indoor Sensor Assembly 1
23 In And Out Pipe Fixer 1
24 Remote Controller 1
25 Power Supply Cord 1
26 WIFI module 1
Not shown in
27 Indoor Carton 1
Explosion view
28 Left Foaming 1
29 Right Foaming 1
30 Middle Pasteboard Supporter 1

20
Air Conditioner Service Manual
 

OUTOOR UNIT: 4TWK1512A9000AA 4TWK1512A1000AA 4TWK1518A1000AA


 
   

7 6 5 4 3 2 1

27

26

25

24

23

22

21

20

19

18

17

10 11 12 13 14 15 16

21
Air Conditioner Service Manual
 

OUTOOR UNIT: 4TWK1512A9000AA 4TWK1512A1000AA 4TWK1518A1000AA

No. Part No. Part Name Q’ty Remark


1 Grille 1 Optional

2 Top Cover 1
3 Condenser 1
4 Outdoor Motor Supporter 1
5 Outdoor Motor 1
6 Propeller Fan 1
7 Left Grille Supporter 1
8 Front Plate 1
9 Fan Guard 1
10 Compressor 1
11 4-way Valve 1
12 4-way Valve Assembly 1
13 Base 1
14 Right Plate 1
15 Two-way Valve 1
16 Valve Supporter 1
17 Three-way Valve 1
18 Electrical Box Cover 1
19 Cable Clamp(φ6) 1
20 Cable Clamp(φ8) 1
21 Terminal 1
22 Fan Motor Capacitor 1
23 Compressor Capacitor 1
24 Capacitor Strip 1
25 Electrical Parts Box 1
26 Capillary Assembly 1
27 Partition plate 1
28 Base Carton 1
29 Base Forming 1 Not shown in the
Explosion view.
30 Cabinet Carton 1
31 Cover Forming 1
 

22
Air Conditioner Service Manual
 
OUTOOR UNIT: 4TWK1524A1000AA 4TWK1530A1000AA

 
 
 
  6 5 3 2 1
 
 
 
  27
 
  26
 
  25
  24
 
23
 
  22
 
  21
 
   
20

19

18

17

10 11 12 13 14 15 16

23
Air Conditioner Service Manual
 
 
OUTOOR UNIT: 4TWK1524A1000AA  4TWK1530A1000AA 
 
No. Part No. Part Name Q’ty Remark
1 Grille 1 Optional

2 Top Cover 1
3 Condenser 1
4 Outdoor Motor Supporter 1
5 Outdoor Motor 1
6 Propeller Fan 1
7 Left Grille Supporter 1
8 Front Plate 1
9 Fan Guad 1
10 Compressor 1
11 4-way Valve 1
12 4-way Valve Assembly 1
13 Base 1
14 Right Plate 1
15 Two-way Valve 1
16 Valve Supporter 1
17 Three-way Valve 1
18 Electrical Box Cover 1
19 Cable Clamp 2
20 Terminal 1
21 Fan Motor Capacitor 1
22 Compressor Capacitor 1
23 Capacitor Strip 1
24 Electrical Parts Box 1
25 AC Contactor 1
26 Capillary Assembly 1
27 Partition plate 1
28 Base Carton 1
29 Lower Foaming 1 Not show in the
30 Cabinet Carton 1 explosion

31 Upper Cover 1
 
 
 

24
Air Conditioner Service Manual
 
 
 
7.Precaution
7.1 SAFETY RULES AND RECOMMENDATIONS FOR THE INSTALLATION
 Read this guide before installing and using the appliance.
 During the installation of the indoor and outdoor units the access to the working area should
be forbidden to children.
Unforeseeable accidents could happen.
 Make sure that the base of the outdoor unit is firmly fixed.
 Check that air cannot enter the refrigerant system and check for refrigerant leaks when
moving the air conditioner.
 Check that air cannot enter the refrigerant system and check for refrigerant leaks when
moving the air conditioner.
 The ratings of the fuse installed in the built in-control unit are T 5A / 250V.
 The user must protect the indoor unit with a fuse of suitable capacity for the maximum input
current or with another overload protection device.
 Ensure that the mains voltage corresponds to that stamped on the rating plate. Keep the switch or
power plug clean. Insert the power plug correctly and firmly into the socket, thereby avoiding the
risk of electric shock or fire due to insufficient contact.
 Check that the socket is suitable for the plug, otherwise have the socket changed.

 The appliance must be fitted with means for disconnection from the supply mains having a contact
separation in all poles that provide full disconnection under over voltage category III conditions, and
these means must be incorporated in the fixed wiring in accordance with the wiring rules.
 The air conditioner must be installed by professional or qualified persons. Do not install the appliance
at a distance of less than 50 cm from inflammable substances (alcohol, etc.) Or from pressurized
containers (e.g. spray cans).
 If the appliance is used in areas without the possibility of ventilation, precautions must be taken to
prevent any leaks of refrigerant gas from remaining in the environment and creating a danger of fire.
 The packaging materials are recyclable and should be disposed of in the separate waste bins .Take
the air conditioner at the end of its useful life to a special waste collection center for disposal.
 Only use the air conditioner as instructed in this booklet. These instructions are not intended to cover every
possible condition and situation. As with any electrical household appliance, common sense and caution are
therefore always recommended for installation, operation and maintenance.
 The appliance must be installed in accordance with applicable national regulations.

 Before accessing the terminals, all the power circuits must be disconnected from the power supply.

 The appliance shall be installed in accordance with national wiring regulations.


This appliance can be used by children aged from 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and user maintenance shall not be made by children without
supervision.

25
 
Air Conditioner Service Manual

7.2 SAFETY RULES AND RECOMMENDATIONS FOR THE USER


 Do not try to install the conditioner alone; always contact specialized technical personnel.
Cleaning and maintenance must be carried out by specialized technical personnel. In any case
disconnect the appliance from the mains electricity supply before carrying out any cleaning or
maintenance.
 Ensure that the mains voltage corresponds to that stamped on the rating plate. Keep the switch or
power plug clean. Insert the power plug correctly and firmly into the socket, thereby avoiding the
risk of electric shock or fire due to insufficient contact.
 Do not pull out the plug to switch off the appliance when it is in operation, since this could create a
spark and cause a fire, etc.
 This appliance has been made for air conditioning domestic environments and must not be used
for any other purpose, such as for drying clothes, cooling food, etc.
 The packaging materials are recyclable and should be disposed of in the separate waste bins.
Take the air conditioner at the end of its useful life to a special waste collection center for
disposal.
 Always use the appliance with the air filter mounted. The use of the conditioner without air filter
could cause an excessive accumulation of dust or waste on the inner parts of the device with
possible subsequent failures.
 The user is responsible for having the appliance installed by a qualified technician, who must check
that it is earthed in accordance with current legislation and insert a thermomagnetic circuit
breaker.
 The batteries in remote controller must be recycled or disposed of properly. Disposal of Scrap
Batteries.
--- Please discard the batteries as sorted municipal waste at the accessible collection point.
 Never remain directly exposed to the flow of cold air for a long time. The direct and prolonged
exposition to cold air could be dangerous for your health .Particular care should be taken in the
rooms where there are children, old or sick people.
 If the appliance gives off smoke or there is a smell of burning, immediately cut off the power
supply and contact the Service Centre.
 The prolonged use of the device in such conditions could cause fire or electrocution.

 Have repairs carried out only by an authoritative Service Centre of the manufacturer. Incorrect
repair could expose the user to the risk of electric shock, etc.
 Unhook the automatic switch if you foresee not to use the device for a long
time. The airflow direction must be properly adjusted.
 The flaps must be directed downwards in the heating mode and upwards in the cooling mode.
Only use the air conditioner as instructed in this booklet. These instructions are not in ended to cover 
every possible condition and situation. As with any electrical household appliance, common sense and 
caution are therefore always recommended for installation, operation and maintenance. 
 
 
 
 

26
 
Air Conditioner Service Manual

8.Names of parts
 
 
INDOOR UNIT
  Indoor unit
  1 2-3 4 No. Na
  1 Front panel
  2 Air filter
  3 Special filter(option)
  4 Display PCB
  5 Vertical vane
  6 Horizontal vane
  6 5 7 Remote controller
   
 
 
7
 
 
 
 
 
 
8
 
 
 
  Outdoor unit
  No. Name
  8 Air outlet grille
9 Electronic box cover
  9
10 2-way valve
  11 3-way valve
  10
 
 
11
 
OUTD OOR UNIT
 
 
 
 
 
 
 
 

27
Air Conditioner Service Manual

9. Installation manual
9.1 Installation Details
Connecting pipe length
Pipe size(Inch)
Model
Liquid Gas
4MWW1512A9000AA/4TWK1512A9000AA 1/4 3/8
4MWW1512A1000AA/4TWK1512A1000AA 1/4 3/8
4MWW1518A1000AA/4TWK1518A1000AA 1/4 1/2
4MWW1524A1000AA/4TWK1524A1000AA 1/4 5/8
4MWW1530A1000AA/4TWK1530A1000AA 1/4 5/8

Outdoor unit Indoor unit

Pipe l ength is
Pi pe length is 15 meters Max.
15 meters Max.
be l ess than 5m

Indoor unit
Height should

be less tha n 5m
Height sh ould

Outdoor unit

Refrigerant piping
Max. length: m Additional refrigerant
Model Standard length: m
Calculation: ×g=20g/m(A-5m)
A
4MWW1512A9000AA/4TWK1512A9000AA  3.5  15  20g/m 
4MWW1512A1000AA/4TWK1512A1000AA  3.5  15  20g/m 
4MWW1518A1000AA/4TWK1518A1000AA  5.0  15  30g/m 
4MWW1524A1000AA/4TWK1524A1000AA  5.0  15  30g/m 
4MWW1530A1000AA/4TWK1530A1000AA  5.0  15  30g/m
Connecting cables
The power cord should be selected according to the following specifications sheet.
Appliance Amps Wire Size
5 AWG21/0.75 mm2
10 AWG18/1.0 mm2
13 AWG15 /1. 5 mm2
18 AWG14/1.6 mm2
25 AWG12/2.0 mm2
30 AWG10/2.5 mm2

28
 
Air Conditioner Service Manual

9.2 Installation for the first time


Indoor unit
 Install the indoor unit level on a strong wall
that is not subject to vibrations
 The inlet and outlet ports should not be
obstructed: the air should be able to blow all

150mm
over the room. Mounting plate
 Do not install the unit near a source of heat,
150mm
heat, steam or flammable gas.
 Do not install the unit in too windy or dusty 150mm
places.
 Do not install the unit where people often
pass. Select a place where the air condensed water drain pip e
discharge and operating sound level will Sleeve
not disturb the neighbors. insulatin g covering
 Install the unit where connection between electrica l cable
indoor and outdoor unit is as easy as
possible. water dra in pipe
 Install the unit where it is easy to drain the
condensed water.
 Check the machine operation regularly and
leave the necessary spaces as shown in the
picture.
 Install the indoor unit where the filter can
Minimum space to be left (mm) showing in the
be easily accessible.
picture.
OUTDOOR UNIT
 Do not install the outdoor unit near sources of
heat, steam or flammable gas.
 Do not install the unit in too windy or dusty
500mm

places.
 Do not install the unit where people often
pass. Select a place where the air
discharge and operating sound level will
not disturb the neighbors.
 Avoid installing the unit where it will be
exposed to direct sunlight (other wise use a
300mm
protection, if necessary, that should not 300
interfere with the air flow). mm
 Leave the spaces as shown in the picture
for
 The air to circulate freely. 500
200 mm
 Install the outdoor unit in a safe and solid 0 mm
place.
 If the outdoor unit is subject to vibration,
place rubber gaskets onto the feet of the
unit.

29
 
Air Conditioner Service Manual

 Install the indoor unit in the room to be air


conditioning, avoiding to installation in
corridors or communal areas.
 Install the indoor unit at a height of at least
2.5m from the ground.
To install, proceed as follows:
9.2.1 Installation of the mounting plate.
1) By using a level, put the mounting plate in a
perfect square position vertically and horizontally.
2) Drill 32mm deep holes in the wall to fix the plate.
3) Insert the plastic anchors into the hole.
4) Fix the mounting plate by using the provided
tapping screws.
5) Check that the mounting plate is correctly fixed.
Note: The shape of the mounting plate may be
different from the one above, but installation
method is similar.
9.2.2 Drilling a hole in the wall for the piping
1) Decide where to drill the hole in the wall for the
piping (if necessary) according to the position of Indoors Out doors
the mounting plate
2) Install a flexible flange through the hole in the
wall to keep the latter intact and clean.
The hole must slope downwards towards the
exterior.
5mm
Note: Keep the drain pipe down towards the
direction of the wall hole, otherwise leakage may
occur.
9.2.3 Electrical connections---Indoor unit
1).Lift the front panel.
2).Take off the cover as indicated in the picture
(by removing a screw or by breaking the Front panel
hooks).
3).For the electrical connections, see the
Wiring diagram
circuit diagram on the right part of the unit
under the front panel.
4).Connect the cable wires to the screw terminals
by following the numbering, Use wire size
suitable to the electric power input (see name
Terminal block cover
plate on the unit) and according to all current
national safety code requirements.
5).The cable connecting the outdoor and indoor
units must be suitable for outdoor use.

30
 
Air Conditioner Service Manual

6).The plug must be accessible also after the


appliance has been installed so that it can be
pulled out if necessary.
7).An efficient earth connection must be
ensured.
8).If the power cable is damaged, it must be
replaced by an authorized Service Centre.
9.2.4 Refrigerant piping connection
The piping can be run in the 3 directions 1
indicated by numbers in the picture. When the
piping is run in direction 1 or 3, cut a notch
along the groove on the side of the indoor unit
2 3
with a cutter.
Run the piping in the direction of the wall hole
and bind the copper pipes, the drain pipe and
the power cables together with the tape with the
drain pipe at the bottom, so that water can flow  
  Shape the connection pipe
freely.
 
9.2.5 Connecting the pipes.
 
 Do not remove the cap from the pipe
 
until connecting it, to avoid dampness
 
or dirt from entering.
 
 If the pipe is bent or pulled too often, it
 
will become stiff. Do not bend the pipe YES NO
 
more than three times at one point.
  Extending the rolled pipe
 When extending the rolled pipe,
 
straighten the pipe by unwinding it
 
gently as shown in the picture.
 
9.2.6 Connections to the indoor unit
 
1).Remove the indoor unit pipe cap (check that
there is no debris inside).  
2).Insert the fare nut and create a flange at the  
extreme end of the connection pipe.  
3).Tighten the connections by using two  
wrenches working in opposite directions.   torque wrench
9.2.7 Indoor unit condensed water drainage  
The indoor unit condensed water drainage is  
fundamental for the success of the installation.
 
1).Place the drain hose below the piping,
 
taking care not to create siphons.
2).The drain hose must slant downwards to aid   
drainage.   YES

3).Do not bend the drain hose or leave it   
protruding  or twisted and do not put the end   
of it in water. If an extension is connected to   
the drain hose,  ensure that it is lagged when   
it passes into the indoor unit.
 
  NO NO

31
 
Air Conditioner Service Manual

4).If the piping is installed to the right, the pipes,   
power cable and drain hose must be lagged and   
secured onto the rear of the unit with a pipe   
connection.   
 Insert the pipe connection into the relative  
slot.  
 Press to join the pipe connection to the  
base.  
9.2.8 Electronic connections Wiring diagram on the back of the cover
1. Take the cover away.  
 
2. Connect the cable wires to the terminal  
board using the same numbering as in the  

indoor unit. Screw


3. For the electrical connections, see the wiring  
Remove the upper cover
diagram on the back of the cover
Outdoor unit
4. Fasten the cables with a cable-clamp.
 
5. An efficient earth connection must be
ensured.   connection pipes

6. Replace the covers.  


9.2.9 Connecting the pipe  
Screw the flare nuts to the outdoor unit   flare nuts
liquid tap
coupling with the same tightening procedures  
described for the indoor unit.   gas tap
Note: If the tightening torque is not sufficient,   indoor unit
there will probably be some leakage. With   gas valve Liquid valve
excessive tightening torque there will also be tap
 
some leakage, as the flange could be  
damaged. service port nut protection caps
 
9.2.10 Bleeding
 
Air and humidity left inside the refrigerant circuit
 
can cause compressor malfunction. After having
 
connected the indoor and outdoor units, bleed
 
the air and humidity from the refrigerant circuit
by using a vacuum pump.  
The air and humidity left inside the refrigerant  
circulation can cause compressor  
malfunction. After having connected the  
vacuum pump
s ervice port
indoor and outdoor units, bleed the air and  
humidity from the refrigerant circulation using  
a vacuum pump.  
   
   
   
   
   
   
 
 

32
 
Air Conditioner Service Manual

10. Trouble shooting


10.1 Product does not operate at all.
 
 
 
  Power receptable voltage 
  Power supply voltage check Product input voltage 
  PCB assembly 
 
 
  Power input voltage 
Driving load terminal   Connector contact check 
 
Display PCB connector 
 
 
 
 
 
Power trans output voltage AC about 12±3V 
 
 
 
  PCB assembly check
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
33
 
Air Conditioner Service Manual

10.2 Indoor fan does not operate at all (E6). 


 
  Check: 
  Connector contact Motor output connector 
  Motor capacitor 
  Check: 
Motor bearing inserted 
 
state  Motor-related parts
  Fan(Blower) fixed state 
  Fan(Blower) contact 
  state 
  Motor detail check
 
 
  Operation mode check
 
 
Check:
 
PCB assembly check Motor driving circuit
  Relay output
 
 
  Replace motor or
  PCB assembly
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
34
 
Air Conditioner Service Manual

10.3 Compressor or outdoor fan does not operate at all. 


 
  Re-input after power off
 
 
  Set the desired temperature of remote controller to be lower by 2°C or
over than room temperature, and start the cooling operation.
 
 
 
 
Repeat running/stopping
  Does not operate at all.
at a short time period.
 
 
 
  Thermistor and evaporator
Temperature sensor surface contact check.-
  open/short check Clearance is needed (5mm).
 
 
 
  Connector check Connector check
(Contact & power) (Contact & power)
 
 
 
  Disconnection/short OLP/High pressure
  circuit check of switch/Low pressure
 
connecting wire switch check
 
 
  Operation mode
Electric wire connection
  check for outdoor side (dehumidifying) check
 
 
 
 
Compressor & motor
  detail check
 
  PCB assembly check
 
 
Insulation resistance
Coil resistance
  Capacitor capacity Check:
  Compressor OLP Temperature sensing circuit
  Relay output
 
 
 
 
35
 
Air Conditioner Service Manual

10.4 Vane does not operate at all. 


 
 
  Vane bending, structures
  interference check
 
 
  Connector check
  (Broken/short circuit/mal-
  connection)
 
 
 
Vane motor check Replace the vane motor
 
 
 
  PCB assembly check(vane
motor driving circuit) Replace the PCB
 
 
 
10.5 Cooling/heating conversion is disable.
 
  Heating operation ON by remote
  controller
 
 
Connector check
 
 
  PCB assembly
If the 4-way valve is ON, "tick" h k
 
sounds.
 
 
  4-way valve connection check
  outdoor unit connecting wire check
 
 
  Check the voltage of 4-way valve
  coil
 
 
4-way valve coil resistance check
 
 
 

 
36

You might also like