Installation Operating & Maintenance Manual: Rooftop Flexy™
Installation Operating & Maintenance Manual: Rooftop Flexy™
Installation Operating & Maintenance Manual: Rooftop Flexy™
OPERATING &
MAINTENANCE MANUAL
ROOFTOP
FLEXY™
English
August 2003
INSTALLATION
OPERATION
MAINTENANCE MANUAL
Ref. FLEXY_IOM/0803-E
FXA 25 - FXA 30 - FXA 35 - FXA 40 - FXA 55 - FXA 70 - FXA 85 - FXA 100 - FXA 110 - FXA 140 - FXA 170
FXK 25 - FXK 30 - FXK 35 - FXK 40 - FXK 55 - FXK 70 - FXK 85 - FXK 100 - FXK 110 - FXK 140 - FXK 170
The technical information and specifications contained in this manual are for reference only. The manufacturer reserves the right to modify these without
warning and without obligation to modify equipment already sold.
CONTENTS
INSTALLATION
TRANSPORT - HANDLING .............................................................................................. 4
INSTALLATION ............................................................................................................... 12
INSTALLATION ON A ROOF MOUNTING FRAME ........................................................... 13
INSTALLATION ON POSTS ............................................................................................ 15
COMMISSIONING ........................................................................................................... 16
OPERATION
VENTILATION ................................................................................................................. 21
AIR FLOW BALANCING .................................................................................................. 23
FILTERS ......................................................................................................................... 39
FANSTART OPERATION ................................................................................................. 40
FX AIR FLOW BALANCING ............................................................................................. 41
HOT WATER COILS ....................................................................................................... 44
GAS BURNERS .............................................................................................................. 45
CONTROL FUNCTIONS
USING THE KP 17 COMFORT DISPLAY ........................................................................ 57
USING THE KP02 MAINTENANCE DISPLAY ................................................................. 58
USING THE KP07 REMOTE GRAPHICAL DISPLAY ...................................................... 72
BMS CONTACTS KIT ...................................................................................................... 81
CLIMATIC™ PARAMETERS ............................................................................................ 82
CONTROL INTERFACE CLIMALINK/CLIMALOOK ......................................................... 88
WIRING DIAGRAMS
ELECTRICAL WIRING DIAGRAMS LIST OF ITEMS ....................................................... 96
ELECTRICAL WIRING DIAGRAMS .............................................................................. 100
TROUBLESHOOTING
SAFETY AND ERROR CODES ..................................................................................... 117
MAINTENANCE DIAGNOSTIC ..................................................................................... 123
MAINTENANCE PLAN .................................................................................................. 126
WARRANTY .................................................................................................................. 129
CERTIFICATES
ISO 9001 CERTIFICATION ........................................................................................... 130
PED CERTIFICATION OF CONFORMITY ..................................................................... 131
GLAS WOOL FIRE CLASS ........................................................................................... 132
33 KW GAS BURNER CE CERTIFICATION OF CONFORMITY ................................... 133
60 KW GAS BURNER CE CERTIFICATION OF CONFORMITY ................................... 134
120 KW GAS BURNER CE CERTIFICATION OF CONFORMITY ................................. 135
180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ................................. 136
INSULATION FIRE CLASS ........................................................................................... 137
IMPORTANT NOTICE
All work on the unit must be carried out by a qualified and authorised employee.
Non-compliance with the following instructions may result in injury or serious accidents.
Replacing components:
• In order to maintain CE marking compliance, replacement of components shall be carried
out using spare parts, or using parts approved by Lennox.
• Only the coolant shown on the manufacturer's nameplate shall be used, to the exclusion of
all other products (mix of coolants, hydrocarbons, etc.).
CAUTION:
In the event of fire, refrigerating circuits can cause an explosion and spray coolant gas and oil.
RATING PLATE
The rating plate provides a complete reference for the model
and ensures that the unit corresponds to the model ordered.
It states the electrical power consumption of the unit on start-
up, its rated power and its supply voltage. The supply voltage Figure 2
must not deviate beyond +10/-15 %. The start-up power is
the maximum value likely to be achieved for the specified
operational voltage. The customer must have a suitable
CONDENSATE DRAINS
electrical supply. It is therefore important to check whether
the supply voltage stated on the unit's rating plate is The condensate drains are not assembled when delivered
compatible with that of the mains electrical supply. The rating and are stored
plate also states the year of manufacture as well as the type in the electrical panel with their clamping collars.
of refrigerant used and the required charge for each To assemble them, insert them
compressor circuit. on the condensate tray outlets
and use a screwdriver to
tighten the collars (figure 3).
Figure 3
Figure 1
LENGTH (mm)
HEIGHT (mm)
WIDTH (mm)
HOOD (mm)
WEIGHT (kg) SLING
Condensation Airflow configuration std std high
Standard Centrifugal 1 2 3 4 5 6 7 8 gas gas 1 2 3
FC/FH 060 - Cooling only and heat pump
X - X - - - - - - X 2825 2255 1470 630 1060 - - 2210 - -
X - - - - X - - X - 2825 2255 1470 630 1090 - - 2210 - -
X - - X X - X X - - 2825 2285 1470 630 1090 - - 2210 - -
- X X - - - - - - X 2875 2255 2070 630 1230 - - 2590 1855 -
- X - - - X - - X - 2875 2255 2070 630 1260 - - 2590 1855 -
- X - X X - X X - - 2875 2285 2070 630 1260 - - 2590 1855 -
FG 060 - GAS
X - X - - - - - - X 2825 2255 1470 630 - 1210 1280 2210 - -
- X X - - - - - - X 2875 2255 2070 630 - 1380 1450 2590 1855 -
FC/FH 070 - Cooling only and heat pump
X - X - - - - - - X 2825 2255 1470 630 1075 - - 2210 - -
X - - - - X - - X - 2825 2255 1470 630 1100 - - 2210 - -
X - - X X - X X - - 2825 2285 1470 630 1100 - - 2210 - -
- X X - - - - - - X 2875 2255 2070 630 1245 - - 2590 1855 -
- X - - - X - - X - 2875 2255 2070 630 1270 - - 2590 1855 -
- X - X X - X X - - 2875 2285 2070 630 1270 - - 2590 1855 -
FC/FH 070 - GAS
X - X - - - - - - X 2825 2255 1470 630 - 1230 1300 2210 - -
- X X - - - - - - X 2875 2255 2070 630 - 1400 1470 2590 1855 -
FC/FH 085 - Cooling only and heat pump
X - X - - - - - - X 3785 2255 1495 630 1220 - - 2830 2330 -
X - - - - X - - X - 3785 2255 1495 630 1270 - - 2830 2330 -
X - - X X - X X - - 3785 2285 1495 630 1275 - - 2830 2330 -
- X X - - - - - - X 3835 2255 2080 630 1435 - - 3230 2430 1870
- X - - - X - - X - 3835 2255 2080 630 1485 - - 3230 2430 1870
- X - X X - X X - - 3835 2285 2080 630 1490 - - 3230 2430 1870
FC/FH 085 - GAS
X - X - - - - - - X 3785 2255 1495 630 - 1320 1390 2830 2330 -
- X X - - - - - - X 3835 2255 2080 630 - 1535 1605 3230 2430 1870
FC/FH 100 - Cooling only and heat pump
X - X - - - - - - X 3785 2255 1495 630 1280 - - 2830 2330 -
X - - - - X - - X - 3785 2255 1495 630 1320 - - 2830 2330 -
X - - X X - X X - - 3785 2285 1495 630 1320 - - 2830 2330 -
- X X - - - - - - X 3835 2255 2080 630 1495 - - 3230 2430 1870
- X - - - X - - X - 3835 2255 2080 630 1545 - - 3230 2430 1870
- X - X X - X X - - 3835 2285 2080 630 1545 - - 3230 2430 1870
FC/FH 100 - GAS
X - X - - - - - - X 3785 2255 1495 630 - 1380 1450 2830 2330 -
- X X - - - - - - X 3835 2255 2080 630 - 1595 1665 3230 2430 1870
CASQUETTE (mm)
LENGTH (mm)
HEIGHT (mm)
WIDTH (mm)
WEIGHT (kg) SLING
Condensation Airflow configuration std std high
Standard Centrifugal 1 2 3 4 5 6 7 8 gas gas 1 2 3
FC/FH 120 - Cooling only and heat pump
X - X - - - - - - X 3585 2255 1470 630 1530 - - 2700 - 2080
X - - - - X - - X - 3585 2255 1470 630 1580 - - 2700 - 2080
X - - X X - X X - - 3585 2285 1470 630 1600 - - 2700 - 2080
- X X - - - - - - X 3635 2255 1930 630 1805 - - 3000 2410 1880
- X - - - X - - X - 3635 2255 1930 630 1855 - - 3000 2410 1880
- X - X X - X X - - 3635 2285 1930 630 1875 - - 3000 2410 1880
FG 120 - GAS
X - X - - - - - - X 4035 2255 1470 630 - 1840 1890 3000 - 2310
- X X - - - - - - X 4085 2255 1930 630 - 2115 2165 3300 2700 2080
FC/FH 140 - Cooling only and heat pump
X - X - - - - - - X 3585 2255 1470 630 1630 - - 2700 - 2080
X - - - - X - - X - 3585 2255 1470 630 1680 - - 2700 - 2080
X - - X X - X X - - 3585 2285 1470 630 1700 - - 2700 - 2080
- X X - - - - - - X 3635 2255 1930 630 1905 - - 3000 2410 1880
- X - - - X - - X - 3635 2255 1930 630 1955 - - 3000 2410 1880
- X - X X - X X - - 3635 2285 1930 630 1975 - - 3000 2410 1880
FG 140 - GAS
X - X - - - - - - X 4035 2255 1470 630 - 1920 1970 3000 - 2310
- X X - - - - - - X 4085 2255 1930 630 - 2000 2050 3300 2700 2080
FC/FH 160 - Cooling only and heat pump
X - X - - - - - - X 3595 2255 2070 900 2050 - - 2700 - 2090
X - - - - X - - X - 3595 2255 2070 900 2120 - - 2700 - 2090
X - - X X - X X - - 3595 2285 2070 900 2140 - - 2700 - 2090
- X X - - - - - - X 3645 2255 2070 900 2275 - - 2700 - 2090
- X - - - X - - X - 3645 2255 2070 900 2345 - - 2700 - 2090
- X - X X - X X - - 3645 2285 2070 900 2365 - - 2700 - 2090
FG 160 - GAS
X - X - - - - - - X 4045 2255 2070 900 - 2410 2460 3000 - 2320
- X X - - - - - - X 4095 2255 2070 900 - 2635 2685 3000 - 2320
FC/FH 190 - Cooling only and heat pump
X - X - - - - - - X 3595 2255 2070 900 2175 - - 2700 - 2090
X - - - - X - - X - 3595 2255 2070 900 2245 - - 2700 - 2090
X - - X X - X X - - 3595 2285 2070 900 2265 - - 2700 - 2090
- X X - - - - - - X 3645 2255 2070 900 2400 - - 2700 - 2090
- X - - - X - - X - 3645 2255 2070 900 2470 - - 2700 - 2090
- X - X X - X X - - 3645 2285 2070 900 2490 - - 2700 - 2090
FG 190 - GAS
X - X - - - - - - X 4045 2255 2070 900 - 2540 2600 3000 - 2320
- X X - - - - - - X 4095 2255 2070 900 - 2765 2825 3000 - 2320
HANDLING
The equipment can be moved using the lifting holes on the Some units can only be supported by four slings at right-
top of the unit. angles. Others require different lengths (see figures 4).
The "sling" length is the value that we recommend for safe It is essential that all lifting holes are used and that the slings
handling of the equipment. are all of the same size to avoid damaging the equipment.
FG... 120 & 140 with gas burner and centrifugal fans
FX 25 & 30
2
Sling length 1 = 3000 mm
Sling length 2 = 2350 mm
1
FX 35 - 40 - 55
FX 70 - 85 - 100
1
Sling length 1 = 3900 mm
Sling length 2 = 3000 mm 2
2
Sling length 1 = 4300 mm
Sling length 2 = 3250 mm 1
Figure 5
MODELS A B C D
FC/FH/FG/FD
60 ! 140 1400 2000 1400 2300
160 & 190 2000 2000 2000 2300
FX
25 & 30 * 1100 * 1700
35 ! 55 * 1300 * 2300
70 ! 100 * 1700 * 2300
110 ! 170 * 2000 * 2300
* : according to connection
Figure 6
2
Figure 7
After levelling the frame, fix the surface flaps onto the
trimmer.
Figure 8
1
Figure 9
1
Assembly joint (1 - figure 10)
Figure 10
Before installing the equipment, make sure that the assembly seal is not damaged.
Once in position, the bottom of the equipment must be horizontal and against the roofcurb as shown on figure 11.
Figure 11
The unit can be fitted on corner posts using the frame provided. The minimum height of the posts should be 400mm.
Figure 12
At this point attach the manometers to the refrigerant circuit 1 Liquid crystal display
2 Raise/lower keys
Powering up the system with the unit isolating 3 "FILTER" Led (flashing red)
4 "ADDRESS" key
switch
5 "MODE" key
- Close the blower circuit breaker and the 24V control. 6 "VALUE" key
- Power up the unit by closing the isolator switch. At this 7 "UNIT RUNNING" led
point the blower should start unless the CLIMATIC™ 8 "MODE" led
does not energise the contactor. In this particular case 9 "GENERAL ALARM" led.
the blower can be forced by bridging the COM and NO
wires on the connector J1 on the CLIMATIC controller.
Once the fan is running check the rotation direction.
Refer to the rotation arrow on the fan. - The jumpers are
- The fan and other components direction of rotation is factory set and the
checked during an end of line test. They should configuration switches
therefore all turn in the same direction. are adjusted
- If they run in the opposite direction, disconnect the depending on the
power supply to the machine at the building's mains option selection and
switch, reverse two phases of the incoming supply to the the type of unit.
machine and try again.
Figure 14
Figure 15
Using CLIMATIC™
- Check the voltages recorded against the rated values, in
particular on the system supply fans.
- If the readings on the fans are outside the limits, this
indicates excessive air flow which will affect the
thermodynamic performance. Refer to the "Air flow
balancing" section.
Figure 16
Defrost cycle end value indicating the nr of Start-ups of the Linea set to1
C79
condenser fan to signify the end of defrost Flexy set to 3
C101 Activation of all seasons control option [ON] / [OFF] if fitted
All seasons control option on FLEXY -
Set to 20.0°C for Linea
C73 Otherwise – unloading 50% of the compressors in cooling
Set to 12°C for Flexy
mode
C90 Choice of operating mode for KP17 [ON] = KP17 in ON / OFF mode
C91 Identification number for the J-Bus connections
Identification number for the connections link between
C93
boards
C94 Number of boards linked on the bus
C95 Selection of the operating mode for KP017
Selection of exchange mode for room temperature and
C96
humidity-
Selection of exchange mode for outdoor temperature and
C97
humidity
C100 Activation of the dual-speed option for fan supply (Flexy)
C101 Activation of the all seasons control option
Switches on KP01
1= on ....................... Option : pressure pick-up on air 500 pa (on FLEXY™ off = sensor 1000 pa)
2= on | 3 = off ................... Option : hot water coil
2= off | 3 = on ................... Option : electrical heater
2= on | 3 = on ................... Option : gas burner
4= on ....................... Option : cycle reversing valve, compressors (heat pump)
5= on ....................... Option : heating of great power / or / pump (except freezing of the hot water coil)
6= on ....................... Option : fresh air, economiser
7= on ....................... Option : fresh air, all fresh air
8= on ....................... Option : KP02 / KP17
(5) AIRFLOW PRESS. SENSOR CHECK / VERIF. DES SECURITES PRESSOSTATS D’AIR
Set Points Adjusted / Changement des consignes:
Measured pressure drop / Pertes de charge au pressostat Yes/Oui No/ Non
…………………………… mbar If Yes enter new values/ Si oui noter les nouvelles consignes:
3410: ………… 3411: ………… 3412: …………
Comments.....................................................................................................................................................................................
.......................................................................................................................................................................................................
.......................................................................................................................................................................................................
BELT TENSION
On delivery, the drive belts are new and correctly tensioned. After the first 50 operating
hours check and adjust the tension. 80% of the total elongation of belts is generally
produced during the first 15 hours of operation.
Before adjusting the tension, make sure that the pulleys are correctly aligned.
To tension the belt, set the height of motor support plate by moving the plate
adjustment screws.
Check that according to the diagram below (figure 18), the following ratio remains
the same. P (mm) Figure 17
= 20
A (m)
Replacement belts must have the same rated size as the ones they are replacing.
If a transmission system has several belts, they must all be from the same A P
manufacturing batch (compare serial numbers).
NOTE :
An under-tensioned belt will slip, heat and wear prematurely. On the other hand, if
a belt is over-tensioned, the pressure on the bearings will cause them to over-heat
and wear prematurely. Incorrect alignment will also cause the belts to wear
Figure 18
prematurely.
Screw in fully. The hub and the pulley will separate from each
other.
Figure 19
Remove the hub and the pulley by hand without damaging
the machine.
Pulleys alignment
After adjusting one or both of the pulleys, check the
transmission alignment using a ruler placed on the inner face
of the two pulleys.
The actual resistance of ductwork systems is not always identical to the calculated theoretical values. To rectify this, it may be
necessary to modify the pulley and belt setting. To this effect, the motors are fitted with variable pulleys.
If the absorbed amps are lower than the rated values, your system has a higher pressure drop than anticipated. Increase the
flow by increasing the rpm. At the same time you will increase the absorbed power which may result in having to increase the
motor size.
To carry out the adjustment and to avoid a time-consuming re-start, stop the machine and if necessary lock the main switch.
First unscrew the 4 Allen screw(s) on the pulley (see figure 23).
nr of
Min Ø turns
Pulley Pulley Max Ø Actual Ø (DM) or distance between faces for a given
/ from fully
type external / number of turns from fully closed with SPA belt in (mm)
Min dist. closed to
Ø Max dist. fully
open 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5,0 5,5
8450 / 95 116 5 113,9 111,8 109,7 107,6 105,5 103,4 101,3 99,2 97,1 95,0 -
120
D8450 20,2 28,0 5 21,0 21,8 22,5 23,3 24,1 24,9 25,7 26,4 27,2 28,0 -
8550 / 110 131 5 128,9 126,8 124,7 122,6 120,5 118,4 116,3 114,2 112,1 110,0
136
D8550 20,6 31,2 5 21,6 22,7 23,8 24,8 25,9 26,9 28,0 29,1 30,1 31,2 -
8670 145 166 5 163,9 161,8 159,7 157,6 155,5 153,4 151,3 149,2 147,1 145,0 -
171
D8670 20,5 31,1 5 21,5 22,7 23,8 24,8 25,7 26,9 27,9 29,0 30,0 31,1 -
Figure 22
2nd method when adjusting the pulley : CHECKING AIRFLOW AND ESP
- Close the pulley fully and count the number of turns
Using the fan curves on page 25, 26, 27, the airflow, the total
from fully closed position. Using table 1 determine the
pressure available (PTOT) and the corresponding dynamic
motor pulley actual diameter.
pressure (Pd) can now be estimated, for a specific operating
- Record the fix fan pulley diameter.(DF) point;
- Determine the fan speed using the following formula:
The next step consist in estimating the pressure losses across
the unit.
rpm FAN = rpm MOTOR x DM / DF
This can be achieved using the "dirty filter pressure sensor"
and the accessories pressure drop table:
Where : Also the pressure drop due to the duct inlet into the roof-top
rpm MOTOR : ....... from the motor plate or table 2 unit can be taken as 20 to 30 Pa.
DM : ...................... from table 1
DF: ........................ from machine ∆P = ∆P filter + coil + P Inlet + ∆P Options
INT
Once the pulleys are adjusted and the belt checked and
tensioned, start the fan motor and record the Amps and using the results from above, the external static pressure (ESP)
Voltage between the phases : can then be estimated:
Using the measured data and table 2
- Theoretical mechanical power at the fan shaft :
ESP = PTOT - Pd - ∆PINT
Pmeca fan = V x I x √3 x cosϕ x η meca motor x η Transmission 0,75 kW 1400 rpm 0,77 0,70
1,1 kW 1425 rpm 0,82 0,77
This formula can be approximated in this way 1,5 kW 1430 rpm 0,81 0,75
2,2 kW 1430 rpm 0,81 0,76
Pmeca fan = V x I x 1.73 x 0.85 x 0.76 x 0.9 3,0 kW 1425 rpm 0,78 0,77
4 kW 1425 rpm 0,79 0,80
With the fan "rpm" and the mechanical power at the fan shaft 5,5 kW 1430 rpm 0,82 0,82
an operating point and the supplied airflow can be estimated
using the fan curves.
Table 5.52
Economiser EU7 Hot water coil Electric heater Roofcurb Horizontal Gaz
100% open Filter S H S H Base frame Roofcurb H
SIZE Air flow (m3/h) (Pa) (Pa) (Pa) (Pa) (Pa) (Pa) (Pa) (Pa) (Pa)
Min. 10 000 4 67 12 14 5 8 10 41 22
60 Nom. 12 000 6 93 16 19 8 8 11 59 26
Max. 15 000 9 135 24 28 8 10 13 92 31
Min. 12 000 6 56 6 12 5 5 13 59 29
70 Nom. 14 000 8 73 8 16 5 5 16 80 34
Max. 18 000 12 113 13 25 8 8 22 132 47
Min. 14 000 8 73 8 16 5 8 18 44 7
85 Nom. 16 000 10 113 13 25 8 8 26 57 10
Max. 22 000 16 159 18 36 8 10 32 109 12
Min. 16 000 10 93 10 20 8 10 26 57 10
100 Nom. 20 000 14 135 15 30 10 13 32 90 12
Max. 22 000 16 159 18 36 13 15 38 109 15
Min. 18 000 12 113 13 25 10 13 32 33 29
120 Nom. 22 000 16 159 18 36 13 15 38 49 35
Max. 24 000 18 184 21 41 15 18 44 58 40
Min. 20 000 14 135 15 30 10 15 35 40 31
140 Nom. 24 000 18 184 21 41 15 18 46 58 40
Max. 25 000 19 197 22 44 15 20 50 63 43
Min. 22 000 16 87 9 18 8 8 24 49 45
160 Nom. 28 000 22 132 13 27 8 10 30 79 56
Max. 32 000 26 165 17 34 13 13 34 103 64
Min. 24 000 18 101 10 20 10 10 34 58 64
190 Nom. 33 000 27 174 18 36 13 13 41 109 77
Max. 36 000 30 201 21 41 13 15 48 130 89
EXAMPLE
The unit used for this example is a FHK 060N with standard supply and return airflow configuration. It is also fitted with an
economiser and an electric heater type H.
It is fitted with a AT 18-18 fan which curve is shown on page xxx and a 2.2 kW motor.
- Motor rpm : 1430 rpm
- cos ϕ = 0.81
- Voltage = 400 V
- Current = 4,68A
Pmech fan = V x I x √ 3 x cosϕ
ϕ x ηmech motor x ηTransmission
= 400 x 4.68 x √ 3 x 0.81 x 0.76 x 0.9 = 1,79 kW
The unit is also fitted with a transmission kit 1
- Fixed Fan pulley : 250 mm
- Motor adjustable pulley type "8450" opened 1 turn from fully closed or measured distance between pulley end plates is
21,8 mm: from table xxx it can be determined that the motor pulley has a diameter of 111,8 mm
rpm FAN = rpm MOTOR x DM / DF = 1430 x 118,2 / 250 = 640 rpm
Using the fan curve below the operating point can be located.
It can be determined that the fan is providing approximately 12 000 m3/h with a total pressure PTOT = 420 Pa
AT 18-18
420
∆P = 105 + 6 + 8 = 119 Pa
640
The dynamic pressure at 1200m3/h is
given at the bottom of the fan curve
Pd = 100 Pa
Hd (mmH2O)
12
10
Figure 24
IOM / ROOF-TOP FLEXY™ Series - Page 25
Downloaded from www.Manualslib.com manuals search engine
AIRFLOW BALANCING
AT 12-12 FAN
AT 15-15 FAN
AT 18-13
AT 18-18 FAN
1 - 004 error code (lit LED “filter”) or the following icon (for a KP 17 DISPLAY
FILTER REPLACEMENT :
After opening the filter access panel, unscrew the butterfly
nuts maintaining the filter support and remove it (figure 33).
Figure 33 Figure 34
Current
Over-current limit
Air sock
Inflation
5 to 30s Acceleration 15 to 30s FANSTART off
FAN START
OFF MOTOR OFF MOTOR OFF
Figure 35 Green LED = 0 Green LED = 1
Red LED = 0 Red LED = 1
The motor speed control is achieve through a variation of the
supply voltage of each phase at constant frequency.
Power + Control ON Control ON
The thermal overload limit on the motor imposes a current Green LED = 1 Power OFF
limitation during the acceleration stage. Hence if the selected Red LED = 0
slope is to steep, a predefined current limit can be reached T°C Fault
(potentiometer adjustment) and the controller will automatically Thyristor
reduce the voltage set-point accordingly. Then once the current PHASE
is back under the high current limit it carries on with the start ROTATION NOT OK
up cycle. CHECK
OK
Safety
INFLATION I > I max
Excessive "slow down" limit Green LED = 1 Speed = 0
Red LED = 0 T > 1 min20s
The FANSTART will display a fault (red LED) and stop the I < Imin
motor, if the motor slows down excessively (voltage could
reach 0V) because of the current limitation during the
acceleration stage. ACCELERATION I > I max
Green LED = 1 Speed = 0
Red LED = 0 T > 1 min20s
Missing phase safety (If current control ON) I < Imin
The FANSTART will display a fault (red LED) if the current in
the third phase is too low or reaches 0 Amps (Three phase
supply or motor problem) CONTROL OFF
motor connected
to mains
Figure 37
1 2 3 4 5
Figure 25
- Adjust the extraction grid to reach a pressure in 4 equal to the pressure in 2 (ex : reach -210 Pa when closing).
- Check the Amps absorbed by the extraction fan motor; It must be lower than the value on the plate otherwise reduce the
fan speed.
- Reverse the fresh air percentage: 100 % fresh air at the treatment.
- Measure the Static pressure at the same 5 points
1b : "Treatment " Fan Inlet (ex : -80 Pa)
2b : "Treatment" expansion box (ex : -50 Pa)
3b : Return air box (ex : -200 Pa)
4b : Extraction expansion box (ex : -220 Pa)
5b : Extraction fan inlet (ex : -250 Pa)
- Adjust the grid on the "treatment" side only to reach a pressure at point 2b identical to the pressure at 2a (reach -210 Pa
when closing)
- Check that the pressure measured in the extraction expansion box 5b has not changed too much compared with the
previous measurement 5a. Adjust the bypass grid to compensate any possible difference.
Figure 26
Figure 27 Figure 28
PRINCIPLE SKETCHES
Grid on damper
RETURN
air duct
Figure 29
Grid on damper
By pass
2 500 m3/h grid
10 000 m3/h 2 500 m3/h 12 500 m3/h
10 000 m3/h
SUPPLY Treatment 10 000 m3/h EXTRACTION
air duct fan Extraction air duct
fan
RETURN
air duct
Figure 30
2 500 m3/h
10 000 m3/h 12 500 m3/h
By pass grid
SUPPLY
EXTRACTION
air duct Treatment
Extraction air duct
fan
fan
RETURN
air duct
Figure 31
Figure 37
The antifreeze must protect the unit and avoid icing under
winter conditions.
Warning : monoethylene glycol-based antifreeze may
produce corrosive agents when mixed with air.
You must ensure that the manual or automatic air vents have
been installed on all high points in the system. In order to
drain the system check that all the drain cocks have been
installed on all low points of the system.
To drain, open all the valves and remember to place the
unit in air.
Figure 38
Page 44 - IOM / ROOF-TOP FLEXY™ Series
Downloaded from www.Manualslib.com manuals search engine
GAS BURNER
1. PRELIMINARY CHECKS AND VERIFI- GN 300 mbar option with pressure regulator :
Check the pressure at the regulator inlet.
CATIONS BEFORE START-UP
Propane 37 mbar option :
NOTE :
Check the pressure at the inlet of the HONEYWELL valve.
ANY WORK ON THE GAS SYSTEM MUST BE
CARRIED OUT BY QUALIFIED PERSONNEL.
Propane 148 mbar option with pressure regulation
THIS UNIT MUST BE INSTALLED IN
(yellow spring) :
ACCORDANCE WITH LOCAL SAFETY CODES
Check the pressure at the regulator inlet. A 10% tolerance
AND REGULATIONS AND CAN ONLY BE USED IN
around the nominal pressure is acceptable.
WELL VENTILLATED AREA.
PLEASE READ CAREFULLY THE
MANUFACTURER'S INSTRUCTIONS BEFORE
STARTING A UNIT. 1.5 Probes and electrodes position check
BEFORE COMMISSIONING A UNIT WITH GAZ
BURNER, IT IS MANDATORY TO ENSURE THAT
THE GAZ DISTRIBUTION SYSTEM (type of gas, INCORRECT
available pressure…) IS COMPATIBLE WITH THE
ADJUSTMENT AND SETTINGS OF THE UNIT.
1.4 Pipe-work purging and gas static pressure Check that the end of the ignition electrode is aligned with the
checks side of the inshot burner.
Standard GN 20 mbar :
Check the pressure at the
inlet of the HONEYWELL
valve.
Figure 41
RESET
button
Figure 44
3.2 Set up
- Set the setpoint 59 and 60 to "ON". This will priorities the gas burner.
- Increase the set temperature "1" (room set point temperature) to a temperature higher than the room temperature.
Time in seconds 1 2 3 4 5 6 7 8 9 1 1 2 3 3 3 3 3 3 3 3 33 4 4 4 4 4 4 4 3 3 4 4
0 1 9 0 1 2 3 4 5 6 7 89 0 1 2 3 4 5 6 9 9 0 0
Operations 8 9 0 1
Control operation sequence
Extraction fan
30 to 45 seconds pre-Ventilation
If incorrect sequence refer to the fault analysis table to identify the problem.
- The burner must be run in high heat mode for this check.
- Fit the tube of the "accurate" manometer on the IN pressure port of
the HONEYWELL Block after having loosened the screw by two
turns
Figure 45
Figure 46
Figure 48
Figure 47
Connector x14
- Carefully disconnect the wire numbered 116 for the bottom gas
burner and the wire numbered 126 for the tops gas burner.
- Check and adjust if necessary the OUT pressure to 3,5 mbar (G20)
or 14 mbar for propane (G31).
Figure 49
3.7 Reconnect the wires 116-126
Figure 50 Figure 51
IOM / ROOF-TOP FLEXY™ Series - Page 47
Downloaded from www.Manualslib.com manuals search engine
GAS BURNER
3.8 Rating table for type of gas and corresponding adjusmtent pressure
Type of Gas Category Supply pressure Low heat injection High heat injection
adjustment pressure pressure
Honeywell Valve adjustment adjustment
- With the gas burner running, disconnect the flexible tube fitted to the pressure
taping on the smoke box (figure 53).
- The Flame must disappear and the fan must carry on running.
- However, NO fault will be displayed (HONEYWELL control block or
CLIMATIC™).
- After reconnecting of the tube, the burner will restart after 30 seconds of pre-
ventilation.
Figure 52
- With the gas burner running, close the internal shut off valve in the rooftop.
- The burner stops completely.
- However, No fault light will be displayed on the Honeywell Control box.
- After 6 Minutes, the CLIMATIC 2 will display fault 14 or 15.
- Reset the CLIMATIC™ 2.
Figure 53
- With the gas burner running, disconnect the RAJAH terminal plug.
- The flame disappears
- The fan is still running and attempting to restart the burner (restart cycle 45
seconds).
- At the end of the restart cycle the burner stops completely.
- The fault light on the HONEYWELL Block is ON.
- Manually reset the HONEYWELL controller to eliminate the fault. (Refer to
§2).
Figure 54
Figure 55
Figure 56 Figure 57
- Electrically disconnect the fan and remove the screws holding it in place.
- Take care not to loose any cage nuts in the smoke bos.
- Attention : check the correct position of the pressure tube used by the
extraction pressure switch.
Figure 58
Figure 59
YES
Extraction Fan ON
YES
Pre-ventilation 30 to 45 seconds
Gas control
Fire-up Electrode 4s
Valve closes
BURNER
STOPS
Gas valve open
Gas control
Valve closes
Ionisation 1 second after
NO BURNER STOPS
the end of sparking ?
Fault on Gas
control block
YES
YES
NO
Page 50 - IOM / ROOF-TOP FLEXY™ Series
Downloaded from www.Manualslib.com manuals search engine
GAS BURNERS
Figure 61
Figure 60
NORMAL
STAGES FAULT ACTIONS SOLUTIONS
OPERATION
Heating Contactors Contactors do • Check safety thermostats B29- • Replace component
requested KM21-22 not engage 30 in the air duct before the gas
engaged heat exchanger
Continuous After 2 seconds After 4 second • Check injection pressure during • Remove the air from the
ventilation with the gas burner the GAS Burner start-up (value for high heat) pipe-work
sparks created fires-up still not running • Check the supply voltage to the • Adjust the injection
by electrode and Safety control box (continuous voltage). pressure to high heat
shutdown by Refer to figure 61. value
the Honeywell • Remove the control box from the • Change the control box
Block. gas block. Check using an if the GAS valve is OK.
ohmmeter the solenoid coil of • Change the gas valve
the GAS block (4 kOhm). Refer control
to figure 62
6.2 Maintenance
- Vacuum cleaner
- Paint brush / nylon brush diameter 50
9. REGULAR MAINTENANCE
9.1 Preliminary safety recommendations
Figure 63
2
3
Figure 64
2
3
Figure 65
The CLIMATIC™ 'Comfort' control Display allows an untrained KP17 COMFORT CONTROL DISPLAY
person to easily operate a Lennox Roof-Top.
This display connects to a single Rooftop and, through the
WIRING
use of the control keys, LED's and display the user can see
how the connected Rooftop is operating, wether there are any Failure to install the Comfort control display with the
faults, modify the comfort setpoint and override the Rooftop recommended cable may cause the display to malfunction.
operation. The KP17 remote must be connected to the CLIMATIC™
If installed correctly the CLIMATIC™ "Comfort" control display using a 4 x 0.5 mm2 braid-screened cable.
can be installed up to 1000 m away from the Rooftop unit. This connection is provided through a remote interface card
which is located within the Control panel section.
DISPLAY (1 - figure 66) Refer to the wiring section of this manual.
This display unit allows you to read and modify all the values The dialogue with the controller is initiated by the CLIMATIC™.
of the variables or setpoints of the rooftop to which it is If, after 3 attempts, no communication is established, a
connected. message will be displayed signalling the problem. The unit
will then try to re-connect at regular intervals.
NOTE : If your ROOFTOP already has a KP17 Comfort display
connected (see previous section) simply disconnect it and
connect this panel to the same location, once completed re-
connect the KP17. It is not necessary to switch off the power
to the CLIMATIC™ whilst the KP02/KP17 is being changed.
CALLOUT :
1 LIQUID CRYSTAL DISPLAY
2 RAISE/LOWER KEYS
3 "FILTER" LED (flashing red)
4 "ADDRESS" KEY
5 "MODE" KEY
6 "VALUE" KEY
7 "UNIT RUNNING" LED
8 "MODE" LED
9 "GENERAL ALARM" LED.
Figure 67
1 - DISPLAY FORMATS
Hour
Default display. If the display unit has been inactive for 5 minutes, this screen will automatically be displayed.
Date
Digital Values
Temperatures
Temperatures are displayed in °C, to an accuracy of 0.1 °C
Pressures
Pressure is given in bars, to an accuracy of 0.1 bar.
Specific Displays
Software Version
When the unit is powered up, the KP02 software version number is displayed.
Display Test
The display can only be tested for correct operation when the unit is powered up and by pressing on the 3 keys "A", "M"
and "-" simultaneously. If the display is working correctly, the following will be displayed :
Communication Error
If there is no communication between the KP02 display unit and the CPU card, the following message is displayed :
NOTE : The compatibility of the value for the day of the month
is not checked when it is entered. You might therefore enter
February 31st but when you try to validate, it will be ignored
and the preceding value stored.
[Mode] Hour, Start of mode - (active for the modes Week-End, Night,
C 010 0h #h 22 h
Morning, Midday, Evening)
[Mode] Day of the week, End of mode - (active for the Week-End
C 012 1 # 7
mode)
C 030 [Command] Force the low speed on fan blower supply Off Off On
[Command] Force the fresh air damper in the closed position - (0%
C 031 Off Off On
fresh air)
[Command] Force the fresh air damper to its defined minimum set
C 032 Off Off On
point position.
[Command] Force fresh air damper in the fully open position - (100%
C 033 Off Off On
fresh air)
[Limit safety] Room absolute humidity low limit (in g/kg) - Threshold of
C 042 0.0 g/kg 0.0 g/kg 30.0 g/kg
activation of the safety cut-out
[Limit safety] Room absolute humidity high limit (in g/kg) - Threshold
C 044 0.0 g/kg 30.0 g/kg 30.0 g/kg
of activation of the safety cut-out
[Anticipation function] Bottom of slope (in °c) - Limit of activation of
C 045 the function - This allows an anticipated start-up in the morning mode 0.0 c 10.0 c 20.0 c
depending on the outside temperature.
[Anticipation function] Slope - Number of minutes of anticipation per
C 046 degrees. This allows an anticipated start-up in the morning mode 0 0 100
depending on the outside temperature.
C 047 [Co²] Fresh air dampers opening threshold (in ppm) 0 ppm 1000 ppm 2000 ppm
C 048 [Co²] Fresh air dampers maximum opening limit (in ppm) 0 ppm 1500 ppm 2000 ppm
2nd Level
Mini. Factory Maxi.
[kp17] [Mode] Maximum limit for room temperature, Day mode (in °c)
C 050 21.0 c 27.0 c 35.0 c
- (active for the mode Day)
[kp17] [Mode] Minimum limit for room temperature, Day mode (in °c) -
C 051 8.0 c 17.0 c 21.0 c
(active for the mode Day)
C 052 [Room control] Minimum operation time for a stage (in seconds) 25 s 180 s 1800 s
[Safety limit] Supply temperature low limit (in °c) - Threshold of C 066
C 065 st
+ 2.0 c
8.0c / 10.0 c 19.0 c
activation of the 1 level of safety.
[Safety limit] Supply temperature low limit (in °c) - Threshold of C 067
C 066 nd
+ 2.0 c
6.0c / 8.0 c 17.0 c
activation of the 2 level of safety.
[Safety limit] Water heat exchanger output temperature high limit (in
C 081 20.0 c 45.0 c 46.0 c
°c) - Threshold of activation of the safety
[Control limit] Unloading 100% of electrical heat - Threshold of
C 082 outdoor temperature (in °c). If the outdoor temperature is higher than -20.0 c 10.0 c 30.0 c
this threshold electrical heat are switched off by the control
C 083 [Electric heat] Maximum usable power for electric heat (in %) 0% 100 % 100 %
[Electric heat] (FLEXY FX) All season control - Threshold of mixed air
C 084 temperature (in °c) - If the mixed air temperature is lower than this 0.0 c 5.0 c 10.0 c
threshold electric heat is activated
[Safety limit] Air flow detection - Threshold of pressure difference for
C 085 the loss of pressure detection (in pa) - If the pressure difference 0 pa 20 pa 1000 pa
across the filters is lower than this threshold the safety is activated.
[Safety limit] Clogged filter detection– Threshold of pressure
difference for the detection of clogging (in pa) - If the pressure
C 086 difference across the filters is higher than this threshold the safety is
0 pa 250 pa 1000 pa
activated
[Safety limit] Missing filter detection - Threshold of pressure
difference for the detection of missing filters (in pa) - If the pressure
C 087 0 pa 50 pa 1000 pa
difference across the filter is lower than this threshold the safety is
activated
C 088 [kp12-2] Time delay for the closing of contact n°3 (in seconds) 4s 60 s 65535 s
C 089 [kp12-2] Time delay for the opening of the contact n°2 (in seconds) 2s 300 s 65535 s
C 100 [Configuration] Activation of the dual-speed option for fan supply Off # On
C 104 [Various] Override all set points to factory settings Off Off On
CONFIGURATION
This information is taken into account by the program after having switched off/on the CLIMATIC, and a second time for C091
and C093 setpoints.
Switches on KP01
1= on ....................... Option : pressure pick-up on air 500 pa (on FLEXY™ off = sensor 1000 pa)
2= on | 3 = off ................... Option : hot water coil
2= off | 3 = on ................... Option : electrical heater
2= on | 3 = on ................... Option : gas burner
4= on ....................... Option : cycle reversing valve, compressors (heat pump)
5= on ....................... Option : heating of great power / or / pump (except freezing of the hot water coil)
6= on ....................... Option : fresh air, economiser
7= on ....................... Option : fresh air, all fresh air
8= on ....................... Option : KP02 / KP17
This display unit allows you to operate 1 to 8 machines. The 1 - SCREEN KEYS WITH VARIABLE
icon and schematic display provides a vivid and user-friendly
interface.It uses a liquid crystal monochrome display, with
FUNCTIONS (figure 68)
background lighting, consisting of 240 x 128 pixels. It has 2
LEDs and 12 keys.
The remote console must be connected to the unit using a 4 x
0.5 mm² braid-screened cable (maxi length is 1000 m ).
Plan the console electric supply in 230V/50Hz (500 mA)
On the unit, connection to the KP01 card J18 input will be
done with connection items (screws...) delivered with the
console.
ITEMS :
1 LCD SCREEN, 240x128 PIXELS, MONOCHROME,
BACKGROUND LIGHTING
2 5 KEYS FOR FIXED FUNCTIONS
3 7 "SCREEN" KEYS FOR VARIOUS FUNCTIONS
4 "ON" LED
5 "GENERAL ALARM" LED.
Figure 68
The main display unit functions are as follows :
- Control of a range of interactive screens allowing access There are 7 keys located around the LCD screen :
to all information and control data.
- Continual resetting of all dynamic parameters displayed
in the various screens.
- Recording of successive status of pre-defined variables
to create analog and event histories.
PAGE UP :
PREVIOUS SCREEN :
3 - ON (LED 4 - figure 69) To exit "MODIFICATION" mode and return to the active screen,
press the "MODIFICATION" key.
When lit, it indicates that the machine is powered up.
Note :
- During modification, the screen is no longer updated.
4 - GENERAL FAULT (voyant 5 - figure 69) - If a change is not confirmed, the variable will retain its
previous value.
This LED indicates a general fault has been detected.
CONTRAST SETTING
The display contrast can be set in "MODIFICATION" mode :
- Pressing successively on key [A] increases the contrast.
- Pressing successively on key [B] decreases the
contrast.
- Key [C] allows you to find the default contrast.
Summary
Measurements : Chart :
Temperatures Ambient temperature
Measurements : Chart :
Humidity Ambient humidity
Hourmeters :
Ventilation, customer...
Operational status :
Compressor n° 1
History :
Sécurité & défauts
Operational status :
Compressor n° 2
Hourmeters :
Compressors
Operational status :
Compressor n° 3
Hourmeters :
Operational status : Fan. Capacitors
Compressor n° 4
Hourmeters :
Electrical resistance
Hourmeters :
Humidifier
Password :
Level 1
Settings :
On/Off
Settings : Settings :
Condition ; Day On ; Ventilation
Settings : Settings :
Condition ; Weekend On ; Ventilation
Settings :
Time
Settings : Settings :
Condition ; Night On ; Ventilation
Settings:
Time
Settings : Settings :
Condition ; Morning On ; Ventilation
Settings :
Time
Settings :
Anticipation
Settings : Settings :
Condition ; Noon On ; Ventilation
Settings:
Time
Settings : Settings :
Condition ; Evening On ; Ventilation
Settings :
Time
IOM / ROOF-TOP FLEXY™ Series - Page 75
Downloaded from www.Manualslib.com manuals search engine
USING THE KP07 GRAPHIC CONTROL DISPLAY
Settings : Settings :
Condition ; BMS On ; Ventilation
Settings :
Control ; Cold
Settings :
Control ; Hot
Settings :
Control. ; Dehumidification
Settings :
Control ; Humidification
Settings :
Control ; Misc.
Settings :
Limits ; Ambient
Settings :
Remote controls
Settings :
Limits ; Outside
Settings :
Remote controls
Settings :
Limits ; Blowing
Settings :
Remote controls
Settings :
Air flow ; Filters
Password :
Level 2
Settings :
Std. order ; Ambient
Settings :
Std. order ; Blowing
INDEX OF ICONS
Keys
Increase value
Go to various notices.
Go to error history.
Go to operation hourmeters.
Enter password.
Go to control settings.
Go to safety settings.
Go to anticipation settings.
Logging on
Sensors
Temperature sensor
Humidity sensor
Pressure sensor
Supply data
Outside data
Operating conditions
Operating status
Filters
Compressor defrosting.
Errors
General alarm
/ (Start / End)
Communication interrupted between unit KP07 and a CPU board.
Limits of relays :
• 10A – 250V with resistive load
• 4A – 250V with inductive load.
FAULT RESETTING
NIGHT CONTROL
STOP CONTROL
DAY CONTROL
HUMIDIFIER FAULT
FILTER FAULT
MORNING
DEFINITION OF TIME SLOT PARAMETERS
The CLIMATIC™ allows you to programme 5 operating zones NOON
per day, in addition to an idle zone for the weekend.
Slot activation is :
EVENING
- automatically controlled by the CLIMATIC™, if you have
defined these time parameters for each slot
- forced manually by action on the controller (instructions If none of the time slots listed above is active, the active slot
02/03 and 04 for KP02). is :
- forced by the BMS contacts kit ( see this chapter). DAY
- forced by the computer connection.
A particular time slot :
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DESCRIPTION OF PARAMETERS
Parameters are defined for the time slot. Select by instruction 08 setting.
0 = DAY / 1 = WEEKEND / 2 = NIGHT / 3 = unused / 4 = MORNING / 5 =MIDDAY / 6 = EVENING / 7 = BMS.
Instruction Description
09 Day of the week of start of setting . From 1 to 7, 1 = Sunday.
10 Hour of start of setting
11 Minutes for start of setting
12 Day of the end of setting
13 Hour of end of setting
14 Minutes of end of setting
15 Setpoint in heating
16 Setpoint in air conditioning
17 Defined if the hygrometry values below are taken as absolute (ON) or relative (OFF).
18 Minimum relative humidity of ambient air (%)
19 Maximum relative humidity of ambient air (%)
20 Minimum absolute humidity of ambient air (g/kg of dry air)
21 Maximum absolute humidity of ambient air (g/kg of dry air)
22 Relative value of minimum flow of new air (%)
23 Fan operation in regulation zone *. ON OFF
24 Fan operation in neutral zone*. ON OFF
25 ON, forces low speed fan operation in the cooling zone
26 ON, forces low speed fan operation in the neutral zone*.
27 ON, forces automatic low speed operation in heating zone
28 Low noise
29 Instruction used to force operation in the current setting
* The regulation zone is defined for a temperature less than NOTE : The end of the night slot night is defined by the start
the heating instruction or greater than the air-conditioning of the morning slot : this is why there is no need to define the
instruction. The neutral zone is between these 2 values. end of the night slot in the table below
Setpoint
value DAY WEEK-END NIGHT MORNING MIDDAY EVENING BMS
for KP02 =0 =1 =2 =4 =5 =6 =7
9 - 7 - - - - -
10 - 22 22 6 12 19 -
11 - 0 0 0 0 0 -
12 - 2 - - - - -
13 - 6 - 6 12 19 -
14 - 0 - 0 0 0 -
15 23.0 30.0 30.0 23.0 23.0 23.0 23.0
16 19.0 10.0 10.0 19.0 19.0 19.0 19.0
17 Off Off Off Off Off Off Off
18 0 0 0 0 0 0 0
19 100 100 100 100 100 100 100
20 0.0 0.0 0.0 0.0 0.0 0.0 0.0
21 30.0 30.0 30.0 30.0 30.0 30.0 30.0
22 20 0 0 0 20 20 20
23 On On On On On On On
24 Off Off Off Off Off Off Off
25 Off Off Off Off Off Off Off
26 Off Off Off Off Off Off Off
27 Off Off Off Off Off Off Off
28 Off Off Off Off Off Off Off
29 Off Off Off Off Off Off Off
For example :
- Outside temperature 0 °C
- Gradient start temperature set to + 10 °C (i.e. below
10°C outside, you want to advance start-up)
- Inertia coefficient set to 12
- Start of Morning slot set to 8h30
Inversion by
setpoint 57
100% Inertia
25%
$ Cp1
Min. fresh
Cp1
0% air
Differential in heating Hysteresis in heating Hysteresis in air cond. Differential in air cond.
setpoint 56 setpoint 56 setpoint 53 setpoint 54
! : Gas 2 + Gas 1
" : Gas 2 + 1/2 Gas 1
# : Gas 1
Figure 79
Two power factors, one for cooling (variable 75), and the other A power factor is calculated according to difference in
for heating (variable 76), are calculated according to the temperature between the setpoint and the ambient and outside
difference in temperature between the setpoint and the temperatures.
reference temperature. The progression of the power factor is limited by the maximum
percentage of fresh air (setpoint 72) if the outside temperature
The power factors are periodically recalculated by the is less than the minimum outside air temperature (setpoint
CLIMATIC™. The integration time (setpoint 59) is adjustable 71).
ORDER OF COMPONENTS IN
REGULATION REGULATION IN HUMIDITY
Two power factors, one for dehumidifying (variable 79), the
Heating operation other for humidifying (variable 80), are calculated according
to the difference in relative hygrometry between the setpoint
Setpoint 60 = ON and the reference relative hygrometry.
Water coil or electric coil or gas ! Compressors
The power factors are recalculated periodically by the
Setpoint 60 = OFF CLIMATIC™. The integration time is adjustable (setpoint 63).
Compressors ! Water coil or electric coil or gas
REGULATION IN DEHUMIDIFYING
3rd stage
2nd stage
1st stage
Hysteresis
(setpoint 69)
The minimum value for opening the damper to outside air can Defrost function
be set by instruction (see configuration of operating zones).
This value is expressed directly as a percentage. For heat pump units and air condensation units, cycle inversion
phases are programmed for defrosting the outside coil.
100%
CO2
0 ppm Setpoint 47 Setpoint 48 2000 ppm
ENTHALPY FUNCTION
This function is used to control the use of the economiser
register according to air enthalpy. If the outside hygrometry is
greater than the inside hygrometry, the respective enthalpy
values are then calculated. According to the result obtained,
input of new air is optimised.
It is possible to connect up to 12 CLIMATIC50 with to have a local display of the installation. It can be connected
Climalook2 or 8 rooftops equipped with CLIMATIC2 and 12 to up to 12 CL50 controller via a RS485 interface.
with CLIMATIC 50 when Climalook 3 or Climalink is
installed. CLIMALOOK 3
CLIMALINK 2 Climalook 3 provides the same features as Climalook 2 as it
can be connected to 12 rooftops equipped with CLIMATIC 50
This product consist in a central unit and a communication controller but it can also be connected to 8 rooftops fitted with
interface. CLIMATIC2 controller and KP01 board (Flexy and Linea
This unit is designed to be connected to a maximum of 12 already on site).
rooftops fitted with CLIMATIC 50 controllers via a RS485
interface. A connection diagram is provided in the box. NOTE: In order to connect a unit fitted with CLIMATIC2 you
The central unit must be installed in a dry, secured location. must ensure that the program version is at least LF20.
Once the unit is connected and powered up, it is entirely Otherwise it must be upgraded to LF20 before connection to
automatic and does not require a screen a Climalook 3
keyboard or a mouse. After a power failure, the central unit
must be restarted using the ON/OFF button. Climalook uses the internet explorer interface for local
To avoid this Lennox recommend to connect the central unit operation. The local operating mode is completely automatic
to a pulsating current power outlet or "UPS". Lennox cannot and does not require any configuration. Like Climalink,
be held responsible in the event this recommendation is not Climalook can receive remote queries thanks to its internal
acted upon. modem and an analogue telephone line.
Climalook and Climalink do not work with ISDN telephone lines.
CLIMALOOK 2
This product is identical to the CLIMALINK 2 but it is equipped
with a 15inch TFT flat screen, a mouse and a numeric keypad
KP 01 board KP 14 interface
RS 485 daughter-board
Plug for telephone link
RJ11. Cable supplied with
the unit.
Click
Enter the telephone number to which
your ClimaLook’s modem is con-
nected.
Click on next
Click
Click on next
Click
The first time you log in, Windows asks you to confirm
your login identifiers:
- for User enter
Administrateur
- for password enter
VISION
- leave the workgroup field empty.
The modem dials the number, and then the two modems
hook up.
In the task bar next to the time display you should see the
symbol indicating connection with the remote computer. Enter your access code and confirm. The access code 999
serves as a temporary code until you have configured your
own security code.
If your code is valid you will access the next menu. Otherwise
you remain on the same page.
The colour outline around the roof-top unit and the operating
temperatures indicate the unit’s status:
Green : Operating mode,
White : Stop mode,
Orange : Night mode,
Red: Fault mode,
This page gives you the basic information about how your
installation functions. The roof-top unit’s number corresponds
to its EPROM number.
Position the mouse on one of the units to obtain information It is possible modify several settings at
indicating this unit’s status. the same time.
If the unit does not exist, is not powered up, or if communication The settings will only be modified if the
with it is impossible, its icon disappears from the screen. The «submit» function is confirmed.
program attemps to communicate with absent units every ten
minutes. If your unit has - or had - a fault, it is outlined in red on the
To access a unit’s operating details, just click on it once. main page. You can use the fault module to trouble-shoot:
20 seconds automatic refresh on this screen.
Read-only setting :
For some settings, a small icon is Use the refresh function to update the values read
displayed at the end of the line
Click on it to get a history of this setting.
PROBLEM SOLVING
Impossible to enter your access code, you remain
on the welcome page.
How to check the ClimaLink is functioning correctly after
Local communication has been interrupted. You must restart
installation :
the local unit.
Connect up the unit and the KP14
After restarting, you must wait for 5 to 10 minutes until the unit
Connect the cables to the J18 inputs on the Climatic boards.
is ready to be queried once more.
After a few minutes, the central unit should start its dialogue.
The LED on the Climatic board to the right of the J18 input
should flash.
The values read do not seem to move.
The values are not in fact refreshed automatically, and for all If this does not happen, check the wiring.
the pages you must use the Refresh function to be sure you The only way to examine the problem in more detail is to obtain
are reading the latest values. a monitor and a mouse and contact the Lennox services.
The power cable should be connected to the main isolating as it is directly related to the type of cable you are using, the
switch and is fed from the underside of the unit into the distance separating the equipment from the source but also
electrical panel. various factors relating to the cable fitting.
Refer to the general arrangement drawings in the
documentation to locate the exact entry position. In the following pages you will find references to electrical
diagrams which will allow you to select the wiring for your
The power cable sizes must be calculated with reference to equipment.
the electrical characteristics of your machine. As the diagrams are valid for the entire range, they will refer
We are unable to state the cross sectional area of the cable to items not included in your scope of supply.
FUNCTIONS
FCA / FCK = Cooling only unit FDA / FDK = Cooling only unit
01
-
01
02
-
02
03
-
03
04.2
Gas burner 33/60 kW
04.1
04.3
Gas burner 120 kW
05
Economiser
04.4
Gas burner 180 kW
Extraction fan
06
Economiser
05
07
Firestat
07
Firestat
08
10FC
10FC
Hygiene probe
Consoles KP07 or KP17
12
14
RS232 KP14
Dry contact kit (KP12.2)
15
CL06
17
RS232 KP14
16
KP07
18
17
Pump CL06
19
18
KP07
20
-
22
-
20
KP12.3 (TCB)
25
KP12.4 (Adaptvision)
23
Climalink/Climalook
KP12.3 (TCB)
24
KP12.4 (Adaptvision)
25
Climalink/Climalook
26
FHA / FHK = Heat pump rooftop FDA / FDK = Cooling only unit
01
Electric heater TRIAC -
02
02
03
03
Hot water coil -
- Gas burner 33/60 kW
04.1
04.2
Economiser Gas burner 120 kW
04.3
05
04.4
06
05
Firestat Extraction fan
08
06
Smoke detector All fresh air
09
07
Advanced control pack (FC : cooling- FH : heat pump) Firestat
10FH
08
Digital console KP02 Smoke detector
11
09
Consoles KP07 or KP17
10FH
Advanced control pack (FC : cooling- FH : heat pump)
12
11
12
13
14
15
16
Pump CL06
19
17
18
Intelligent defrost -
21
22
20
21
24
KP12.3 (TCB) -
25
KP12.4 (Adaptvision)
25
Climalink/Climalook
26
FXA / FXK = Heat pump rooftop -B13 Clogged air filter pressure switch / air flow rate
-B14 Hot water battery antifreeze thermostat
Heat pump
01
Hot water coil -B21-B22 Gas manifold extraction air pressure switch
- -B23-B24 Extraction fan motor -ME1-ME2 stoptherme
04.1
CL06
17
KP12.3 (TCB)
-BT23-BT24 Compressor 3-4 antifrost temperature probe
25
-E16 Printed circuit 0/10V vapour humidifier -E4 -Q1-Q2 Blower fan motor -MS1-MS2 protection
-E20 CPU card KP01 -Q5-Q6 Extraction fan motor -ME1-ME2 protection
-E21 ON-OFF input card KP03 -Q9 Condenser -MC1-MC2 fan motor protection
-E22 ON-OFF input card KP08,1 -Q10 Condenser -MC3-MC4 fan motor protection
-E23 Analog output card KP04,1 -Q11-Q12 Compressor -MG1-MG2 protection
-E24 Analog output card KP04,2 -Q13-Q14 Compressor -MG3-MG4 protection
-E25 Analog output card KP04,3 -Q15 Condenser -MC2 fan motor protection
-E26 Analog output card KP04,4 -Q20 Circulation pump -MP1 protection
-E27 ON-OFF input card KP08,2 -Q25 Housing resistance protection
-E28 Input card 4 /20 mA KP05,1 -QF1 Primary circuit protection -T1
-E29.1.2 Input output card KP12 -QF2 Primary circuit protection -T3
-E30 Digital console KP02 ou KP17 -QF3 Secondary circuit protection -T3
-E31 Graphic console KP07 -QF4 Primary circuit protection -T4
-E32 Interface
-E51-E52 Compressor -MG1-MG2 housing resistance -QG Main switch
-E53-E54 Compressor -MG3-MG4 housing resistance -QG1-QG2 Condenser 1 / condenser 2 main switch
FCA / FCK = Cooling only unit FHA / FHK = Heat pump rooftop
FXA/FXK = Heat recovery unit
L3
L2
1112
02
02
12V.H
12V.G
12V.F
12V.E
5.5 kW
L13
L12
L11
Helicoid Centrifugal
Helicoid Centrifugal
Centrifugal Centrifugal
Centrifugal Centrifugal
Centrifugal Centrifugal
Helicoid
Helicoid
Helicoid Helicoid
Helicoid Helicoid
Helicoid Helicoid
Helicoid Helicoid
Helicoid Centrifugal
Helicoid Centrifugal
Centrifugal Centrifugal
Centrifugal Centrifugal
Centrifugal
Centrifugal
Helicoid
Helicoid Helicoid Helicoid
CLIMATIC CONTROLLER
CLIMATIC INPUT FC / FH / FX
CLIMATIC INPUT FG / FD
CLIMATIC OUTPUT FC / FH / FX
TRANSFER
ALARM
ON
STARTER
PROGRESSIVE
FAILURE
HU
CLIMATIC OUTPUT FG / FD
TRANSFER
ALARM
ON
STARTER
PROGRESSIVE
STARTER
FAILURE
HU
RESISTANCE
FEMELLE
UNITES UNITE 1
2,3,4,5,6,7,8
CUSTOMER
ELECTRICAL
GRAPHIC CONTROL
DISPLAY
TRANSFO
DAY CONTROL
FAULT RESETTING
ELECTRICAL WIRING DIAGRAMS
FILTER FAULT
FILTER FAULT
TREATMENT FAN FAULT
TREATMENT FAN FAULT
COMPRESSOR FAULT
COMPRESSOR FAULT
GAS BURNER FAULT
GAS BURNER FAULT ELECTRICAL RESISTANCE
ELECTRICAL RESISTANCE FAULT FAULT
BOTTOM LIMIT
TEMPERATURE FAULT
HUMIDIFIER FAULT
ELECTRICAL WIRING DIAGRAMS
KP 06 (J-BUS INTERFACE)
Relais SPST
Liaison
F1 Fuse 1A
Serial link RS232
J2 Unit size 8k (position 1-2) 32k (position 2-3) The link is used for short distances
Only a master control can be connected to this link
J3 SUBD 9-point connector RS232 link Serial link RS485
J4 15. SUBD 9-point connector RS485 link This link is used for long distances (maximum 100 metres)
Up to 31 controls can be connected (including 1 master)
J7 PHENIX 3-point connector supply 230 V
J14 CLIMATIC link 4-point connector
J15 ADN Inputs 12-point connector
J16 ADN Outputs 12-point connector
LD1 Monitoring LED power 6V link
LD2 Dialogue monitoring LED
LD3 Power Fell monitoring LED
LD4 Monitoring LED power 5V link
SW1 Speed configuration (9600, 4800 ,2400 or 1200 baud)
SW2 Speed configuration (9600, 4800 ,2400 or 1200 baud)
SW3 TXD signal configuration RS232 (position 2-3) / RS485
(position 1-2)
SW4 RXD signal configuration RS232 (position 2-3) / RS485
(position 1-2)
SW5 +10V Converter (Position 1-2)
U7 Programmable EPROM CL06
U9 Configurable EPROM
REPARTITEUR
DE PHASES
REPARTITEUR
DE PHASES
REPARTITEUR
DE PHASES
KP02 KP18
-E32
KP18
-E30 -E31
000 No fault
The following text includes references such as [C11] and [V25]. They relate to the setpoint or variable numbers used with the
KP02 unit.
If the pressure differential obtained by the analog sensor [V21] is less than the setpoint value
[C88] for more than 20 seconds, and if the blower fan has operated for more than 1 minute 30
001 seconds, the air flow safety system is activated and stops the ventilation.
The air flow safety system automatically stops after 1 minute 30 seconds and is automatically
locked out after 3 cut-outs in the same day. In this case a manual reset is obligatory. The cut-
out counter is reset to zero every evening at 20:00 if the value does not exceed 3 failures.
Dirty Filters
If the pressure differential obtained by the analog sensor [V21] is greater than the setpoint
value [C86] for more than one minute, the CLIMATIC™ indicates that the filters are dirty. The
004 unit is not stopped.
Missing Filters
If the pressure differential obtained by the analog sensor [V21] is less than the setpoint value
005 [C87] for more than one minute, the CLIMATIC™ indicates that the filters are missing. The unit
is not stopped.
NOTE : If a unit has a hot water battery, the temperature setpoint value is fixed at +6°C and the
register time set to 5 seconds. In addition, if the antifreeze thermostat is opened, the 3rd safety
level is immediately automatically maintained. In this case, manual resetting of the thermostat
followed by the CLIMATIC™ is obligatory
Faulty Pump
The internal protection of the water pump motor acts directly on the pump contactor. This information is
transmitted to the CLIMATIC™ via an auxiliary contact of the contactor.
041 If the CLIMATIC™ gives the pump the order to operate and if 5 seconds later the auxiliary contact
remains open, the safety system is activated and stops the pump.
The safety system is immediately automatically locked out. In this case, manual resetting is obligatory.
Note: This error is also displayed in the event of a "shunt" of the auxiliary contact of the contactor.
Sensor Status
081 Room temperature sensor missing or faulty.
082
Room relative humidity sensor missing or faulty
083
Outside air temperature sensor faulty
NOTE :
Missing or faulty room, supply air or outside air temperature sensors can affect the overall
control system. A safety device will be activated and all equipment except for the ventilation will
cut out. Failure of the other sensors will only stop the equipment involved.
Water leak
095 If the contact of the water leak detection card is closed for more than 30 seconds, the safety
system is activated.
Error : Smoke
If the contact closes due to the smoke detector card, the smoke safety mechanism is activated.
099 The unit is completely shut down and the fresh air louver is set to the fresh air position.
This safety mechanism is automaticallylocked out. In this case, manual resetting is obligatory.
111
121 Faulty condenser temperature sensor
131
141
112
122
Faulty pressure transmitter sensor, refrigeration system
132
142
113
123 Faulty refrigeration system, frost temperature sensor
133
143
147
REFRIGERATION
Table 15
In Heat Pump Mode the temperature difference If too high check the coils are clean or check
between T outdoor and Tevap. (Dew) is too coil internal pressure drop between the liquid
high line and the suction line
5°C < Delta T < 10°C excellent Good if < 3bar
10°C < Delta T < 15°C acceptable Too high if > 3bar (coil blocked)
LP PROBLEMS 15°C < Delta T < 25°C too high
and
LP CUT OUTS Stop the fan and create icing of the coil.
Refrigeration circuit blocked in distribution Check all circuits freeze evenly across the
whole surface of the coil
If some parts of the coil do not freeze this could
indicate a problem with the distribution
Incorrect insulation of the thermostatic bulb of Superheat too low: adjust superheat
the expansion valve Move the thermostatic element along the pipe
Insulate the Thermostatic element of the valve
LP cut out due to not enough defrost on heat Adjust the CLIMATIC settings to extend the
pumps defrost cycles or shorten the time between
defrosts
Summer operation
Moisture or contaminants in the system Several hours after the unit has stopped, check
the correspondance between the measured
pressure and the outdoor temperature
REFRIGERATION
Very high superheat, very hot compressor Open the superheat adjustment on the expan-
sion valve.
Very high
Check the pressure drop on the filter drier in
discharge
the suction line
temperature,
High amps Four Way reversing valve possibly blocked, Check operation of the valve by going through
measured at abnormal noise from the valve, low LP and cycle inversions. Change if necessary.
compressor increasing HP Refer to LP problems
Unstable running Fan jumping from one operating point to Change rotation speed of the fan.
and high vibration the other.
ELECTRIC HEATER
ELECTRIC HEATER
Cooling mode: Estimate the airflow rate and check the speed
Water carried away from the coil because of is lower than 2.8 m/s
excessive airflow and speed on the coil.
Water found in
the ventilation Low air pressure in the compartment due to a Check filter
section high airflow rate or a high pressure drop before Reduce airflow rate
the fan
Check seals around the ventilation section. Check the door seal
Water ingress in Check for the presence of silicone seals in the
the filter corners of the door and at the bottom of the
compartment refrigeration section bulkhead.
Water ingress through a leaking fresh air hood Check the seals and flanges in the fresh air
or when running 100% fresh air hood
Reduce the airflow rate if necessary
Rooftops are generally placed on the roof but can also be installed in technical rooms. These units are very robust but a
minimum regular maintenance is required. Some moving parts in the units can suffer from wear and tear and must be
checked regularly (belts). Other parts can get clogged by dirt carried in the air (filters) and must be cleaned or replaced.
These units are designed to produce cooled or heated air through the use of a refrigeration vapour compression system, it is
therefore imperative to monitor the refrigeration circuit operating pressures and check the pipe-work for leaks.
The table below, details a possible maintenance plan, including the operations to be carried out and the periodicity at which
they must be accomplished. It is recommended to follow such a plan to keep a rooftop unit in good working order. Regular
maintenance of your rooftop will extend its operating life and reduce operating faults
∆ Operation which must be carried out by qualified personnel, trained to operate on this type of equipment.
NOTE :
- Times are given for information purpose only and may vary depending on the unit size and type of installation.
- Coil cleaning must be carried out by qualified personnel using appropriate methods that won't damage the fins or the
tubes.
- It is recommended to keep a minimum stock of common replacement parts in order to be able to carry out regular
maintenance operations (i.e. filters). You can contact your local Lennox representative which can assist you in
establishing a parts list for each type of equipment.
- The access ports to the refrigeration circuits MUST be leak checked every time gauges are connected to the service
ports.
MAINTENANCE PLAN
TASK OPERATING MODE 6 YEARLY ESTIMATED
MONTHLY QUARTERLY MONTHLY B4 TIME
WINTER (mn)
Visual check of the oil level Visually check the oil level through the sight glass on the side of 0 2
the compressor casing
Position check of the compressor crankcase Check the heating resistance is fitted properly and tight around the 0 2
heater. compressor body.
Belt tension check. Check belt tension (Info in IOM) Replace belt if necessary. 0 10
Isolate unit from the main power supply; Push the fan wheel
Centrifugal fan bearings check manually and check for abnormal noises. Bearings are lubricated 0 10
for life but may need replacement after 10000 hours
Check absorbed Amps Check absorbed Amps on all three phases; compare with the ∆ 15
nominal value given in the electrical wiring diagram.
Check Smoke detector Start the unit. Trigger the smoke detector by moving a magnet ∆ 5
around the detector head. Reset unit and control.
Check Climatic control, set-points and varia- Refer to the commissioning sheet; Check all set points are set ∆ 15
bles according to this document.
Check clock settings Check the time and date of the control 0 5
Check systematically all connections and fixings on the
Check the position and tightness of refrigeration circuit. Check for oil traces, eventually a leak test ∆ 30
refrigeration components should be conducted. Check operating pressures correspond to
the ones indicated on the commissioning sheet
IOM / ROOF-TOP FLEXY™ Series - Page 127
Check Airflow rate safety switch (if fitted). Shut down supply fan. The fault must be detected within 5 0
seconds.
Check freeze protection on HWC ∆ 5
Increase room set-point 10°C above the actual room temperature.
Check three way valve on HWC Check operation of the piston. It must move away from the valve ∆ 5
head. Reset the control.
Check all fixings and transmission. Stop the unit using the control.
Check economiser actuator operation The fresh air damper must closes. Start the unit the fresh air ∆ 5
damper should open
With the unit running in cooling mode increase the room set-point
Check refrigeration 4way valve temperature by 10°C. The unit should switch to heat pump mode. ∆ 5
Reset the control.
Power down the unit and check and tighten all screws, terminal ∆ 30
Check tightness of all electrical connections and electric connections, taking a particular attention to the power
lines and low voltage control wires
MAINTENANCE PLAN
TASK OPERATING MODE 6 YEARLY ESTIMATED
MONTHLY QUARTERLY MONTHLY B4 TIME
WINTER (mn)
In the absence of any other written agreement, the guarantee The sole effect of any repair, modification or replacement of
shall only apply to design faults which occur within a 12 month an item during the warranty period must be to extend the
period (warranty period). material's warranty period.
The warranty period starts on the date of commissioning and Maintenance must be carried out in accordance with
at the latest six months after the delivery of the Rooftop. regulations.
Note : With the exception of the casing, the rest of the machine
is covered by the warranty of our general terms of sale.
www.lennoxeurope.com
Due to Lennox's ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
FLEXY_IOM/0803-E Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.