Chapter 10 - Special Hazards
Chapter 10 - Special Hazards
Chapter 10 - Special Hazards
Special Hazards
Introduction
Tyco Fire Protection Products manufacturers and provides a
wide range of equipment suitable for use in hazardous
areas both onshore and offshore where normal equipment
cannot be safely used.
S200 Plus Triple IR Solar Blind Flame Detector-IEC 61580 Approved (SIL2)
Unlike other flame detectors on the market the MINERVA The flameproof models are suffixed by the letter " f " and are
S200 PLUS is available in both Intrinsically Safe (EEx ia) and ATEX Certified EEx d IIC T6. The detectors are suitable for
Flameproof (EEx d) models. zones 1 and 2 where group IIC gases or lesser hazards can
be intermittently present in explosive concentrations.
The intrinsically safe models are suffixed by the letter " i "
and are ATEX Certified EEx ia IIC T5. As part of an
intrinsically safe circuit, it is suitable for zones 0,1 and 2
where group IIC gases or lesser hazards can be
continuously present in explosive concentrations.
Approvals
Various models are certified by a number of approval
bodies including those listed below.
Additional Features
• Flexible mounting and angular adjustment
• 2 x 20mm field cable entries
• IP66/67 housing designed for external use
• Rugged 316 stainless steel housing and mounting bracket
• Variable response times and sensitivity settings
• Remote self test and range setting
• True window test in detection area (i.e. not in the edge of the
window)
• Terminals provided for Remote LED connection where relevant
• BASEEFA (CENELEC) certified
• Approved to EN54 Pt 10 (Except FV282F)
• IEC 61508 Approved (SIL2)
• FM, DNV and LRS certified
• Very low power consumption (0.35mA)
• Models available with Conventional or Analogue Addressable
interface (requires 2 core cable only)
Approvals
Interface ATEX FM Product Codes
Conventional 4-20mA MZX Addressable Relay Ex ‘ia’ Ex ‘d’ Ex ‘d’
S231i+ 4 4 516.037.004
S231f+ 4 4 516.037.003
S232f+ 4 4 516.037.015
S241i+ 4 4 516.038.004
S241f+ 4 4 516.038.003
S261f+ 4 4 516.040.002
S271i+ 4 4 516.041.004
S271f+ 4 4 516.041.003
FV282F+ 4 4 4 516.040.014
Product Code
576.501.017
IS28 Mark 5 Banshee Sounder
IS Barrier Enclosure
The MTL ’DX’ Series enclosures will Product Codes
house the EXI800 (20mm pitch), 517.001.248
Pepperl & Fuchs KFDO-CS-Ex1.54 DX070 Enclosure
Galvanic Isolator (20mm pitch) and 517.001.247
the MTL5525 I.S. Sounder Driver DX170 Enclosure
(16.2mm pitch). The units are DIN
rail mounted with 70mm of rail
supplied with the DX070 and 170mm
of rail with the DX170. The
enclosures are usually selected on
the number of units they will
accommodate. The following table
shows the capacity of each of the
enclosure types.
BG MIM800 Callpoint EX II 2 GD
An Ex II 2 GD Dust Approved & Increased Safety (EExemd)
Resettable Manual Alarm Call Point for use with the EExd
Flameproof MIM800 input module in EExd housing on an
Addressable Detection & Releasing System in gas and dust
explosive risks.
The MR601TEX has been developed burning liquids which do not Product Code
to overcome the slower response of generate smoke particles. 516.054.011.Y (Vol 01B-04-D12)
the optical detectors to hot burning
MR601TEX Conventional High
fires, by increasing the sensitivity of
ATEX Code: Ex II 1GD Performance Optical Smoke Detector
the optical detector when it is
Cenelec Code: Ex ia IIC T5/
associated with a rapid change in
Ex iaD 20
temperature. In this way it is intended
T100°C
to become a detector which can
Operating Temp Range:
cover some of the risks currently
-20°C to +70°C
covered by ion chamber detectors.
Storage Temp: -25°C to +80°C
Smoke detectors will not detect
Relative Humidity: 95% non-
burning alcohol or other clean
condensing
Heat Detectors
If environmental conditions rule out er rooms, sudden, large changes in Product Codes
the use of smoke detectors, then a temperature are considered 'normal'. 516.052.051.Y (Vol 01B-04-D11)
heat detector of the type Rate-of-rise detectors are generally
MD601EX Conventional Rate of Rise
MD601Ex/MD611Ex may provide an not suitable in these cases and fixed
Heat Detector
acceptable, though less sensitive, temperature [static] types should be
alternative. For general use, and par- 516.052.041.Y (Vol 01B-04-D11)
used.
ticularly where the ambient tempera- MD611EX Conventional Fixed
ture may be low, a 'Rate-of-Rise' heat ATEX Code : Ex II 1GD Temperature Heat Detector
sensor is to be preferred. This type of Cenelec Code: Ex ia IIC T5/
sensor reacts to abnormally high Ex iaD 20
rates of change of temperature and T100°C
provides the fastest response over a Operating Temp Range:
wide range of ambient temperatures. -20°C to +70°C
A fixed temperature limit is also incor- Storage Temp: -25°C to +80°C
porated in these detectors. In many Relative Humidity: 95% non-
environments, e.g. kitchens and boil- condensing
Flame Detectors
Flame detectors, unlike smoke and clean-burning fuels such as alcohol ATEX Code: Ex II 1GD
heat detectors, do not rely on or methane, i.e. fires which would not Cenelec Code: Ex ia IIC T4/
convection to transport the fire be detected by smoke detectors. The Ex iaD 20
products to the detector nor do they 601FEx Flame Sensor, by virtue of its T135°C
rely on a ceiling to trap the products. operating wavelength and flicker Operating Temp Range:
They can therefore be used to discrimination is insensitive to normal -20°C to +70°C
protect large open areas without environmental influences. For Storage Temp: -40°C to +80°C
sacrificing speed of response to outdoor use a solar-blind detector Relative Humidity: 90% non-
flaming fires. In order to ensure full [e.g. the S200 Plus] should be used. condensing
coverage however, flame detectors The 601FEx Flame detector should,
Product Codes
do require direct line of sight to all normally, only be used inside
parts of the protected area. buildings to supplement heat and 516.600.066 (Vol 01C-02-D10)
smoke detectors. 601FEx Infra-Red Flame Detector
Infra-red flame detectors such as the
601FEx are designed to respond 516.600.067 (Vol 01C-02-D10)
rapidly to fires which involve 601FEx-M Infra-Red Flame Detector
(Marine)
Features
• Intrinsically safe
• Weatherproof to IP66/IP67
• Robust GRP Housing
BG Conventional Callpoint EX II 2 GD
This EX II 2 GD Dust Approved & Increased Safety It is also fitted with a removable link which allows it to be
(EExemd) Conventional Break Glass Manual Alarm Call connected on its own or with other Conventional Devices to
Point is fitted with a 470 ohm Alarm Level Resistor and a a Tyco Conventional Detection Circuit.
4K7 ohm EOL Resistor for use with Tyco Conventional
Detection Circuits including the DIM800 and DDM800 MX
Modules.
Technical Specification
Terminals: 6 x 2.5mm2 *Output measured with 24VDC input voltage. Tone set to
Mounting: Stainless steel bracket with ratchet 970Hz continuous.
facility
Cable Entries: 2 x 20mm EExd. Weight: 6.0kg approx
Tone Selection: 27 user selectable tones. Ingress Protection: IP66 / IP67
Certification: CENELEC EN50014,18,19 Voltage: 12VDC to 48VDC
BASEEFA Cert. No. Certified Temperature: -20o C to +70o C
BAS00ATEX2097X, EExd IIC.
Zones 1 and 2.
Material: Body & horn in anti-static, UV
stable, glass reinforced polyester.
Swivel bracket & captive cover
screws in stainless steel.
On all issues of intrinsically safe system design, please refer to Manual 26A for guidance.
The MTL5561 is a two channel The MTL5525 Isolating Sounder When designing new systems or
interface for use with conventional Driver enables an intrinsically safe upgrading existing MTL3000 series
detectors located in hazardous areas. sounder located in the hazardous systems to MTL5500 series, please
This galvanic isolator is CE marked, area, to be controlled from the safe use the appropriate MTL “DX” series
and replaces the MTL3043 barrier area. The MTL5525 barrier is enclosure equipment (16.2mm
option. It is suitable for connecting designed as a CE marked pitch).
loads in Zone 0, IIC, T4-T6 hazardous replacement for the existing Product Codes
areas if suitably certified. MTL3021 barrier. It has one channel 517.001.302
and is suitable for connecting loads
MTL5561 2 Channel Galvanic Isolator
in Zone 0, IIC, T4-T6 hazardous
517.001.304
areas if suitably certified.
MTL5525 I.S. Sounder Driver
The MTL7700 Series intrinsically safe One secondary replaceable fuse for Please note that this barrier is a
shunt-diode safety barriers are each barrier channel is provided and direct alternative for the MTL728+
innovative devices designed to is lower in value than the safety barrier.
provide exceptionally high packing related fuse. Fuses are packaged in
densities, straightforward installation small mouldings which can be
and simplified connection, latched in a disconnect position to Product Code
commissioning and maintenance break the safe and hazardous areas
517.001.301
facilities. The MTL7700 Series during commissioning, maintenance
include secondary replaceable and fault finding, thus avoiding the MTL7728 + Zener Safety Barrier for
fuses. These are useful where there need for additional disconnect conventional detection circuits
is the possibility of faults occurring terminals. designed in accordance with System
during commissioning, which would 601
otherwise blow the barriers’ internal
safety fuses.
Safety Enclosures
UC Series Enclosures
MT Series Enclosures
Ancillaries
The ERL7 earth rail is a nickel plated Product Codes
3 x 10mm rail (1 metre long), 517.001.205
suitable for a do-it-your self
ERL7 Earth rail for I.S. systems
mounting arrangement. It will
accommodate up to 2.5 ETM7 earth 517.001.206
terminals per barrier location for ETM7 Earth termination connection
terminating earth returns and cable system
screens from the hazardous area. 517.001.207
IMB7 Insulating mounting block
The IMB7 mounts on a flat surface or
top hat rail (35mm) or G-profile rail
and acts as a convenient method for
mounting the earth busbar.
Mounting Materials
For professional mounting of the sensor cables four
different types of mounting sets are available. These sets
are designed for different applications. They can be used
for the mounting of the sensor cable to the wall and the
ceiling. Every set contains 100 x clamps, 100 x anchors and
1 x SDS drill bit.
LAN (10/100M)
Modbus / TCP/IP SCPI/FTP Modbus/TCP/IP/SCPI/FPT SCPI
SCADA
System
Controller Unit
Supervisory Control
and Data Acquisition
Interface Box 20 Relay Outputs
1 Fault
PC Work Station 19 Alarms
MZX Panel
Relay Controller
Set Relay Extension
Set
By means of the Relay Controller Set and the Relay Extension Set an
additional 256 relays per sensor cable can be connected.