GES-6122C: Multiples of Current Rating

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Temp.

0 25 40 50 60
Shift index for
long-time delay only. MULTIPLES OF CURRENT RATING

10000
1000

2000

3000

4000

5000
6000
7000
8000
9000
100

200

300

400

500
600
700
800
900
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900
800 800
700 700
600 Enclosure compensated. For other 600
500 than 40°C ambient, shift unity index 500

400
for long-time delay (thermal) portion 400
of curve to desired ambient.
300 300

200 200

100 100
90 90
80 80
70 70
60 60
TIME IN SECONDS

TIME IN SECONDS
50 50

40 40

30 30
Minimum Total Maximum Total
Clearing Time Clearing Time
20 20

10 10
9 9
8 8
7 7
6 6
5 5

4 4

3 3

2 2

1 1
.9 .9
.8 .8
.7 .7
GES-6112C

GES-6112C
.6 .6
.5 .5
.4 .4

.3 .3

.2 .2

.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04

.03 .03
Application determines
end of curve
.02 .02

.01 .01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100

200

300

400

500
600
700
800
900
1000

2000

3000

4000

5000
6000
7000
8000
9000
10000

MULTIPLES OF CURRENT RATING

Molded Case Circuit Breaker


GE Consumer & Industrial -
Electrical Distribution E 100 LINE GES-6122C
Current Ratings Type TEB, 15-50 Amperes Adjustments
15, 20, 25, 30, 35, 40, 45 and 50 Amperes Enclosure Compensated Long-time delay thermal trip: not adjustable.
Long-time Delay and Instantaneous Instantaneous magnetic trip: not adjustable.
Voltage Ratings Time-current Curves
1 pole – 120 Vac (125 Vdc) Curves show enclosure-compensated circuit breaker
2 and 3 pole – 240 Vac (250 Vdc) in open air, 40ºC ambient, wired with conductors of
corresponding rating, no prior load. For all other
Frequency Rating ambients, use shift index at top of sheet.
60 Hertz
7.85 1M