Inrow Direct Expansion Air Conditioners: Acrd100, Acrd200, Acrd600, and Acrd600P Series
Inrow Direct Expansion Air Conditioners: Acrd100, Acrd200, Acrd600, and Acrd600P Series
Inrow Direct Expansion Air Conditioners: Acrd100, Acrd200, Acrd600, and Acrd600P Series
990-5801C-001
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Table of Contents
Technical Data .............................................................................................5
Model Identification.....................................................................................5
Overview ...................................................................................................6
Capacities ............................................................................................6
Room Air Distribution ............................................................................6
Compliance Approval ............................................................................7
Working Conditions and Environmental Limits.........................................8
Scalable Solution for Critical Environments...................................................9
InRow Advantages................................................................................9
Scalable for High Density ......................................................................9
Standard Features and Options .................................................................10
Standard Features ..............................................................................10
Optional Features ...............................................................................13
Microprocessor Controller .........................................................................14
ACRD100 and ACRD200 Series ..........................................................14
ACRD600 and ACRD600P Series ........................................................15
Microprocessor Controller....................................................................15
Open Architecture...............................................................................15
Control Type.......................................................................................15
Functions ...........................................................................................16
Logging..............................................................................................16
Control ...............................................................................................16
Alarms ...............................................................................................16
Component Identification ..........................................................................19
External Components..........................................................................19
Internal Components...........................................................................21
Electrical Panels .................................................................................27
Performance Specifications.......................................................................33
Net Cooling Capacity ..........................................................................33
General Data ......................................................................................41
Altitude Correction Factors ..................................................................45
Electrical Data ....................................................................................46
Sound Data ........................................................................................47
Dimensions and Weights...........................................................................48
ACRD100 and ACRD200 Series ..........................................................48
ACRD600 and ACRD600P Series ........................................................49
Piping and Electrical Access Locations .................................................51
ACRD600 and ACRD600P Series..............................................................55
Water-Cooled Bottom Piping (ACRD200 Series) .........................................56
Glycol-Cooled Bottom Piping (ACRD200 Series).........................................57
Outdoor Heat Exchanger Data ...............................................................58
Mechanical Data.......................................................................................58
Air-Cooled Condensers (ACRD100 Series)...........................................58
Air-Cooled Condensers (ACRD600 Series)...........................................59
Fluid Coolers (ACRD200 Series)..........................................................60
Electrical Data ..........................................................................................61
Air-Cooled Condensers (ACRD100 Series)...........................................61
Air-Cooled Condensers (ACRD600 Series)...........................................61
990-5801C-001 3
ACRD100, ACRD200, ACRD600, and ACRD600P Series
4 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Model Identification
ACRD100 Series and ACRD200 Series—300 mm Units
The model number can be found on the outside of the shipping crate and on the
name plate located on the unit as shown. Use the table below to verify that the
equipment is the right type and voltage.
REAR
NAME PLATE
na4402b
SKU Range of Heat Rejection Voltage Frequency Reheat Humidifier Air Pattern
Capacity
990-5801C-001 5
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Overview
This modular, row-based computer room cooling system offers efficient,
predictable, and economical cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the
traditional data center or computer room to encompass a larger suite of
applications, referred to as technology rooms. Critical environment applications
include the following:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
• Medical equipment rooms
• LAN/WAN environments
A worldwide network by Schneider Electric representatives is fully qualified to
provide engineering, sales, installation, and service for our products.
Capacities
InRow® Direct Expansion (DX) units are available in two sizes (300 mm and 600
mm) with nominal capacities ranging from 2–10 kW (300 mm) and 8–42 kW (600
mm).
6 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Compliance Approval
UL and cUL X X X X X
RCM X X
CE X X
EAC X
CMIM X X
UL and cUL X X X X X
RCM X X
CE X X
EAC X X X X X
CMIM X X
990-5801C-001 7
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
8 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
na5859a
HOT AISLE
990-5801C-001 9
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Cabinet
The frame is constructed of 16-gauge formed steel for maximum strength. The
cabinet is serviceable from the front and rear. All exterior panels and corner posts
on the frame are powder coated for durability and an attractive finish. The front
and rear exterior panels are constructed of 18 gauge perforated steel with 80%
10 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
open free area. All panels, which include a key latch for safety and security, allow
easy access and removal. Insulation (ACRD100 and ACRD200 series only) is
80.1 kg/m3 (5 lb/ft3) density and complies with ASTM E84 rating of 25/50.
Condensate Pump
• ACRD100 and ACRD200 series: A condensate pump is factory wired and
piped internally to the condensate drain pan. The pump is capable of pumping
34 l/h (9 g/hr) against head pressures of up to 50 ft (15.2 m) of total run. Of
that run, 16 ft (4.9 m) can be vertical lift as measured from floor level. Dual
floats are included with the unit. One float is used for condensate pump
control, and the other float generates a condensate pump failure alarm. The
InRow RD unit can be set to either continue running in an alarm condition or
shut down to prevent condensate pan overflow.
• ACRD600 and ACRD600P series: A condensate pump is factory wired and
piped internally to the condensate drain pan. Within the condensate pump,
there is a dual position float. The first position is used for condensate pump
control and the other float generates a condensate pump failure alarm to
prevent condensate pan overflow.
Filters
Filtration of conditioned air is extremely vital to maintaining the clean, particle-free
environment required by electrical equipment. Filters are easily replaceable from
the rear of the unit. The ACRD100 and 200 series systems use greater-than 20%
efficiency ASHRAE 52.1, 12.7 mm (1/2 in.) washable filters that meet HF-1
standards for electronics (MERV 1 per ASHRAE 52.2). The ACRD600 and
ACRD600P series system uses a 30% efficient, 102 mm (4 in.), deep loading,
pleated filter (MERV 8 per ASHRAE 52.2, EN779 G4).
990-5801C-001 11
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Joining Kit—InRow/NetShelter SX
Joining kits made of 16-gauge steel enable joining the InRow unit to NetShelter
enclosures.
Variable-Speed Fans
Each unit is equipped with variable speed fans to allow for varying heat loads. In
order to provide uniform airflow over the cooling coil, the fans provide a draw-
through air pattern. The ACRD100 and ACRD200 series units are equipped with
six direct-drive fan modules. These fans are easily replaceable while the unit is in
operation. The ACRD600 and ACRD600P series is equipped with two backward
inclined, direct drive fans.
12 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Optional Features
Aisle Containment
This containment solution isolates pods (two rows of InRow cooling units sharing a
common aisle) from the whole IT environment, increasing cooling efficiency at any
density.
Data Partition
Overhead cable distribution between adjacent NetShelter racks allows for removal
of the InRow DX units without disrupting overhead cabling.
Filters
Electrical equipment requires clean, particle-free air, thus making air filtration
extremely important. As an optional feature, higher efficiency filters can be
purchased for the InRow DX units. The
Height Adapters
To match height of the InRow DX cooling units to various rack heights, height
adapters are available for NetShelter 42-U VX and 48-U SX racks.
Network Cable
Various lengths of network cable are available to ship with your cooling system.
The network cable is used to interconnect multiple units in a redundant group, as
well as to connect the Network Management Card to your LAN.
Power Trough
Overhead power distribution between adjacent NetShelter racks allows for
removal of the InRow DX cooling units without disrupting overhead power cabling.
Seismic Latch
Users must obtain and install this latch kit for deployments that require seismic
certification (ACRD100 and ACRD200 series only).
990-5801C-001 13
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Microprocessor Controller
ACRD100 and ACRD200 Series
Display Interface
Status
ESC
Check
Log
?
Warning
Critical
na1582a
Item Description Function
Critical alarm LED When illuminated, a critical alarm condition
(red) exists that requires your immediate attention.
Warning alarm LED When illuminated, a warning alarm condition
(yellow) exists. Failure to correct this condition could
cause a critical alarm.
Check log LED When illuminated, at least one new event has
(yellow) been logged since the last time the log was
checked. Only events that pertain to the
operation of the cooling unit will activate this
LED.
Check log LED When illuminated, the cooling unit is receiving
(yellow) electrical power. When the LED is flashing, the
cooling unit is downloading firmware for the
controller. This may take a few minutes.
Liquid crystal display View alarms, status data, context-sensitive
(LCD) help, and modify configurable items.
Up and down arrow Select menu items and access information.
keys
ESC key Return to previous screen or cancel current
operation.
Enter key Open menu items and input changes to the
cooling unit settings.
Help key Display context-sensitive help. Press the help
key for information about each option on the
screen and for instructions on performing the
tasks.
14 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Display Interface
Display
Reset 10/100
Micro
SD
Service
Port
USB
Console
na4820a
Item Description Function
LCD Display 4.3-inch touch-screen color display
Power LED The cooling unit is powered when the LED is
illuminated. Unit firmware is updating when
LED is blinking.
Check Log LED When this LED is illuminated, a new entry has
been made to the event log.
Alarm LED Displays current alarm condition of unit.
Status LED Displays current network management card
status.
Display Reset button Resets the display microprocessor. This has
no effect on the air conditioner controller.
Link-RX/TX (10/100) Displays current network link status.
LED
Micro SD card slot Memory card expansion slot.
Service port USB-B port used only by service personnel.
USB-A port Supports firmware upgrades.
Serial Configuration Connects the display to a local computer to
port configure initial network settings or access the
command line interface (CLI).
Microprocessor Controller
The microprocessor controller is standard on each system. The easy-to-use
display allows the operator to select options from the device menu-driven interface
to control and monitor the connected air conditioning system.
Open Architecture
The InRow Direct Expansion protocol is open for integration with all building
management systems. Communication interface on the system can be MODBUS
RS485 or Ethernet.
Control Type
The controller uses proportional/integral/derivative (PID), a time-proven precision
environmental control method. This allows for custom tuning of control variables to
achieve desired system response.
990-5801C-001 15
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Functions
• Supply and return air conditions
• Operational mode control
• Event logging
• Alarms
• Redundant group control
• Fan speed adjustment
• Input/Output module programming
Logging
The event log keeps a record of all alarms and events. Each event log contains a
time/date stamp. The controller also displays run time, in hours, for major
components (air filters, fans, and condensate pump, as well as humidifier, heater,
and compressor for the air-cooled unit).
Control
ACRD100/ACRD200 Series
The back-lit, four-line by twenty-character display is password configurable.
Alarms
The microprocessor controller shall activate a visible and audible alarm in the
following occurrences:
All Series
• Cool fail
• Air filter clogged
• Return air sensor fault
• Supply air sensor fault
• Rack temperature sensor fault
• High discharge pressure
• Low suction pressure
• Fan fault
• Water detected (if optional leak detector used)
• Check condensate management system
• Air filter run hours violation
• Group communication fault
16 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
990-5801C-001 17
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
18 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Component Identification
External Components
na2625a
Item Description
Removable rear door
Side panel latch
Removable side panel
Rear casters (non-swiveling)
Front casters (swiveling)
Adjustable leveling foot
Display interface
Removable front door
Door lock
990-5801C-001 19
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
na5807a
Item Description
Removable rear doors
Side panel lock
Removable side panel
Adjustable leveling foot
Caster
Door handle and lock
Display interface
Removable front door
20 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Internal Components
Internal Components—Front
na2626a
Item Description
Electrical control box 1
Electrical control box 2
Temperature sensor (7 total)
Condensate pan floats (2)
Condensate pan
Compressor
Front air block panel
Evaporator fans (6)
Expansion valve
Evaporator coil
990-5801C-001 21
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Internal Components—Rear
na2627a
Item Description
Filter drier
Pressure transducer (2) (located behind air block)
Filter differential pressure port
Air filter (2)
Condensate pump (2)
Electrical control box 2
Sight glass
Hot gas bypass valve
Liquid line shutoff solenoid
Electrical control box 1
Power supply unit #2
Power supply unit #1
Service junction box (top entry shown)
22 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Front (ACRD60x)
na5823a
Item Description Item Description
Condensate drain pan Fan (2)
Electronic expansion valve Fan guard (2)
Compressor Electrical panel
Variable frequency drive for Communication and external device
compressor (VFD) connectors
Supply air temperature sensor Ground lug
Main circuit breaker Humidity sensor
990-5801C-001 23
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Rear (ACRD60x)
na5824a
24 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Front (ACRD60xP)
na5821a
Item Description Item Description
Electric heater Main circuit breaker
Condensate drain pan Fan (2)
Electronic expansion valve Fan guard (2)
Humidifier Electrical panel
Compressor Communication and external device
connectors
Variable frequency drive for Ground lug
compressor (VFD)
Supply air temperature sensor Humidity sensor
990-5801C-001 25
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Rear (ACRD60xP)
na5822a
26 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Electrical Panels
na2664a
Item Description
Leak detector port
Remote temperature sensor port
A-Link ports
Reset button
Network port
Building management system (BMS) RS-485 port
Control RS-485 port
Form C and shutdown input
RS-232 console port
Outdoor heat exchanger (OHE) ports (optional)
990-5801C-001 27
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
NOTE: For a top installation, control wiring is routed through the wire channel
located at the top-left corner, just above the user interface connectors.
For a bottom installation, the control wiring is routed to the access hole in the
bottom of the equipment through wire clamps from the interface connectors. Then,
the wiring is routed down along the electrical panel and secured with wire clamps
na2724b
28 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
NOTE: For a top installation, control wiring is routed through the wire channel
located at the top-left corner, just above the user interface connectors.
For a bottom installation, the control wiring is routed to the access hole in the
bottom of the equipment through wire clamps from the interface connectors. Then,
the wiring is routed down along the electrical panel and secured with wire clamps
na2032b
990-5801C-001 29
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
LEAK DETECT
COM RUN
NO OUTPUT
+ ALARM
OHE - INPUT
24V AC/DC
COM RUN
NO OUTPUT
+ ALARM
INPUT
- 24V AC/DC
RACK
TEMPERATURE
USER INTERFACE
CONNECTIONS
WIRE AS CLASS 2
CIRCUITS ONLY
RS-232
CONSOLE PORT
9600-8-N-1
DTE
SHUTDOWN INPUT
CONTACTS AND NC
COM OUTPUT
RELAY
ALARM OUTPUT NO
GND
+12 V
VOLTAGE
OUTPUT
CONTACTS +24 V
+
-
SHUTDOWN
INPUT
12-30V AC/DC
D1
CONTROL
D0 RS-485
GND
CONTROL D1
D0
GND
MODBUS
RS-485
LINK RX/TX
10 = GREEN
100 = ORANGE
RESET
24VDC
na2688a
885-3432_REVE1
30 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
990-5801C-001 31
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Item Description
Rack inlet temperature sensors 1, 2, Three temperature sensors which must be installed on
3 the cold aisle side of the server racks. See
A-Link IN In and out connections for A-Link. The terminators
A-Link OUT supplied with the equipment must be plugged into the
first A-link port and the final A-Link port for the group.
Network port 10/100 Base-T Network port. Connects the equipment
to the network; Status and Link LEDs indicate network
traffic.
• Status LED—blinks orange and green at startup;
indicates the status of the network connection
(solid green—IP address established; blinking
green— attempting to obtain an IP address).
• Link LED—blinks to indicate network traffic (green
— operating at at 10 mbps; orange—operating at
100
Customer output, NC (normally Customer-configurable output relay which can be
closed) activated for all types of alarms or critical alarms. The
Customer output, COM (common) relay can be connected to external equipment using
Customer output, NO (normally 30 VAC/VDC, 2 A.
open)
Supply GND (Ground) Can be used for customer input and output interface.
Supply 12 VDC (current limit: 20 mA) Can be used for customer input and output interface.
Current limit is 20 mA.
Supply 24 VDC (current limit: 20 mA) Can be used for customer input and output interface.
Current limit is 20 mA.
Customer input + (12–30 VAC/VDC, Used for remote shutdown of an InRow DX unit.
24 VDC @ 11 mA) Voltage is applied from the internal power supply or by
using an external power supply.
Supply COM Ground connection point for remote shutdown supply
source.
RTRX(-) Connections for Building Management System. Wire a
RTRX(+) 150-Ohm terminator resistor (supplied) into the final
Modbus GND InRow DX unit, between Modbus D0 and Modbus D1.
Supply air temperature sensor (front) Temperature sensor installed on the front of the
equipment.
Supply air humidity sensor (front) Humidity sensor installed on the front of the
equipment.
32 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Performance Specifications
Net Cooling Capacity
990-5801C-001 33
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
34 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Water-Cooled Units
Cooling Performance at a Fixed Compressor Speed
Airflow is reduced to 887 l/s (1880 SCFM) at the condition below to maintain adequate evaporating temperature.
Airflow is reduced to 717 l/s (1520 SCFM) at the condition below to maintain adequate evaporating temperature.
Airflow is reduced to 599 l/s (1270 SCFM) at the condition below to maintain adequate evaporating temperature.
Airflow is reduced to 510 l/s (1080 SCFM) at the condition below to maintain adequate evaporating temperature.
Airflow is reduced to 448 l/s (950 SCFM) at the condition below to maintain adequate evaporating temperature.
Airflow for the ACRD200 series is 1081 l/s (2290 SCFM) at full evaporating fan speed.
NOTE: Minimum recommended loads: ACRD200 series—2 kW (6831 BTU)
NOTE: For ACRD200 series, a 0.64 l/s (10 gpm) entering water temperature is 29.4°C (85°F).
990-5801C-001 35
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
ACRD100 Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Net Sensible
Air Flow – L/S Unit Power – Condenser Fan Supply Air
Fan Speed – % Voltage/Ph/Hz Capacity – kW
(SCFM) kW Power – kW Temp – ° C (°F)
(BTU/h)
36 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Net Sensible
Air Flow – L/S Unit Power – Condenser Fan Supply Air
Fan Speed – % Voltage/Ph/Hz Capacity – kW
(SCFM) kW Power – kW Temp – ° C (°F)
(BTU/h)
990-5801C-001 37
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
ACRD200 Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Net Sensible
Air Flow – L/S Supply Air Temp –
Fan Speed – % Voltage/Ph/Hz Unit Power – kW Capacity – kW
(SCFM) °C (°F)
(BTU/h)
38 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Fan Speed – % Voltage/Ph/Hz Air Flow – L/S Unit Power – kW Net Sensible Supply Air Temp –
(SCFM) Capacity – kW °C (°F)
(BTU/h)
990-5801C-001 39
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Net Sensible
Air Flow – L/S Condenser Fan Supply Air Temp –
Fan Speed – % Unit Power – kW Capacity – kW
(SCFM) Power – kW °C (°F)
(BTU/h)
*In this case, the compressor will cycle because its speed is down to the minimum of 25 Hz.
The minimum fan speed for the InRow mode is 30%; the minimum fan speed for HACS and RACS mode is 40%.
NOTE: Outdoor temperature is 35°C (95°F).
40 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
General Data
990-5801C-001 41
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
42 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACRD100 series 6
Number of Fans
ACRD600, ACRD600P series 2
ACRD100 series 2
Rows Deep
ACRD600, ACRD600P series 4
Filters—Washable (Standard)
Quantity 2
Filters—Pleated (Standard)
Quantity 3
Efficiency (%) 30
Filters—Pleated (Optional)
Quantity 2
Filters—Pleated (Optional)
Quantity 3
Efficiency (%) 85
990-5801C-001 43
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Connection Sizes
Refrigerant
Condensate Drain
Humidifier
Supply Line – mm (in.) ACRD600, ACRD600P series 6.35 (1/4)
Refrigerant
44 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Altitude – m (ft) Specific Volume – cm3/ Density –g/m3 (lb/ft3) Density Ratio* Capacity Correction**
kg (ft3/lb)
990-5801C-001 45
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Electrical Data
Compressor
Model MCA** MOP** FLA** LRA RLA Power
ACRD100—208-240 V, 1 Ph, 60 Hz 25.0 40 N/A 87.5 16.0 4.6
ACRD101—220-240 V, 1 Ph, 50 Hz N/A N/A 21 97.0 16.3 4.4
ACRD200—208-240 V, 1 Ph, 60 Hz 25.0 40 N/A 87.5 16.0 4.6
ACRD201—220-240 V, 1 Ph, 50 Hz N/A N/A 21 97.0 16.3 4.4
ACRD600—200-240 V, 3 Ph, 50/60 Hz 52.6 80 N/A 29.7* 36.6 14.6
ACRD601—460-480 V, 3 Ph, 60 Hz 24.4 40 N/A 28.1* 16.6 14.6
ACRD602—380-415 V, 3 Ph, 50/60 Hz 31.1 50 25.2 28.1* 16.6 14.6
ACRD600P—200-240 V, 3 Ph, 50/60 Hz 78.6 110 N/A 29.7* 36.6 23.5
ACRD601P—460-480 V, 3 Ph, 60 Hz 36.9 50 N/A 28.1* 16.6 23.5
ACRD602P—380-415 V, 3 Ph, 50/60 Hz 45.8 60 34.2 28.1* 16.6 23.5
NOTE: Above data is based on maximum operating condition. Evaluated at maximum allowable operating
conditions of: 39°C (102°F) DB, 11.1°C (52.0°F) DP, 46.0°C (115.0°F) ambient, 100% fan speed, 78 Hz
compressor.
NOTE: Installation must comply with national and/or local electrical codes.
NOTE: All models are hard-wired.
NOTE: Use LRA for estimation of inrush current.
* The compressor is powered by the VFD.
**Cells marked N/A indicate that this information is not required because of regional differences in electrical
codes.
46 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Sound Data
60 2300 0.66 (1400) 62.3 68.3 69.8 74.8 67.8 59.3 53.3 76.5 70.5
70 3000 0.78 (1650) 65.3 76.3 74.8 77.8 73.8 67.8 61.3 80.8 74.7
80 3450 0.85 (1800) 67.3 80.3 77.3 78.2 76.3 71.8 66.3 82.7 76.6
90 3800 0.92 (1950) 68.3 81.8 78.8 80.8 77.3 74.3 68.3 84.5 78.4
100 4300 1.08 (2290) 70.3 80.8 83.3 85.3 80.3 77.8 72.3 88.3 82.2
*Weighted sound pressure dBA in a 28.3 m3 (1000 ft3) room at 1.5 m (5-ft) distance.
**Based on compressor operating at full speed.
50 0.95 (2000) 85.1 83.0 78.1 80.4 74.6 75.5 66.1 84.1 71.1
75 1.43 (3000) 89.4 84.7 86.1 83.5 78.8 76.8 68.0 88.1 75.0
100 1.89 (4000) 100.1 100.4 92.2 90.7 85.6 80.2 73.6 96.3 83.3
*Weighted sound pressure dBA in a 28.3 m3 (1000 ft3) room at 1.5 m (5-ft) distance.
**Based on compressor operating at full speed.
990-5801C-001 47
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
Cooling Units
)
1070 (42
1991 (78
)
na2231a
300 (12)
74.8 (
2.94)
300 (11
.8)
48 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
na2788a
265.3
(10.44
)
300 (1
1.8)
Cooling Units
) 600 (23.6)
1070 (42.1
2156 1991
(84.9) (78.4)
na5811a
990-5801C-001 49
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
na2445a
74.8 (
2.94)
600 (2
3.6)
265.3
na2446a
(10.44
)
600 (2
3.6)
50 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
REAR—HOT AISLE
88.9 (3.5)
55.1 (2.2)
47.8 (1.9)
42.6 (1.7)
85.6 (3.4)
38.2 (1.5)
109.7
(3.4)
87.6
(4.3)
154.6
143.4
(6.1)
(5.6)
na2813a
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item Description
Low voltage wiring input
Electrical input
Hot gas discharge line (ACRD100 series)
Water/glycol out (ACRD200 series)
Liquid line (ACRD100 series)
Water/glycol in (ACRD200 series)
Condensate pump outlet
990-5801C-001 51
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
REAR—HOT AISLE
102 (4.0)
88.9 (3.5)
55.1 (2.2)
102.1
122.1
(4.0)
133.6
(4.4)
(4.8)
(5.3)
113
168.8
(6.6)
na2814a
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item Description
Electrical input
Low voltage wiring input
Liquid line (ACRD100 series)
Water/glycol in (ACRD200 series)
Condensate pump outlet
Hot gas discharge line (ACRD100 series)
Water/glycol out (ACRD200 series)
52 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
REAR—HOT AISLE
547 (21.54)
105 (4.12)
73 (2.86)
123 (4.84)
75 (2.95)
325 (12.78)
380 (14.94)
738 (29.04)
47 (1.85)
na2071a
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item Description
Refrigerant discharge line
Refrigerant liquid line
Trough for communication cables
Power connections
Humidifier water supply (ACRD600P series only)
Condensate drain line outlet
990-5801C-001 53
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
REAR—HOT AISLE
480 (18.90)
345 (13.58)
404 (15.91)
115 (4.53)
184 (7.24)
199 (7.84)
420 (16.54)
796 (31.34)
893 (35.16)
57 (2.25)
na5837a
140 (5.51)
178 (7.00)
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item Description
Humidifier water supply (ACRD600P series only)
Condensate drain line outlet
Power connections
Communication connections—27.80 mm (1.09 in.)
Condensate overflow—50.00 mm (1.97 in.)
Refrigerant discharge line
Refrigerant liquid line
54 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
CONDENSER CONDENSER
HOT GAS
LIQUID
HOT GAS
LIQUID
na2543a
DX RECEIVER
UNIT RECEIVER
DX
UNIT
*When condenser is installed below unit level, use 7/8 in. pipe for liquid line.
NOTE: The condenser can be placed higher than indoor cooling unit but height shall be no more than 27 m (90 ft), regardless of piping
length.
990-5801C-001 55
ACRD100, ACRD200, ACRD600, and ACRD600P Series Technical Data
na2765a
Item Description
InRow DX
Balancing valve*
Strainer, 20 mesh*
Gate valve*
Hose bib*
*Field supplied and field installed
56 990-5801C-001
Technical Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
na2766a
Item Description
Expansion tank*
Tank fill*
Fluid-cooler
Airtrol fitting*
Temperature and pressure gauges*
Air vent*
Hose bibs*
Gate valve*
Balancing valve*
Check valve
Pump package*
Flow switch
Strainer, 20 mesh*
InRow DX
*Field supplied and field installed
990-5801C-001 57
ACRD100, ACRD200, ACRD600, and ACRD600P Series Outdoor Heat Exchanger Data
35.0–40.6 2140 48
ACCD75216 (95.0–105.1) 59 (4,530) 1 0.8 22 mm 18 mm (105.8) 2.35 1.24
46.0 4280 89
ACCD75217 (114.8) 62 (9,060) 2 1.6 28 mm 22 mm (196.2) 4.30 2.27
35.0–40.6 2140 48
ACCD75218 (95.0–105.1) 59 (4,530) 1 0.6 22 mm 18 mm (105.8) 2.35 1.24
46.0 4280 89
ACCD75219 (114.8) 62 (9,060) 2 1.3 28 mm 22 mm (196.2) 4.30 2.27
35.0–40.6 2140 48
ACCD75220 (95.0–105.1) 59 (4,530) 1 0.6 22 mm 18 mm (105.8) 2.35 1.24
58 990-5801C-001
Outdoor Heat Exchanger Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
46.0
ACCD75229 67.2** 64.5** 7488 (16,045) 3 3.19
(114.8)
35.0–40.6
ACCD75230 67.8** 65.0** 7780 (16,672) 3 3.13
(95.0–105.1)
46.0
ACCD75231 67.8** 64.5** 7488 (16,045) 3 3.19
(114.8)
35.0–46.0
ACCD75232 60.7 56.6 5133 (11,000) 2 1.20
(95.0–114.8)
35.0–46.0
ACCD75232-C 60.7 56.6 5133 (11,000) 2 1.32
(95.0–114.8)
–40.0–46.0
ACCD75232-40C*** 60.7 56.6 5133 (11,000) 2 1.32
(–40.0–114.8)
35.0–46.0
ACCD75233-C 60.7 56.6 5133 (11,000) 2 1.44
(95.0–114.8)
35.0–40.6
ACCD75234* 64 59 5400 (11,500) 1 1.45
(95.0–105.1)
35.0–40.6
ACCD75235* 64 59 5400 (11,500) 1 1.45
(95.0–105.1)
990-5801C-001 59
ACRD100, ACRD200, ACRD600, and ACRD600P Series Outdoor Heat Exchanger Data
Air Capacity
Ambient Temp Fan – Con- Weight –
Sound Quantity – Unit –
Model – °C (°F) Qty. nection kg (lb)
Pressure* l/s (CFM) kW MBH/1°F kW/1°C
Size
TD TD
4760
ACFC75210 40.0 (104.0) 68 2 2.0 1 3/8 in. 205 (450) 3.20 1.69
(10,100)
ACFC75255 35.0 (95.0) 65 2380 (5050) 1 1.0 1 1/8 in. 150 (330) 2.36 1.24
ACFC75256 35.0 (95.0) 62 4220 (8950) 2 1.6 1 1/2 in. 90 (198) 2.50 1.32
5500
ACFC75257 40.0 (104.0) 56 2 1.4 2 in. 151 (333) 3.30 1.74
(11,650)
60 990-5801C-001
Outdoor Heat Exchanger Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
Electrical Data
Air-Cooled Condensers (ACRD100 Series)
Voltage, Phase,
Model Receiver Model Receiver Qty. FLA* MCA* MOP*
Frequency
208-240V, 1 ph,
ACCD75214 ACAC75009 1 4.8 15 15
60 Hz
208-240V, 1 ph,
ACCD75215 ACAC75009 2 4.8 15 15
60 Hz
380-415V, 3 ph,
ACCD75216 ACAC75009 1 1.35 N/A N/A
50 Hz
380-415V, 3 ph,
ACCD75217 ACAC75009 1 2.7 N/A N/A
50 Hz
220-240V, 1 ph,
ACCD75218 ACAC75009 1 3.0 N/A N/A
50 Hz
220-240V, 1 ph,
ACCD75219 ACAC75009 1 6.0 N/A N/A
50 Hz
220-240V, 1 ph,
ACCD75220 ACAC75009 1 3.0 N/A N/A
50 Hz
* Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
NOTE: ACCD75220 is CCC certified for use in China.
NOTE: ACCD75216, ACCD75217, and ACCD75218 are CMIM compliant.
Voltage, Phase,
Model Receiver Model Receiver Qty. FLA* MCA* MOP*
Frequency
208-240 V, 3 ph,
ACCD75228 ACAC75014 1 N/A 10.7 15
60 Hz
208-240 V, 3 ph,
ACCD75229 ACAC75014 1 N/A 10.7 15
60 Hz
460-480 V, 3 ph,
ACCD75230 ACAC75014 1 N/A 6.5 15
60 Hz
460-480 V, 3 ph,
ACCD75231 ACAC75014 1 N/A 6.5 15
60 Hz
230 V, 1 ph, 50
ACCD75232 ACAC75013 1 6.0 N/A N/A
Hz
230 V, 1 ph, 50
ACCD75232-C ACAC75015 1 6.0 N/A N/A
Hz
ACCD75232- 230 V, 1 ph, 50
ACAC75015 1 7.0 N/A N/A
40C Hz
230 V, 1 ph, 60
ACCD75233-C ACAC75015 1 6.0 N/A N/A
Hz
208-240 V, 3 ph,
ACCD75234* ACAC75014 1 6.4 8.8 15
60 Hz
460-480 V, 3 ph,
ACCD75235* ACAC75014 1 2.9 4.0 15
60 Hz
* Make-to-order. Additional lead times may apply.
**Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
NOTE: ACCD75232-C is CMIM compliant.
990-5801C-001 61
ACRD100, ACRD200, ACRD600, and ACRD600P Series Outdoor Heat Exchanger Data
Voltage, Phase,
Model Frequency FLA* MCA* MOP*
* Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
NOTE: ACFC75257 is CMIM compliant.
Dimensions
ACCD75234, ACCD75235
NOTE: Dimensions are shown in mm (in.).
NOTE: Make-to-order. Additional lead times may apply.
2055
(80.90
)
1387
)
(54.62
na6253a
1472 1175
(57.94 (46.24
) 1243
) )
(48.92
1318 824
(51.88 )
) (32.45
1317 973
(51.87
) (38.3)
1003
)
( 9.48
3
62 990-5801C-001
Outdoor Heat Exchanger Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACCD75232
NOTE: Dimensions are shown in mm (in.).
NOTE: Condensers shown have eight 22-mm (0.875 in.) mounting holes on
their lower rails.
2167
(85.31
)
1248.5
(49.15
) 700
)
(27.56
na5854a
1000
(39.37 1025 1050
)
) 1110
(40.35 ( 1.34
4
) (43.7)
1344
)
(52.91 700
)
( 7.56
na5855a
1000
(39.37 1030 1050
)
) 1110
(40.55 (41.34
) (43.7)
990-5801C-001 63
ACRD100, ACRD200, ACRD600, and ACRD600P Series Outdoor Heat Exchanger Data
ACCD75214
NOTE: Dimensions are shown in mm (in.).
958
(37.71)
na2891a
762 1085
(30.00) (42.72)
ACCD75215
NOTE: Dimensions are shown in mm (in.).
958
(37.71)
na2895a
1016 1085
(40.00) (42.72)
1442
(56.77)
890
na2893a
(35.04)
900 900
(35.43) (35.43
64 990-5801C-001
Outdoor Heat Exchanger Data ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACCD75217, ACCD75219
NOTE: Dimensions are shown in mm (in.).
2222
(87.48
)
890
)
(35.04
na2896a
1680
(66.14 900
)
)
(35.43
ACFC75210
NOTE: Dimensions are shown in mm (in.).
958
)
(37.72
na2890a
1524
(60.00 1079
) )
(42.50
ACFC75255
NOTE: Dimensions are shown in mm (in.).
958
)
(37.72
na2899a
762 1079
)
(30.00
) (42.50
990-5801C-001 65
ACRD100, ACRD200, ACRD600, and ACRD600P Series Outdoor Heat Exchanger Data
ACFC75256
NOTE: Dimensions are shown in mm (in.).
2222
(87.48)
890
( 5.04)
3
na2894a
1680
(66.14) 900
(35.43)
ACFC75257
NOTE: Dimensions are shown in mm (in.).
2942
(115.8
3)
890
)
(35.04
na2898a
2400
(94.50
) 1260
)
(49.60
66 990-5801C-001
Worldwide Customer Support
Customer support for this or any other product is available at no charge in any of the
following ways:
• Visit the Schneider Electric Web site to access documents in the Schneider
Electric Knowledge Base and to submit customer support requests.
- www.schneider-electric.com (Corporate Headquarters)
Connect to localized Schneider Electric Web sites for specific countries, each of
which provides customer support information.
- www.schneider-electric.com/support/
Global support searching Schneider Electric Knowledge Base and using
esupport.
• Contact the Schneider Electric Customer Support Center by telephone or e-mail.
Local, country-specific centers: go to www.schneider-electric.com/support/
contactwww.schneider-electric.com > Support > Operations around the
world for contact information.
For information on how to obtain local customer support, contact the representative
or other distributors from whom you purchased your product.
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com