Catalogue
Catalogue
Catalogue
1
Proposte
Lamborghini:
Continual
innovation
Lamborghini Caloreclima Company
steadily engages itself in the search for
technical solutions aimed at introducing
innovations into its products.
Lamborghini supplies a brand-new range
of products capable of meeting the
market’s needs, these becoming more and
more demanding.
Here is the philosophy adopted by
“Proposte Lamborghini 2004”.
You will find below the most attractive
news of this edition.
Enjoy your choice!
Quality
above all
Lamborghini is renowned all over the
world for the high quality featuring its
products, which are type approved in
most countries.
Innovations
2
Index
Steel boilers
Condensing stainless steel boilers
Steel boilers
Air heaters
Gas “Wall-hung” air heaters
“Industrial” air heaters
Box zone
3
Water treatment system
Water softeners
Filters
Dosagers pump
Polifosphate dosagers
Accessories
4
High-efficiency steel boilers
In compliance with:
DIRECTIVE 90/396/EEC ON GAS APPLIANCES
DIRECTIVE L.V. 72/23/EEC (Act No. 791 of 18/10/77)
EFFICIENCY DIRECTIVE 92/42/EEC
SILVER (S-BS)
SILVER
SILVER “sovrap.”
NEINOX BT/G
NEINOX BT
NEINOX
MINIA R-MINIA CI
MINIA CB
MINIA N CBX
MEGA PREX BT
MEGA PREX
MEGA PREX SL
DUO PREX
13,7 22 29,9 30,5 31 31,7 70 93 100 105 150 186 232 300 407 581 1162 2907
kW
5
Condensation gas steel boilers
¥SILVER S - SILVER BS
– Ultra high-efficiency stainless steel condensation proof boiler for
heating (SILVER S) and hot sanitary water heating and supply (SILVER
BS).
- Ideal for low-temperature system operation.
- Boiler shell in stainless steel AISI 316 Ti.
- Flame injection wet bottom cylindrical furnace
- Flues made up of plates being printed on the inner surface whose
special corrugated shape increases turbulence thus allowing
condensation.
- Low NOx emissions in the environment.
- Operation through gas blown burners.
components.
40
Ø80
¥ Certification
850
Ø80
930
SILVER 31 S
600 865
SILVER
40
Ø80
65
1255
Ø80
SILVER 31 BS
Boiler Furnace power Useful efficiency Maximum pressure Power voltage Hot sanitary Weight
type a 50/30°C a 80/60°C water supply
min./max. min./max. bar
kW kcal/h % % risc. sanit. V/Hz l/min. Kg
SILVER 31 S 14÷ 30,8 12.100÷ 26.500 108,5/107 97,8/97 3 - 230/50 - 158
SILVER 31 BS 14÷ 30,8 12.100÷ 26.500 108,5/107 97,8/97 3 6 230/50 12,5 205
6
Condensation gas steel boilers
¥SILVER
– Ultra high-efficiency boiler.
- Boiler shell in stainless steel AISI 316 Ti.
- Flame injection wet bottom cylindrical furnace
- Flues made up of plates being printed on the inner surface whose
special corrugated shape increases turbulence thus allowing
condensation.
- Ideal for low-temperature system operation.
- Low NOx emissions in the environment.
- Operation through gas blown burners.
- Heat loss preventing high-thickness insulation.
- External instrument panel for unit control and adjustment.
¥ Maintenance
– Maintenance is made simple thanks to easy accessibility to internal
components.
¥ Certification
– SILVER boilers are EC type approved.
¥ Hydraulic connections
a6 a1
160
Øi 151
65 (mod. 110÷ 150) a3
a3 Low temperature system return DN 50 (mod. 44÷ 80) and DN 65
1014
Ø1
900
881
(mod. 110÷ 150) 30 a4
a2
a4 System feeding/discharge inlet Ø _”
530
503
a5 Condensation discharge Ø _”
174
a6 Temperature control pocket a5
126
680 785
746 1430
1462
SILVER 44 ÷ SILVER 80
a6 a1
160
S I LV E R CALORECLIMA
Øi 181
a3
1114
Ø1
1000
980
45 a4
a2
580
553
174
a5
126
780 785
Combustion path Detail of the STAINLESS STEEL 846 1723
along the flue gas plates AISI 316 Ti flue gas plates 1755
7
Condensation gas steel boilers
¥ Maintenance
– Maintenance is made simple thanks to easy accessibility to internal
components.
¥ Certification
– SILVER boilers are EC type approved.
200 200
a6 a8 a6 a7 a1
S I LV E R CALORECLIMA
¥ Hydraulic connections
Øi 181
a1 System delivery DN 65
a2 Medium temperature system Ø1
45
return DN 65 a4
2089
DN 65 S I LV E R CALORECLIMA
a6 a5
1670
1642
Øi 181
_” Ø1
980
45
a5 Condensation discharge Ø _” a4
388
580
553
8
High-efficiency steel boilers
¥NEINOX BT/G
Ultra high-efficiency and polluting emissions lowered
to the minimum
– Ideal boilers for small-size buildings heating.
- Low variable temperature boilers.
- Ultra low NOx emissions in the environment.
- Operation through low NOx emissions light oil burner ECO LN.
- Steel boiler shell with flame injection wet bottom cylindrical furnaces.
- Heat resistant protection of the combustion chamber allowing easy
control of the flue gas temperature.
G
- Two ultra thick steel concentric flues enabling even distribution of heat
and avoiding condensation.
- Heat loss preventing high-thickness insulation.
- Standard special front insulation.
- Door opening adjustable arm.
- Stainless steel turbolators.
- External instrument panel for unit control and adjustment.
- Control thermometer pocket.
¥ Optional accessories
– For optional accessories intended for NEINOX BT/G boilers see page 85.
¥ Certification
– NEINOX BT/G boiler is EC type approved. 160
a1
a2
400
273
a3
Boiler Furnace power Useful efficiency Maximum Power voltage Heating Heating Boiler Flue Weight
type a 50/30°C a 80/60°C heating pressure delivery return discharge connection
kW kcal/h 100 % 100 % 30 % bar V/Hz Ø a1 Ø a2 Ø a3 Ø a4 Kg
NEINOX BT 31G 34 29.240 93 91,6 91,2 3 230/50 1” 1” 1” 30 145
9
High-efficiency steel boilers
¥NEINOX BT
– Ideal boilers for small-size buildings heating.
- Low variable temperature boilers for maximum efficiency.
- Ultra low NOx emissions in the environment.
- Operation through of low light oil or gas burners.
- Steel boiler shell with flame injection wet bottom cylindrical furnaces.
- Heat resistant protection of the combustion chamber allowing to keep
high flue gas temperature.
- Two ultra thick steel concentric flues enabling even distribution of heat
and avoiding condensation.
- Heat loss preventing high-thickness insulation.
- Standard special front insulation.
- Door opening adjustable arm.
- Stainless steel turbolators.
- External instrument panel for unit control and adjustment.
- Control thermometer pocket.
- NEINOX BT boilers can be combined with BITHERM boilers.
¥ Optional accessories
– For optional accessories intended for NEINOX BT boilers see page 85.
¥ Certification
– NEINOX BT boilers are EC type approved.
160
a1
a2
400
273
a3
Boiler Furnace power Useful efficiency Maximum Power voltage Heating Heating Boiler Flue Weight
type a 50/30°C a 80/60°C heating pressure delivery return Discharge connection
kW kcal/h 100 % 100 % 30 % bar V/Hz Ø a1 Ø a2 Ø a3 Ø a4 Kg
NEINOX BT 31 34 29.240 93 91,6 91,2 3 230/50 1” 1” 1” 30 145
10
High-efficiency steel boilers
¥NEINOX
– Ideal boilers for small- and medium-size buildings heating.
- Steel boiler shell with flame injection wet bottom cylindrical furnaces.
- Ultra low NOx emissions in the environment.
- Operation through of low light oil or gas burners.
- Heat loss preventing high-thickness insulation.
- Standard special front insulation.
- Door opening adjustable arm.
- Stainless steel turbolators.
- Ultra thick steel flues.
- External instrument panel for unit control and adjustment.
- Control thermometer pocket.
- NEINOX boilers can be combined with BITHERM boilers.
¥ Optional accessories
– For optional accessories intended for NEINOX boilers see page 85.
¥ Certification
– NEINOX boilers are EC type approved.
160
a1
a4
Ø 120
E
a2
C
a3
B
Insulation D A
Boiler Furnace power Useful efficiency Maximum Power Heating Heating Boiler Flue A B C D E Weight
type % heating pressure voltage delivery return discharge connection
kW kcal/h 100 % 30 % bar V/Hz Ø a1 Ø a2 Ø a3 Ø a4 mm. mm. mm. mm. mm. Kg
NEINOX 22 24 20.700 91,7 91,4 3 230/50 1” 1” 1” 127 525 280 460 780 620 110
NEINOX 31 34 29.240 91,6 91,2 3 230/50 1” 1” 1” 127 580 300 500 810 670 130
NEINOX 40 44 37.840 91,3 91,1 3 230/50 1 1/4” 1 1/4” 1” 178 660 320 550 920 760 160
NEINOX 50 55 47.300 91,2 91 3 230/50 1 1/4” 1 1/4” 1” 178 660 320 550 920 760 160
NEINOX 70 77 66.220 91,5 91,3 3 230/50 1 1/4” 1 1/4” 1” 178 660 320 550 1.010 760 200
11
High-efficiency steel boilers
•MINIA R - MINIA CI
– High-efficiency steel boilers for hot sanitary water heating (mod. R) and
instantaneous supply, ideal for domestic heating.
- Ultra thick steel boiler shell.
- Instantaneous exchanger for hot sanitary water (mod. CI).
- Burner fitted with external air intake.
- Expansion tank 101.
- Heating circuit circulator.
- Hydraulic 3-way valve (mod. CI).
- Stainless steel turbolators.
- IPX4D protection degree.
• Optional accessories
– For optional accessories intended for MINIA R – MINIA CI boilers see
page 85.
• Certification
– MINIA R and MINIA CI boilers are EC type approved.
450 610
a4
a2 a5
a1
850
Ø100
620
a3
Boiler Furnace power Useful efficiency% Maximum Power Hot sanitary Heating Heating Boiler Entrata Uscita Weight
type heating pressure voltage water production delivery return discharge acqua F acqua C
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/h Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 kg
MINIA 31 R 33,9 29.154 90,26 91,02 3 - 230/50 - 60 3/4” 3/4” 1/2” - 72
MINIA 31 CI 33,9 29.154 90,26 91,02 3 6 230/50 14,5 60 3/4” 3/4” 1/2” 1/2” 80
12
High-efficiency steel boilers
•MINIA CB
– High-efficiency proof steel boilers for hot sanitary water heating supply,
ideal for domestic heating.
- Ultra thick steel boiler shell.
- 120 Lt. storage boiler in painted steel for big amounts of hot sanitary
water.
- 12 Lt. expansion tank for heating circuit.
- Sanitary and heating circuit circulators.
- Stainless steel turbolators.
- IPX4D protection degree.
• Optional accessories
– For optional accessories intended for MINIA CB boilers
see page 85.
600 150 600 179
– External probe allowing variable temperature management
within the operation range intended for the boiler. a1
– Room thermostat or “remote” control with/without
a2 1
external probe.
Ø100
1240
Boiler Furnace Useful Maximum Power Hot sanitary water Heating Heating Air Cold water Hot water Burner Light oil Gas Weight
type power efficiency % heating voltage production ΔT 30°C delivery return change inlet outlet suction unit connection connection
kW kcal/h 100 % 30 % pressure V/Hz l/h Ø a2 Ø a3 Ø a4 Ø a6 Ø a5 Ø a1 Ø a7 Ø a8 kg
MINIA 31 CB 33,9 29.154 90,26 91,02 3 6 230/50 765 3/4” 3/4” 3/4” 3/4” 3/4” 80 3/4” 3/8” 202
13
High-efficiency steel boilers
• Certification
– MINIA N CBX boilers are EC type approved.
a6 Ø 100
89
a1
a2
47,5 47,5
1400
a7
1215,5
1125,5
a8 a7
a5
660
635
424,5
474
a3
252
a4
68
79,5
Boiler Furnace Useful Maximum Power Hot sanitary water Heating Heating Air Cold water Hot water Burner Light oil Gas Weight
type power efficiency % heating voltage production ΔT 30°C delivery return change inlet outlet suction unit connection connection
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/h Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Ø a6 Ø a7 Ø a8 kg
MINIA N 31 CBX 34,8 29.930 91 91,5 3 6 230/50 800 3/4” 3/4” 3/4” 3/4” 3/4” 80 3/8” 3/4” 150
14
High-efficiency steel boilers
¥MEGA PREX BT
Low temperature and low emission
- Pressurized boilers, ideal for medium/big-size buildings heating.
- Low variable temperature for maximum efficiency.
- Steel boiler shell featuring 3 pass exaust way
- Low NOx emissions in the environment.
- Heat resistant protection of the combustion chamber allowing to keep
high flue gas temperature.
- Two ultra thick steel concentric flues enabling even distribution of heat
and avoiding condensation.
- Stainless steel turbolators.
- Hinged opening door.
- Standard special front insulation.
- Heat loss preventing ultra thick insulation.
- Vertically arranged shell and tube structure, placed over the furnace.
- Reduced width (<90 cm).
- External instrument panel for unit control and adjustment.
- Control thermometer pocket.
- Light oil and gas burner operation.
I L
¥ Installation and Maintenance a2 a3 a5 a6 a1
160
- A burner can be fitted onto the boiler plate.
M
- Maintenance is made simple thanks to easy accessibility to internal
components.
a8
¥ Certification
– MEGA PREX BT boilers are EC type approved. a9
H
D
a7
a4
E
B A
C A1
boiler A A1 B C D E H I L M weight
type mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. kg
MEGA PREX BT 100 660 715 1.252 1.655 978 374 1.225 565 740 52 625
MEGA PREX BT 150 660 715 1.252 1.655 978 374 1.225 565 740 52 655
MEGA PREX BT 180 700 755 1.412 1.815 1.082 410 1.345 565 900 52 750
MEGA PREX BT 230 700 755 1.412 1.815 1.082 410 1.345 565 900 52 790
MEGA PREX BT 290 745 800 1.462 1.865 1.210 460 1.500 615 900 57 900
MEGA PREX BT 350 820 875 1.744 2.147 1.340 495 1.630 665 1.075 53 1.100
MEGA PREX BT 400 820 875 1.744 2.147 1.340 495 1.630 665 1.075 53 1.160
MEGA PREX BT 460 890 945 1.744 2.147 1.422 520 1.750 665 1.075 50 1.380
MEGA PREX BT 580 890 945 1.744 2.147 1.422 520 1.750 665 1.075 50 1.450
15
High-efficiency steel boilers
• Certification
- MEGA PREX boilers are EC type approved.
16
High-efficiency steel boilers
¥ Certification
- MEGA PREX boilers are EC type approved.
17
High-efficiency steel boilers
boiler furnace power useful efficiency maximum power heating heating Instrument Boiler expansion flue burner thermostat
type % heating pressure voltage delivery return connection discharge tank connection connection socket
kW kcal/h 100 % 30 % bar V/Hz DN a1 DN a2 Ø a3 Ø a4 Ø a5 Ø a6 Ø a7 Ø a8
MEGA PREX 90 102 87.740 91,18 89,7 5 230/50 50 50 1” 1” - 200 130 1/2”
MEGA PREX 100 115 98.570 91,3 90,11 5 230/50 50 50 1” 1” - 200 130 1/2”
MEGA PREX 115 127 109.480 90,63 90,05 5 230/50 50 50 1” 1” - 200 130 1/2”
MEGA PREX 150 165 142.050 90,42 91,15 5 230/50 50 50 1” 1” - 250 160 1/2”
MEGA PREX 180 203 174.620 90,73 90,36 5 230/50 50 50 1” 1” - 250 160 1/2”
MEGA PREX 230 252 217.240 90,63 90,23 5 230/50 65 65 1” 1” - 250 180 1/2”
MEGA PREX 290 314 270.690 90,91 89,74 5 230/50 65 65 1” 1” - 250 180 1/2”
MEGA PREX 340 378 324.930 90,18 89,91 5 230/50 80 80 1” 1” 1 1/4”** 250 225 1/2”
MEGA PREX 400 442 380.100 90,04 89,82 5 230/50 80 80 1” 1” 1 1/4”** 250 225 1/2”
MEGA PREX 460 504 443.550 90,29 90,07 5 230/50 80 80 1” 1 1/4” 1 1/4” 300 225 1/2”
MEGA PREX 580 633 544.750 90,22 89,94 5 230/50 80 80 1” 1 1/4” 1 1/4” 300 225 1/2”
MEGA PREX 700 760 653.300 90,05 89,76 5 230/50 100 100 1” 1 1/4” 1 1/2” 350 280 1/2”
MEGA PREX 800 889 764.500 90,14 89,89 5 230/50 100 100 1” 1 1/4” 1 1/2” 350 280 1/2”
MEGA PREX 930 1.018 875.700 90,20 89,94 5 230/50 100 100 1” 1 1/4” 1 1/2” 350 280 1/2”
MEGA PREX 1050 1.139 980.020 90,17 89,86 5 230/50 125 125 1” 1 1/4” 1 1/2” 400 280 1/2”
MEGA PREX 1150 1.265 1.088.640 90,78 90,13 5 230/50 125 125 1” 1 1/4” 1 1/2” 400 280 1/2”
MEGA PREX 1400 1.528 1.314.410 90,23 90,02 5 230/50 150 150 1” 1 1/4” 1 1/2” 400 320 -
MEGA PREX 1550 1.719 1.479.060 90,22 90,09 5 230/50 150 150 1” 1 1/4” 1 1/2” 400 320 -
MEGA PREX 1750 1.907 1.640.190 90,36 90,09 5 230/50 150 150 1” 1 1/4” 1 1/2” 400 320 -
MEGA PREX 2000 2.170 1.866.900 90,39 90,23 5 230/50 200 200 1 1/2” 1 1/4” 2” 500 360 -
MEGA PREX 2300 2.554 2.196.990 90,08 89,81 5 230/50 200 200 1 1/2” 1 1/4” 2” 500 360 -
MEGA PREX 2900 3.197 2.749.400 90,25 89,94 5 230/50 200 200 1 1/2” 1 1/4” 2” 550 400 -
* Only one connection
C
M L
116
C a2 a3 a5 a1
M L
a2 a3 a5 a1
160
E
a7
a8
a7
H
a6
H
D
a6
D
a4 a4
A A
B A1 B A1
boiler A A1 B C D E H L M weight
type mm. mm. mm. mm. mm. mm. mm. mm. mm. kg
MEGA PREX 90 700 750 755 1.195 415 56 855 265 484 240
MEGA PREX 100 700 750 755 1.195 415 56 855 265 484 240
MEGA PREX 115 700 750 755 1.195 415 56 855 265 484 240
MEGA PREX 150 750 800 1.000 1.440 440 56 905 475 484 320
MEGA PREX 180 750 800 1.000 1.440 440 56 905 475 484 320
MEGA PREX 230 850 900 1.250 1.690 490 56 1.005 700 484 440
MEGA PREX 290 850 900 1.500 1.940 490 56 1.005 980 484 500
MEGA PREX 340 890 940 1.502 1.900 500 80 1.015 850 600 540
MEGA PREX 400 890 940 1.502 1.900 500 80 1.015 850 600 540
MEGA PREX 460 1.110 1.160 1.502 1.950 610 80 1.205 850 660 800
MEGA PREX 580 1.110 1.160 1.792 2.240 610 80 1.205 1.150 660 900
MEGA PREX 700 1.240 1.290 1.753 2.255 675 82 1.335 1.100 710 1.140
MEGA PREX 800 1.240 1.290 2.003 2.500 675 82 1.335 1.200 710 1.340
MEGA PREX 930 1.240 1.290 2.003 2.500 675 82 1.335 1.200 710 1.340
MEGA PREX 1050 1.390 1.440 2.003 2.500 750 83 1.485 1.200 710 1.760
MEGA PREX 1150 1.390 1.440 2.003 2.500 750 83 1.485 1.200 710 1.760
MEGA PREX 1400 1.270 1.470 2.300 2.850 880 - 1.630 1.300 795 2.600
MEGA PREX 1550 1.270 1.470 2.300 2.850 880 - 1.630 1.300 795 2.600
MEGA PREX 1750 1.270 1.470 2.510 3.060 880 - 1.630 1.850 735 2.750
MEGA PREX 2000 1.400 1.600 2.510 3.190 945 - 1.760 1.550 870 3.650
MEGA PREX 2300 1.400 1.600 2.770 3.450 945 - 1.760 1.950 870 3.900
MEGA PREX 2900 1.670 1.870 2.770 3.450 1.080 - 2.030 2.050 870 5.200
18
High-efficiency steel boilers
¥MEGA PREX SL
- Pressurized boilers, ideal for medium/big-size buildings heating.
- Ultra reduced width (<80 cm), for easy replacement in existing heating
plants.
- Flame injection furnace steel boiler.
- Vertically arranged shell and tube structure, placed over the furnace.
- Light oil and gas burner operation.
- External instrument panel for unit control and adjustment.
- Heat loss preventing ultra thick insulation.
- Standard special front insulation.
- Hinged opening door.
- Stainless steel turbolators.
- Ultra thick steel flues.
- Control thermometer pocket.
¥ Certification
- MEGA PREX SL boilers are EC type approved.
80
160
160
Ø 250
Ø 250
1200
1290
a6 a6
900
950
a4 a4
440
460
MEGA PREX SL 230 - MEGA PREX SL 290 MEGA PREX SL 340 - MEGA PREX SL 400
boiler furnace power useful efficiency maximum power heating heating Instrument Boiler Safety burner weight
type % heating pressure voltage delivery return connection discharge valve connection
kW kcal/h 100 % 30 % bar V/Hz DN a1 DN a2 Ø a3 Ø a4 Ø a5 Ø a6 kg
MEGA PREX SL 230 255 219.300 91,7 90,85 5 230/50 65 65 1” 1” 1” 155 720
MEGA PREX SL 290 319 274.340 90,86 90,56 5 230/50 65 65 1” 1” 1” 155 780
MEGA PREX SL 340 384 330.240 90,98 90,71 5 230/50 80 80 1 1/4” 1 1/4” 1” 180 900
MEGA PREX SL 400 448 385.280 90,84 90,62 5 230/50 80 80 1 1/4” 1 1/4” 1” 180 980
19
High-efficiency steel boilers
¥DUO PREX
- Pressurized boilers ideal for medium/big-size buildings heating.
- 2 superposed steel boiler shells with flame injection.
- High heating power with reduced overall dimensions.
- Operation through gas blown burners.
- External instrument panel for unit control and adjustment.
- Heat loss preventing ultra thick insulation.
- Standard special front insulation.
- Hinged opening door.
- Stainless steel turbolators.
- Ultra thick steel flues.
- Control thermometer pocket.
¥ Certification
- DUO PREX boilers are EC type approved.
C E E
a3 a1
a6 a5
a4 a2
H
G
a6 a5
D1
D1
F
a4
D
D
A
A1 185
boiler A A1 B C D D1 E F G H weight
type mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. kg
DUO PREX 180 700 750 755 1470 415 1245 270 780 1610 1693 454
DUO PREX 200 700 750 755 1470 415 1245 270 780 1610 1693 476
DUO PREX 230 700 750 755 1470 415 1245 270 780 1610 1693 500
DUO PREX 300 750 800 1000 1745 440 1320 295 830 1710 1793 695
DUO PREX 360 750 800 1000 1745 440 1320 295 830 1710 1793 725
DUO PREX 460 850 900 1250 2000 490 1470 345 930 1910 1993 870
DUO PREX 580 850 900 1250 2000 490 1470 345 930 1910 1993 1116
boiler furnace power useful efficiency maximum power voltage heating heating Instrument Boiler flue burner
type % heating pressure delivery return connection discharge connection connection
kW kcal/h 100 % 30 % bar V/Hz DN a1 DN a2 Ø a3 Ø a4 Ø a5 Ø a6
DUO PREX 180 204 175.800 91,18 90,3 5 230/50 65 65 1” 1” 200 120
DUO PREX 200 230 198.000 90,87 90,3 5 230/50 65 65 1” 1” 200 120
DUO PREX 230 257 220.800 90,66 90,15 5 230/50 65 65 1” 1” 200 120
DUO PREX 300 333 286.400 90,69 90,25 5 230/50 80 80 1” 1” 250 155
DUO PREX 360 411 353.200 90,51 90,3 5 230/50 80 80 1” 1” 250 155
DUO PREX 460 512 440.000 90,82 90 5 230/50 80 80 1” 1” 250 155
DUO PREX 580 639 549.400 90,92 90,2 5 230/50 80 80 1” 1” 250 155
20
High efficiency cast iron boilers
SEC B
EXA
VIT
BIA F
BIG F
BIG FK
In compliance with:
DIRECTIVE 90/396/EEC ON GAS APPLIANCES
DIRECTIVE L.V. 72/23/EEC (Act No. 791 of 18/10/77)
EFFICIENCY DIRECTIVE 92/42/EEC
SEC B
EXA
VIT
BIAF
BIGF
BIGFK
20,9 30,6 32,55 46,5 93,3 107 200 252 650
kW
21
High efficiency cast iron boilers
•SEC B
- Basement boiler suitable for hot sanitary water heating and supply.
- Cast iron boiler shell.
- Stainless steel 90 Lt. boiler.
- Sanitary circuit circulator.
- Combustion chamber and exchanger being designed for over 90%
guaranteed efficiency.
- Operation through gas blown burners.
- Instrument panel for proper operation control.
- Heat loss preventing ultra thick insulation.
- Suitable for clock controller fitting.
• Certificazione
- SEC B boilers are EC type approved.
500 600
a4
a6
a5
1500
a1
1248
Ø105
Ø130
711
a2 a3
542
Code Description
274
85
boiler furnace power useful efficiency max. pressure power hot sanitary water heating heating Boiler Boiler Boiler Ricircolo weight
type % bar voltage supply ΔT 30°C delivery return discharge delivery return
kW kcal/h 100 % 30 % heating sanitary V/Hz l/h Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Ø a6 kg
SEC 30 B 34 29.240 90 92 4 6 230/50 900 1 ˚” 1 ˚” 1/2” 3/4” 3/4” 3/4” 135
22
High efficiency cast iron boiler
•EXA
- Basement boiler suitable for hot sanitary water heating and supply.
- Cast iron boiler shell.
- Combustion chamber and exchanger being designed for over 90%
guaranteed efficiency.
- Operation through gas blown burners.
- Heat loss preventing ultra thick insulation.
- Instrument panel for proper operation control.
- EXA boilers can be combined with PAC S and BITHERM boilers.
• Certification
- EXA boilers are EC type approved.
450 A a1
C
850
Code Description B
08515320 EXA-PAC S electrical connection kit.
64
80
85
boiler furnace power useful efficiency maximum sanitary power voltage heating heating Boiler A B C weight
type % heating pressure delivery return discharge
kW kcal/h 100% 30% bar V/Hz DN a1 DN a2 Ø a3 mm. Ø mm. Ø mm. Kg
EXA 20 23,25 19.995 90 92 4 230/50 1 ˚” 1 ˚” 1/2” 420 105 130 80
EXA 27 34 29.240 90 92 4 230/50 1 ˚” 1 ˚” 1/2” 420 105 130 105
EXA 32 38,6 33.196 90,4 92,08 4 230/50 1 ˚” 1 ˚” 1/2” 420 105 130 105
EXA 40 51,4 44.204 90,4 92,14 4 230/50 1 ˚” 1 ˚” 1/2” 620 105 130 130
EXA 50 64,1 55.126 90,6 92,23 4 230/50 1 ˚” 1 ˚” 1/2” 620 105 180 155
EXA 60 77,2 66.392 90,4 92,17 4 230/50 1 ˚” 1 ˚” 1/2” 820 125 180 180
EXA 70 89,7 77.142 90,7 92,25 4 230/50 1 ˚” 1 ˚” 1/2” 820 125 180 205
EXA 80 103,2 88.752 90,4 92,2 4 230/50 1 ˚” 1 ˚” 1/2” 920 125 180 230
23
High efficiency cast iron boiler
•VIT
- Basement boiler suitable for hot sanitary water heating and supply.
- Cast iron boiler shell.
- Instantaneous exchanger for hot sanitary water (models VIT CI).
- Pre-assembled and pre-calibrated light gas burner, complete with
nozzle pre-heater.
- Burner fitted with external air inlet.
- Heating circuit 10 Lt. expansion tank.
G
- Heating circuit circulator.
- 3-way electrical valve.
- Combustion chamber and exchanger being designed for over 90%
guaranteed efficiency.
- Heat loss preventing ultra thick insulation.
- Instrument panel for proper operation control.
- IP X4D protection degree.
• Certification
- VIT boilers are EC type approved (only for light gas operation).
• Range of product
- VIT R boiler: only for heating.
- VIT CI: for hot sanitary water heating and supply.
boiler furnace power useful efficiency maximum pressure power hot sanitary water heating heating Cold waterHot water weight
type % bar voltage supply ΔT 30°C delivery return inlet outlet
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/min. Ø a1 Ø a2 Ø a3 Ø a4 kg
VIT 30 R 34,76 29.900 91,5 92,2 3 - 230/50 - 3/4” 3/4” 1/2” - 160
VIT 30 CI 34,76 29.900 91,5 92,2 3 6 230/50 2,5÷ 15,5 3/4” 3/4” 1/2” 1/2” 160
24
High efficiency cast iron boiler
•“proof” BIA F
- Proof basement boilers suitable for hot sanitary water heating and supply.
- Cast iron boiler shell.
- Combustion chamber and exchanger being designed for over 90%
guaranteed efficiency.
- Stainless steel boiler, covered with high-density polystyrene: 90 Lt. for
model BIA 30-90 and 120 Lt. for model BIA 40-120.
- Burner fitted with external air inlet.
- Heating circuit 10 Lt. expansion tank.
- Sanitary circuit 4 Lt. expansion tank.
- Heating and sanitary circuit circulators.
- IP X4D protection degree.
• Certification
- BIA F boilers are EC type approved.
Gas thermal couplings are supplied on demand. Please contact
our Sales Department to be informed on the delivery time.
Ø 130 Ø 130
a1 a1
a6 a6
1400
1400
a2 a2
1037
1037
a3 a3
a5 a5
a4 a4
boiler furnace useful maximum power hot sanitary water heating heating boiler boiler hot water tank burner weight
type power efficiency % pressure bar voltage supply ΔT 30°C delivery return delivery return ricirculation suction unit
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/h Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Ø a6 kg
BIA F 30-90 34 29.240 90 92 3 7 230/50 800 1” 1” 3/4” 3/4” 3/4” 80 180
BIA F 40-120 51,4 44.204 90,4 92,14 3 7 230/50 900 1” 1” 3/4” 3/4” 3/4” 80 240
25
High efficiency cast iron boiler
¥BIG F
- Proof basement boilers suitable for medium-sized systems.
- Pre-assembled high-quality cast iron boiler shell.
- Combustion chamber and exchanger being designed for over 90%
guaranteed efficiency.
- Light gas and gas burner operation.
- Heat loss preventing ultra thick insulation.
- Instrument panel for proper operation control.
- IP X4D protection degree.
¥ Certification
- BIG F boilers are EC type approved.
- Available in FK version “to be assembled”
160
CALORECLIMA
a1
C
1196
867
B
726
375
84
600 A a2 a3
boiler furnace power useful efficiency maximum power heating heating Burner A B C weight
type Light oil Gas pressure voltage delivery return discharge
kW kcal/h 100% 100% 30% bar V/Hz DN a1 DN a2 Ø a3 mm. Ø mm. Ø mm. Kg
BIG F 107 116 99.760 91,8 91,3 92,2 6 230/50 80 - 3” 80 - 3” 3/4” 757 180 120 411
BIG F 126 136,9 117.734 91,9 91,2 92,4 6 230/50 80 - 3” 80 - 3” 3/4” 867 180 120 462
BIG F 144 156,5 134.590 92,2 91,5 92,3 6 230/50 80 - 3” 80 - 3” 3/4” 977 200 120 513
BIG F 162 176 151.360 92,3 91,7 92,4 6 230/50 80 - 3” 80 - 3” 3/4” 1.087 200 150 564
BIG F 180 195,6 168.216 92,3 91,8 92,4 6 230/50 80 - 3” 80 - 3” 3/4” 1.197 200 150 615
BIG F 198 215,2 185.072 92,2 91,8 92,4 6 230/50 80 - 3” 80 - 3” 3/4” 1.307 200 150 666
BIG F 216 234,7 201.842 92,4 91,9 92,5 6 230/50 80 - 3” 80 - 3” 3/4” 1.417 200 150 720
BIG F 234 254,3 218.698 92,4 91,9 92,6 6 230/50 80 - 3” 80 - 3” 3/4” 1.527 200 150 775
BIG F 252 273,9 235.554 92 92 92,6 6 230/50 80 - 3” 80 - 3” 3/4” 1.637 200 150 830
26
High efficiency cast iron boiler
¥BIG FK to be assembled
- Proof basement boilers suitable for medium- and big-sized systems.
- High-quality cast iron boiler shell, with components to be assembled
during the installation of the boiler at the heating plant; three pass
exaust way.
- Combustion chamber and exchanger being designed for over 90%
guaranteed efficiency.
- Light gas and gas burner operation.
- Ideal for low temperature (35°C) system operation.
- Heat loss preventing ultra thick insulation.
- Instrument panel for proper operation control.
- IP X4D protection degree.
¥ Certificazione
- BIG FK boilers are EC type approved.
160
CALORECLIMA
a3 281,5 a1
10 a4
1180
898
B
463
463
83
850 A a2
boiler furnace power useful efficiency maximum power voltage heating heating heating heating A B C weight
type % pressure delivery return delivery BTreturn BT
kW kcal/h 100% 30% bar V/Hz DN a1 DN a2 DN a3 DN a4 mm. Ø mm. Ø mm. Kg
BIG FK 200 217 186.620 92,2 95,4 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.040 180 145 890
BIG FK 250 270 232.200 92,6 96 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.170 180 150 1.000
BIG FK 300 324 278.640 92,6 96,5 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.300 250 150 1.110
BIG FK 360 388 333.680 92,8 97,1 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.430 250 180 1.220
BIG FK 420 452 388.720 92,9 97,1 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.560 250 180 1.330
BIG FK 480 516 443.760 93 97,2 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.690 250 180 1.440
BIG FK 560 600 516.000 93,3 97,3 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.820 250 205 1.550
BIG FK 650 695 597.700 93,5 97,3 6 230/50 80 - 3” 80 - 3” 80 - 3” 80 - 3” 1.950 250 205 1.660
27
28
Air heaters
AIR-A
AIR-AC
AIR ACE
LGE
LGE OUT
3,35 4,91 22,9 28 29,7 31,9 75,6 1047
kW
29
“Wall-hung” air heaters
•AIR-ACE
- Outdoor wall-hung proof and ducted gas air heaters.
- Zone heating allowed.
- Stainless steel exchanger, combustion chamber and enbloc flue header.
- Stainless steel atmospheric burner suitable for all kinds of gas.
- Panels treated for external use.
- Flue discharge electrical fan.
- Electronic ignition.
- Ionization flame control.
- Centrifugal fan unit.
- IP X4D protection degree.
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Standard accessories
- GPL nozzles.
- Delivery duct union.
- Air inlet duct horizontal union.
- Air duct sloped union complete with grid.
- Flue discharge kit.
- Combustion air suction kit.
- Remote control panel equipped with electrical cable and 10 Mt. sheath.
• Optional accessories
- For the accessories relating to heaters AIR-ACE, please see on page 85.
• Certification
- AIR-ACE air heaters are
EC type approved.
heater furnace power useful 20°C air power voltage Noise Prevalence A B weight
type efficiency capacity level a 5 m.
kW kcal/h % m3/h V/Hz dB PA mm. mm. kg
AIR 30 ACE 34,8 29.900 91,7 2.500 230/50 mon. 48,5 80 1.385 167 73
AIR 49 ACE 57 49.000 90,5 5.000 230/50 mon. 51,5 80 1.385 167 125
AIR 73 ACE 85 73.100 89 7.300 230/50 mon. 53 80 1.464 102 207
31
“Industrial” air heaters
•LGE
- High-efficiency basement industrial air heaters.
- Light oil and gas burner operation.
- Stainless steel combustion chamber.
- Low-revolution ventilation unit, consisting of double suction centrifugal
fans.
- Instruments for unit control and adjustment, complete with triple
thermostat and electrical panel.
- Pre-painted sheet panels covered with soundproofing and lagging
coating.
- Side closing panel.
- For models LGE 25 ÷ LGE 65, fan units with 230V/50Hz single-phase
motor are fitted. For remaining models, fan units with 400V/50Hz
three-phase motors are provided.
- Summer ventilation.
- LGE 500 ÷ LGE 900 models are supplied on demand. Please
contact our Sales Department to be informed on the delivery
time.
• Certification
- LGE air heaters are EC type approved.
G F
C
E
heater A B C D E F G H I Ø weight
type mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. kg
LGE 25 - LGE 35 660 530 1.430 305 1.215 490 620 480 620 150 147-155
LGE 51 - LGE 65 870 636 1.750 305 1.500 596 830 630 830 180 220-230
LGE 80 - LGE 100 1.000 750 1.900 405 1.675 670 920 770 920 200 325-335
LGE 125 - LGE 150 1.260 900 2.060 405 1.750 820 1.180 760 1.180 250 493-503
LGE 175 - LGE 200 1.440 1.020 2.340 405 1.975 940 1.360 760 1.360 250 570-595
LGE 250 - LGE 300 1.790 1.020 2.340 405 1.975 940 1.710 760 1.710 300 840-870
LGE 375 1.960 1.280 2.660 405 2.280 1.200 1.880 930 1.880 300 1.230
LGE 425 - LGE 500 2.300 1.340 2.660 405 2.280 1.260 2.220 930 2.220 300 1.515-1.585
LGE 600 2.820 1.550 2.960 445 2.572 1.470 2.740 970 2.740 350 1.935
LGE 750 2.820 1.620 3.100 445 2.672 1.540 2.740 970 2.740 400 2.395
LGE 900 3.720 1.620 3.100 445 2.672 1.540 3.640 970 3.640 400 2.920
32
33
34
35
Zone management devices
•BOX ZONE
- Zone managament devices for systems up to 35 kW.
- Ideal for embedded-type assembly; wall-hung installation is also possible.
- Zone delivery circulators.
- Operation management electronic card.
- Safety thermostat in low temperature zone (Box Mix Zone).
- Circulator anti-blocking function.
- Post-circulation (10 seconds).
- Temperature regulation for precedence probe (25÷ 45°C).
- Anti-freeze device (5÷ 7°C).
- Possible connection of an external probe to the Box Mix Zone (on
demand).
- Electromechanical mixing valve (Box Mix Zone).
- Delivery temperature regulation of low temperature zone (Box Mix Zone).
- Water circuit breaker.
- Led Check Control for defect detection.
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components
• Optional accessories
- To see the accessories suitable for BOX ZONE, see page 85.
• Range of accessories
- Box Mix Zone: for managing 1 high temperature zone and 1 low
temperature zone.
- Box Zone A2: for managing 2 high temperature or low temperature
zones (only for suitable boilers).
- Box Zone A3: for managing 3 high temperature or low temperature
zones (only for suitable boilers).
RC MC RC MC RC MC
RA3 MA 3
RB MB RA2 MA 2 RA2 MA 2
RA MA RA1 MA 1 RA1 MA 1
Box zone Water Maximum Maximum operating Post power Transformer Transformer Width Height Depth Weight
type content operating pressure pressure circulation voltage protection fuse protection fuse
l bar °C sec. V/Hz W A kg
BOX ZONE MIX 5 3 90 10 230/50 260 3,15 440 550 175 17
BOX ZONE A2 5 3 90 10 230/50 230 3,15 440 550 175 18,5
BOX ZONE A3 5 3 90 10 230/50 340 3,15 440 550 175 20,5
36
Wall-hung gas boilers and heating modules
In compliance with:
DIRECTIVE 90/396/EEC
DIRECTIVE E.M.C. 89/336/EEC (Act No. 476 of the 04/12/92)
DIRECTIVE L.V. 72/23/EEC (Act No. 791 of 18/10/77)
EFFICIENCY DIRECTIVE 92/42/EEC
FUTURIA L
FUTURIA N
FUTURIA PLUS
REPLY
REPLY N
XILO LN
XILO
XILO T - XILO D
VELA XN
ALMA
15 22,5 22,75 23,24 23,4 23,66 23,92 24,5 27,48 27,7 27,8 28 28,36 28,5 31,74 31,9 45,2 49 90,4
kW
37
Wall-hung pre-mixed condensation gas boilers
•FUTURIA L “thermal”
- Ultra-high efficiency proof condensation boilers, suitable for heating.
- Ideal for low temperature system operation.
- Special casting aluminium corrosion proofing enbloc exchanger.
- Stainless steel pre-mixing burner.
- Wet-type combustion chamber. Classe
NOx
- Ionization flame control electronic ignition. 5
- Electronically controlled continuous modulation for the heating circuit
with steady air/gas ratio.
- Natural gas or G.P.L. operation.
- Instruments for retraction unit control and regulation.
- High-prevalence circulator.
- 8 Lt. expansion tank.
- Proof combustion circuit with flue discharge electrical fan.
- Water trap siphon.
- Sanitary circulator arrangement.
- Class: NOx = 5.
- IP X4D protection degree.
- Boiler electrical kit (on demand) for combination with PAC B boilers.
• Certification
- FUTURIA L boilers are EC type approved.
Heat exchanger
38
Wall-hung pre-mixed condensation gas boilers
•FUTURIA L “instantaneous”
- Ultra-high efficiency proof condensation boilers, suitable for hot
sanitary water heating and supply.
- Ideal for low temperature system operation.
- Special casting aluminium corrosion proofing enbloc exchanger.
- Instantaneous exchanger for hot sanitary water with 5 Lt. micro-storage Classe
NOx
unit, complete with foamed polyurethane insulation. 5
- Stainless steel pre-mixing burner.
- Wet-type combustion chamber.
- Ionization flame control electronic ignition.
- Electronically controlled continuous modulation for the heating circuit
with steady air/gas ratio.
- Natural gas or G.P.L. operation.
- Instruments for retraction unit control and regulation.
- High-prevalence circulator.
- 8 Lt. expansion tank.
- Three-way electrical valve.
- Proof combustion circuit with flue discharge electrical fan.
- Water trap siphon
- Class: NOx = 5.
- IP X4D protection degree.
• Certification
- FUTURIA L boilers are EC type approved.
900
190 220
450 420
Heat exchanger
boiler furnace power useful efficiency Maximum pressure power hot sanitary Weight
type a 50/30°C a 80/60°C bar voltage water supply. ΔT 30°C
kW kcal/h 100% 30% 100% risc. sanit. V/Hz l/min Kg
FUTURIA L 24 MC W TOP/IT 8,8÷ 25 7.568÷ 21.500 103,7 106,2 98,1 3 6 230/50 2,5÷ 11,7 72
FUTURIA L 28 MC W TOP/IT 10÷ 29 8.600÷ 24.940 102,8 106,6 97,8 3 6 230/50 2,5÷ 13,6 72
* Flue connections: concentric or split discharge
39
Wall-hung pre-mixed condensation gas boilers
•FUTURIA L “boiler”
- Ultra-high efficiency proof condensation boilers, suitable for hot
sanitary water supply.
- Ideal for low temperature system operation.
- Special casting aluminium corrosion proofing enbloc exchanger.
- 50 Lt. storage unit stainless steel boiler, complete with foamed Classe
NOx
polyurethane insulation. 5
- Stainless steel pre-mixing burner.
- Wet-type combustion chamber.
- Ionization flame control electronic ignition.
- Electronically controlled continuous modulation for both heating
circuits with steady air/gas ratio.
- Natural gas or G.P.L. operation.
- Instruments for retraction unit control and regulation.
- High-prevalence circulator.
- 8 Lt. expansion tank.
- 2 Lt. sanitary circuit expansion tank.
- Three-way electrical valve.
- Proof combustion circuit with flue discharge electrical fan.
- Water trap siphon
- Class: NOx = 5.
- IP X4D protection degree.
• Certification
900
190 220
600 470
Heat exchanger
boiler furnace power useful efficiency Maximum pressure power hot sanitary Weight
type a 50/30°C a 80/60°C bar voltage water supply ΔT 30°C
kW kcal/h 100% 30% 100% risc. sanit. V/Hz l/h Kg
FUTURIA L 24 MB W TOP/IT 8,8÷ 25 7.568÷ 21.500 103,7 106,2 98,1 3 6 230/50 702 95
FUTURIA L 28 MB W TOP/IT 10÷ 29 8.600÷ 24.940 102,8 106,6 97,8 3 6 230/50 766 95
* Flue connections: concentric or split discharge
40
Floor-standing pre-mixed condensation gas boilers
•FUTURIA PLUS
- Ultra-high efficiency proof condensation boilers, suitable for hot
sanitary water heating and supply.
- Ideal for low temperature system operation.
- Special casting aluminium corrosion proofing enbloc exchanger.
- 90 Lt. storage unit stainless steel boiler for big amounts of hot sanitary Classe
NOx
water. 5
- Stainless steel pre-mixing burner.
- Wet-type combustion chamber.
- Ionization flame control electronic ignition.
- Electronically controlled continuous modulation for both heating
circuits with steady air/gas ratio.
- Slow opening gas valve.
- Instruments for retraction unit control and regulation.
- High-prevalence circulator.
- 8 Lt. expansion tank.
- 3 Lt. sanitary circuit expansion tank.
- Three-way electrical valve.
- Proof combustion circuit with flue discharge electrical fan.
- Water trap siphon
- Class: NOx = 5.
- IP X4D protection degree.
• Certification
- FUTURIA PLUS boilers are EC type approved.
1675
40 410
70
450 617
boiler furnace power useful efficiency Maximum pressure. power hot sanitary Weight
type a 50/30°C a 80/60°C bar voltage water supply ΔT 30°C
kW kcal/h 100% 30% 100% risc. sanit. V/Hz l/h Kg
FUTURIA 24 PLUS MB W TOP U/IT 8,8÷ 25 7.568÷ 21.500 103,7 106,2 98,1 3 6 230/50 680 89
41
Wall-hung pre-mixed condensation gas boilers
•“termo” FUTURIA N
- Ultra-high efficiency proof condensation boilers, suitable for heating.
- Ultra-high heat exchange aluminium lamellar exchanger.
- Flame injection pre-mixed ceramic burner.
- Ideal for low temperature system operation.
- Suitable for water and electrical connection to the boiler kit (boiler Classe
circulator and temperature probe). NOx
- Special casting aluminium corrosion proofing enbloc exchanger. 5
- Adjustable opening pneumatic gas valve.
- Microprocessor electronic card suitable for connection to the cascade
control board and possible external probe.
- Variable speed fan.
- Ionization flame control electronic ignition.
- Electronically controlled continuous modulation for both heating
circuits with steady air/gas ratio.
- Natural gas or G.P.L. operation.
- Instruments for retraction unit control and regulation.
- High-prevalence circulator.
- 10 Lt. expansion tank (models 15, 25 and 35).
- Check valve.
- G.P.L. kit supplied with the boiler.
- Water trap siphon
- Class: NOx = 5.
- IP X4D protection degree.
• Optional accessories
- For accessories suitable for FUTURIA N boiler, see page 85. Aria*
Air* B C D E
- Flue inlet/outlet kits are not included in the supply. See accessories on
demand on page 85. Aria*
Air*
- Water connection kits are not included in the supply. See accessories on Fumi*
Exaust*
demand on page 85.
- When installing a Ø60/ Ø100 concentric kit, a “flanged
800
• Certification
- FUTURIA N boilers are EC type approved.
A 410
42
Wall-hung pre-mixed condensation gas boilers
•“instantaneous” FUTURIA N
- Ultra-high efficiency proof condensation boilers, suitable for hot
sanitary water heating and supply.
- Ultra-high heat exchange aluminium lamellar exchanger.
- Flame injection pre-mixed ceramic burner.
- Ideal for low temperature system operation. Classe
- 5 Lt. hot sanitary water micro storage unit, complete with foamed NOx
polysterene insulation. 5
- Instantaneous exchanger for plate hot sanitary water.
- Adjustable opening pneumatic gas valve.
- Microprocessor electronic card suitable for connection to the cascade
control board and possible external probe.
- Variable speed fan.
- Ionization flame control electronic ignition.
- Electronically controlled continuous modulation for both heating
circuits with steady air/gas ratio.
- Natural gas or G.P.L. operation.
- Instruments for retraction unit control and regulation.
- Sanitary and heating circuit circulators.
- 10 Lt. expansion tank.
- Check valve.
- G.P.L. kit supplied with the boiler.
- Water trap siphon
- Class: NOx = 5.
- IP X4D protection degree.
• Optional accessories
- For accessories suitable for FUTURIA N boiler, see page 85.
- Flue inlet/outlet kits are not included in the supply. See accessories on
demand on page 85. Aria*
Air* 120 120 A 180
- Water connection kits are not included in the supply. See accessories
on demand on page 85. Aria*
Air*
- When installing a Ø60/ Ø100 concentric kit, a “flanged
Fumi*
Exaust*
concentric connection kit” (code 08516310) shall be assembled
between the boiler and the concentric kit.
800
• Certification
- FUTURIA N boilers are EC type approved.
490 410
boiler furnace power useful efficiency Maximum pressure power hot sanitary A Weight
type a 50/30°C a 80/60°C bar voltage water supply ΔT 30°C
kW kcal/h 100% 30% 100% risc. sanit. V/Hz l/min mm. Kg
FUTURIA N 25 MC W TOP/IT 7,5÷ 25,2 6.450÷ 21.670 104,7 109 98 3 10 230/50 11,8 80 58,5
FUTURIA N 35 MC W TOP/IT 10,4÷ 34,8 8.940÷ 29.920 104,7 109,1 99,5 3 10 230/50 16,5 125 59,5
* Flue connections: concentric or split discharge
43
Pre-mixed condensation gas heating modules
•REPLY
- Ultra-high efficiency condensation heating module, suitable for heating
(Reply R) and hot sanitary water heating and supply (Reply C).
- Ideal for low temperature system operation.
- Special casting aluminium corrosion proofing enbloc exchangers.
- Wet-type combustion chambers. Classe
- Stainless steel pre-mixing burner. NOx
- Electronically controlled continuous modulation for both heating 5
circuits with steady air/gas ratio.
- Ionization flame control electronic ignition.
- Instruments for unit control and regulation.
- Boiler circuit high-prevalence circulator.
- Three-way electrical valve (Mod. Reply C).
- Proof combustion circuit with high-prevalence flue discharge electrical
fan.
- Water trap siphon
- Class: NOx = 5.
- IP X4D protection degree.
- Containment module structure suitable for external fitting.
• Optional accessories
- For the accessories suitable for REPLY heating module, see page 85.
- Discharge kits of the heating module are on demand.
• Certification
- REPLY heating modules are EC type approved.
200 200
255
255
Reply Reply
540
540
1800
1800
a4
a1
a3 a3
300
a5
a2
300
a6 a6
390
390
360
240
155
155
module furnace power useful efficiency Maximum power Heating . Heating gas boiler boiler Cold water Weight
type a 50/30°C a 80/60°C pressure voltage delivery return conn. delivery return inlet
kW kcal/h 100% 30% 100% bar V/Hz DN a1 DN a2 Ø a3 DN a4 DN a5 Ø a6 Kg
REPLY 49 C 8,8÷ 50 7.568÷ 43.000 103,7 106,2 98,1 3 230/50 50 50 1 1/4" 50 50 3/4" 273
44
Pre-mixed condensation gas heating modules
- REPLY C: heating module for hot water heating and supply, complete
with all the I.S.P.E.S. devices and flue discharge header (Ø 150).
2 Fuel on-off valve, calibrated at 98° and 7 Manual resetting regulation and safety 13 Expansion tank (optional).
I.S.P.E.S.L. type-approved. double-thermostat (I.S.P.E.S.L. type-
approved). 14 Boiler (optional).
3 Manual resetting safety pressure switch
(I.S.P.E.S.L. type-approved). 8 Heating circuit header. 15 Filling cock (optional).
5 Ø 1/2” safety valve, calibrated according to 10 Condensation discharge. 17 Three-way cock with sample flange, in
I.S.P.E.S.L. standards. compliance with I.S.P.E.S.L. standards.
11 Circulators (optional).
45
Pre-mixed condensation gas heating modules
•REPLY N
- Ultra-high efficiency condensation heating module
- Single-furnace (REPLY N 50) or double-furnace (REPLY N 70 and
REPLY N 100) with ultra-high heat exchange aluminium lamellar
exchangers.
- Flame injection pre-mixed ceramic burner. Classe
NOx
- Ideal for low temperature system operation. 5
- Ideal for outdoor installation, even for uncovered places.
- Variable opening pneumatic gas valves.
- Microprocessor electronic card suitable for connection to the cascade
control board and possible external probe.
- Variable speed fans.
- Ionization flame control electronic ignition.
- Electronically controlled continuous modulation with steady air/gas
ratio.
- Natural gas or G.P.L. operation.
- Utility interface display for each module assembled on the machine.
- Instruments for unit control and regulation.
- Independent exchanger water circuits, being connected to the relevant
delivery and return headers.
- Primary unit circulators.
- Check valve.
- Condensation discharge on disposal circuit complete with siphon.
- Silked stainless steel AISI 316 containment module structure, reduced in
size.
- G.P.L. kit supplied with the boiler.
- Class: NOx = 5.
- IP X4D protection degree.
a4
390
225
- For the accessories suitable for REPLY N heating module, see page 85.
145
• Certification 700 35
- REPLY N heating modules are EC type approved. 115
250
275
module furnace power useful efficiency Maximum power Heating Heating gas condensation Weight
type a 50/30°C a 80/60°C pressure voltage delivery return conn. discharge
kW kcal/h 100% 30% 100% bar V/Hz DN a1 DN a2 DN a3 Ø a4 Kg
REPLY N 50 13,8÷ 46 11.868÷ 39.560 105,3 109 98,2 6 230/50 80 80 50 40 114
REPLY N 70 13,8÷ 70 11.868÷ 60.200 105,3 109 98,2 6 230/50 80 80 50 40 165
REPLY N 100 13,8÷ 92 11.868÷ 79.120 105,3 109 98,2 6 230/50 80 80 50 40 165
46
Pre-mixed condensation gas heating modules
• Cascade connection
- REPLY N is a heating module intended for single or cascade operation. Two or more REPLY modules can be cascade connected (5
heating modules at maximum), as shown in the figure below.
Attacco
gas Gas
connection
delivery
Mandata
return
Ritorno
• Flue
- For cascade connection of more than one module, connect the flue outlet (Ø 150) of each single module as shown in the figure, making
sure that the header and flue diameter values correspond to those reported in the table below.
3°
150
47
Wall-hung indoor gas boilers
• Certification
- XILO LN boilers are EC type approved.
770
440 330
97
250
boiler furnace power useful efficiency Maximum pressure power voltage hot sanitary A Weight
type % bar water supply ΔT 30°C
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/min. Ø mm kg
XILO LN 20 MCS W TOP/IT 25 21.500 93,9 92,5 3 8 230/50 2,5÷ 11,2 * 43
* Flue connections: concentric or split discharge
48
Wall-hung indoor gas boilers
•XILO T
- Open (mod. M) and proof chamber (mod. MS) boilers suitable for
heating.
- Suitable for low temperature system operation.
- Reduced overall dimensions (-20% if compared to the standard
boilers).
- High-efficiency primary copper exchanger.
- Atmospheric burner, in stainless steel for all kinds of gas.
- Ionization flame control electronic ignition.
- Electronically controlled proportional modulation for heating circuit.
- Proof combustion circuit with flue discharge electrical fan (mod. MS).
- Safety FLUE CONTROL preventing burnt gases from entering the
room (mod. M).
- High-prevalence circulator.
- 8 Lt. expansion tank.
- Slow opening gas valve.
- Combustion chamber provided with ceramic fibre insulation.
- Instruments for unit control and regulation.
- Flue standard intake in the boiler (mod. MCS).
- IP X4D protection degree.
- XILO T 24 boilers can be combined with PAC B boilers.
220
• Installation and Maintenance A 160
- Easy installation thanks to template connections and water connection
kits (on demand).
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Optional accessories
770
• Certification
- XILO T boilers are EC type approved. 440 330
97
250
XILO T MS
dimensions
boiler furnace power useful efficiency Maximum heating power voltage A Weight
type % circuit pressure
kW kcal/h 100 % 30 % bar V/Hz Ø mm kg
XILO T 20 M W TOP U/IT 26 22.360 91 88,7 3 230/50 132,5 33
XILO T 20 MS W TOP U/IT 26 22.360 91,3 89 3 230/50 * 35
XILO T 24 M W TOP U/IT 30,2 25.972 91,2 90 3 230/50 152,5 34
XILO T 24 MS W TOP U/IT 30,2 25.972 91 88,9 3 230/50 * 36
* Flue connections: concentric or split discharge
49
Wall-hung indoor gas boilers
• Optional accessories
- For accessories suitable for XILO boiler, see page 85.
- Flue inlet/outlet kits are not included in the supply. See accessories on
770
• Certification
- XILO boilers are EC type approved.
440 330
97
boiler furnace power useful efficiency Maximum pressure power hot sanitary A Weight
type % bar voltage water supply ΔT 30°C
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/min. Ø mm kg
XILO 20 MC W TOP U/IT 25 21.500 90 87,3 3 8 230/50 2,5÷ 10,8 132,5 38
XILO 20 MCS W TOP U/IT 25 21.500 91 87,3 3 8 230/50 2,5÷ 11 * 40
* Flue connections: concentric or split discharge
50
Wall-hung indoor gas boilers
• Optional accessories
- For accessories suitable for XILO D boiler, see page 85.
- Flue inlet/outlet kits are not included in the supply. See accessories on 440 330
demand on page 85.
97
• Certification
250
XILO D MCS
- XILO D boilers are EC type approved.
dimensions
boiler furnace power useful efficiency Maximum pressure power hot sanitary A Weight
type % bar voltage water supply ΔT 30°C
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/min. Ø mm kg
XILO D 20 MC W TOP U/IT 26 22.360 91 88,7 3 8 230/50 2,5÷ 11,3 132,5 39
XILO D 20 MCS W TOP U/IT 26 22.360 91,3 89 3 8 230/50 2,5÷ 11,3 * 41
XILO D 24 MC W TOP U/IT 30,2 25.972 91,2 90 3 8 230/50 2,5÷ 13,2 152,5 40
XILO D 24 MCS W TOP U/IT 30,2 25.972 91 88,9 3 8 230/50 2,5÷ 13,1 * 42
* Flue connections: concentric or split discharge
51
Wall-hung indoor gas boilers
• Optional accessories
- For accessories suitable for VELA XN boiler, see page 85.
- Flue inlet/outlet kits are not included in the supply. See accessories on
demand on page 85. CALORECLIMA
VELA XN
dimensions
**
boiler furnace power useful efficiency Maximum pressure power hot sanitary A B C Weight
type % bar voltage water supply ΔT 30°C
kW kcal/h 100% 30% risc. sanit. V/Hz l/min Ø mm. mm. mm. Kg
VELA XN 24 MB W TOP/IT 26 22.360 90 86,8 3 8 230/50 11,2 132,5 130 220 64
VELA XN 24 MBS W TOP/IT 26 22.360 92 88,7 3 8 230/50 11,4 * 94,5 222 69
* Flue connections: concentric or split discharge - ** Air suction Ø80.
52
Wall-hung indoor gas boilers
ALMA MBS
• Certification
dimensions
- ALMA boilers are EC type approved.
53
54
Water heaters and floor-standing gas boilers
ERA F
ERA FS
ERA F 60
ERA F 90
GASTER N
SIL
SAL S
SAL
4,7 8 23 23,7 27,49 27,8 28 28,02 30,3 31,9 32 51 56 289
kW
55
Indoor floor-standing gas boilers
• Optional accessories
- For accessories suitable for ERA F boiler, see page 85.
• Certification
- ERA F boilers are EC type approved.
E F E 80
C B C
a1 a2 a1
a3
a3
850
850
D
B D
617
582
582
a2
530
F
a4
182
133
A 615 A 615
ERA F 23 - ERA F 32 - ERA F 45 - ERA F 56 ERA F 32 PK
boiler furnace power useful efficiency Maximum power A B C D E F Heating Heating gas Cold water Weight
type % pressure voltage delivery return conn. inlet
kW kcal/h 100 % 30 % bar V/Hz mm. mm. mm. mm. mm. mm. Ø a1 Ø a2 Ø a3 Ø a4 kg
ERA F 23 10,1÷ 25,3 8.686÷ 21.758 90,9 92 4 230/50 450 137 134 65 130 70 3/4” 3/4” 1/2” - 139
ERA F 32 14,9÷ 34,9 12.814÷ 30.014 91,7 92,5 4 230/50 450 94 91 22 150 80 3/4” 3/4” 1/2” - 165
ERA F 45 19,7÷ 49,5 16.942÷ 42.570 90,9 92,1 4 230/50 600 126 123 86 150 80 3/4” 3/4” 1/2” - 190
ERA F 56 24,5÷ 61,6 21.070÷ 52.976 90,9 92,1 4 230/50 600 83 80 40 180 95 3/4” 3/4” 1/2” - 216
model equipped with circulator and expansion tank
ERA F 32 PK 14,9÷ 34,9 12.814÷ 30.014 91,7 92,5 4 230/50 450 94 91 22 150 33 3/4” 3/4” 1/2” 1/2” 175
56
Indoor floor-standing gas boilers
• Optional accessories
- For accessories suitable for ERA F S boiler, see page 85.
- Flue suction/exhaust kits are not included in the supply
• Certification
- ERA F S boilers are EC type approved.
120 157
40
a1 a7 a6
55 55
a3
850
a2
708
a4 a5
439
182
84
50
500 600
163
boiler furnace power useful efficiency Heating max. power Heating Heating gas Cold water boiler Flue Air Weight
type % pressure voltage delivery return conn. inlet return exhaust suction
kW kcal/h 100 % 30 % bar V/Hz Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Ø a6 Ø a7 kg
ERA F 32 S 15,9÷ 34,9 13.674÷ 30.014 91,7 90,5 4 230/50 3/4” 3/4” 1/2” - - * 80 170
model equipped with circulator and expansion tank
ERA F 32 S PK 15,9÷ 34,9 13.674÷ 30.014 91,7 90,5 4 230/50 3/4” 3/4” 1/2” 1/2” 1” * 80 180
* Flue connections: concentric or split discharge
57
Indoor floor-standing gas boilers
a3
• Optional accessories a1
a5
850
785
a6
- Flue suction/exhaust kits are not included in the supply
a4
a2
• Certification
- ERA F 60 boilers are EC type approved. 800 600
ERA F 32 B 60
40
a3
a1
a5 a8 a7
850
785
a6
707
a4
a2
800 600
ERA F 32 BS 60
boiler furnace power useful Maximum power hot sanitary water Heating gas Cold water inletRicirc. Flue Air Weight
type efficiency % pressure bar voltage supply ΔT 30°C delivery/return conn.Hot water outlet exhaust suction
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/h Ø a1/Ø a2 Ø a3 Ø a4/Ø a5 Ø a6 Ø a7 Ø a8 kg
ERA F 32 B 60 14,9÷ 34,9 12.814÷ 30.014 91,7 92,5 4 7 230/50 800 3/4” 1/2” 1/2” 1/2” - - 179
Proof model
ERA F 32 BS 60 15,9÷ 34,9 13.674÷ 30.014 91,7 90,5 4 7 230/50 800 3/4” 1/2” 1/2” 1/2” * 80 175
* Flue connections: concentric or split discharge
58
Indoor floor-standing gas boilers
• Optional accessories
- For accessories suitable for ERA F 90 boiler, see page 85.
- Flue suction/exhaust kits are not included in the supply
• Certification
- ERA F 90 boilers are EC type approved.
a1
40
a1 a3
a3 a2 a8 a7
a2
1400
1400
1190
1100
1064
976
921
940
a5 a5
655
a6 a6
422
422
252
252
82
82
a4 a4
500 706 500 706
ERA F 32 B 90 ERA F 32 BS 90
boiler furnace power useful Maximum power hot sanitary water Heating delivery gas Cold water inlet Hot water Flue Air Weight
type efficiency % pressure bar voltage supply ΔT 30°C Heating return conn. Hot water outlet tank ricirc. exhaust suction
kW kcal/h 100 % 30 % risc. sanit. V/Hz l/h Ø a1/Ø a2 Ø a3 Ø a4/Ø a5 Ø a6 Ø a7 Ø a8 kg
ERA F 32 B 90 14,9÷ 34,9 12.814÷ 30.014 91,7 92,5 4 7 230/50 800 1” 1/2” 3/4” 3/4” - - 200
Proof model
ERA F 32 BS 90 15,9÷ 34,9 13.674÷ 30.014 91,7 90,5 4 7 230/50 800 1” 1/2” 3/4” 3/4” * 80 206
* Flue connections: concentric or split discharge
59
Indoor floor-standing gas boilers
• Optional accessories
- For accessories suitable for GASTER N boiler, see page 85.
• Certification
- GASTER N boilers are EC type approved.
B C
D
a3
a1
1000
762
672
a2
E
222
A 900
boiler first furnace useful Heating max. power A B C D E Heating Heating gas Weight
type stage power efficiency pressure voltage delivery return conn.
furnace power %
kW kcal/h kW kcal/h 100 % 30 % bar V/Hz mm. mm. mm. mm. mm. Ø a1 Ø a2 Ø a3 kg
GASTER N 51 AW 32,7 28.122 56 48.160 91,1 92,3 6 230/50 550 103,5 180 43 35 1 1/2” 1 1/2” 3/4” 214
GASTER N 68 AW 46,6 37.496 74,8 64.328 90,9 92,3 6 230/50 640 103,5 180 46 38 1 1/2” 1 1/2” 3/4” 252
GASTER N 85 AW 54,5 46.870 93,5 80.410 90,9 92,3 6 230/50 720 113,5 200 44 36 1 1/2” 1 1/2” 3/4” 300
GASTER N 102 AW 65,4 56.244 112 96.320 91,1 92,3 6 230/50 800 113,5 200 42 34 1 1/2” 1 1/2” 3/4” 348
60
Indoor floor-standing gas boilers
• Optional accessories
- For accessories suitable for GASTER N boiler, see page 85.
• Certification
- GASTER N boilers are EC type approved. B C
E
a1
1050
a3
a2
672
567
D
222
A F
boiler first stage furnace useful Heating max. power A B C D E F Heating Heating gas Weight
type furnace power efficiency pressure voltage delivery return conn.
power %
kW kcal/h kW kcal/h 100 % 30 % bar V/Hz mm. mm. mm. mm. mm. mm. Ø a1 Ø a2 Ø a3 kg
GASTER N 119 AW 77 66.220 131 112.660 91,2 92,3 6 230/50 930 133 220 50 42 1.050 2” 2” 1” 430
GASTER N 136 AW 89 76.540 149 128.140 91,3 92,2 6 230/50 1.020 148 250 53 45 1.050 2” 2” 1” 490
GASTER N 153 AW 100 86.000 168 144.480 91,4 92,2 6 230/50 1.100 148 250 58 43 1.050 2” 2” 1 1/2” 535
GASTER N 170 AW 110 94.600 187 160.820 91,5 92,1 6 230/50 1.190 173 300 60 46 1.050 2” 2” 1 1/2” 575
GASTER N 187 AW 122 104.920 206 177.160 91,6 92,1 6 230/50 1.270 173 300 58 44 1.050 2” 2” 1 1/2” 625
GASTER N 221 AW 144 123.840 243 208.980 91,7 92 6 230/50 1.440 173 300 57 45 1.050 2” 2” 1 1/2” 720
GASTER N 255 AW 166 142.760 280 240.800 91,9 91,9 6 230/50 1.610 198 350 62 46 1.100 2” 2” 1 1/2” 835
GASTER N 289 AW 188 161.680 317 272.620 92 91,7 6 230/50 1.780 198 350 66 49 1.100 2” 2” 1 1/2” 905
61
Instantaneous gas water heaters
•SIL
- High-efficiency open chamber (mod. SIL 14 top) and proof (mod. SIL
14S top) water heaters suitable for hot sanitary water supply.
- High-efficiency copper exchanger.
- Electronic ignition with ionization flame control.
- Stainless steel atmospheric burner for all kinds of gas.
- Proof combustion circuit with flue exhaust electrical fan (mod. S).
- Continuous modulation gas valve.
- Safety FLUE CONTROL preventing burnt gases from entering the
room (mod. SIL TOP).
- Combustion chamber provided with ceramic fibre insulation (mod. S).
- Instruments for unit control and regulation.
- Sanitary flow meter.
- IP X4D protection degree.
• Optional accessories
- For accessories suitable for SIL water heater, see page 85.
- Flue suction/exhaust kits are not included in the supply. See accessories
on demand on page 85.
- Polyphosphate doser type DPO/B. 220
A 94,5
• Certification
- SIL water heaters are EC type approved.
675
440 250
97
dimensions for
184,5
** SIL S Top
water heater furnace power hot sanitary water Sanitary circuit power A Cold water Hot water gas Weight
type supply (ΔT 25°C) l/min. max. pressure voltage inlet outlet inlet
kW kcal/h min max bar V/Hz mm. Ø Ø Ø kg
SIL 14 TOP 27 23.220 2,5 13,6 10 230/50 132,5 1/2” 1/2” 1/2” 25
SIL 14 S TOP 27 23.220 2,5 13,6 10 230/50 * 1/2” 1/2” 1/2” 26
* Flue connections: concentric or split discharge
62
Gas storage water heaters
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Optional accessories
- For accessories suitable for SAL S water heater, see page 85.
- Flue suction/exhaust kits are not included in the supply. See
accessories on demand on page 85.
• Certification
- SAL S water heaters are EC type approved.
Ø60
Ø38
190
30
210
B
C
a2
a3 a1
325 75
170
250
60
460
80 185 80
450 Vistatop
Superiore
view
water heater furnace power hot sanitary water Sanitary circuit max. power A B C Gas Hot water Cold water Weight
type supply A.C.S. ΔT 40°C pressure voltage Inlet outlet inlet
kW kcal/h l/h bar V/Hz mm. mm. mm. Ø a1 Ø a2 Ø a3 kg
SAL 80 S 5 4.300 92 6 230/50 1.040 895 850 3/8” 1/2” 1/2” 49
SAL 120 S 5 4.300 92 6 230/50 1.400 1.255 1.210 3/8” 1/2” 1/2” 74
63
Gas storage water heaters
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Optional accessories
- For accessories suitable for SAL S water heater, see page 85.
- Flue suction/exhaust kits are not included in the supply. See
accessories on demand on page 85.
• Certification
- SAL S water heaters are EC type approved.
Ø100
Ø60
220
a2
a4
F
a1
G
A
a3
B
C
D
50
251
101 139
139
251
101
520
251
Ø80
139
520 101
Vista
topSuperiore
view
water heater furnace hot sanitary water Sanitary circuit max. power A B C D F G gas Hot water Cold water Hot water Weight
type power supply ΔT 40°C pressure voltage inlet outlet inlet tank ricirculation
kW kcal/h l/h bar V/Hz mm. mm. mm. mm. mm. mm. Ø a1 Ø a2 Ø a3 Ø a4 kg
SAL 150 S 18 15.481 328 6 230/50 1.615 715 420 385 1.925 1.750 1/2” 3/4” 3/4” 3/4” 100
SAL 180 S 19 16.341 349 6 230/50 1.815 715 420 385 2.125 1.950 1/2” 3/4” 3/4” 3/4” 110
64
Gas storage water heaters
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Optional accessories
- For accessories suitable for SAL S water heater, see page 85.
- Flue suction/exhaust kits are not included in the supply. See
accessories on demand on page 85.
• Certification
- SAL S water heaters are EC type approved.
Ø100
Ø60
295
a2
a4
a3
B
a1
C
E
a5
D
565
480
110
420
239
481
95
720
95 239 95
720 Vistatop
Superiore
view
water heater furnace hot sanitary water Sanitary circuit power A B C D E gas Hot water Cold water Hot water Scarico Weight
type power supply ΔT 40°C max. pressure voltage inlet outlet inlet tank ricirculation
kW kcal/h l/h bar V/Hz mm. mm. mm. mm. mm. Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 kg
SAL 220 S 28,5 24.512 527 6 230/50 1.660 1.495 1.365 970 1.300 1/2” 1 1/4” 1 1/4” 1” 1” 202
SAL 300 S 31 26.662 573 6 230/50 2.015 1.840 1.720 970 1.655 1/2” 1 1/4” 1 1/4” 1” 1” 245
SAL 400 S 31 26.662 573 6 230/50 2.365 2.190 2.070 1.135 2.000 1/2” 1 1/4” 1 1/4” 1” 1” 286
65
Gas storage water heaters
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Certification
- SAL water heaters are EC type approved.
Ø180
200
a2
a4
a3
a1 A
B
E
a5
D
605
545
110
460
Ø180
720
720
Vista
topSuperiore
view
water heater furnace hot sanitary waterSanitary circuit power A B D E gas Hot water Cold water Hot water Scarico Weight
type power supply ΔT 40°C max. pressure voltage inlet outlet inlet tank ricirculation
kW kcal/h l/h bar V/Hz mm. mm. mm. mm. Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 kg
SAL 220 34 29.242 621 6 230/50 1.600 1.400 1.010 1.330 1/2” 1 1/4” 1 1/4” 1” 1” 160
SAL 300 34 29.242 621 6 230/50 1.960 1.750 1.010 1.680 1/2” 1 1/4” 1 1/4” 1” 1” 202
SAL 400 34 29.242 621 6 230/50 2.310 2.100 1.175 2.030 1/2” 1 1/4” 1 1/4” 1” 1” 243
66
Zone management devices
•BOX ZONE
- Zone management devices for systems up to 35 kW.
- Ideal for embedded-type assembly; wall-hung installation is also possible.
- Zone delivery circulators.
- Operation management electronic card.
- Safety thermostat in low temperature zone (Box Mix Zone).
- Circulator anti-blocking function.
- Post-circulation (10 seconds).
- Temperature regulation for precedence probe (25÷ 45°C).
- Anti-freeze device (5÷ 7°C).
- Possible connection of an external probe to the Box Mix Zone (on demand).
- Electromechanical mixing valve (Box Mix Zone).
- Delivery temperature regulation of low temperature zone (Box Mix Zone).
- Water circuit breaker.
- Led Check Control for defect detection.
• Maintenance
- Maintenance is made simple thanks to easy accessibility to internal
components.
• Optional accessories
- To see the accessories suitable for BOX ZONE, see page 85.
• Range of accessories
- Box Mix Zone: for managing 1 high temperature zone and 1 low
temperature zone.
- Box Zone A2: for managing 2 high temperature or low temperature
zones (only for suitable boilers).
- Box Zone A3: for managing 3 high temperature or low temperature
zones (only for suitable boilers).
RC MC RC MC RC MC
RA3 MA 3
RB MB RA2 MA 2 RA2 MA 2
RA MA RA1 MA 1 RA1 MA 1
Box zone Water Max. operating Max. operating Post power power Transformer Width Height Depth Weight
type content pressure temperature circulation voltage input protection fuse
l bar °C sec. V/Hz W A mm. mm. mm. kg
BOX ZONE MIX 5 3 90 10 230/50 260 3,15 440 550 175 17
BOX ZONE A2 5 3 90 10 230/50 230 3,15 440 550 175 18,5
BOX ZONE A3 5 3 90 10 230/50 340 3,15 440 550 175 20,5
67
68
Boilers, Regulation systems and Radiators
PAC B
PAC S
PAV/N
BITHERM
80 120 145 150 250 600
Litri
69
Boilers for hot sanitary water supply
•PAC B - PAC S
- Enamelled steel boilers.
- Foamed polyurethane insulation.
- High-prevalence circulator.
- Thermostat.
- Thermometer.
- Magnesium anode.
- Safety valve.
- Check valve.
- Air bleed automatic valve.
- Inspection flange.
• Certification
- PAC B and PAC S boilers are EC type approved.
• Range of products
- PAC B, white covering (RAL 9003). Possible combination with ERA F,
XILO T 24 and ERA F S boilers.
- PAC S, dark grey covering (RAL 9007). Possible combination with SEC
and EXA.
a4 a1
a3 a2 a5
CALORECLIMA
80
1 3
0 4
850
A 600
Boiler exchange accumulator pipe coil Hot sanitarypeak samplingMaximum coil A Cold Hot coil coil Ricircolo Weight
type power capacity capacity water supply during storage maxmimum water water inlet outlet
ΔT 30°C the first 10’ pressure pressure inlet outlet
kW kcal/h l l l/h l bar bar mm. Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Kg
PAC 80 B 28,5 24.500 80 3,5 816 185 6 12 450 1/2” 1/2” 3/4” 3/4” 1/2” 73
PAC 120 B 34,9 30.000 120 4,25 1.000 260 6 12 600 1/2” 1/2” 3/4” 3/4” 1/2” 105
PAC 80 S 28,5 24.500 80 3,5 816 185 6 12 450 1/2” 1/2” 3/4” 3/4” 1/2” 73
PAC 120 S 34,9 30.000 120 4,25 1.000 260 6 12 600 1/2” 1/2” 3/4” 3/4” 1/2” 105
00047600 PAC 80 S 80
00047610 PAC 120 S 120
70
Boilers for hot sanitary water supply
•PAV/N
- two-layer glazed and enamelled steel boilers.
- scratch-resistant polyethylene coating.
- Foamed polyurethane insulation.
- Magnesium anode.
- Boiler safety control eletrical panel.
- Possible combination with GASTER N, BIG F, MEGA PREX (BT-SL) and
DUO PREX.
• Certification
- PAV/N boilers are EC type approved.
a5
a3
B
a4
a1
Boiler exchange accumulator pipe coil hot sanitary peak sampling Maximum coil A B Cold Hot coil coil Hot water Weight
type power capacity capacity water supply during the storage maxmimum water water inlet outlet tank
ΔT 30°C first 10’ pressure pressure inlet outlet ricirculation
kW kcal/h l l l/h l bar bar mm. mm. Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Kg
PAV 150 N 30,6 26.350 145 5 1.032 145 6 10 600 890 1” 1 1/4” 1” 1” 1/2” 56
PAV 200 N 42 36.125 193 7,2 1.417 230 6 10 600 1.150 1” 1 1/4” 1” 1” 1/2” 72
PAV 300 N 58,3 50.150 296 9,6 1.965 340 6 10 600 1.660 1” 1 1/4” 1” 1” 1/2” 96
PAV 500 N 73,5 63.220 494 12,1 2.782 690 6 10 750 1.640 1” 1 1/4” 1” 1” 1/2” 125
PAV 600 N 89,7 77.150 591 14,4 2.963 795 6 10 750 1.950 1” 1 1/4” 1” 1” 1/2” 152
71
Boilers for hot sanitary water supply
•BITHERM
- enamelled steel boilers.
- Foamed polyurethane insulation.
- Magnesium anode.
- Fitted with registering (mininimum and maximum) thermostat and
thermometer
- Possible combination with SEC, EXA, NEINOX, NEINOX BT.
• Optional accessories
- Kits for water connections to Neinox and Neinox BT boiler are not
included in the supply.
• Certification
- BITHERM boilers are EC type approved.
a2
a4 a3
code description a5
B
a1
08510830 Kits for water connections
Boiler exchange accumulator Pipe coil hot sanitary peak sampling Max. coil A B C Cold Hot coil coil Hot Weight
type power capacity capacity water supply during the storage max water water inlet outlet water tank
ΔT 30°C first 10’ pressure pressure inlet outlet ricirculation
kW kcal/h l l l/h l bar bar mm. mm. mm. Ø a1 Ø a2 Ø a3 Ø a4 Ø a5 Kg
BITHERM 150 29,3 25.200 150 7 840 225 6 6 1.000 610 610 3/4” 3/4” 1” 1” 3/4” 100
BITHERM 200 36 31.000 200 10 1.033 300 6 6 1.125 660 660 3/4” 3/4” 1” 1” 3/4” 130
BITHERM 250 42,7 36.800 250 13 1.226 375 6 6 1.375 660 660 3/4” 3/4” 1” 1” 3/4” 160
72
Regulation systems
•CLASS PIÙ
- Digital chronothermostat.
- Three-time-bracket weekly programme, set up for each day of the
week
- Half-week programme and one/two/three-time-bracket daily
programme
- Optimum start-up control.
- Self-adapting system, allowing automatic adaptation to the system
control.
- Summer/winter switching programme.
- Possible temperature adjustment for anti-freeze protection.
- Possible new calibration of the room probe (unless previously
calibrated).
- Fitted with anti-scuff periodic circulator control.
• Certification
- CLASS PIÙ chronothermostats are EC type approved. 135
104
41
73
Aluminium radiators
•Aluminium radiators
- High radiant power radiators, made by high-pressure die-casting
special aluminium alloy.
- Thermal emission is optimized thanks to bigger convective fins with
respect to wet surfaces.
- Maximum operation pressure: 10 bar
- Battery inspection through hydropneumatic system.
- The radiators are suitable both for standard and single-pipe systems.
- Fitted with 1” Ø connections allowing direct assembly of the valves in
single-pipe systems.
- Paint covering is protected by a thermo retractile polyethylene film.
• Optional accessories
- For optional accessories intended for aluminium radiators, see page?
80 98 800
• Technical data
74
Water treatment line
Water softeners
SWEET-M
EAU-M
EAU-E BIOS
DOUBLE-E
PLUS-E
In compliance with:
DIRECTIVE E.M.C. 89/336/EEC (Act No. D.L. 476 of 4/12/92)
DIRECTIVE L.V. 72/23/EEC (Act No. 791 of 18/10/77)
Water filters
FCO
FCP
FCA
FT
FF
FD
In compliance with:
DIRECTIVE E.M.C. 89/336/EEC (Act No. D.L. 476 of 4/12/92) (only FT-FF-FD fitlers)
DIRECTIVE L.V. 72/23/EEC (Act No. 791 of 18/10/77) (only FT-FF-FD fitlers)
Dosing pumps
PDC
PDPH
In compliance with:
DIRECTIVE E.M.C. 89/336/EEC (Act No. D.L. 476 of 4/12/92)
DIRECTIVE L.V. 72/23/EEC (Act No. 791 of 18/10/77)
SWEET-M
EAU-M
EAU-E BIOS
DOUBLE-E
PLUS-E
40 125 210 720 960 3.360
m3 °F
75
Water softeners
•SWEET-M
- Time regeneration water softeners for domestic heating.
- Time electromechanical operation and programme valve.
- Rigid, shock-resistant, parallelepiped, compact and stylish shell in non-
toxic polyethylene.
- Realized in compliance with the standards ruling the materials for
alimentary use.
- Fitted with 1 gearless traction electric motor.
- No water hammering during operation and regeneration.
- Reduced loss of pressure during operation.
- Possible chlorine producing unit assembly in compliance with D.M. No.
443 standard.
- SWEET-M water softeners are supplied preloaded and equipped with
hardness mixer and by-pass.
- Hardness test.
• Optional accessories
- For optional accessories intended for SWEET-M water softeners, see
page 113.
• Certification
- SWEET-M water softners are EC type approved.
A B
water softener average maximum maximum power Salt consumption salt A B C D weight**
type capacity capacity pressure voltage for regeneration container
l/h l/h bar V/Hz kg kg mm. mm. mm. Ø kg
SWEET 8 M 600 1.200 6 230/50 mon. 2,2 55 316 559 673 3/4” 23
SWEET 15 M 1.200 1.600 6 230/50 mon. 2,7 100 316 559 1.006 3/4” 29
SWEET 22 M 1.600 2.500 6 230/50 mon. 3,7 125 316 559 1.127 3/4” 35
* Non-continuous maximum capacity - ** Weight: with filling material
Cyclic capacity has been calculated with water overall hardness being 26° F (260 ppm CaCO3); turbidity free, colourless, iron and oil free, and supplied at continuous
average capacity.
76
Water softeners
•EAU-M
- Time regeneration water softeners for domestic heating.
- Time electromechanical operation and programme valve.
- Rigid, shock-resistant, parallelepiped, compact and stylish shell in non-
toxic polyethylene.
- Realized in compliance with the standards ruling the materials for
alimentary use.
- Fitted with two gearless traction electric motors.
- No water hammering during operation and regeneration.
- Reduced loss of pressure during operation.
- Possible chlorite producing unit assembly in compliance with D.M. No.
443 standard.
- Hardness test.
- EAU-M water softeners are supplied preloaded.
• Optional accessories
- For optional accessories intended for EAU-M water softeners, see
page 113.
• Certification
- EAU-M water softners are EC type approved.
A B
water softener average maximum maximum power Salt consumption salt A B C D Peso**
type capacity capacity* pressure voltage for regeneration container
l/h l/h bar V/Hz kg kg mm. mm. mm. Ø kg
EAU 8 M 600 1.200 6 230/50 mon. 2,2 55 330 540 740 3/4” 23
EAU 15 M 1.200 1.600 6 230/50 mon. 2,7 100 330 540 1.040 3/4” 29
EAU 22 M 1.600 2.500 6 230/50 mon. 3,7 125 330 540 1.160 3/4” 35
* Non-continuous maximum capacity - ** Weight: with filling material
Cyclic capacity has been calculated with water overall hardness being 26° F (260 ppm CaCO3); turbidity free, colourless, iron and oil free, and supplied at continuous
average capacity.
77
Water softeners
•EAU-E Bios
- Time, volume* and volume/time combined regeneration water
softeners for domestic heating.
- Microprocessor electronic servocontrol operation and programme
valve.
- Equipped with “BIO COMPURITY SYSTEM” protection against build
up of bacteria.
- Rigid, shock-resistant, parallelepiped, compact and stylish shell in non-
toxic polyethylene.
- Realized in compliance with the standards ruling the materials for
alimentary use.
- Countercurrent regeneration for efficient resin feeding and reduced
water and salt consumption.
- Data storage guaranteed by a self-recharging accumulator for at least
three months of black out.
- The supply includes flexible pipes and a by-pass fitted with hardness
proportional mixer, backflow valves and built-in chlorine producing unit.
- In compliance with D.M. No. 443 standard.
- Hardness test.
• Optional accessories
- For optional accessories intended for EAU-E Bios water softeners, see
page 113.
- For volumetric* regeneration a pulse shaper kit shall be installed. See D
optional accessories on page 113.
• Certificazione
– EAU-E Bios water softners are EC type approved.
C
A B
water softener average maximum maximum power Salt consumption salt A B C D weight**
type capacity capacity* pressure voltage for regeneration container
l/h l/h bar V/Hz kg kg mm. mm. mm. Ø kg
EAU 8 E BIOS 600 1.200 6 230/50 mon. 2,2 55 330 540 740 3/4” 20
EAU 15 E BIOS 1.200 1.600 6 230/50 mon. 2,7 100 330 540 1.040 3/4” 30
EAU 22 E BIOS 1.600 2.500 6 230/50 mon. 3,7 125 330 540 1.160 3/4” 40
* Non-continuous maximum capacity - ** Weight: with filling material
Cyclic capacity has been calculated with water overall hardness being 26° F (260 ppm CaCO3); turbidity free, colourless, iron and oil free, and supplied at continuous
average capacity.
78
Water softeners
•DOUBLE-E
- Time, volume* and volume/time combined regeneration water
softeners for domestic/residential heating.
- Microprocessor electronic servocontrol operation and programme
valve.
- Cylinder in polyethylene strengthened with plastic reinforced by fiber
glass.
- Three-way proportional by-pass with non-return valve for models
Double 35E – Double 50E - Double 65E.
- Hardness mixer for models Double 35E – Double 50E - Double 65E.
- Connecting flexible pipes.
- Salt container in polyethylene.
- Possible chlorine producing unit assembly in compliance with D.M. No.
443 standard.
- Hardness test.
- Models DOUBLE 35E and 50E are supplied preloaded.
• Optional accessories
- For optional accessories intended for DOUBLE-E water softeners, see B A
page 113. G
- For volumetric* regeneration a pulse shaper kit shall be installed. See
optional accessories on page 113.
useful space
utile)
• Certification E
D
(spazio
– DOUBLE-E water softners are EC type approved. C
• Range of products
- DOUBLE 35E-50E-65E: for domestic heating. F
- DOUBLE 85E-125E: for residential heating.
water softener average maximum maximum power Salt consumption salt A B C D E F G weight**
type capacity capacity* pressure voltage for regeneration container
l/h l/h bar V/Hz kg kg mm. mm. mm. mm. mm. mm. Ø kg
DOUBLE 35 E 1.800 2.700 6 230/50 mon. 7 200 800 260 1.335 1.435 530 1.050 1 1/4” 60
DOUBLE 50 E 2.400 3.000 6 230/50 mon. 9,5 200 900 330 1.600 1.700 530 1.050 1 1/4” 85
DOUBLE 65 E 3.500 5.500 6 230/50 mon. 16 300 1.100 370 1.600 1.700 700 1.060 1 1/4” 101
DOUBLE 85 E 5.700 8.100 6 230/50 mon. 21 300 1.150 400 1.900 2.000 700 1.060 1 1/2” 164
DOUBLE 125 E 7.500 10.000 6 230/50 mon. 31 300 1.150 400 1.900 2.000 700 1.060 1 1/2” 176
* Non-continuous maximum capacity - ** Weight: with filling material
Cyclic capacity has been calculated with water overall hardness being 26° F (260 ppm CaCO3); turbidity free, colourless, iron and oil free, and supplied at continuous
average capacity.
79
Water softeners
•PLUS-E
- Time, volume* and volume/time combined regeneration water
softeners for industrial heating.
- Electronic servocontrol operation and programme valve.
- Cylinder in polyethylene strengthened with plastic reinforced by fiber
glass for models PLUS 165E and PLUS 215E.
- Hot-galvanized steel cylinder for models PLUS 265E and PLUS 550E.
- Connecting flexible pipes.
- Salt container in polyethylene.
- Hardness test.
• Optional accessories
- For optional accessories intended for PLUS-E water softeners, see
page 113.
- For volumetric* regeneration a pulse shaper kit shall be installed. See
optional accessories on page 113.
• Certification
B A
– PLUS-E water softners are EC type approved.
G
utile)
(spaziospace
Sales Department.
E
D
useful
C
water softener average maximum maximum power Salt consumption salt A B C D E F G weight**
type capacity capacity* pressure voltage for regeneration container
l/h l/h bar V/Hz kg kg mm. mm. mm. mm. mm. mm. Ø kg
PLUS 165 E 9.000 15.000 6 230/50 mon. 40 800 1.600 470 2.030 2.330 1.000 1.200 2” 246
PLUS 215 E 10.000 16.800 6 230/50 mon. 53 800 1.600 470 2.030 2.330 1.000 1.200 2” 288
PLUS 265 E 12.600 18.000 6 230/50 mon. 65 1.000 1.670 600 2.330 2.630 1.160 1.350 2” 387
PLUS 330 E 18.000 25.000 6 230/50 mon. 82 1.000 2.060 750 2.415 2.720 1.160 1.350 2” 683
PLUS 425 E 18.600 25.500 6 230/50 mon. 106 1.000 2.060 750 2.415 2.720 1.160 1.350 2” 718
PLUS 550 E 24.000 32.000 6 230/50 mon. 137 1.500 2.315 900 2.450 2.750 1.265 1.350 2” 932
* Non-continuous maximum capacity - ** Weight: with filling material
Cyclic capacity has been calculated with water overall hardness being 26° F (260 ppm CaCO3); turbidity free, colourless, iron and oil free, and supplied at continuous
average capacity.
80
Water filter
•“cartridge” FCO
- Chromium-plated and polished brass header.
- Shatterproof and non-ageing trogamid T transparent glass.
- Long-lasting washable cartridge.
- Chromium-plated bronze connection header for models FCO _” and
FCO 1”.
- Washable plaited stainless steel cartridge with high-filtering wide surface
for models FCO 1 1/2” and FCO 2”.
• Installation and Maintenance
- Easy installation thanks to high adaptability to house appliances. Simply
connect the filter to the water delivery system outlet.
- Maintenance is made simple thanks to the filter’s simple structure.
• Certification
- FCO filters are EC type approved.
filter filter maximum recommended maximum max. operation filtering connections weight
code type capacity capacity temperature pressure degree
l/min. l/min °C bar micron Ø kg
00052770 FCO 3/4” 70 45 30 7 60 3/4” 3
00052780 FCO 1” 100 55 30 7 60 1” 3
00052790 FCO 1 1/2” 150 100 30 7 50 1 1/2” 4
00052800 FCO 2” 250 170 30 7 50 2” 3,5
•“cleaning” FCP
- Brass header.
- Shatterproof and non-ageing trogamid T transparent glass.
- AISI 316 stainless steel cartridge.
- Internal parts in plastic material for alimentary use.
- Maintenance spanner.
• Installation and Maintenance
- Easy installation thanks to high adaptability to house appliances. Simply
connect the filter to the water delivery system outlet.
- Maintenance is made simple thanks to the filter’s simple structure.
• Certification
- FCP filters are EC type approved.
filter filter maximum recommended maximum max. operation filtering connections weight
code type capacity capacity temperature pressure degree
l/min. l/min °C bar micron Ø kg
00053440 FCP 3/4” 50 40 30 10 90 3/4” 2
00053450 FCP 1” 75 60 30 10 90 1” 2
00053460 FCP 1 1/4” 80 70 30 10 90 1 1/4” 2
•“self-cleaning” FCA
- All plastic parts are made of acetal resin.
- All metal parts are made of brass.
- Shatterproof and non-ageing trogamid T transparent glass.
- AISI 316 stainless steel cartridge.
- NBR gasket.
- Maintenance spanner.
- Adjustable inlet-outlet flange.
- Backwashing turbojet.
• Installation and Maintenance
– Easy installation thanks to high adaptability to house appliances. Simply
connect the filter to the water delivery system outlet.
- Maintenance is made simple thanks to the filter’s simple structure.
• Certification
- FCA filters are EC type approved.
filter filter maximum recommended maximum max. operation filtering connections weight
code type capacity capacity temperature pressure degree
l/min. l/min °C bar micron Ø kg
00053400 FCA 3/4” 50 40 30 10 90 3/4” 3
00053410 FCA 1” 75 60 30 10 90 1” 3
00053420 FCA 1 1/4” 80 70 30 10 90 1 1/4” 3
81
Water filter
•FT - FF - FD
- Mineral container in plastic reinforced by fiber glass
- Automatic valve with microprocessor control.
• Certification
- FT – FF - FD filters are EC type approved.
• Range of products
- FT filter: turbidity
- FF filter: deferrizator
- FD fitler: cleaner
82
Dosing pumps
•PDC
- Gradual regulation automatic dosing pump.
- Antacid header.
- Injection capacity regulation by means of % graduated switch.
- Maximum injection of 2 Lt./h of chemical product for PDC 2 and of 5
Lt./h for PDC 5.
• Installation and Maintenance
- Easy installation thanks to high adaptability to house appliances.
- Maintenance is made simple thanks to the dosing pump’s simple
structure.
• Optional accessories
- For the chemical product container intended for dosing pumps, see
optional accessories on page 113.
• Certification
– - PDC dosing pumps are EC type approved.
•PDPH
- Meter proportional automatic dosing pump.
- Meter shell in OT 58 equipped with variable proportionality dosing
pump control reader, 3.5 p.p.m. maximum dosage of Aquasil 20/40 P2
O5 chemical product for models PDPH 1.5 and PDPH 2,7.
- Models PDPH 1.5 and PDPH 2.7 are used to avoid boiler scaling and
corrosion.
- Antacid header for models PDPH 5 and PDPH 30.
- Bronze meter with pulse shaper automatic header for variable
proportionality dosing pump control maximum injection of 10 Lt./h of
chemical product for models PDPH 5 and PDPH 30.
- Regulation of the product amount by means of maximum 1000 p.p.m.
graduated switch for models PDPH 5 and PDPH 30.
• Optional accessories
- For the chemical product container intended for dosing pumps, see
optional accessories on page 113.
- For PLC chemical product use, see page 113.
• Certification
- PDPH dosing pumps are EC type approved.
83
Polyphosphate dosing units
•DPO
- Chromium-plated bright brass header.
- Chromium-plated brass unions male-male (only for model DPO 1”).
- Shatterproof and non-ageing trogamid T transparent glass.
• Certification
- DPO dosing units are EC type approved.
• Range of products
- DPO/A dosing unit, corrosion inhibitor for water featuring a hardness
degree up to 15°F.
- DPO/B dosing unit, corrosion inhibitor and anti-scale fluid for water
featuring a hardness degree exceeding 15°F.
dosing unit dosing unit minimum loss of amount of water treated maximum maximum polyphosphate weight
code type maximum pressure with inhibiting charge pressure temperature charge
capacity max. tipo A tipo B
l/min. bar m3 max. m3 max. bar °C g kg
00052730 DPO 1/2" A 2-25 0,25 20 – 10 40 80 1,5
00052740 DPO 1" A 4-60 0,25 180 – 10 40 800 4,5
00052750 DPO 1/2" B 2-25 0,25 – 20 10 40 80 1,5
00052760 DPO 1" B 4-60 0,25 – 180 10 40 800 4,5
84
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08509860 Split simple high kit Ø 80 XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
85
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
86
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
• Concentric roof-top discharge kit 1 , with lead propeller nut 2 and berm discharge 3
Technical description
- one concentric pipe L=1.2 Mt. Ø 125 with flue terminal
- Aluminium reduction stub pipe Ø 60/80 1
- Plastic reduction stub pipe Ø 100/125
3
- Coaxial connection stub pipe Ø 60/80 with inspection outlets 2
- Aluminium reduction M/F Ø 60
For model FUTURIA N 50, a flanged concentric 120 mm stub pipe “kit” is
necessary Ø 80/125 with flue inspection outlets “code 08516120”.
08507590 Concentric roof-top discharge kit Ø 125 FUTURIA L - FUTURIA N 50 - FUTURIA PLUS - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08507600 lead propeller nut Kit FUTURIA L - FUTURIA N 50 - FUTURIA PLUS - XILO LN - XILO - XILO D
XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08508100 berm discharge connection Kit FUTURIA L - FUTURIA N 50 - FUTURIA PLUS - XILO LN - XILO - XILO D
XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
• Concentric roof-top discharge kit 1 , with lead propeller nut 2 and berm discharge 3
Technical description
- one concentric pipe L=1.2 Mt. Ø 100 with flue terminal
- Coaxial connection stub pipe Ø 60/100 with inspection outlets 1
- Aluminium reduction M/F Ø 60
3
2
Warning: For models FUTURIA N 15 – FUTURIA N 25,
a flanged concentric connection “kit” is necessary “code 08516310”.
08514120 Concentric roof-top discharge kit Ø 100 FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
08507600 lead propeller nut Kit FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
08508100 berm discharge connection Kit FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
87
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08509000 Concentric extension 1 Mt. kit Ø 60/100 - A XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08515070 Concentric extension 1 Mt. kit Ø 60/100 - B XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08510130 Concentric extension 1 Mt. kit Ø 60/100 (condensation) - A FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
FUTURIA PLUS
08516110 Concentric extension 1 Mt. kit Ø80/Ø125 FUTURIA N 50
08511220 concentric terminal kit Ø60/Ø100 XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
L = 0,85 mt concentrica - A LED - ERA F S - ERA F BS - SIL S
08515160 concentric terminal kit Ø60/Ø100 XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA - LED
L = 0,83 mt concentrica - B ERA F S - ERA F BS - SIL S
08509030 concentric 90° bend kit Ø60/Ø100 - A XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08515100 concentric 90° bend kit Ø60/Ø100 - B XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
88
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08510140 concentric 90° bend kit Ø60/Ø100 (condensation) - A FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
FUTURIA PLUS
08516430 concentric 90° bend kit Ø80/Ø125 FUTURIA N 50
08509020 concentric 45° bend kit Ø60/Ø100 - A XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08515090 concentric 45° bend kit Ø60/Ø100 - B XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08510150 concentric 45° bend kit Ø60/Ø100 (condensation) - A FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
FUTURIA PLUS
08509490 concentric flanged 90° bend kit Ø60/Ø100 XILO LN - ERA F S - ERA F BS - SIL S
with flue inspection outlets - A
08515150 concentric flanged 90° bend kit Ø60/Ø100 XILO LN - ERA F S - ERA F BS - SIL S
with flue inspection outlets - B
08515200 concentric flanged 90° bend kit Ø60/Ø100 - B XILO - XILO D - XILO T - VELA XN - ALMA
08509060 Concentric flanged 120 mm stub pipe kit XILO LN - ERA F S - ERA F BS - SIL S
with flue inspection outlets Ø60/Ø100 - A
08515130 Concentric flanged 120 mm stub pipe kit XILO LN - ERA F S - ERA F BS - SIL S
with flue inspection outlets Ø60/Ø100 - B
08515190 Concentric flanged 120 mm stub pipe kit Ø60/100 - B XILO - XILO D - XILO T - VELA XN - ALMA
08514180 Concentric flanged 120 mm stub pipe kit Ø60/Ø100 FUTURIA L - FUTURIA N 15 - FUTURIA N 25 - FUTURIA N 35
with flue inspection outlets (condensation) - A FUTURIA PLUS
08516120 Concentric flanged 120 mm stub pipe kit Ø80/Ø125 FUTURIA N 50
with flue inspection outlets (condensation)
Warning: For models FUTURIA N 15 – FUTURIA N 25 – FUTURIA N 35, a flanged concentric connection “kit” is necessary “code 08516310”.
89
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08509010 Vertical concentric 1 Mt. Extension kit Ø60/Ø100 XILO LN - ERA F S - ERA F BS - SIL S
with flue inspection outlets* - A
08515080 Vertical concentric 1 Mt. Extension kit Ø60/Ø100 XILO LN - ERA F S - ERA F BS - SIL S
with flue inspection outlets - B
08515180 Vertical concentric 1 Mt. Extension kit Ø60/Ø100 - B XILO - XILO D - XILO T - VELA XN - ALMA
08509050 concentric bend strip kit Ø60/Ø100* - A XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
TREND - TREND L - ERA F S - ERA F BS - SIL S
08515120 concentric bend strip kit Ø60/Ø100 - B XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08509040 concentric extension strip kit Ø60/Ø100* - A XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08515110 concentric extension strip kit Ø60/Ø100 - B XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08506940 Split Ø80 0.5 Mt. extension kit XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
ALMA - ERA F S - ERA F BS - SIL S
08510050 Split Ø80 0.5 Mt. extension kit (condensation) FUTURIA L - FUTURIA N - FUTURIA PLUS
08506210 Split Ø80 1 Mt. extension kit INOVA L - XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
ALMA - ERA F S - ERA F BS - SIL S
08510060 Kit prolunga 1 mt. Ø 80 sdoppiata (condensa) FUTURIA L - FUTURIA N - FUTURIA PLUS
90
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08509840 split Ø80 90° bend kit FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08506930 split Ø80 45° bend kit FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509460 Inspection stub pipe kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08508090 tee reduction kit Ø 80/125 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509660 external washer kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08512030 internal washer kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
91
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08511360 split extension kit 0,5 mt. Ø 60 FUTURIA L - FUTURIA N - FUTURIA PLUS
08511390 vertical condensation collection stub pipe kit Ø 60 FUTURIA L - FUTURIA N - FUTURIA PLUS
08511370 horizontal condensation collection stub pipe kit Ø 60 FUTURIA L - FUTURIA N - FUTURIA PLUS
92
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08511400 extension connection joint kit F/F Ø 60 FUTURIA L - FUTURIA N - FUTURIA PLUS
08509830 External thermally insulated extension Kit 0,5 Mt XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
Ø 80 internal Ø 125 ALMA - ERA F S - ERA F BS - SIL S
08508370 External thermally insulated extension Kit 1 mt. XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
Ø 80 internal Ø 125 ALMA - ERA F S - ERA F BS - SIL S
08508400 condensation collection stub pipe kit Ø 80 XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
ALMA - ERA F S - ERA F BS - SIL S
08513590 Roof-top discharge terminal kit XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN - ALMA
ERA F S - ERA F BS - SIL S
08508930 split insulated 90° bend kit XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
ALMA - ERA F S - ERA F BS - SIL S
08508950 neck kit for thermally insulated pipe Ø 125 XILO-IN - XILO LN - XILO - XILO D - XILO T - VELA XN
ALMA - ERA F S - ERA F BS - SIL S
93
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08509610 extension kit 0,5 mt. Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509620 extension kit 1 mt. Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509630 extension kit 1,95 mt. Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509600 condensation collection 90° bend kit FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509640 spacer strip kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509650 strip kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
94
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08509590 air terminal kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN
XILO - XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08509670 flue terminal kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08510040 inspection plate kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
08510030 wall-fastened bracket kit Ø 80 FUTURIA L - FUTURIA N - FUTURIA PLUS - XILO-IN - XILO LN - XILO
XILO D - XILO T - VELA XN - ALMA - ERA F S - ERA F BS - SIL S
95
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08512080 condensation collection 90° bend kit Ø 60 FUTURIA L - FUTURIA N - FUTURIA PLUS
96
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
97
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
98
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
99
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08514610 flexible pipe flue covering kit Ø80 FUTURIA L - FUTURIA N - FUTURIA PLUS
08514630 flexible pipe inspection kit Ø80 FUTURIA L - FUTURIA N - FUTURIA PLUS
• Concentric accessories for flue suction and discharge for SAL water heaters
code description water heater
100
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
• Split accessories for flue suction and discharge for SAL water heaters
code description water heater
08513440 split discharge kit Ø80 SAL 150 S - SAL 180 S - SAL 220 S - SAL 300 S - SAL 400 S
08513510 split extension kit 1 m Ø80 SAL 150 S - SAL 180 S - SAL 220 S - SAL 300 S - SAL 400 S
08513520 split extension kit 0,5 m Ø80 SAL 150 S - SAL 180 S - SAL 220 S - SAL 300 S - SAL 400 S
08513530 split extension kit 0,25 m Ø80 SAL 150 S - SAL 180 S - SAL 220 S - SAL 300 S - SAL 400 S
08513500 split bend kit 90° Ø80 SAL 150 S - SAL 180 S - SAL 220 S - SAL 300 S - SAL 400 S
08513490 split bend kit 45° Ø80 SAL 150 S - SAL 180 S - SAL 220 S - SAL 300 S - SAL 400 S
101
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
Technical description
- 5 nichel-plated copper pipes
- 1 gas cock Ø 3/4”
- 1 gas cock Ø 3/4”
- Nipples and various unions
102
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
08512240 stainless steel universal water connection kit FUTURIA L - FUTURIA PLUS - ALMA - VELA XN
• Installation template
• By-pass kit
Technical description
In the event of total closure of zone thermostatic valves or of thermostatic controls of heating units, it
assures boiler heating system circulation.
- By-pass valve – Union pipes
code description boiler
103
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
• Disconnector kit
Technical description
It prevents heating system water from getting in contact with the water supply system water.
- disconnector – union pipes
code description boiler
104
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
• Probe kit
• Kit sequenziatore
08902550 anti-lime DPO kit XILO-IN - XILO LN - XILO - XILO D - XILO T - ALMA - VELA XN - SIL
105
Accessories for wall-hung and floor-standing gas boilers – gas water heaters
106
Accessories for wall-hung and floor-standing gas boilers – gas water heaters, Regulation systems and radiators
107
Accessories for gas and light oil boilers
• Remote kit
108
Accessories for gas and light oil boilers and radiators
• Kit sequenziatore
109
Air heaters accessories
08711390 Air suction kit Ø 140 AIR 21A÷ 73A - AIR 73AC
08506210 condensation discharge bend kit Ø 80 L=1 mt AIR 21A÷ 30A - AIR 30AC
08711410 condensation discharge bend kit Ø 100 L=1 mt AIR 43A÷ 73A - AIR 43AC÷ 73AC
08509840 condensation discharge bend kit 90° Ø 80 AIR 21A÷ 30A - AIR 30AC
08711430 condensation discharge bend kit 90° Ø 100 AIR 43A÷ 73A - AIR 43AC÷ 73AC
08711440 condensation discharge bend kit 90° Ø 80 AIR 21A÷ 30A - AIR 30AC
08711450 condensation discharge bend kit 90° Ø 100 AIR 43A÷ 73A - AIR 43AC÷ 73AC
08711460 Roof-top discharge terminal Kit Ø 80 AIR 21A÷ 30A - AIR 30AC
08711470 Roof-top discharge terminal Kit Ø 100 AIR 43A÷ 73A - AIR 43AC÷ 73AC
08507600 Kit raccordo scarico a terrazzo 1 AIR 21A÷ 73A - AIR 30AC÷ 73AC
08508100 berm discharge union kit 2 AIR 21A÷ 73A - AIR 30AC÷ 73AC
08711480 vertical grid kit AIR 21A - AIR 26A - AIR 30A
08711490 vertical grid kit AIR 43A - AIR 49A
08711500 vertical grid kit AIR 73A
110
Air heaters accessories
08711510 remote control panel AIR 21A÷ 73A - AIR 30AC÷ 73AC
• Kit mensola
08711520 Bracket kit AIR 21A÷ 73A - AIR 30ACE÷ 73ACE - IDRO LAMBY
08711540 Bracket kit AIR 30AC÷ 73AC
• Kit testata
08707490 Case filter kit LGE 25 - LGE 35 - LGE 25 OUT - LGE 35 OUT
08707500 Case filter kit LGE 51 - LGE 65 - LGE 51 OUT - LGE 65 OUT
08707510 Case filter kit LGE 80 - LGE 100 - LGE 80 OUT - LGE 100 OUT
08707520 Case filter kit LGE 125 - LGE 150 - LGE 125 OUT - LGE 150 OUT
08707530 Case filter kit LGE 175 - LGE 200 - LGE 175 OUT - LGE 200 OUT
08707540 Case filter kit LGE 250 - LGE 300 - LGE 250 OUT - LGE 300 OUT
08707550 Case filter kit LGE 375 - LGE 375 OUT
08707560 Case filter kit LGE 425 - LGE 500 - LGE 425 OUT - LGE 500 OUT
08707570 Case filter kit LGE 600 - LGE 600 OUT
08707580 Case filter kit LGE 750 - LGE 750 OUT
08707590 Case filter kit LGE 900 - LGE 900 OUT
111
Accessories for air heaters and regulation systems
• Grid kit
• Probe kit
112
Softeners Accessories
08902530 Pulse shaper kit (k 0,4 - 3/4”) EAU 8 E BIOS - EAU 15 E BIOS - EAU 22 E BIOS
08902440 Pulse shaper kit (k 0,4 - 1 1/4”) DOUBLE 35 E ÷ DOUBLE 65 E
08902080 Pulse shaper kit (k 0,1 - 1 1/2”) DOUBLE 85 E - DOUBLE 125 E - PLUS 165 E - PLUS 215 E
08902090 Pulse shaper kit (k 0,1 - 2”) PLUS 265 E ÷ PLUS 425 E
08902260 Pulse shaper kit (k 0,1 - 3”) PLUS 550 E
• Disinfecting Kit
Technical description
– This apparatus is intended for the protection against build up of bacteria which may arise from the softener cationic resins. Highly advanced
electrolytic automatic operation for the production of chlorine. The apparatus manufacturing complies to M.D. No. 443 of the 21/12/90.
• Chemical products
– All the chemical products reported below are supplied by our Spare Parts Service
• Acquasil 20/40: anti-scale fluid for alimentary use, corrosion proofing for pumps of the PDPH 15-40 type.
• LPC Polifosf A: powdered – for softened water – alimentary use.
• LPC-A-010: fluid – for softened water – alimentary use.
• LPC-T-011: fluid – for raw water – heating system use
• LPC Polifosf B: powdered - for raw water – alimentary use.
• LPC-A-020: fluid - for raw water – alimentary use.
• LPC-T-021: fluid - for raw water – cooling tower use.
• LPC-A-030: fluid – for softened water – alimentary use – boiler conditioning system.
• LPC-A-031: fluid - for softened water – alimentary use – condensation steam line.
• LPC-T-040: algaecide fluid.
• LPC-T-050: powdered for boiler cleaning, exchangers, etc.
113
Fastening template
GS GS condensation
condensation condensation
discharge discharge SC discharge
MB M
M C
RB G
SC F
G
R
F
AE
R
AE
80
52
102
152
188
225
283
348
398
G Gas Ø 3/4” (boiler) Ø 1/2” (connections) C hot water Ø 1/2” C hot water Ø 1/2”
F boiler feeding water Ø 1/2” G Gas Ø 3/4” (boiler) Ø 1/2” (connections) G Gas Ø 3/4” (boiler) Ø 1/2” (connections)
AE power supply F Boiler feeding water Ø 1/2” F Boiler feeding water Ø 1/2”
M system delivery Ø 3/4” AE Power supply AE Power supply
R system return Ø 3/4” M system delivery Ø 3/4” M system delivery Ø 3/4”
MB boiler delivery Ø 3/4” R system return Ø 3/4” R system return Ø 3/4”
RB boiler return Ø 3/4” GS supporting hooks Ø 10 mm. RC water tank recirculation Ø 1/2”
GS supporting hooks Ø 10 mm. SC condensation discharge Ø 80 mm. GS supporting hooks Ø 10 mm.
SC condensation discharge Ø 80 mm. SC condensation discharge Ø 80 mm.
FS additional supporting holes Ø 10 mm.
N.B. provide with female connections N.B. provide with female connections N.B. provide with female connections
Futuria Plus
comfort water
connections kit
114
Fastening templates
C hot water Ø 1/2” G Gas Ø 3/4” (boiler) Ø 1/2” (connections) G Gas Ø 3/4” (boiler) Ø 1/2” (connections)
G Gas Ø 3/4” (boiler) Ø 1/2” (connections) F boiler feeding water Ø 1/2” F boiler feeding water Ø 1/2”
F boiler feeding water Ø 1/2” AE power supply AE power supply
AE power supply M system delivery Ø 3/4” M system delivery Ø 3/4”
M system delivery Ø 3/4” R system return Ø 3/4” R system return Ø 3/4”
R system return Ø 3/4” GS supporting hooks Ø 10 mm. MB boiler delivery Ø 3/4”
GS supporting hooks Ø 10 mm. RB boiler return Ø 3/4”
GS supporting hooks Ø 10 mm.
N.B. provide with female connections N.B. provide with female connections N.B. provide with female connections
115
Fastening templates
Vela XN Sil
13,5
GS
600 10
476 29 382 29
62
21,5 102,5 290 105
440
146
Fissaggio
Fix 675
staffa
System AE 854 900
G
C G F
126 24,5
226
110 110 110 110
304
382
452
522
N.B. provide with female connections N.B. provide with female connections
116
Fastening templates
Silver S
328 272
292
57 95 50
75 69
a13
a12 a6
a1 a2
a10 a5
a11
706
a4
a7 70
421
225
201
191
155
162
122
72 a3 97
84 a9 102
167 a8
Boiler back
a1 system delivery Ø 1”
a2 Average temperature system return Ø 1”
a3 low temperature system return Ø 1”
a4 cold water inlet Ø 1/2”
a5 gas connection Ø 1/2”
a6 flue exhaust Ø 80”
a7 air inlet Ø 80”
a8 boiler discharge Ø 1/2”
a9 condensation discharge Ø 3/4”
a10 electric cable outlet Ø 40 mm.
a11 safety valve bleed Ø 14 mm.
a12 and a13 system zone delivery pipes Ø 1” (optional)
Silver BS
328 272
292
57 95 50
75 69
a13
a12 a6
a1 a9
a10 a8
a11 a2
a3 a5
a7 28 70
1111
a12
826
625
606
560
567
527
a13
302
77
a14
72 97
167 102
Boiler back
117
Notes
118
Notes
119
Notes