Operation Manual: Super Silent Technology 230V/400V - 50 HZ - 6,5 KW
Operation Manual: Super Silent Technology 230V/400V - 50 HZ - 6,5 KW
Operation Manual: Super Silent Technology 230V/400V - 50 HZ - 6,5 KW
Marine Generator
Marine_Panda_8000NE_Operation Manual
Panda 8000 NE
Super silent technology
230V/400V - 50 Hz - 6,5 kW
Dokument
Actual: Marine_Panda_8000NE_Operation Manual.R03_14.3.08
Revision Page
Copyright
Duplication and change of the manual is permitted only in consultation with the manufacturer!
Fischer Panda GmbH, 33104 Paderborn, reserves all rights regarding text and graphics. Details are given to
the best of our knowledge. No liability is accepted for correctness. Technical modifications for improving
the product without previous notice may be undertaken without notice. Before installation, it must be ensu-
red that the pictures, diagrams and related material are applicable to the genset supplied. Enquiries must be
made in case o doubt.
2
Contents
Current revison status ........................................................................................................... 2
Tools ........................................................................................................................................ 7
D Generator Failure..........................................................................................................85
D.1 Tools and Measuring Instruments ................................................................................ 85
D.2 Overloading the Generator ............................................................................................ 85
D.2.1 Monitoring the Generator Voltage ..................................................................................... 86
D.2.2 Automatic Voltage Monitoring and Auto-Shut Down ......................................................... 87
D.3 Setting the Speed Governor of the Actuator ................................................................ 87
D.3.1 Setting the maximum upper speed setting ........................................................................ 88
D.3.3 Greasing the trapezoidal thread spindle on the speed actuator ........................................ 90
D.3.4 Consequences of a continual overloading of the Actuator ................................................ 91
D.4 Generator-Output Voltage is too low ............................................................................ 93
D.4.1 Discharging the Capacitors ............................................................................................... 93
D.4.2 Checking the Capacitors ................................................................................................... 94
D.4.3 Check the Generator Voltage ............................................................................................ 95
D.4.4 Measuring the Ohm Resistance of the Generator Windings ............................................. 95
D.4.5 Check the Windings for Short Circuiting ............................................................................ 96
D.4.6 Measuring the Inductive Resistance ................................................................................. 96
D.5 Generator provides no voltage ..................................................................................... 97
D.5.1 Rotor Magnetism Loss and "Re-magnetising" ................................................................... 97
D.6 Engine Starting Problems ............................................................................................. 97
D.6.1 Fuel Solenoid Valve .......................................................................................................... 97
D.6.2 Re-start with Failure Bypass Switch .................................................................................. 98
D.6.3 Troubleshooting Table ....................................................................................................... 99
E Tables.......................................................................................................................... 101
E.1 Troubleshooting ........................................................................................................... 101
E.2 Types of coil ................................................................................................................. 111
E.3 Inspection checklist for services ................................................................................ 113
E.4 Engine oil ...................................................................................................................... 114
E.5 Coolant .......................................................................................................................... 115
B Measurements............................................................................................................ 143
B.1 Hole pattern .................................................................................................................. 143
Blank
since since since since since
1977 1978 1988 1988 1988
Icemaster GmbH Fischer Marine Conclusion Fischer - 100 % water cooled Panda Vehicle
Generators Icemaster GmbH Panda generators Generators
Fischer Panda
FISCHER GENERATORS have been manufactured since 1978 and are a well-known brand for first class diesel
generators with especially effective sound-insulation.
Fischer has been one of the leading manufacturers in respect of quality and know-how during this period.
FISCHER, as the worldwide manufacturer of modern marine diesel generators, developed the Sailor-Silent series for
example and produced a GFK sound-insulated capsule as early as 1979 and the basis for new generator technology.
The companies Fischer and Icemaster amalgamated under the direction of Icemaster in 1988, in order to concentrate
on the development of new products. Production was moved to Paderborn.
The amalgamation of the two qualified companies led to the development of a complete new programme within a short
space of time. The generators developed at that time set new technological standards worldwide.
The generators became more efficient and powerful than other generators in the same nominal performance range,
because of the improved cooling. Panda generator demonstrated its superiority in several tests by renowned institutes
and magazines during the past years. The patented VCS (voltage Control System) means it can meet all demands
including motor speed. The start-booster (ASB) means Panda generators meet the highest demands in respect of
voltage stability and starting values. A Panda generator, with the same drive motor, produces 15 % more effective
output than the majority of conventional generators. This superiority in efficiency also ensures a fuel saving to the same
extent.
The 100% water-cooled Panda generators are currently manufactured in the performance range from 2 to 100 kW in
various versions. Fast running motors are preferred for performances up to approx. 30 kW (nominal speed 3000 rpm).
The heavier slow runners are preferred for the higher range. The fast running generators have proved themselves
many times for many uses, that they meet the demands in quality of yachts and vehicles, and offer space and weight
saving of 50 % compared to slow running generators.
In addition to the Panda series, Fischer Panda also supply the super compact high-tech sound-insulated battery
charging generators from the DC/AC Panda AGT series, which is a very interesting solution for the production of mobile
power.
The HTG-alternators ensure that a charging rate of 285 amps is achieved that was scarcely thought possible for this
compact construction. This alternator replaces a separate shipboard generators (constant 230 volts AC with up to 3500
kW from the main machine)
Fischer Panda GmbH, 33104 Paderborn, reserves all rights regarding text and graphics. Details are given to the best of our knowledge. No liability is accepted for correct-
ness. Technical modifications for improving the product without previous notice may be undertaken without notice. Before installation, it must be ensured that the pictures,
diagrams and related material are applicable to the genset supplied. Enquiries must be made in case o doubt.
5
Safety first
These symbols are used throughout this manual and on labels on the machine itself to warn of the possibility of per-
sonal injury. Read these instructions carefully. It is essential that you read the instructions and safety regulations
before you attempt to assemble or use unit.
This danger symbol refers to toxic danger and draws attention to special warnings,
instructions or procedures which, if not strictly observed, may result in severe perso-
nal injury or loss of life.
This danger symbol refers to electric danger and draws attention to special
warnings, instructions or procedures which, if not strictly observed, may result in
electrical shock which will result in severe personal injury or loss of life.
6
Tools
This symbols are used throughout this manual to show which tool must be used at maintenance or installation.
Spanners
X = required size
X
Screw driver, for slotted head screws and for recessed head screws
7
CALIFORNIA
Proposition 65 Warning
1. The installation certificate must be completed when taken into use, and certified by a signature.
2. The installation certificate must be despatched within two weeks of use to Fischer Panda.
3. The official guaranty confirmation will be completed by Fischer Panda after receipt and sent to the customer.
4. A guaranty must be shown to make any claims.
Claims against the guaranty will not be accepted of the above said instructions are not, or only partially, carried out.
8
Safety Precautions
• The generator must not be taken into use with the cover removed.
• If the generator is being installed without a sound insulation capsule, then make sure, that all rotating parts (belt-
pulley, belts etc) are covered and protected so that there is no danger to life and body!
• If a sound insulation covering will be produced at the place of installation, then well-placed signs must show that
the generator can only be switched on with a closed capsule.
• All servicing-, maintenance or repair work may only carried out, when the motor is not running.
• There is full current in the AC control box when the generator is running. It must therefore be ensured that the con-
trol box is closed and cannot be touched when the generator is running.
• Do not work in an ambient, where there are explosives. Working on an electrical system in an ambient where there
are flammable gases is dangerous.
• Electrical voltages above 48 volts (battery chargers greater than 36 volts) are always dangerous to life). The rules
of the respective regional authority must be adhered to. Only an electrician may carry out installation of the elec-
trical connections for safety reasons.
Ground Wire:
The generator, is "earthed" as series (centre and ground are connected together in the generator terminal box by a
bridge). This is an initial ground fuse, which offers protection, as long as no other measures are installed. Above all,
it is conceived for the delivery and possible test run.
This "neutralisation" (Protective Earthing Neutral - PEN) is only effective, if all parts of the electrical system are com-
monly "earthed" to a common potential. The bridges can be removed, if this is necessary for technical reasons and
another protective system has been setup.
The battery must always be disconnected, if work on the generator or electrical system is to be carried out, so that
the generator cannot be unintentionally started. It is not allowed to disconnect the battery during operation!
After the generator has been stopped, the battery can be disconnected!
All load must be disconnected, in order to avoid damages to the devices. In addition the semi conductors in the AC
control box must be disconnected in order to avoid the boat capacitors being activated. The minus pole of the battery
ought to be removed.
9
Safety Instructions concerning the capacitors
Capacitors are required to run the generator. These have two varying functions:
A) The working capacitors
B) The (Booster) capacitors
Both Groups are located in a separate AC-Control box.
Capacitors are electrical stores. There could be a residual of high electrical current at the contacts for a period dis-
connection from the circuit. The contacts may not be touched for safety reasons, If the capacitors are to be
exchanged or checked, and then a short circuit between the contacts should be made so that the stored energy is
discharged.
If the generator is switched off in the normal manner, the working capacitors are automatically discharged by means
of the windings. The booster capacitors are discharged by means of internal discharge resistors.
All capacitors must be short-circuited before work is carried out on the AC-Control box for safety reasons.
Cable Type
It is recommended is that the cable used be UL 1426 (BC-5W2) compliant, with Type 3 stranding (ABYC Section E-
11)
Cable Size
The cable size must be selected taking into account the amperage, voltage and conductor length (from the positive
power source connection to the electrical device and back to the negative power source connection.
Cable Installation
It is recommended that a self draining wire loom classified as V-2 or better in accordance with UL 94 be installed in
the section of the cable routed in the interior of the sound capsule. Care should be taken to avoid hot surfaces such
as the exhaust manifold or engine oil drain bolt and routed clear of any possible sources of chafing.
Battery
Warning:
Do not use Gel-Cel batteries, because the regulation voltage is high for this type of batteries.
Do not use large batterybanks as a starting battery. The generator must have a dedicated starter battery (maximum
size group 24).
Recommend starter battery size (if model not shown - please see engine manual)
Panda 6000 -8000 12V, 28AH equivalent Panda 18 12V, 65AH equivalent
Panda 9000-14000 12V, 36AH equivalent Panda 24-30 12V, 70AH equivalent
Panda 16 12V, 52AH equivalent Panda 33-42 12V, 100 to 120AH equi-
valent
10
5 Safety steps to follow if someone is the
victim of electrical shock
If you cannot turn off the electrical power, pull, push, or lift the person to safety using a
14 wooden pole, rope, or some nonconductive material.
After the injured person is free of contact with the source of electrical shock, move them a
15 short distance away and immediately start necessary first aid procedures.
11
WHEN AN ADULT STOPS BREATHING
WARNING
DO NOT attempt to perform the rescue breathing techniques provided on this page, unless
certified. Performance of these techniques by uncertified personnel could result in further
injury or death to the victim.
12
The Panda Generator
01
03
02
04
05 06
07 08
09
10
11
13
12
14
15 16
06
07
02
01 08
03
04
09
05
10
11
12
13 14 15
06
01
07
03
08
02
09
04
10
05
11 12 13 14 15 16 17 18 19 20 21
01) Ventilation screw internal cooling water pump 12) Fuel intake connection
02) Fuel solenoid valve 13) Fuel backflow connection
03) Pulley for internal cooling water pump 14) Fuel pump cable (2x1,5mm²)
04) Seawater pump 15) Oil drain hose
05) Fuel fine filter 16) Remote control panel cable (12x1mm²)
06) Ventilation screw thermostat housing 17) Electronic Voltage Control cable VCS (5x1mm²)
07) Thermostat housing with thermostat set 18) AC-Control box cable
08) Alternator 12 V 19) Load
09) V-belt for DC-alternator and internal cooling water pump 20) Batterie minus (-)
10) Engine oil filter 21) Batterie mlus (+)
11) Seawater inlet
01 02
03
04
05
06
07 08 09
01
07
02
08
09
03
04 05
10
06
11 12
Seite 18 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
Heat exchanger
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 19
The Panda Generator
Ventilation valve
Freshwater backflow
Seite 20 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
Ventilation pipe
Heat exchanger
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 21
The Panda Generator
Seite 22 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 23
The Panda Generator
1. Fuel intake
2. Fuel backflow 1 2
Fuel Filter
Seite 24 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
The fuel solenoid valve opens automatically if "START"is pressed on the remote control panel".
The solenoid closes, if the generator is switched to "OFF"position.
It takes a few seconds before the generator stops. If the generator does not start or does not run
smoothly (i.e. stutters), or does not attain full speed, then the cause is fore-mostly the solenoid.
Injection Nozzles
Glow plugs
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 25
The Panda Generator
Seite 26 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 27
The Panda Generator
Exhaust outlet
Seite 28 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
Main Power
1. Fuel pump
3. VCS
4. AC-Control-Box
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 29
The Panda Generator
Starter motor
2. Solenoid switch
Seite 30 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
DC Alternator
Sample Picture
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 31
The Panda Generator
Sample Picture
F1 F2
Seite 32 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
Thermo-switch at water-cooled
exhaust elbow
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 33
The Panda Generator
Seite 34 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
Oil dipstick
Oil filter
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 35
The Panda Generator
AC Control Box
An AC-Control box is necessary for run-
ning the generator. This AC-Control Box
contains electronics for the VCS control
as well as different monitoring elements
and condensers necessary for the excita-
tion of the generator.
Seite 36 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator 14.3.08
The Panda Generator
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 37
The Panda Generator
Blank
14.3.08 Marine_Panda_8000NE_Operation Manual.R03 - Chapter A: The Panda Generator - Description of the Generator Seite 38
Installation Instructions
B. Installation Instructions
B.1 Placement
Since Panda generators have extremely compact dimensions, they can be installed in tight locati-
ons. Attempts are sometimes made to install them in almost inaccessible places. Please consider
that even almost maintenance-free machinery must still remain accessible at least at the front
(drive belt, water pump) and the service-side (actuator, dipstick). Please also note that in spite of
the automatic oil-pressure sensor it is still essential that the oil level has to be checked regularly.
The generator should not be placed in the proximity of light walls or floors, which can have reso-
nance vibrations because of airborne sounds. If this should be unavoidable, then it is recommen-
ded that this surface is lined with 1 mm lead foil, which will change the mass and the vibration
behaviour.
You should avoid fixing the generator on a slippery surface with little mass (i.e.). This acts as an
amplifier of airborne sounds in the most unreasonable case. An improvement can be achieved by
reinforcing these surfaces with ribs. In addition, the breakthroughs, which interrupt these sur-
faces, should be sawed off. The lining of the surrounding walls with a heavy layer (i.e lead) and
foam additionally improve the conditions.
The generator sucks its air from the surrounding engine room. Therefore it must be ensured that
sufficient ventilation openings are present, so that the generator cannot overheat.
High temperature of the intake air decline the power of the generator and increases the coolant
temperature. Air temperatures of more than 40 °C red uce the power by 2 % per temperature rise
of 5 °C. In order to keep these effects as small as possible, the temperature in the engine room
should not be higher than 15 °C in relation to the o utside temperature.
Connect all electrical wires within the capsule tightly to the motor and the generator. This is also
the case for fuel lines and cooling water lines.
The electrical connections MUST be carried out according to the respective valid regulati-
ons. This also concerns used cable materials. The cable supplied is meant for laying "pro-
tected" (i.e. in pipe) at a temperature up to a max of. 70 °C (160 °F). The on-board circuit
must also be fitted with all essential fuses.
1
10 11
2 3 4 5 6 7 8 9
1 2
The genset should have its own raw water (coolant water) inlet and should not be connected to
any other engine systems. Ensure that the following installation instructions are complied with:
For the avoidance of galvanic corrosion, refer to the chapter "Service instruction for
marine generators (corrosion protection)".
In order to keep the suction resistance in the line at a minimum, the raw water intake system (i.e.
sea cock, thru-hull fitting, inlet filter, etc.) must have an inner diameter of at least 1" (25 mm).
This applies also to installation components such as thru-hull fitting, sea cock, raw water filter etc.
The intake suction line should be kept as short as possible. Install the raw water inlet in close pro-
ximity to the genset.
After start-up the cooling water quantity must be measured (e.g. by catching at the
exhaust). The flow rate, as well as the necessary cross section of the cooling water pipe
see section E.3, “Technical Data Generator,” on page 83
The Panda is equipped with a direct drive water intake pump mounted directly on the motor.
Since the intake pump is an impeller pump there are wearing parts which are likely to require
replacement after a period of time. Ensure that the genset is installed so that the intake pump can
be easily accessed. If this is not possible, an external intake pump could be installed in an easily
accessible location.
If the generator is installed above the waterline, it is possible that the impeller will wear out faster,
because after starting, the pump runs dry for some seconds.
The raw water hose should form a loop as near as possible to the raw water inlet of the generator
(see picture below). This ensures the pump only sucks in air for a short time. The impeller pump
will be lubricated by raw water and the impeller life span will be increased.
By the installation of a check valve in the raw water inlet line, which is under the waterline, this
problem can be restricted.
The impeller pump will remain intact longer, if an electrical booster pump is installed, and is stron-
gly recommended in order to preserve the impeller pump.
NOTE:
Never change the impeller for many years, without exchanging the old pump. If the
sealing ring is defective within the pump, raw water runs into the sound cover of the
genset. A repair is then very expensive.
Replacement impeller and also a spare pump should always be on board. The old
pump can be sent back to Fischer Panda.
B.3.7 Indirect Cooling of the Genset Housing (by the Heat Exchanger)
B.4.2 Ventilating at the first filling of the Internal Cooling Water Circuit
10
10
Fig. B.4.2-3: venting screw
6. Repeat the steps 1-4 till no air comes out of the vent screw at tthermostat housing.
Close the vent screws.
Fill up the expansion tank.
Close the expansion tank.
7. Re-ventilating process 10 Operating hours after the first start-up (and if necessary)
Also after the first implementing a small amount of air can be reside in the cooling circuit. To
ensure an imaculate und actual operating of the cooling system the ventilating process must be
repeated casual in the next few days (weeks, if necessary). Small amount of air will still exit out of
the ventilating openings, especially if the generator stood still for a long time.
Anti-freeze
In the interest of safety, the freezing point of the closed circuit coolant should be checked on a
regular basis. Be sure that the coolant/antifreeze mixture is good for at least -15°C (5 ° F) and if i t
is possible that your genset experiences lower temperatures, for example during storage or trans-
portation, then the entire cooling system should be drained and purged
Check if a temperature difference exists between cooling water in-flow and cooling water return
flow by use of the hand.
Feel the cooling water in-flow line at the internal cooling water pump.
Feel the cooling water return pipe either at the outlet of the water-cooled exhaust elbow union or
at the side, where this pipe exits at the heat exchanger.
The temperature difference between in-flow and return should be approx 10 degrees.
Fig. B-1: Scheme for Freshwater Circuit at Two Circuit Cooling System
Check if a temperature difference exists between cooling water in-flow and cooling water return
flow by use of the hand.
Feel the cooling water in-flow line at the internal cooling water pump.
Feel the cooling water return pipe either at the outlet of the water-cooled exhaust elbow union or
at the side, where this pipe exits at the heat exchanger.
The temperature difference between in-flow and return should be approx 10 degrees.
Fig. B-2: Scheme for Freshwater Circuit at Two Circuit Cooling System
By injecting the outlet raw water into the exhaust manifold, the exhaust gases are cooled and the
noise emissions from the exhaust system are reduced.
The generator exhaust system must remain completely independent and separate from the
exhaust system of any other unit(s) on board. The exhaust hose has an inner diameter of 30 mm.
The water lock must be installed at the lowest point of the exhaust system. An optional noise
insulated water lock can also be installed. The exhaust hose descends from the capsule to the
water lock. Then the hose rises via the "goose neck" to the silencer (see drawing). The goose
neck must be vertical and sit preferably along the ship's keel centre line. The exhaust system
must be installed so that the back pressure inside the exhaust does not exceed 0.4 bar (6 psi)
and total length does not exceed 6 m (20 ft.).
Exhaust diameter see section E.3, “Technical Data Generator,” on page 83.
1. Generator 4. Silencer
2. Water lock 5. Hull outlet
3. Goose neck
In order to reduce the noise level of the generator unit to a minimum, an optional exhaust outlet
muffler can be mounted next to the thru-hull fitting. Additionally there is a component at Fischer
Panda, which acts as both an "exhaust goose neck", and water separator. With this "exhaust/
water separator" the cooling water is derived over a separate pipe. The exhaust noises emana-
ting from the exterior of the yacht are strongly decreased. Particularly the "water splash".
If the exhaust/water separator was sufficiently highly installed, a goose neck is no longer neces-
sary. The exhaust/water separator fulfils the same function. If the "Super silent" exhaust system
were installed correctly, the generator will not disturb your boat neighbour. The exhaust noise
should be nearly inaudible. The best result is reached, if the hose line, which derive the cooling
water, is relocate on a short way "falling" directly to the outlet and this outlet is under the water-
line.
1 2 3 4
1. Generator 4. Silencer
2. Silencer / Water lock 5. Sea cock
3. Exhaust-Water-Separator 6. Hull outlet
If the thru-hull exhaust outlet has to be mounted far from the generator, an exhaust-water separa-
tor must definitely be installed. The raw water from the separator must then run along the shortest
possible path is the thru-hull outlet. For such long exhaust routes, the exhaust hose diameter
should also be increased from NW40mm to NW50mm in order to reduce the back-pressure. The
exhaust may have a length of over 10m (32 ft.) if the exhaust hose diameter is increased to
50mm. An additional outlet exhaust muffler close to the hull outlet will help further to reduce noise
emissions.
The generator will not disturb your boat neighbours, if the "Super silent Exhaust System has been
correctly installed. The exhaust noise should be almost inaudible.
Inside the generator capsule itself, there is the fuel filter installed (exception: Panda 4200 and
4500). Additional fuel filters (with water separator) must be mounted outside the capsule in easily
accessible places in the fuel lines between the tank intake fuel pump and the diesel motor's fuel
pump.
Generally forward and return fuel flow pipes must be mounted to the diesel tanks. Do not connect
the generator fuel supply lines with any other fuel lines of other diesel systems.
• The following items need to be installed:
• Fuel supply pump (12 V - DC)
• Pre-filter with water separator (not part of the delivery)
• Fine particle fuel filter
• Return fuel line to fuel tank (unpressurized)
The fuel supply pump should be mounted as close to the fuel tank as possible. The electric cable
for the fuel pump is already installed on the generator (length 5 m).
1 2 3 4 5
6
8
Lead the return fuel pipe connected to the day tank to the floor
The return pipe connected to the tank must be dropped to the same depth as the suction pipe, if
the generator is mounted higher than the tank, in order to prevent fuel running back into the tank
after the motor has been switched off, which can lead to enormous problems, if the generator is
switched off for a long period.
A non-return valve must be fitted to the suction pipe, which prevents the fuel flowing back after
the generator has been switched off, if it is not possible to use the return flow pipe as a submerge
pipe placed in the tank. The instructions "Bleeding Air from the Fuel System" must be read after
initial operation or after it has stood still for a long period, in order to preserve the starter battery.
If the fuel tank should be installed over the level of the generator (e.g. daily
tank), then a non-return valve must be installed into the fuel return pipe to
guarantee that through the return pipe no fuel is led into the injection pump.
Normally, the fuel system is designed to vent air itself i.e. as soon as the electric starter motor
starts; the fuel pump starts working and the fuel system will be air-vent automatically after some
time. It is, nevertheless essential, to vent the system as follows prior to the first operation (as all
hoses are empty):
1. Switch main power switch on control panel "ON".
2. Push failure bypass switch and hold tight.
The electric fuel pump has to be run audibly. By moving the failure bypass switch you can hear
the solenoid valve of the generator starting and stopping (when the sound insulation cover is
taken off).
3. After the fuel pump has been running 3 to 4 minutes, because the failure bypass switch has
been pressed down, the bleeding screw of the solenoid valve has to be unscrewed. The switch
has to be continuously depressed, when opening the screw. A piece of cloth or absorbent paper
should be put under the connection to avoid fuel entering the sound insulation cover.
4. The air vent screw can be screwed in again, as soon as fuel runs out without bubbles. Then
release the depressing the failure bypass switch.
5. Starting the generator
Now the generator can be started by pushing the "START"-button. The generator should start
after a short while. One of the pipe union nuts of an injection hose has to be unscrewed, should
the unit not start; then try to restart the generator. After the generator has started, the pipe union
nut has to be tightened again.
Main power switch "OFF"
The Panda generators from 8.000 NE upwards have their own dynamo to charge a 12 V starter
battery.
It is recommended to install an additional starter battery for the generator.
The generator is then independent from the remaining battery set. This enables you to start the
genset at any time with its own starter battery even if the other batteries are discharged. A further
advantage of a separate starter battery is that it isolates the generator's electric system from the
rest of the boat's DC system, i.e. minus pole (-) is not connected electrically to Earth/Ground.
The generator is then Earth/Ground free.
1 2 3
Fig. B.7.1-3: DC-Relay
B.7.2 Connection of the remote control panel - see separate control panel
manual
A power source selector switch must be installed between the generator (or if applicable,
AC-Control box) and the ship's electrical supply system. This switch must used to ensure
that all AC consumers can be switched off at once. This switch should also be installed to
keep the generator and shore (grid) power systems separate.
The cam-type switch must have 2 poles, so that "MP" and "phase" can be switched off.
If a 3-phase current system is also installed with the option of supplying from either the generator
or shore power, an additional switch must be installed to keep these systems separate.
An alternative to a manual rotating switch is an automatic power relay. When the generator is not
running, the relay remains in the shore power position. As soon as the generator is running, the
power relay switches automatically to the generator position.
Note: If the system has both single and 3-phase AC, it is CRITICAL that the two systems
remain SEPARATE!
Protection conductor
The generator is provided with a PEN safety system, as standard, which connects the 3-phase
delta centre point "N" to the safety ground strap.
If a separate ground protection cable is necessary (i.e. due to national safety regulations), the
bridge between the generator housing and ground (in the AC-Control box) must be disconnected.
Once such a ground protection cable is installed, it must be connected to the ground straps of all
on board electrical devices.
In order to monitor the electrical system, it is recommended to install a voltmeter (and, if possible,
a current meter) down line from the power source selector switch so that all respective power
sources can be monitored. A separate voltmeter for the generator, itself, is therefore not required.
Electrical fuses
It is absolutely essential that the electrical system installation is inspected by a qualified electrical
technician. The generator should have its own AC input electrical fuses. The fuses should be
sized such that the rated current of the generator on each of the individual phases is not excee-
ded by more than 25%.
Data for gensets with power output greater than 30 kW on request!
The fuses must be of the slow type. A 3-way motor protection switch must be installed to protect
the electrical motor.
Required fuses see Tabelle 8, “Rated current,” auf Seite 108
The required capacitors for the excitation of the generator are located in the AC-Control box, as
well as the electronic control for voltage/speed regulation (VCS) and the starting current re-
inforcement (ASB). The AC-Control box must be connected by electrical wires (high voltage and
low-voltage) to the generator.
The front panel must always be closed, since the AC-Control box produces 400 V during opera-
tion.
The AC-Control box must be electrically connected to the generator (high and low
voltage).
ATTENTION! Before working on the System read the "Section Safety Instruc-
tions in this Manual".
All Panda generators from Panda 8000 upwards are fitted with the electronic voltage control
"VCS" as standard.
The VCS controls the generator voltage and motor speed. A actuator on the injection pump can
increase the engine speed by up to 8%.
If the generator is run without load, the voltage should be 231V with a frequency of approx 48.5 to
49Hz. The frequency (equates to the speed) can be increased by up to 8%. This ensures that the
engine speed is increased when there is an extra load. The maximum speed is achieved when
80% load is reached.
The speed gauge is governed by an adjusting screw, above and below. Adjustment of this screw
may not occur without the expressive approval of the manufacturer.
All signals pass through the circuit board in the AC-Control box. The signal impulse for the actua-
tor is passed to the electric motor by means of the 5 core wire.
The generator maintains its full capability if the VCS has a defect.
In this case the base current must be raised to at least 240 V by adjusting the minimum setting on
the speed gauge, in order to ensure that the generator output voltage at 70% nominal load does
not drop below 215 V.
1 2 3
4 5 7
Additionally, the automatic start booster is located on the circuit control board. The starting cur-
rent is increased by connecting a second group of capacitors (C2), if the voltage drops below a
pre-set voltage. The starting current can be increased by 300% for a short period by combining
both components voltage/speed control and ASB Start booster.
Blank
C. Maintenance Instructions
• Oil level
• Visual check for any changes, leaks oil drain system, v-belt, cable connections, hose clips, air
filter, fuel lines
Once a month
• Grease/oil the servo motor - Trapezoid thread-Spindle
Maintenance invervals siehe “Inspection checklist for services” auf Seite 113.
C.1.2 Check of Hoses and Rubber Parts in the sound insulated capsule
Check all hoses and hose connections for good condition. The rubber hoses are very sensitive to
environmental influences. They wear quickly in an environment of dry air, oil and fuel vapours,
and high temperatures. The hoses must be checked regularly for elasticity. There are operating
situations, when hoses must be renewed once a year.
Additionally to usual tasks of maintenance (oil level check, oil filter control etc.) further mainte-
nance activities are to be accomplished for marine generators, such as control of the sacrificial
anode (cooling water connection block) and the front seal cover at the generator.
The first oil change is to be accomplished after a period of operation from 35 to 50 hours. After-
wards the oil is to be changed after 100 hours. For this the oil SAE30 for temperatures over 20°C
and SAE20 for temperatures between 5°C and 20°C is to be used. At temperatures under 5°C oil
of the viscosity SAE10W or 10W-30 is prescribed.
17
Refill Oil
New oil is poured in, after opening the cap
of the oil filler neck. Please wait a
moment, before measuring the oil level;
the oil must first settle in the sump.
Oil Dipstick
The oil level is checked by use of the
engine oil dipstick. The prescribed filling
level may not exceed the "Max"marking.
Normally, the fuel system is designed to ventilate air itself i.e. as soon as the electric starter motor
starts operation the fuel pump starts working and the fuel system will be de-aerated after some
time automatically. It is nevertheless essential to ventilate the system as follows prior to the first
operation (as all hoses are empty):
1. Main power switch "OFF"
10
17
ATTENTION! The
generator must be
switched off before
opening the ventila-
ting points!
10
10
The external compensation tank should be filled to a max 20% in a cold state. It is very
important that a larger expansion area is maintained above the cooling water level.
If there is no change to the state of the cooling water level, the generator is re-started for 5 minu-
tes. Thereafter the de-aeration must be repeated two to three times.
Fig. C.4-5: Ventilation Screw above the Cooling Water Pump Casing
C.4.5 Exchange of the V-Belt for the Internal Cooling Water Pump
The relative high ambient temperature in the closed sound insulated capsule (about 85°C) can be
a reason for a reduced lifespan of the v-belts. It is possible that the "softener" in the rubber com-
pound lose their effect after a short operating time because the air in the sound insulated capsule
can be relative warm and dry. The v-belt must be controlled at very short time intervals. It may be
required to change the v-belt after several weeks because of unfavourable conditions. Therefore,
control should be carried out after an interval of 100 operating hours. The v-belt is a wearing part.
There should be enough spare v-belts on board. We recommend that you have the respective
manual within reach.
13
13
ATTENTION! On the side, the fixing bolts must be applied with an electrically neutral fat
(e.g. anti seize). If the fixing bolts (high-grade steel) are screwed into the aluminium
threads without the grease being used, then there is a danger of corrosion, and it is possi-
ble that the thread wears out when loosening the screws.
• Before starting, turn the engine once with the hand, in order to eliminate the beginnings of exi-
sting corrosion to the bushes. If necessarily carry out normal engine inspection.
• Change engine oil and engine oil filters.
• Reintegrate the impeller of the cooling water pump and check pump for leakage.
• Charge starter battery of the generator, connect cables and check battery voltage.
• Start generator and check the basic adjustments of the generator such as voltage, speed re-
gulation etc...
• Check all switching off devices for function by operational procedures.
D. Generator Failure
In order to be able to manage disturbances while driving, the following tools and measu-
ring instruments should belong to the equipment kept on board:
Please ensure that the generator is not overloaded. This must be considered, especially with
regards to multi power generators. In this case the extra load including the electrical performance
can be considerably greater than the drive performance of the motor, which can eventually lead
to a damaged motor.
The full nominal performance of the generator is fore-mostly for short term use. It is, however,
required to start electric motors with high starting current or achieve special starting procedures at
peak loads. 70% nominal load is ideal for a long motor life. (Continual use means uninterrupted
use of the generator for many hours). This should be taken into consideration when connecting
devices. This ensures extended motor life.
It is no problem for the motor to be run occasionally for 2 - 3 hours at full load. The complete con-
ception of Panda Generator ensures that even during extreme conditions, an overheating of the
motor will not occur. Accumulation of soot will occur if run for long periods at full load.
With the operation of electric motors it must be considered that these take up a multiple of their
rated output as starting current (six to tenfold).
If the power of the generator for the engine is not sufficient, the voltage in the generator breaks
down after switching on the engine. For special approach problems the manufacturer can give
recommendations regarding the accomplishment of the situation (e.g. amplified condensers, gra-
dual start switch or extra developed starting unit for electric motors).
The system efficiency can be improved up to 50 % and the starting current can be improved up to
100 % by a professional adjustment of the engines. If the inductive load (electrical motors etc.)
lies over 20 % of the generator rated output compensation is appropriate (see in addition also the
writing: "Operation Instructions for Generators with Inductive Loads").
ATTENTION!
see “Safety Precautions” on Page 9.
The voltage range of the power stations normally lies between 200 and 240 V (100 - 130 V in the
60 Hz version). In some countries even substantially larger tension deviations are being called
"normally". The Fischer Panda generators are aligned that they keep these default values during
normal load.
With high load or overload it can occur that the voltage drops on 190 V (95 V in the 60 Hz ver-
sion) and partly still more deeply. That can become critical for certain devices (e.g. for electric
motors, cooling compressors and possibly for electronic devices). It must be paid attention that
the voltage for such consumers are sufficient. This can be supervised by a voltmeter.
The voltmeter should be always installed behind the change over switch generator/land power, so
that each voltage source is shown. No further voltmeter is provided for the generator itself.
If additional consumers are switched on, the voltage must be controlled in each case at the volt-
meter. Sensitive devices must be switched off so long, until the voltage exceed the critical para-
meter.
Under certain circumstances the generator provides overvoltage. This arises if the number of
revolutions of the generator is increased. Changing the number of revolutions may be made only
with a tachometer and/or a voltmeter.
If sensitive and/or valuable devices are used, which are to be protected against this risk, an auto-
matic overvoltage protection must be mounted (voltage control with disconnection).
If air conditioning units (compressors) or other such valuable equipment is installed on-board, it is
recommend that an automatic voltage monitoring unit be installed to protect this equipment from
possible sharp voltage drops. The voltage monitoring system shuts down the entire system (and
therefore all users) by means of a circuit breaker relay as soon as the voltage falls below a set
value (the monitor will also shut down the on-board grid automatically when the generator is stop-
ped). Such a relay with contactor can be obtained from the installator or as a complete unit from
your Fischer Panda dealer.
The speed of the generator is determined by two independent settings; an upper and lower speed
governor:
• By means of the adjusting nuts on the spindle of the servomotor right and left from the spindle
nut (Setting of the normal speed limit).
• By means of an adjusting screw that is located on the base of the speed control lever. (Setting
of the maximum upper speed).
After working on the components of the actuator, the speed must be checked.
1. Servo motor
2. Trapezoidal Thread Spindle
3. Adjusting nuts for max. speed
4. Spindle nut with speed adjusting lever
5. Adjusting nuts for the lower setting
1 2 3 4 5
During any operation at the generator all consumers have to be switched off to avoid damages at
the equipments. Also the solid state relay, which is installed in the AC control box must be discon-
nected to avoid an accidentally activation of the booster capacitors.
1. Remove the plug from the electrical input for the actuator.
2. Loosen the counter nuts of the speed governor screws with a combination wrench SW 10.
3. Connect a voltmeter with a range up to 300 Volts AC to the AC Output of the AC Control Box.
4. Ensure that no electrical load has been set.
5. Start generator.
6. Raise the speed of the generator by turning the spindle of the servomotor until the voltmeter
reaches 260 Volts (130 Volts).
7. Turn the governor screw firmly against the stop setting of the speed adjustment lever.
8. Secure the governing screw by means of the counter nut.
9. Once again check whether the generator voltage is governed to 260 Volts (130 Volts).
The upper speed settings serve as an additional safety factor. The value for the maximum voltage
is therefore approx 5 volts above the normal running limit.
1. Counter nut
2. Adjustment screw for upper setting
3. Speed Adjustment Lever
10
Fig. D.3.1-1: Counter nut, Adjustment screw and speed adjustment lever
1. Continue as above and tighten the counter nuts at a voltage of max. 260 volts (130 volts).
2. Once again check whether the upper generator voltage without load is limited to 260 V (130 V)
1 2
The electrical plug must be reconnected to drive the actuator servo motor, once the adjustment
has been completed.
The connection must be remade should the electrical input wires have been removed from the
AC control box.
(The speed setting of the trapezoidal thread spindle must be regularly greased. Only high tempe-
rature-resistant grease (up to 100 °C) may be used. The end of the nuts must also be smeared
with grease.
If the spindle has not been sufficiently greased, then it can jam. The generator then cuts out when
over or under-heated.
All screws on the rotary servomotor and the spindle should be secured with a screw securing
solution, so that they can be easily loosened.
The trapezoidal thread spindle must be checked, if the generator has cut out, because of under or
over voltage.
Servicing intervals also includes the checking of cut out functions in cases of defect. Only by
making regular checks can it be ensured that the generator switches off, if there is a fault The
generator will not switch off, if the cut out control of the solenoid valve does not function.
1. Speed actuator
2. Trapezoidal Thread Spindle
1 2
If the generator is overloaded the voltage falls on account of a not adequate motor power under
the nominal value. The actuator stays at the upper keystroke and tries to rev up the diesel engine.
An internal regulation limits the current to the actuator, nevertheless a longer overload can
damage the winding of the actuator. (short of the winding). The motor gets not strictly inoperative
but it can happen that the cranking torque of the actuator is getting weak. This has the consecu-
ence that the rev spindle can not be turned to all positions faultless. Therefore the voltage of the
generator is regulated not good or sometimes not at all.
If the generator is overloaded, the voltage falls under the nominal value due to insufficient engine
power. The actuator is already at the upperst speed limit and still tries to rise the rev. speed of the
engine. There is an internal control which limits the actuator current, but an overloading over a
longer period of time can still damage the winding of the actuator.
This will not effect the operation ability of the engine, but it can happen that the cranking torque of
the actuator is getting weak. This has the consequence that the rev. spindle can not be turned to
all positions correctly. Therefore the voltage regulatiron of the generator is very bad or the gene-
rator is temporarily not beeing regulated at all.
If you should notice that the actuator for the spindle sometimes does not run smoothly, then a
check must be made to determine whether the generator has been effectively overloaded for
periods, therefore causing damage to the internal winding of the actuator. The actuator must then
be exchanged.
The electrical fuses on the circuit board must be checked, if the actuator for controlling the speed
does not turn.
Fig. D.3.4-1: Fuse for the actuator at the remote control panel
True, overloading cannot damage the actual generator, since the windings are safe from overloa-
ding and short circuiting, but damage is always possible to peripheral consumers. This is especi-
ally the case for connected consumers, which can easily be damaged because of current that is
too low.
Fuse on the printed circuit board of the • Constant overload of the generator.
VCS control is melted.
The VCS circuit board should be exchanged if these measures do not produce clarity.
If the AC generated is too low, then the consumers should be disconnected, one after the other, in
order to reduce the load on the generator. Generally the problem is then solved. The frequency
should be checked, if the output voltage is correct after the consumers have been disconnected.
Should this be above the prescribed generator idling speed, it can be assumed that one or
several condensers are defective.
ATTENTION: If the capacitors are to be checked, make sure that the capa-
citors has been discharged.
Should a steady sound or no sound be heard, the capacitors are defective and must be replaced.
A capacity measuring instrument must be used in order to check whether the capacitors
have full capacity.
The capacitors, which do meet the prescribed capacity value at this measurement, should be
exchanged as fast as possible. If all capacitors prove to be still functional, then a check must be
made, as to whether the connections to the strip are correct.
It must be ensured that the electrical connections to the capacitors are always tight fitting. Loose
connections with transitional resistance can mean that the contact surfaces will become heated
externally. This can lead to an increased deterioration of the capacitors.
The following steps must be taken, in order to test whether the stator winding generates
sufficient voltage:
1. The following steps must be taken, in order to test whether the stator winding generates suf-
ficient voltage:
2. Ensure that the connection to the shipboard circuit is interrupted.
3. Remove all electrical wires in the generator junction box.
4. Starter battery must be connected to the generator.
5. Start generator.
6. Measure the current between the phases and neutral. It can be assumed that damage has
been caused to the windings, if the measured values are below the values given in Table 5 on
Page 106
Both partial windings must be connected for the 60Hz Version, i.e. there must be a connection
made between wire 1 and 3 (see circuit plan).
(Note: The current arises from the rest magnetism of the rotor, which induces a voltage in the winding).
If a short circuit could not be found by using a multi-meter, then the windings parts of the
generator must be checked by means of an Ohmmeter that is suitable for low resistance
values.
• Set the measuring device to measure resistance. If you hold the poles of the measuring device
against each other, then 0.00 Ohms should be shown. If the pole has been isolated then the
display should show an overflow. Please carry out this test to check the device.
• Measure the resistance within the individual windings.
If there are large deviations, it must be assumed that there is a windings short circuit. This also
leads to non-excitation of the generator.
The actual values between the windings parts and the earth cannot, however, be exactly determi-
ned. Fore-mostly, the values of all three measurements must be the same, if possible. Deviations
from each other show there is windings short-circuit. In this case, the generator windings must be
renewed by an electrician.
Ensure that the generator has been switched off and cannot be inadvertently switched on. Dis-
connect the wires to the battery for this.
1. All wires in the junction box or - if necessary - in the circuit distribution box must be disconnec-
ted. Ensure that the wires are no longer carrying an electrical current, before being disconnec-
ted (see “Discharging the Capacitors” on Page 93.)
2. Remove the Bridges between "N"and "PE", so that the windings and casing do not come into
electrical contact.
3. Make a check, by means of a Multimeter, as to whether there is a current between the indivi-
dual winding terminals and the casing (PE).
HP1 - 50 Hz: L, Z
HP1 - 60 Hz: L, Z
The generator must be sent for a check to the factory or be re-winded locally, when a pass (beep)
should be detemined. Windings data can be requested for this, if it is necessary.
Fig. D.4.5-1: Generator type plate
An Ohm measurement of a winding does not always give reliable information concerning the
state of the winding. If there are resistance irregularities between the windings parts, this is a sure
sign that the winding is defective. This means the opposite cannot be concluded. This means a
winding can also be defective, if the resistance values between the windings parts do not show
great deviation.
Measurement of the inductive resistance gives a better reading. A Special measuring device is
necessary for this.
The inductivity is measured in the same manner as the resistance, i.e. the windings parts are
compared. The value of the inductive resistance is given in mH (milli Henry).
The correct values for the inductive resistance can be obtained from Table 4 on Page 106.
Note: The values are greatly dependent upon the measuring method (type of ohmmeter).
In the case of asynchronous generators, the generator cannot independently increase voltage
after standing still, or, if it is switched off under full load. This is because the rotor has lost its
remaining magnetism.
The fuel solenoid valve is located in front of the injection pump. It opens automatically, if the
"START"-button is pressed on remote control panel. If the generator is switched to "OFF", the
solenoid valve closes. It takes some seconds, before the generator stops.
If the generator fails to start, runs rough, does not reach the proper RPM, or does not stop pro-
perly, the first item to suspect in most cases it is the fuel solenoid valve and should be inspected
first.
A check of the fuel solenoid valve by removing the plug from the fuel solenoid valve for a short
period whilst in operation (first remove the small retention screw) and replace it immediately. The
motor should "react immediately" by revving high. If the motor does not react sharply to the
reconnection of the solenoid wire, it is a sign that the solenoid valve could be faulty.
The start-failure bypass switch enables an immediate restart facility of the generator, should it cut
out, even if this was caused by over-heating. There is normally a requirement to wait until the
motor has cooled down to the correct temperature. This can last for several hours in certain cir-
cumstances, since the generator is enclosed in a sound-insulated casing, which prevents heat
loss.
This period can be reduced by pushing the button on the front of the generator. The generator
can be started by means of the remote control as long as the button is depressed. The switch/
button bypasses any faults allowing the generator to run.
Before depressing the button, a manual check of the oil dip stick must be carried out to determine
whether the generator has sufficient oil, as it is possible that the oil pressure switch causes the
generator to cut out. If it has been ascertained that the reason for the motor cutting out is over-
heating and not lack of oil, the generator can be run for several minutes without load, so that the
motor is cooled by the circulating coolant.
BEWARE:
If the temperature is the reason for the generator cutting out when it is running under load, then
an immediate check must be made to determine the cause. It could be a fault with the cooling
system, one of the fans, the air-intake or a fault with the external cooling system.
Continual use of the starter-failure bypass switch should be avoided, while the generator cuts out
during operation.
The generator must always run without load for several minutes before being switched off, so that
temperature compensation occurs. Heat accumulation can cause the generator to overheat, even
after it has been switched off.
Should the overheating alarm be set off, caused by heat accumulation, after the generator has
been switched off, then this can also be bypassed using the switch.
The starter is fitted with a free wheel or axial rotating spring cog, which prevents the starter being
driven externally by means of the motor. The free wheel will be heavily worn, if the starter still
operates, thereby causing damage to the springs, roller bearings or cog teeth. This could lead to
complete destruction of the starter.
It is important that every person who operates the generator is informed of this situation.
This is practically the only handling error that can be made on board that can lead to fatal
consequences for both generator and operator.
Blank
Seite 100 Panda PMS 8.000 NE - 42 NE Manual.R04 - Kapitel D: Generator Failure 14.3.08
Tables
E. Tables
E.1 Troubleshooting
Cause Solution
Motor is not reaching the rated rpm. Refer to "motor faults" section.
Cause Solution
Over-energizing due to wrong capacitors. Check capacitors type and replace if necessary.
Measurering voltage on the VCS circuit board is mis- Check VCS System, check cable connections.
sing.
Cause Solution
Cause Solution
If the generator is unable to supply enough power to Check the motor's current draw required for starting
start an electric motor (230 V - 50 Hz), it is usually (switch to 380 V, if possible). This could be remedied
because the motor draws too much current during star- by providing stronger capacitors or installing an optio-
ting process. nal "Easy Start Booster Set" (see Appendix).
Enquire at your nearest Panda dealer or directly at the
manufacturer.
Cause Solution
Starter battery switched "OFF". Check position of battery switch and switch "ON" (if
installed).
Starter battery voltage insufficient (battery too weak). Inspect battery terminals and cables for a good electri-
cal connection (Inspect against corrosion, tattered
wires, etc.).
Starting current disrupted. During the normal starting process, the battery voltage
drops to 11V with a fully charged battery. If the voltage
does not drop during starting, the electrical connection
is faulty. If the battery voltage drops lower than 11V,
then the battery has been discharged.
Cause Solution
Fuel inlet solenoid valve not opening. Check wire connections and circuitry to solenoid valve.
(ref. DC wiring diagram: Relay K2, Fuse)
Fuel pump not working. Check fuel-filter and pump: clean if necessary.
Glow-plugs not working correctly. Check glow plugs and heating time.
Too much air in fuel lines. Test fuel system for leakage. Bleed air from fuel system
(refer to section "Bleeding Air from Fuel System").
Cause Solution
Cause Solution
Cause Solution
Generator overloaded by too many load. Reduce the electrical load (switch off load).
Generator overloaded by over-energizing. Check that the proper capacitor type is installed and
that they are connected correctly.
Defective generator (windings, bearings, or other). Generator must be sent to manufacturer for repair of
damaged bearings or winding.
Cause Solution
Fuel inlet solenoid valve or throttle shut solenoid is not Check wire connections to solenoid. Check valve
switching off. functions as in the "Fuel Solenoid Valve" or in the trottle
shut off solenoid sections. Replace if necessary.
Cause Solution
Excess heat in cooling system (thermo switch tripped)- Check cooling water system flow: water pump, inlet
lack of cooling water. Is indicated on the remote control water filter, extra heat exchanger coolant flow.
panel.
Lack of oil (oil pressure sensor tripped). Is indicated on Check oil-level and if necessary top up.
the remote control panel.
Check motor's oil-pressure and have repaired by
Kubota-Service if necessary.
Cause Solution
Generator is overloaded. Check electrical load and switch off unnecessary load.
Poor fuel quality. Use better quality diesel (recommended: 2-D Diesel).
Poor combustion. Incorrect AFR (air/fuel ratio) due to motor timing adjust-
ment. Have motor serviced by Kubota.
Cause Solution
- motor rpm suddenly rises or drops Refer to respective section of manual and if necessary,
- unusual noise comes from genset have repaired by Kubota-Service, or Panda represen-
- exhaust colour suddenly becomes dark tative.
- leakage in the cooling water system.
Table 1: Resistor generator coil HP1 Table 2: Inductance generator coil HP1
Panda 8000 ca. 0,7 ca. 0,7 Panda 8000 ca. 2,8 ca. 2,8
Panda 9000 ca. 0,65 ca. 0,65 Panda 9000 ca. 2,8 ca. 2,8
Panda 12000 ca. 0,45 ca. 0,45 Panda 12000 ca. 3,5 ca. 3,5
Panda 18 ca. 0,2 ca. 0,2 Panda 18 ca. 3,2 ca. 3,2
Panda 24 ca. 0,06 ca. 0,06 Panda 24 ca. 0,3 ca. 0,3
Panda 8000 ca. 0,9 ca. 0,9 Panda 8000 ca. 3,7 ca. 3,7
Panda 9000 ca. 0,8 ca. 0,8 Panda 9000 ca. 3,7 ca. 3,7
Panda 12000 ca. 0,3 ca. 0,3 Panda 12000 ca. 3,5 ca. 3,5
Panda 14000 ca. 0,25 ca. 0,25 Panda 14000 ca. 2,3 ca. 2,3
Panda 18 ca. 0,25 ca. 0,25 Panda 18 ca. 1,8 ca. 1,8
Panda 24 ca. 0,17 ca. 0,17 Panda 24 ca. 1,3 ca. 1,3
Panda 30 ca. 0,1 ca. 0,1 Panda 30 ca. 0,9 ca. 0,9
Panda 8000 ca. 0,7 ca. 0,7 ca. 0,7 ca. 0,15 ca. 0,15
Panda 9000 ca. 0,65 ca. 0,65 ca. 0,65 ca. 0,17 ca. 0,17
Panda 12000 ca. 0,45 ca. 0,45 ca. 0,45 ca. 0,15 ca. 0,15
Panda 18 ca. 0,2 ca. 0,2 ca. 0,2 ca. 0,05 ca. 0,05
Panda 24 ca. 0,06 ca. 0,06 ca. 0,06
Panda 8000 ca. 0,9 ca. 0,9 ca. 0,9 ca. 0,4
Panda 9000 ca. 0,8 ca. 0,8 ca. 0,8 ca. 0,4
Panda 12000 ca. 0,3 ca. 0,3 ca. 0,3 ca. 0,2
Panda 14000 ca. 0,25 ca. 0,25 ca. 0,25 ca. 0,12
Panda 18 ca. 0,25 ca. 0,25 ca. 0,25 ca. 0,1
Panda 24 ca. 0,17 ca. 0,17 ca. 0,17 ca. 0,1
Panda 30 ca. 0,1 ca. 0,1 ca. 0,1 ca. 0,08
Panda 8000 ca. 2,8 ca. 2,8 ca. 2,8 ca. 0,8 ca. 0,8
Panda 9000 ca. 2,8 ca. 2,8 ca. 2,8 ca. 0,9 ca. 0,9
Panda 12000 ca. 3,5 ca. 3,5 ca. 3,5 ca 1,0 ca. 1,0
Panda 18 ca. 3,2 ca. 3,2 ca. 3,2 ca. 0,4 ca. 0,4
Panda 24 ca. 0,3 ca. 0,3 ca. 0,3
L1 - L2 3-5 Volt 4-6 Volt 5-7 Volt 6-9 Volt 6-10 Volt 6-11 Volt 7-12 Volt
L2 - L3 3-5 Volt 4-6 Volt 5-7 Volt 6-9 Volt 6-10 Volt 6-11 Volt 7-12 Volt
L3 - L1 3-5 Volt 4-6 Volt 5-7 Volt 6-9 Volt 6-10 Volt 6-11 Volt 7-12 Volt
L1’ - N (50Hz) ~ 2-3 Volt ~ 2-3 Volt ~ 3-4 Volt ~ 3-5 Volt ~ 3-5 Volt ~ 3-5 Volt ~ 3-6 Volt
4 - 2 (60Hz) ~ 2-3 Volt ~ 2-3 Volt ~ 3-4 Volt ~ 3-5 Volt ~ 3-5 Volt
L-N ~ 2-3 Volt ~ 2-3 Volt ~ 3-4 Volt ~ 3-5 Volt ~ 3-5 Volt ~ 3-5 Volt ~ 3-6 Volt
4 - 2 (60Hz) ~ 2-3 Volt ~ 2-3 Volt ~ 3-4 Volt ~ 3-5 Volt ~ 3-5 Volt
Automatic startbooster yes yes yes yes yes yes yes yes
Cylinder 2 2 3 3 3 3 4 4TD
Stroke volume 479cm3 479cm3 719cm3 719cm3 782cm3 1123cm3 1498cm3 1498cm3
Max. power (DIN 6271-NB) at 3000rpm 9,32kW 9,32kW 14,0kW 14,0kW 13,5kW 18,7kW 23,3kW 31,3kW
Rated speed 50 Hz 3000rpm 3000rpm 3000rpm 3000rpm 3000rpm 3000rpm 3000rpm 3000rpm
Idle running speed a 3120rpm 2900rpm 3120rpm 2900rpm 2900rpm 2900rpm 2900rpm 2900rpm
Valve clearance (engine cold) 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm
Cylinder head nut torque 42Nm 42Nm 42Nm 42Nm 68Nm 68Nm 68Nm 68Nm
Compression ratio 23:1 23:1 23:1 23:1 23:1 22:1 22:1 23:1
Lubrication oil capacity 2,5l 2,5l 3,8l 3,8l 3,8l 5,1l 6,0l 6,7l
Fuel consumption b ca. 0,53-1,4l ca. 0,68-1,8l ca. 0,79-2,1l ca. 1,05-2,8l ca. 1,25-3,3l ca. 1,68-4,5l ca. 2,20-5,85 ca. 2,7-7,2l
Cooling water requirement for seawater cir- 16-28l/min 16-28l/min 16-28l/min 16-28l/min 16-28l/min 28-40l/min 28-40l/min 40-50l/min
cuit
Permissible max. permanent tilt of engine a) 25° across the longitudinal axis
b) 20° in the longitudinal direction
a. progressive speed by VCS
b. 0,35l/kW electrical power, the randomized values between 30% and 80% of the rated speed
Tables
Panda PMS 8.000 NE - 42 NE Manual - Chapter E: Tables
33 KU 42 KU 32 YA 50 YA 60 YA 50 MB 60 MB 75 MB
Cylinder 4 5 4 4 4 5 6
Stroke volume 2197cm3 2746cm3 cm3 cm3 cm3 2298cm3 2874cm3 3000cm3
Max. power (DIN 6271-NB) at 3000rpm 32,7kW 40,8kW kW kW kW 58kW 70kW 75kW
Rated speed 50 Hz 3000UpM 3000UpM 3000UpM 3000UpM 3000UpM 3000UpM 3000UpM 3000UpM
Idle running speed a 2900UpM 2900UpM 2900UpM 2900UpM 2900UpM 2900UpM 2900UpM 2900UpM
Valve clearance (engine cold) 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm 0,2mm
Fuel consumption b ca. 2,94-7,5l ca. 3,8-10,1l ca. 2,9-7,8l ca. 4,3-11,5 ca. 5,5-14,6l ca. 4,4-11,8l ca. 5,4-14,3l ca. 6,8-18,2l
Cooling water requirement for seawater cir- 50-60l/min 50-60l/min 50-60l/min 50-60l/min 60-75l/min 50-60l/min 60-75l/min 75-85l/min
cuit
Permissible max. permanent tilt of engine a) 25° across the longitudinal axis
b) 20° in the longitudinal direction
a. progressive speed by VCS
b. 0,35l/kW electrical power, the randomized values between 30% and 80% of the rated speed
Tables
HP1 - 230V / 50 Hz
HP1 - 120V / 60 Hz
HP3 - 400V / 50 Hz
HP3 - 120V / 60 Hz
DVS - 400V / 50 Hz
Inspection-Category
Inspection work
D 100 h
A Installation check / 1) check r 4) changer
E 500 h
2) measure 5) sealing
B daily F 1000 h
3) clean 6) check isolation
C 35 - 50 h G 5000 h
Inspection-Category
Inspection work
A B C D E F G
01. 5) 5) 5) 5) 5) 5) 4) coolant water hoses
02. 1) 1) 1) 1) 1) 4) 4) raw water pump (impeller)
03. 1) 1) 3) 3) 3) 3) 3) water separator / fuel pre-filter
04. 1) 1) 4) 4) 4) 4) 4) engine oil
05. 3) 3) 3) 3) oil strainer / oil filter
06. 1) 1) 1) 4) 4) 4) 4) air filter
07. 1) 1) 1) 1) 1) 1) 1) fuel lines (leaks)
08. 1) 1) 1) 4) 4) 4) 4) fine particle fuel filter
09. 1) 1) 1) 1) 1) valve clearance
10. 1) 1) 4) 5) 4) 4) 4) valve cover gasket
11. 1) 1) 1) 1) coolant therm (sensor)
12. 1) 1) 1) 1) exhaust temp sensor
13. 1) 1) 1) 1) oil pressure sensor
14. 1) 1) 1) 1) 1) 1) belt tension
15. 1) 1) 1) 1) 4) 4) 4) toothed-belt
16. 1) 1) thermostat
17. 1) 1) 1) 1) 1) 1) 1) generator & engine screws
18. 1) 1) 1) 1) 1) 1) 1) unit's base mount screws
19. 6) 6) 6) 6) 6) 6) 6) check electrical cables
20. 1) 1) 1) 1) 1) 1) 1) motor reinforced mountings
21. 1) 1) 1) 1) 1) 1) 1) starter motor mounting screws
22. 1) 1) 1) 1) 1) 1) 1) screws generator-engine
23. 2) 2) 2) 2) 2) 2) input temp of coolant under load
24. 2) 2) 2) 2) 2) 2) outlet temp of coolant under load
25. 4) 4) generator rotor bearing
26. 1) 1) 1) 1) 1) signs of corrosion to generator
27. 1) 1) 1) 1) 1) check generator coolant block
28. 1) 1) 1) 1) 1) capacitors in AC-Control box
29. 1) 1) 1) 1) 1) 1) ASB function test
30. 1) 1) 1) 1) 1) 1) VCS function test
31. 2) 2) 2) 2) 2) 2) voltage without load
32. 2) 2) 2) 2) 2) 2) voltage under load
33. 2) 2) 2) 2) 2) 2) generator output under load
34. 2) 2) 2) 2) 2) 2) engine speed (rpm)
35. 1) 4) injector test
36. 1) 1) compression
37. 1) 1) 1) 1) 1) 1) 1) hose clips
Operating range:
The operating range of an engine oil is determined by SAE class. "SAE" is for the union of American engineers
(Society of Automotives Engineers). The SAE class of an engine oil only informs over the viscosity of the oil (lar-
ger number = more viscous, lower number = more highly liquidly) e.g. to 0W, 10W, 15W, 20, 30, 40. The first num-
ber shows the liquid of cold weather, the second number refers to the fluidity with heat. Complete yearly oils have
usually SAE 10W-40, SAE 15W-40 etc.
Quality of oil:
The quality of an engine oil is specified by the API standard ("American Petroleum Institutes"). The API designa-
tion is to be found on each engine oil bundle. The first letter is always a C.
The second letter is for the quality of the oil. The more highly the letter in the alphabet, the better the quality.
Examples for diesel engine oil:
E.5 Coolant
Use a mixture of water and antifreeze. The antifreeze needs to be suitable for aluminium. The antifreeze concen-
tration must be regularly checked in the interests of safety.
Fischer Panda recommend to use the product: GLYSANTIN PROTECT PLUS/G 48.
Water/antifreeze Temperature
70:30 -20°C
65:35 -25°C
60:40 -30°C
55:45 -35°C
50:50 -40°C
Bez. Impellerfilter for Marine Panda P6, P8, P9, P10, P12 and
P14
F.1 General
Starting with March 2007 the Fischer Panda generators type 6, 8, 9, 10, 12 and 14 has got an extra impellerfilter.
Open the generator sound cover like it is explained in the generator manual
Attention!!! Parts of the generator and the cooling water may be hot after operation
!!!DANGER!!!
Some raw water may flow out of the hose or the impeller-
filter
The hose can be closed with the cap you get toge-
ther with the impellerfilter spare part pack.
Some raw water may flow out of the hose or the impeller-
filter
The hose can be closed with the cap you get toge-
ther with the impellerfilter spare part pack.
F.5 Dimensions
Document
Replace:
Revision Page
126
General operation
A. General operation
01 02 03 04 05 06 07
08 09 10
11 12 13 14 15
01. LED for coolant temperature red1 08. LED for pre-glow „heat“ orange1
02. LED for waterleak red/yellow1 (sensor optional) 09. LED for Generator „start“ green1
03. LED for AC-voltage fault red/yellow1 10. LED for Generator „stand-by“ green1
04. LED for AC-voltage ok green1 11. Push button for pre-glow „heat“
12. Push botton for Generator „start“
05. LED for winding temperature red1
13. Operating hours counter
06. LED for oil pressure red1 14. Push button panel „off“
07. LED for battery charge voltage fault green/red1 15. Push button panel „on“
1
LED green: normal operation mode, LED red: fault, LED yellow: warning, LED orange: active
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation Page 127
General operation
01 02
03 04
Page 128 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
01 02
03
04 05 06
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 129
General operation
Error “coolant temperature”. Input for thermo-switch to GND. The input is adjustable for NC/NO
3 T-Engine IN (N = no error) (must be adjusted by solder Jumper). The input loads the switch with ≥22mA to
+12V (with 24V-operated internally generated). The occurrence of an error is delayed, for ana-
lysis and displayed, around 100ms. Omission not. The in/out status is indicated with red LED.
Error “water leak”. Input for sensor switch to GND. The input is adjustable for NC/NO (N = no
error) (must be adjusted by solder Jumper). The input loads the switch with ≥10mA to +12V
Water leak (with 24V-operated internally generated). The occurrence of an error is delayed, for analysis
4 (Replace air fil- IN and displayed, around 100ms. Omission not. The input status is indicated with red LED.
ter)
The input can be used alternatively for the signal “Replace air filter” (must be adjusted by sol-
der Jumper). Then the signal does not lead to switching off and is indicated with yellow LED.
Error “oil pressure“. Input for oil pressure switches to GND. The input is adjustable for NC/NO
5 Oil-Press IN (N = no error) (must be adjusted by solder Jumper). The input loads the switch with ≥22mA to
+12V (with 24V-operated internally generated). The occurrence of an error is delayed, for ana-
lysis and displayed, around 1s. Omission not. The input status is indicated with red LED.
Load control display. Input for signal of the dynamo. The input is adjustable for GND = OK or
12V/24V = OK (must be adjusted by solder Jumper). The input loads the signal with 5mA at
IN / 12V and 10mA at 24V. The input status is indicated with red and green LED.
6 DC-Control
OUT The connection can supply an energizing current for the dynamo over a fixed resistor with 68R.
Either with the control panel switched on or with “Fuel pump” switched on (must be adjusted by
solder Jumper). This function is available only in 12V-operation.
Output for pre-glow relays. The output is so long active, as the button “Heat” is pressed. The
8 Heat OUT output supplies, if active, the voltage of clamp 1. Additionally the output can be operated via the
button “start” (must be adjusted by solder Jumper). Consider (notes 1-4).
Output for fuel pump relay. The output is active, if no error is present (inputs 3, 4, 5, 11 and 12,
if configured accordingly). The button “start” suppresses the error analysis and the output is
9 Fuel-Pump OUT then also active in the case of error, if the button “start” is pressed. The output supplies, if
active, the voltage of clamp 1. Consider (notes 1-4).
10 Start OUT Output for starting relay. The output is active, as long as the button “start” is pressed. The out-
put supplies, if active, the voltage of clamp 1. Consider (notes 1-4).
Error “winding temperature”. Input for thermo-switch to GND. The input is adjustable for NC/NO
12 T-Winding IN (N = no error) (must be adjusted by solder Jumper). The input loads the switch with ≥22mA to
+12V (with 24V-operated internally generated). The occurrence of an error is delayed, for ana-
lysis and displayed, around 100ms. Omission not. The input status is indicated with red LED.
Page 130 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
Notes:
1. Power rating of the output: max. 0,5A in continuous operation and briefly 1,0A.
2. The supply of all output currents may not exceed (less 0,2A power consumption) the rated current of the safety
device of the control panel.
3. The output has a free wheeling diode, which short circuits negative voltages (related to GND).
4. The output has a Z-diode, which prevents a supply of positive voltage (related to GND) into the output.
1-2 Input Water leak has red LED and switches off
J206
2-3 Input Water leak has yellow LED and does not switch off
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 131
General operation
NC = normal closed
NO = normal open
The solder jumper are marked on the printed circuit board (with jumper no. and at three-part solder jumper with
solder area no.).
5. Visual inspection.
Control fixing bolts, check hose connectors for leakages, control electrical connections.
Page 132 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
3. Visual inspection.
Control fixing bolts, check hose connectors for leakages, control electrical connections.
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 133
General operation
4. Switch on load.
The load should only be switched on if the generator voltage is within the permissible range. Parallel connection of several loads
should be avoided, especially if there are loads with electric motors, such as air-conditioning units in the system. In this case, the load
must be connected Step by Step.
2. Recommendation: With turbo engines and during load more than highly 70% of the rated output, stabilize
generator temperature at least 5 minutes with load switched off.
At higher ambient temperatures (more than 25°C) the generator should always run for at least 5 minutes without load, before it is swit-
ched off, regardless of the load.
NOTE: Never switch off the battery until the generator has stopped, if nec-
essary close fuel valve!
Page 134 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
03
02
01
Function:
The automatic adapter RE0704 extends the generator control panel P6+ with an automatic input. A potential-free
contact can be attached to this input. If this contact is closed, then the generator, which is attached to the genera-
tor control panel P6+, is started automatically. If the contact is opened, then the generator is stopped automati-
cally.
The automatic starting procedure consists of pre-heating (heat) and operating the starter (start). It can be again
aborted at any time by opening the contact at the automatic input.
For automatic stopping (stop) the output “Fuel pump” (clamp 9 generator control panel) is switched off. The time
for the automatic stop procedure can be terminated only by switching off generator control panel prematurely.
The times for “heat”, “start” and “stop” are separately adjustable (see below).
The additional automatic adapter switched on and off using the generator control panel with its push buttons “on”
and “off”.
If the contact at the automatic input is connected, while the generator control panel is switched on, then the auto-
matic starting procedure is carried out.
If the current supply is attached or switched on using the generator control panel, while the contact of the automa-
tic input is closed, then the automatic starting procedure won´t be carried out, because the generator control
panel is always switched off after attaching the current supply (generator the control panel must have been sepa-
rate from the current supply for at least 60s).
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 135
General operation
Data:
Parameter Information
Operation voltage The automatic adapter power is supplied via the generator control panel P6+. The
same absolute maximum ratings obtain as with the generator control panel P6+.
Operation temperature The same absolute maximum ratings obtain as with the generator control panel
P6+.
Proper power consumption 10mA - 20mA
5s ON OFF
Heat-time
10s X OFF ON
20s ON ON
8s X OFF
Start-time
16s ON
32s X ON OFF
Stop-time
64s OFF ON
128s ON ON
Normal X OFF
Operation-mode
Test (all times over 16) ON
7mA X ON
Attention:
The automatic adapter must only be used together with a device. The star-
ter should only be switched on when the generator stationary (shut-
down)!
Page 136 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
Connection for the automatic adapter X2 (row with odd pin numbers // I/O viwe from operating panel)
5 VBFS O Current supply + switched (voltage Pin 1, with panel switched on)
7 12V O Current supply + switched, at 12V-operation over closed soldered jumper J101 connected with
VBFS (at optional 24V-operation: VBFS over internal voltage regulator at 12,9V regulated)
The Fuel pump signal is switched off, as long as the input is switched to GND, (also when star-
27 /Stop-signal I
ting)
29 FP-Int O Fuel pump signal internally, decoupled over diode from external signal
31 /Fault-signal O Output is switched to GND, if an error is present (inputs 3, 4, 5, 11 and 12, if configured and
generally for 2s, after switching on the panel)
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 137
General operation
02
01
02
01
Page 138 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
The Master-Slave-Adapter RE0706 offers the possibility to combine two Generator Control Panels P6+ RE0703
into a Master-Slave-Combination. This constellation is achieved by connecting a Master-Slave-Adapter RE0706
to each Generator Control Panels P6+ RE0703. The generator Control Panels P6, are connected using the 13
pole connectors found in each Master-Slave-Adapter in a 1:1 method. The Master-Panel is hereby defined when
the generator is connected to the main connector. Thus, the main connector of the Slave-Panel should not be
occupied (unconnected).
The solder jumpers on the Master-Panel have to be coded in the same manner as for a Master-Panel without a
Slave-Panel as in normal operation. The solder jumpers on the Slave-Panel are coded as for slave operation
(please see the appropriate adjustment pages for the Generator Control Panel P6+ RE0703). The Master-Panel
and Slave-Panel are identical, and only differs as a result of the coding. Both Master-Slave-Panels are also iden-
tical.
Terminal Connections:
X2: (13 poles) Master-Slave-Connection (1:1 wired)
X3: (2 poles) Panel-ON-Signal from Generator Control Panel P6+ RE0703
The Panel-ON-Signal is active when the panel is switched on. The voltage level is 0,7V less than the supply
voltage for the generator Control Panel P6+ RE0703. This output has a free wheeling diode which short circuits
externals voltage supplies under 0V and a decoupling diode which decouples the circuitry from external power
feeding. Both X3 connectors are have the same Panel-On-Signal.
Fuse:
1 VBF O Current supply + (operation voltage behind fuse 12Vdc or 24Vdc depending on system)
3 ON-Signal I/O Panels are switched on, if the connection is switched using a push button (on master or slave)
to VBF
4 OFF-Signal I/O Panels are switched off, if the connection is switched using a push button (on master or slave)
to VBF
5 /Heat-Signal I/O Heat is active, if the connection is switched over a push button (on master or Slave) to GND
6 /Start-Signal I/O Start is active, if the connection is switched over a push button (on master or Slave) to GND
7 LED-T-Engine O Output for LED T-Engine on the Slave panel, is switched to GND, if the LED is illuminated
LED-Water
8 leak (Replace O Output for LED Waterleak on the Slave panel, is switched to GND, if the LED is illuminated
air filter)
9 LED-Oil- O Output for LED Oil-Press on the Slave panel, is switched to GND, if the LED is illuminated
Press
LED-AC-Fault
10 (Fuel Level) O Output for LED AC-Fault on the Slave panel, is switched to GND, if the LED is illuminated
LED-T-Win-
11 O Output for LED T-Winding on the Slave panel, is switched to GND, if the LED is illuminated
ding
12 DC-Control O Output for LED DC-Control-display on the Slave panel, is switched to GND, if the LED is illumi-
nated
Output for LED AC-Control-display on the Slave panel, is switched to GND, if the LED is illumi-
13 AC-Control O
nated
Fig. A.9.1-1: Terminal connections terminal X2 (IN/OUT from the view of the master-control-panel)
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 139
General operation
The use of these connections for other purposes, other than the master-slave connection of two generator control
panels, is generally forbidden. In individual cases, after consultation and clarifying the technical details, a release
for another use can, if technically possible, be allowed.
1 Panel ON OUT
With panel (ON/OFF) switched voltage of clamp X2.1 (VBF). (Consider notes 1-4)
2 Panel ON OUT
Notes:
1. Power rating of the output: max. 0,5A in continuous operation and briefly 1,0A.
2. The supply of all output currents may not exceed (less 0,2A power consumption) the rated current of the safety
device of the control panel.
3. The output has a free wheeling diode, which short circuit negative voltages (related to GND).
4. The output has a Z-diode, which prevents an overvoltage (related to GND) into the output.
Standard jumpering for use as Slave panel in connection with an master-slave adapter RE0706 and a generator
control panel P6+ RE0703 as master panel. Both 12V operation, and 24V operation is possible (see J101).
A 0,63AT fuse must be installed.
The circuitry is designed for a rating of 24V.
Page 140 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
General operation
1-2 M Input Water leak has red LED and switches off
J206
2-3 M Input Water leak has yellow LED and does not switch off
Fig. A.9-1: Settings of soldered jumper for this configuration (column Conf.)
NC = normal closed
NO = normal open
The jumpers are marked on the printed circuit board (with jumper no. and at three-part jumper with solder area
no.).
X = Jumper must be set as seen
XM = Jumper must be set as seen, function is selected on the master panel
M = Jumper must be set exactly the same, as on the master panel
14.3.08 Panel Generator Control P6+ RE0703_Kunde_eng .R01 - Chapter A: General operation Page 141
General operation
Intentionally Blank
Page 142 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter A: General operation 14.3.08
14.3.08
Measurements
Q:\Zeichnungen\7067e00.idw
6 5 4 3 2 1
D D
25
n 4
185
3
n
4x
B.1 Hole pattern
B. Measurements
88
95
95
105
87
177
C C
185
195
Maßstab: Gewicht:
Material: Halbzeug:
Otto-Hahn-Str. 32-34 D-33104 Paderborn Tel.: (05254) 9202-0 Artikel Nr.: 21.02.02.009H
Fax (05254) 85724 info@fischerpanda.de www.fischerpanda.de
Datum Name Panel Generator Control
Bearb. 06.03.2007 jschaefers
A A
Gepr.
Norm.
Allgemeintoleranzen nach Blatt
DIN ISO 2768-mK 2D Zeichnungs Nr. 1
Alle nicht 7067e00
bemaßten Fasen Schutzvermerk nach A3
Page 143
Measurements
Intentionally Blank
Page 144 Panel Generator Control P6+ RE0703_Kunde_eng.R01 - Chapter B: Measurements 14.3.08