IEE On-Site Guide
IEE On-Site Guide
IEE On-Site Guide
TO BS 7671 : 2001
Email: sales@iee.org.uk
http://www.iee.org.uk/Publish/Books/WireAssoc/
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system
or transmitted in any form or by any means – electronic, mechanical, photocopying, recording
or otherwise – without the prior written permission of the publisher.
While the author publisher and contributors believe that the information and
guidance given in this work is correct, all parties must rely upon their own
skill and judgement when making use of it. Neither the author, the publisher
nor and any contributor assume any liability to anyone for any loss or damage
caused by any error or omission in the work, whether such error or omission
is the result of negligence or any other cause. Where reference is made to
legislation it is not to be considered as legal advice. Any and all such liability
is disclaimed.
CONTENTS
Page
PREFACE
8
FOREWARD
9
SECTION 1. INTRODUCTION
11
1.1 Scope
11
1.2 Basic Information Required
13
SECTION 3. PROTECTION
17
3.1 Types of Protective Device(s)
17
3.2 Overload Protection
17
3.3 Fault Current Protection
17
3.4 Protection Against Electric Shock
17
3.5 Disconnection Times
19
3.6 Residual Current Devices (RCD)
19
Areas
24
4.3 Main Equipotential Bonding – Plastic
Services
25
4.4 Earthing
25
4.5 Supplementary Equipotential Bonding
Metal Pipework
25
4.6 Supplementary Bonding in other
Installations
26
4.8 Earth Electrode (Fig 4c)
32
4.9 Types of Earth Electrode
32
4.10 Typical Earthing Arrangements
33
Maintenance
35
5.4 Emergency Switching
35
SECTION 6. LABELLING
36
6.1 Labels to be Provided
36
SHOCK
58
8.1 Locations containing a bath or shower
58
8.2 Shower cubicles in a Room used for
Other Purposes
60
8.3 Temporary and Garden Buildings,
Current
60
TESTING OF INSTALLATIONS
66
10.1 Safety and Equipment
66
10.2 Sequence of Tests
66
10.3 Test Procedures
67
7288
81
11.5 Additional Requirement for
Supplementary Protection
82
11.6 Integral Test Device
82
Page
APPENDICES
external influences
94
conductors
157
INDEXES
(v) Alphabetical
174
Co-operating Organisations
The Institution of Electrical Engineers acknowledges the contribution made
by the following organisations in the preparation of this guide.
PREFACE
FOREWARD
BS7671 and the On-Site Guide are not design guides. It is essential
Any specification should set out the detailed design and provide
description of how the system is to operate and all of the design and
operational parameters.
manual.
The Designer(s)
The Installer(s)
The Architect
10
ON-SITE GUIDE
SECTION 1. INTRODUCTION
1.1 Scope
11
12
(v) the type and rating of the supplier’s fusible cut-out 313-01-01(iv)
or protective device
13
Where the meter tails are protected against fault current 473-02-04(iv)
by the supplier’s cut-out the method of installation,
maximum length and minimum cross-sectional area must
comply with the requirements of the supplier.
14
Fig 2a: Layout when the supplier does not provide a main switch
Note: Earthing arrangements have been omitted for clarity. Tails between the meter
and consumer’s installation are provided by the consumer
Fig 2b: Layout when the supplier does provide a main switch
Note: Earthing arrangements have been omitted for clarity. Tails between any main
switch provided by the supplier and the consumer’s installation are provided by the
consumer
15
16
SECTION 3. PROTECTION
The consumer unit (or distribution board) contains devices for the protection Ch 43
of the final circuits against:
Functions (I) and (ii) are carried out usually by one device, a fuse or circuit-
breaker.
Function (iii) may be carried out by the fuse or circuit-breaker provided for 413-02-04
functions (I) and (ii), or by an RCD.
For other protective devices the breaking capacity must be adequate for the
prospective fault current at that point.
17
SELV
411-02
Separated extra-low voltage (SELV) systems
PELV 471-14-01
Protective extra-low (PELV) systems must meet all the 471-14-02
requirements for SELV, except that the circuits are not electrically
separated from earth
18
For SELV and PELV systems protection against direct contact 411-02-09
need not be provided if voltages do not exceed the following: 471-14-02
A disconnection time of not more than 0.4s is required for final circuits
supplying :
(iii) fixed equipment outside the equipotential zone with accessible 471-08-03
exposed-conductive-parts
Note: Residual current device (RCD) is a device type that includes residual
current circuit-breakers (RCCBs) and residual current circuit breakers with
integral overcurrent protection (RCBOs).
19
(i) where the earth fault loop impedance is too high to provide the 413-02-19
required disconnection time e.g. where the supplier does not
provide an earth – TT systems
(iv) circuits supplying portable equipment for use outdoors by means 471-16-02
of a flexible cable
Installations are required to be divided into circuits to avoid danger and 314-01-01
minimise inconvenience in the event of a fault and to take account of
hazards that might arise from the failure of a single circuit, e.g. a lighting 314-01-02
circuit.
Where an RCD is fitted only because the earth loop impedance is too high
for shock protection to be provided by an overcurrent device, for example in
a TT system, the rated residual operating current should not be less than
100 mA.
If two RCDs are installed they should preferably control separate circuits,
see Fig 3a(I), or a time delay 100 mA or greater RCD (S type) should be
installed, see Fig 3a(ii).
The use of RCBOs, see Fig 3a(iii), will minimise inconvenience in the event
of a fault.
20
21
22
(iii) other metal service pipes (including oil and gas supply
pipes) and ducting
23
Note that:
(iii) the connection to the gas, water, oil, etc service should 547-02-02
be within 600 mm of the service meter, or at the point of
entry to the building if the service meter is external, and
must be on the consumer’s side before any branch
pipework and after any insulating section in the service.
The connection must be made to hard pipe, not to soft or
flexible meter connections
(iv) the connection must be made using clamps (to BS 951) 542-03-03
which will not be subject to corrosion at the point of
contact
24
4.4 Earthing
25
Note: Metal waste pipes in contact with earth should be main bonded back
to the main earthing terminal.
26
27
28
29
30
31
Metal gas or water or other metal service pipes are not to be used 542-02-04
as the earth electrode, although they must be bonded as
paragraph 4.1.
(vi) lead sheaths and metal coverings of cables, which must 542-02-05
meet the following conditions:
32
The protective conductor sizes shown in these Figures refer to Table 54G
copper conductors and are related to 25 mm2 supply tails from the Table 54H
meter. 547-02-01
Note: For TN-S and TN-C-S installations, advice about the availability of an
earthing facility and the precise arrangements for connection should be
obtained from the electricity supplier.
33
5.1 Isolation
(ii) other than at the origin of the installation every circuit, or 476-01-02
group of circuits, which may have to be isolated without
interrupting the supply to the other circuits should be
provided with it’s own isolating device, which must switch 537-02-01
all live conductors in a TT system and all phase
conductors in a TN system.
34
35
(i) readily accessible from the place where the danger may 537-04-04
occur
SECTION 6. LABELLING
36
37
IMPORTANT
38
39
Lt xU o
Lp =
230
where:
40
(c) Reference Method 6 (M6)
(iv) the ambient temperature throughout the length of the Table 4C1
circuit does not exceed 30°C
(i) In domestic premises, except for heating cables, the Table 4B1
conventional circuit design permits any number of single
layer circuits when the spacing between adjacent
surfaces of the cables exceeds one cable diameter and,
for other than semi-enclosed fuses, (BS 3036) up to 5
touching, single-layer circuits, when clipped to a non
metallic surface (Installation Method 1)
41
42
43
44
45
46
All the circuits are limited by voltage drop other than those marked
below:
47
7.2.3 Checklist
(i) what is the load current and can the distribution board
and supply arrangements accommodate it? (see
Appendix 1 for guidance on assessing load currents)
(ix) is the earth loop impedance value below the values given
in 7.1(I) or 7.2.4(ii)?
48
7.2.4 TT Systems
49
TABLE 7.2A
Rated Short-Circuit-Capacities
Rated short
Device
Device Type circuit capacity
designation
kA
Semi-enclosed fuse to BS 3036 S1A 1
With category of duty S2A 2
S4A 4
Circuit-breakers to BS 3871 M1 1
(replaced by BS EN 60898) M1.5 1.5
M3 3
M4.5 4.5
M6 6
M9 9
The difference between the two is the condition of the circuit-breaker after
manufacturer’s testing. Icn is the maximum fault current the breaker can interrupt
safely, although the breaker may no longer be usable. Ics is the maximum fault
current the breaker can interrupt safely without loss of performance. The Icn value is
normally marked on the device in a rectangle e.g. 6000 and for the majority of
applications the prospective fault current at the terminals of the circuit-breaker should
not exceed this value. For domestic installations the prospective fault current is
unlikely to exceed 6kA up to which value Icn and Ics values are the same. The short
circuit capacity of devices to BS EN 60947-2 is as specified by the manufacturer.
50
TABLE 7.2B
Cb Instantaneous
Application
type trip current
51
Notes:
52
7.3.2 Walls
53
Notes:
1. Where the LV cables share the same tray then the normal
separation should be met.
54
55
The cable for the power supply to each self-contained unit and for
56
A - physical segregation
A - installation in conduit, ducting, trunking or a channel
by a minimum distance of
reserved for fire alarms, or
300 mm, or
B - a mechanically strong, rigid and continuous partition B - use of mineral cables,
of non-combustible material, or or
C - mounting at a distance of at least 300 mm from C - cables to BS 6387 Cat
conductors of other systems, or B
D - wiring in cables complying with BS 7629, or
alarm circuits must be separated from other cables and from each
57
58
59
Equipment
Circuits
The wiring of every final circuit and distribution circuit having a 607-02-04
protective conductor current likely to exceed 10 mA shall have
high integrity protective conductor connections comprising either:
(i) a single copper protective conductor complying with
2
Section 543 and of csa not less than 10 mm , or
60
When the two protective conductors are provided the ends must
be terminated independently of each other at all connection points
e.g. distribution board and socket-outlet. Accessories are required
to have two separate earth terminals.
61
9.2 Inspection
Inspection shall precede testing and shall normally be done with 712-01-01
that part of the installation under inspection disconnected from the
supply.
62
- SELV
63
Band I circuit:
Band II circuit:
(xi) p
resence of undervoltage protective devices (where 451
appropriate)
64
9.3 Testing
713
65
Note: The advice given does not preclude other test methods.
66
tester
(viii) earth fault loop impedance
(ix) prospective fault current measurement, if not determined
by enquiry of the electricity supplier
(x) functional testing.
67
68
Test Method 1
Test Method 2
final circuit. The test results show if the ring has been inter-
Step 1:
the same (within 0.05 ohm) if the conductors are the same size.
69
Step 2:
The phase and neutral conductors are then connected together so
that the outgoing phase conductor is connected to the returning
neutral conductor and vice-versa (see Fig 10.2b). The resistance
between phase and neutral conductors is measured at each
socket outlet. The readings at each of the sockets wired into the
ring will be substantially the same and the value will be
approximately one quarter of the resistance of the phase plus the
neutral loop resistances, i.e. (r1+rn)/4. Any sockets wired as spurs
will have a higher resistance value due to the resistance of the
spur conductors.
Note: Where single core cables are used, care should be taken to verify
that the phase and neutral conductors of opposite ends of the ring circuit
are connected together. An error in this respect will be apparent from the
readings taken at the socket outlets, progressively increasing in value as
readings are taken towards the midpoint of the ring, then decreasing again
towards the other end of the ring.
Step 3:
The above step is then repeated, this time with the phase and cpc
cross-connected (see Fig 10.2c). The resistance between phase
and earth is measured at each socket. The readings obtained at
each of the sockets wired into the ring will be substantially the
same and the value will be approximately one quarter of the
resistance of the phase plus cpc loop resistances, i.e. (r1+r2)/4. As
before, a higher resistance value will be recorded at any sockets
wired as spurs. The highest value recorded represents the
maximum (R1+R2) of the circuit and is recorded on Form F4. The
value can be used to determine the earth loop impedance (Zs) of
the circuit to verify compliance with the loop impedance
requirements of BS 7671 (see Appendix 9).
70
71
Pre-test checks
10.3.3(I)
10.3.3(ii)
Tests should be carried out using the appropriate d.c. test voltage
specified in Table 10.1.
The tests should be made at each distribution with the main switch
off, all fuses in place, switches and circuit-breakers closed, lamps
removed and other current-using equipment disconnected. Where
the removal of lamps and/or the disconnection of current-using
equipment is impracticable, the local switches controlling such
lamps and/or equipment should be open.
72
Where electronic devices are disconnected for the purpose of the 713-04-04
tests on the installation wiring (and the devices have exposed-
conductive-parts required by Bs 7671 to be connected to the
protective conductors) the insulation resistance between the
exposed-conductive parts and all live parts of the device (phase
and neutral connected together) should be measured separately
and should not be less than the values stated in Table 10.1.
Test between all the live (phase and neutral) conductors at the
distribution board (see Fig 10.3).
73
74
Single-phase
Test between the live conductors (phase and neutral) and the
circuit protective conductors at the distribution board (see
Fig10.4).
Three-phase
Test between SELV and PELV circuits and live parts of other
circuits at 500 V d.c.
75
76
77
The measured resistance should meet the following criteria and 542-02-02
those of 10.3.6 but in any case should not exceed 200 ohms:
78
The values of Zs determined should be less than the value given in 413-02-08
Appendix 2 for the particular overcurrent device and cable. 543-01-03
79
80
The tests are made on the load side of the RCD, as near as
practicable to its point of installation, and between the phase
conductor of the protected circuit and the associated circuit
protective conductor. The load supplied should be disconnected
during the test.
81
The test button will only operate the RCD if the RCD is energised.
Confirm that the notice to test the RCD quarterly (by pressing the 514-12-02
test button) is fixed in a prominent position (see 6.1(xi)).
82
APPENDICES
CONTENTS
Appendix Page
external influences
94
conductors
157
83
APPENDIX 1 311
84
TABLE 1A
Current demand to be assumed for points of utilisation and current-
using equipment
Note 1: See Appendix 8 for the design of standard circuits using socket
outlets to BS 1363-2 and BS 4343.
Note 2: Final circuits for discharge lighting must be arranged so as to be
capable of carrying the total steady current, viz. That of the
lamp(s) and any associated gear and also their harmonic
currents. Where more exact information is not available, the
demand in volt-amperes is taken as the rated lamp watts
multiplied by not less than 1.8. This multiplier is based upon the
assumption that the circuit is corrected to a power factor of not
less than 0.85 lagging, and takes into account control gear losses
and harmonic current.
85
TABLE 1B
Allowances for diversity
Types of premises
Purpose of final
circuit fed from
conductors or Individual household Small shops,
switchgear to Small hotels,
installations including stores, offices
which diversity boarding houses,
individual dwellings and business
applies guest houses, etc
of a block premises
100% f.l. of
100% of total current
100% f.l. of largest appliance
demand up to 10
2. Heating and largest appliance +80% f.l. of
amperes +50% of
power (but see 3 +75% of second largest
any current demand
to 8 below) remaining appliance +60%
in excess of 10
appliances f.l. of remaining
amperes
appliances
100% f.l. of
4. Motors (other largest motor
100% f.l. of
than lift motors +80% f.l. of
largest motor
which are subject Not applicable second largest
+50% f.l. of
to special motor +60% f.l.
remaining motors
consideration of remaining
motors
86
TABLE 1B Continued
Allowances for diversity
Types of premises
Purpose of final
circuit fed from
conductors or Individual household Small shops,
switchgear to Small hotels,
installations including stores, offices
which diversity boarding houses,
individual dwellings and business
applies guest houses, etc
of a block premises
6. Water-heaters
(thermostatically No diversity allowable ⊗
controlled)
7. Floor warming
No diversity allowable ⊗
installations
8. Thermal
storage space
No diversity allowable ⊗
heating
installations
100% of current
demand of
largest point of
10. Socket 100% of current
100% of current utilisation +75%
outlets other than demand of
demand of largest of current
those included in largest point of
point of utilisation demand of every
9 above and utilisation +70%
+40% of current other point in
stationary of current
demand of every main rooms
equipment other demand of every
other point of (dining rooms,
than those listed other point of
utilisation etc) +40% of
above utilisation
current demand
of every other
point of utilisation
⊗ It is important to ensure that the distribution boards and consumer units are of
sufficient rating to take the total load connected to them without the application of
diversity
87
APPENDIX 2
The tabulated values apply only when the nominal voltage to earth
(Uo) id 230 V.
88
Note: The impedances tabulated in this Appendix are lower than those
in Table 41B1, Table 41B2 and Table 41D of BS 7671 as these
are measured values at an assumed conductor temperature of
10°C, whilst those in BS 7671 are design figures at the conductor
normal operating temperature.
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is Table 54C
suitable for pvc insulated and sheathed cables to Table 5 or
Table 6 of BS 6004 and for lsf insulated and sheathed cables to
Table 7 of BS 7211. The k value is based on both the
thermoplastic (pvc) and thermosetting (lsf) cables operating at a
maximum temperature of 70°C.
89
TABLE 2B BS 88 fuses
Maximum measured earth fault loop impedance (in ohms) when
overcurrent protective device is a fuse to BS 88 (see Note)
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is Table 54C
suitable for pvc insulated and sheathed cables to Table 5 or
Table 6 of BS 6004 and for lsf insulated and sheathed cables to
Table 7 of BS 7211. The k value is based on both the
thermoplastic (pvc) and thermosetting (lsf) cables operating at a
maximum temperature of 70°C.
90
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is Table 54C
suitable for pvc insulated and sheathed cables to Table 5 or
Table 6 of BS 6004 and for lsf insulated and sheathed cables to
Table 7 of BS 7211. The k value is based on both the
thermoplastic (pvc) and thermosetting (lsf) cables operating at a
maximum temperature of 70°C.
91
92
TABLE 2E
0 0.96
5 0.98
10 1.00
20 1.04
25 1.06
30 1.08
Notes:
corrects from 10°C and Table 9B from 20°C. The values in Tables 2A to 2D
93
APPENDIX 3
TABLE 3A
Application of cables for fixed wiring
Type of cable Uses Comments
(i) intermediate support may be
Thermoplastic (pvc) In conduits, cable ducting required on long vertical runs
or thermosetting or trunking
(ii) 70°C maximum conductor
insulated non
temperature for normal wiring
sheathed
grades – including thermosetting
types (4)
(iii) cables run in pvc conduit shall
not operate with a conductor
temperature greater than 70°C
(4)
94
TABLE 3A continued
Application of cables for fixed wiring
Type of cable Uses Comments
mechanical protection is desirable for all underground cables which might otherwise
subsequently be disturbed. Route marker tape should also be installed, buried just
used where the ambient temperature is consistently below 0°C or has been within the
preceding 24 hours. Where they are to be installed during a period of low temperature
minimum ambient temperature of 5°C is advised in BS 7540 : 1994 for some types of
3 – Cables must be suitable for the maximum ambient temperature, and shall be
protected from any excess heat produced by other equipment, including other cables.
4 – Thermosetting cable types (to BS 7211 or BS 5467) can operate with a conductor
temperature of 90°C. This must be limited to 70°C when drawn into a conduit etc. with
equipment (512-02-01 and 523-01-01), or when such cables are installed in plastic
conduit or trunking.
further guidance may be obtained from those standards. Additional advice is given in
BS 7540 : 1994 “Guide to use of cables with a rated voltage not exceeding 450/750V”
95
6 – Cables for overhead wiring between buildings must be able to support their own
weight and any imposed wind or ice/snow loading. A catenary support is usual but
hard drawn copper types may be used.
Thermal Insulation
Cable Clips
Grommets
Wood Preservatives
Creosote
96
TABLE 3B
Applications of flexible cables and cords to BS6500:2000 and
BS7919:2001 generally
Type of flexible cord Uses
Light thermoplastic (pvc) Indoors in household or commercial premises in
insulated and sheathed dry situations, for light duty
(i) indoors in household or commercial premises,
including damp situations, for medium duty
Ordinary thermoplastic (ii) for cooking and heating appliances where not
(pvc) insulated and in contact with hot parts
sheathed (iii) for outdoor use other than in agricultural or
industrial applications
(iv) electrically powered hand tools
60°C thermosetting
Indoors in household or commercial premises
(rubber) insulated braided
where subject only to low mechanical stresses
twin and three-core
(i) indoors in household or commercial premises
60°C thermosetting where subject only to low mechanical stresses
(rubber) insulated and (ii) occasional use outdoors
sheathed
(iii) electrically powered hand tools
60°C thermosetting (i) general, unless subject to severe mechanical
(rubber) insulated oil stresses
resisting and flame (ii) fixed installations protected in conduit or other
retardant sheath enclosure
85°C thermosetting
General, including hot situations, e.g. night
(rubber) insulated HOFR
storage heaters and immersion heaters
sheathed
85°C heat resisting
General, including hot situations, e.g. for pendant
thermoplastic (pvc)
luminaires
insulated and sheathed
preferably not be used where the ambient temperature is consistently below 0°C.
Where they are to be installed during a period of low temperature, precautions should
97
2 – Cables and cords shall be suitable for the maximum ambient temperature, and
shall be protected from any excess heat produced by other equipment, including other
cables.
3 – For flexible cords and cables to BS 6007, BS 6141 and BD 6500 further guidance
may be obtained from those standards, or from BS 7540 : 1994 “Guide to use of
the minimum practical length to minimise danger and in any case of such a length that
against tension, crushing, abrasion, torsion and kinking, particularly at the inlet point
to the electrical equipment. At such inlet points it may be necessary to use a device
which ensures that the cable is not bent to an internal radius below that given in the
appropriate part of Table 4 of BS 6700. Strain relief, clamping devices or cord guards
6 – Flexible cables and cords should not be used under carpets or other floor
coverings, or where furniture or other equipment may rest on them. Flexible cables
and cords should not be placed where there is a risk of damage from traffic passing
over them.
7 – Flexible cables and cords should not be used in contact with or close to heated
surfaces, especially if the surface approaches the upper thermal limit of the cable or
cord.
98
Special care is required in the choice of materials for clips and 522-05-02
other fittings for bare aluminium sheathed cables and for aluminium 522-05-03
conduit, to avoid risk of local corrosion in damp situations.
Examples of suitable materials for this purpose are the following:
- porcelain
- plastics
- aluminium
99
APPENDIX 4 522-08
Cables generally
100
Overhead wiring
101
102
103
TABLE 4B
Maximum lengths of span and minimum heights above ground for overhead
wiring between buildings etc
In positions
accessible In positions
to vehicular inaccessibl
Maximum traffic, other e to
length of At road than vehicular
Type of system span crossings crossings traffic*
1 2 3 4 5
m m m m
104
TABLE 4B continued
Maximum lengths of span and minimum heights above ground for overhead
wiring between buildings etc
In positions
accessible In positions
to vehicular inaccessibl
Maximum traffic, other e to
length of At road than vehicular
Type of system span crossings crossings traffic*
1 2 3 4 5
m m m m
(5.8) (5.8)
Aerial cables incorporating Subject to
for all for all 3.5
a catenary wire (Item 14) item 14
types) types)
Note: In some special cases, such as in yacht marinas or where large cranes are
present, it will be necessary to increase the minimum height of span above
ground given in Table 4B. It is preferable to use underground cables in such
locations.
105
106
107
TABLE 4E
Minimum internal radii of bends in cables for fixed wiring
Not exceeding
3(2)^
10mm
Thermosetting or
thermoplastic (pvc) Non-armoured Exceeding 10mm
(circular, or circular but not exceeding 4(3)^
stranded copper or 25mm
aluminium Exceeding 25mm 6
conductors)
Armoured Any 6
Thermosetting or
thermoplastic (pvc)
Armoured or non-
(solid aluminium or Any 8
armoured
shaped copper
conductors)
^^ Mineral insulated cables may be bent to a radius not less than 3 times the
cable diameter over the copper sheath, provided that the bend is not re-
worked, i.e. straightened and re-bent.
108
APPENDIX 5
109
For each cable it is intended to use, obtain the factor from Table
5A.
Add the cable factors together and compare the total with the
conduit factors given in Table 5B.
TABLE 5A TABLE 5B
Cable factors for use
Conduit factors for
In conduit in
Use in short
Short straight runs
Straight runs
Conductor
Conduit
Type of cross- Cable Conduit
diameter
conductor sectional factor factor
2 mm
area mm
1 22
16 290
Solid 1.5 27
2.5 39 20 460
1.5 31 25 800
2.5 43 32 1400
4 58
38 1900
Stranded 6 88
10 146
50 3500
16 202
25 385 63 5600
110
Add the cable factors together and compare the total with the
conduit factors given in Table 5D, taking into account the length of
run it is intended to use and the number of bends and sets in that
run.
TABLE 5C
Cable factors for use in conduit in long straight runs over 3m, or runs
of any length incorporating bends
2
Type of conductor Conductor csa mm Cable factor
Solid 1 16
Or 1.5 22
Stranded
2.5 30
4 43
6 58
10 105
16 145
25 217
The inner radius of a conduit bend should be not less than 2.5
times the outside diameter of the conduit.
111
112
Add all the cable factors so obtained and compare with the factors
for trunking given in Table 5F
TABLE 5E
Cable factors for trunking
Conductor Thermosetting
PVC, BS6004
Type of conductor cross-sectional BS7211 cable
cable factor
area factor
Note:
(i) These factors are for metal trunking and may be optimistic for
plastic trunking where the cross-sectional area available may be
significantly reduced from the nominal by the thickness of the wall
material.
113
TABLE 5F
Factors for trunking
Dimensions of Dimensions of
trunking Factor trunking Factor
mm x mm Mm x mm
For sizes and types of cable trunking other than those given in
Tables 5E and 5F, the number of cables installed should be such
that the resulting space factor does not exceed 45% of the net
internal cross-sectional area.
114
APPENDIX 6 Ch 52
Current-carrying capacity
Procedure
In ≥ Ib
The tabulated current-carrying capacity of the selected
cable It is then given by:
In
It ≥
C a Ci C g C r
for simultaneously occurring factors.
Where :
115
Voltage Drop
(mV / A / m)xI b xL
voltage drop =
1000
The requirements of BS 7671 are deemed to be satisfied for a
230V supply, if the voltage drop between the origin of the
installation and a socket-outlet or fixed current-using equipment
does not exceed 9.2V at full load. 525-01-02
Ambient temperature °C
Type of Operating
insulation temperature 25 30 35 40 45 50 55 60 65
Thermoplastic
(general 70°C 1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.50 0.35
purpose pvc)
Note: Where the device is a semi-enclosed fuse to BS 3036 the table only
applies where the device is intended to provide short-circuit protection only.
TABLE 6A2
Correction factors for ambient temperature where the overload
protective device is a semi-enclosed fuse to BS 3036 Table 4C2
Ambient temperature °C
Type of Operating
insulation temperature 25 30 35 40 45 50 55 60 65
Thermoplastic
(general 70°C 1.03 1.0 0.97 0.94 0.91 0.87 0.84 0.69 0.48
purpose pvc)
116
Thermal Insulation
Length in insulation
Derating Factor
(mm)
50 0.89
100 0.81
200 0.68
400 0.55
500 and over 0.50
117
118
119
120
121
122
123
124
1 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.8 2.8 2.4
r r
Note: The reactive element of voltage drop usually provided for 25mm2 and
above conductor sizes is omitted for simplicity. For a fuller treatment
see Appendix 4 of BS 7671.
125
Installation
Installation
Method
Method 6*
15* Reference Voltage
(enclosed
Conductor (installed Method 1 drop (per
in conduit
cross directly in (clipped ampere
in an
sectional an direct) per metre)
insulated
area insulated
wall
wall
1 two-core cable, single-phase a.c. or d.c.
1 2 3 4 5
Mm2 (A) (A) (A) MV/A/m
1 11.5 12 16 44
1.5 14.5 15 20 29
2.5 20 21 27 18
4 26 27 37 11
6 32 35 47 7.3
10 44 47 64 4.4
16 57 63 85 2.8
Notes :
126
APPENDIX 7
App 6
CERTIFICATION AND REPORTING
The certificates are used with the kind permission of the BSI
The introduction to Appendix 6 of BS 7671 : 2001 (Model forms for certification and
reporting) is reproduced on this page.
Introduction
(i) The Electrical Installation Certificate required by Part 7 of BS 7671 shall be made out and
signed or otherwise authenticated by a competent person or persons in respect of the
design, construction, inspection and testing of the work.
(ii) The Minor Works Certificate required by Part 7 of BS 7671 shall be made out and signed or
otherwise authenticated by a competent person in respect of the inspection and testing of
an installation.
(iii) The Periodic Inspection Report required by Part 7 of BS 7671 shall be made out and
signed or otherwise authenticated by a competent person in respect of the inspection and
testing of an installation.
(iv) Competent persons will, as appropriate to their function under (I), (ii) and (iii) above, have a
sound knowledge and experience relevant to the nature of the work undertaken and to the
technical standards set down in this British Standard, be fully versed in the inspection and
testing procedures contained in this Standard and employ adequate testing equipment.
(v) Electrical Installation Certificates will indicate the responsibility for design, construction,
inspection and testing, whether in relation to new work or further work on an existing
installation.
Where design, construction and inspection and testing is the responsibility of one person a
Certificate with a single signature declaration in the form shown below may replace the multiple
signatures section of the model form.
I being the person responsible for the Design, Construction, Inspection &
Testing of the electrical installation (as indicated by my signature below),
particulars of which are described above, having exercised reasonable skill and
care when carrying out the Design, Construction, Inspection & Testing, hereby
CERTIFY that the said work for which I have been responsible is to the best of
my knowledge and belief in accordance with BS 7671:………., amended to
………. (date) except for the departures, if any, detailed as follows.
(vi) A Minor Works Certificate will indicate the responsibility for design, construction, inspection
and testing of the work described in Part 4 of the certificate.
(vii) A Periodic Inspection Report will indicate the responsibility for the inspection and testing of
an installation within the extent and limitations specified on the form report.
(viii) A Schedule of Inspections and a Schedule of Test Results as required by Part 7 shall be
issued with the associated Electrical Installation Certificate or Periodic Inspection Report.
(ix) When Making out and signing a form on behalf of a company or other business entity,
individuals shall state for whom they are acting.
(x) Additional forms may be required as clarification, if needed by non-technical persons, or in
expansion, for larger or more complex installations.
(xi) The IEE Guidance Note 3 provides further information on inspection and testing on
completion and for periodic inspections.
127
5. The page numbers for each of the Schedule of Test Results should
be indicated, together with the total number of sheets involved.
7. The proposed date for the next inspection should take into
consideration the frequency and quality of maintenance that the
installation can reasonably be expected to receive during its
intended life, and the period should be agreed between the
designer, installer and other relevant parties.
128
129
130
131
132
133
134
135
This safety Certificate has been issued to confirm that the electrical
installation work to which it relates has been designed, constructed,
inspected and tested in accordance with British Standard 7671 (The IEE
Wiring Regulations)
You should have received an original Certificate and the contractor should
have retained a duplicate Certificate. If you were the person ordering the
work, but not the user of the installation, you should pass this Certificate, or
a full copy of it including the schedules, immediately to the user.
136
137
138
139
140
141
This Certificate has been issued to confirm that the electrical installation
work to which it relates, has been designed, constructed and inspected and
tested in accordance with British Standard 7671, (The IEE Wiring
Regulations).
You should have received an original Certificate and the contractor should
have retained a duplicate. If you were the person ordering the work, but not
the owner of the installation, you should pass this Certificate, or a copy of it,
to the owner.
142
1. This Periodic Inspection Report form shall only be used for the
reporting on the condition of an existing installation.
5. The ‘Extent and Limitations’ box shall fully identify the elements of
the installation that are covered by the report and those that are
not; this aspect having been agreed with the client and other
interested parties before the inspection and testing is carried out.
143
144
145
You should have received an original Certificate and the contractor should
have retained a duplicate. If you were the person ordering the work, but not
the owner of the installation, you should pass this Certificate, or a copy of it,
to the owner.
The ‘Extent and Limitations’ box should fully identify the extent of the
installation covered by this Report and any limitations on the inspection and
tests. The contractor should have agreed these aspects with you and with
any other interested parties (Licensing Authority, Insurance Company,
Building Society etc.) before the inspection was carried out.
146
147
148
149
APPENDIX 8
Introduction
150
General
A single 30A or 32A ring circuit may serve a floor area of up to 433-02-04
100m2. Sockets for washing machines, tumble dryers and
dishwashers should be located so as to provide reasonable sharing
of the load in each leg of the ring, or consideration should be given
to a separate circuit.
TABLE 8A
Final circuits using BS 1363 socket-outlets and connection units
Minimum conductor
cross-sectional area*
Copper
Overcurrent Maximum
conductor Copper
Type of protective floor area
thermoplastic conductor
circuit device served
or mineral
thermosetting insulated
insulated cables
cables
2 2 2
Rating A mm mm m
1 2 3 4 5 6
A1 Ring 30 or 32 2.5 1.5 100
A2 Radial 30 or 32 4 2.5 75
A3 Radial 20 2.5 1.5 50
*The tabulated values of conductor size may be reduced for fused spurs
151
Where two or more ring final circuits are installed the socket-outlets
and permanently connected equipment to be served are to be
reasonably distributed among the circuits.
Circuit Protection
BS EN 60947-2 and
Conductor Size
protective device),
protective device)
The conductor size for a fused spur is determined from the total
current demand served by that spur, which is limited to a maximum
of 13A.
152
Spurs
The total number of fused spurs is unlimited but the number of non
fused spurs should not exceed the total number of socket-outlets
and items of stationary equipment connected directly in the circuit.
General
Circuit protection
153
Conductor size
Types of socket-outlets
A circuit of rating 15A but not exceeding 50A may supply two or
more cooking appliances where these are installed in one room.
The control switch or cooker control unit should be placed within
two metres of the appliance, but not directly above it. Where two
stationary cooking appliances are installed in one room, one switch
may be used to control both appliances provided that neither
appliance is more than two metres from the switch. Attention is
drawn to the need to provide discriminative operation of protective
gear as stated in Regulation 533-01-06.
154
Number of socket-outlets
155
Table 8B
Recommended provision of socket-outlets
(All socket-outlets are twin)
Notes:
(1) The number of outlets depends on the size of the room.
(9) The use of IT and other electrical equipment with high earth 607-02-06
protective conductor currents may require the application of
Regulation 607 to accommodate cumulative leakage currents.
156
APPENDIX 9
Where
Zs=Ze+R1+R2
Where
157
TABLE 9A
Value of resistance/metre for copper and aluminium conductors and
of R1+R2 per metre at 20°C in milliohms/metre
2 Resistance/metre
Cross-sectional area (mm )
Or (R1+R2)/metre (mΩ/m)
Phase Protective
Copper Aluminium
conductor conductor
1 - 18.10
1 1 36.20
1.5 - 12.10
1.5 1 30.20
1.5 1.5 24.20
2.5 - 7.41
2.5 1 25.51
2.5 1.5 19.51
2.5 2.5 14.82
4 - 4.61
4 1.5 16.71
4 2.5 12.02
4 4 9.22
6 - 3.08
6 2.5 10.49
6 4 7.69
6 6 6.16
10 - 1.83
10 4 6.44
10 6 4.91
10 10 3.66
16 - 1.15 1.91
16 6 4.23 -
16 10 2.98 -
16 16 2.30 3.82
25 - 0.727 1.20
25 10 2.557 -
25 16 1.877 -
25 25 1.454 2.40
35 - 0.524 0.87
35 16 1.674 2.78
35 25 1.251 2.07
35 35 1.048 1.74
50 - 0.387 0.64
50 25 1.114 1.84
50 35 0.911 1.51
50 50 0.774 1.28
158
TABLE 9B
Ambient temperature multipliers to Table 9A
5°C 0.94
10°C 0.96
15°C 0.98
20°C 1.00
25°C 1.02
Note:
The correction factor is given by:
For verification purposes the designer will need to give the values
of the phase and circuit protective conductor resistances at the
ambient temperature expected during the tests. This may be
different from the reference temperature of 20°C used for Table 9A.
The correction factors in Table 9B may be applied to the Table 9A
values to take account of the ambient temperature (for test
purposes only).
(a) earth fault loop impedance of Table 41B1, Table 41B2 or Table 41B1
Table 41D of BS 7671 Table 41B2
Table 41D
(b) earth fault loop impedance and resistance of protective
conductor of Table 41C of BS 7671. Table 41C
159
Note 2 See Table 54C of BS 7671: applies where the protective Table 54C
conductor is a core in a cable or is bunched with cables.
160
APPENDIX 10
TABLE 10A
Main earthing and main equipotential bonding conductor sizes
(copper equivalent) for TN-S and TN-C-S supplies
Phase conductor or
2
neutral conductor of mm 4 6 10 16 25 35 50 70
PME supplies
Earthing conductor
not buried or buried 542-03-01
protected against 2
543-01-01
mm 6 6 10 16 16 16 25 35
corrosion and
mechanical damage
see notes
Main equipotential
2 547-02-01
bonding conductor mm 6 6 6 10 10 10 16 25
see notes
Main equipotential
bonding conductor 2 Table 54H
mm 10 10 10 10 10 10 16 25
for PME supplies
(TN-C-S)
corrosion
2
50mm steel if not protected against mechanical damage or corrosion
2
16mm copper if not protected against mechanical damage but
2
16mm coated steel if not protected against mechanical damage but
161
162
163
164
PICTORIAL INDEX
Pages
To use the index, turn to the relevant index and find paragraph
references against the appropriate schematic drawing.
165
166
167
168
169
170
171
172
173
Para Page
A
Alarms, smoke 7.4.1 56
B
Band I 9.2.2 64
Band II 9.2.2 64
Bathrooms 4.5 25
4.7 26
7.2.5 48
8.1 58
Bonding 4 23
Appx 10 161
BS 1363 socket outlets Appx 8 150
Building Regulations 1.1 12
Fig 8A 155
C
Cable
Bends Table 4E 108
Floors and ceilings 7.3.1 52
Ratings Appx 6 115
Resistance Appx 9 157
Selection Appx 3 94
Spans (overhead wiring) Table 4B 104
Supports Appx 4 100
Walls 7.3.2 53
Capacities
Conduits Appx 5 109
Trunking Appx 5 109
Ceilings 7.3.1 52
Central heating 4.1 23
Certificates 9.1 62
Appx 7 127
Checklist
Circuit 7.2.3 48
Inspection 9.2.2 62
Testing 9.3.1 65
Circuit arrangement Appx 8 150
Circuit-breaker selection Table 7.2B 51
Circuits 7 40
Corrosion Appx 3 94
Competent person Preface 8
Conduit supports Table 4C 106
174
D
Diagrams 6.1(x) 39
Direct contact 3.4(I) 17
Disconnection times 3.5 19
7.2.5 49
Distribution board 3.3 17
Figs 3a, 3b 21
Figs 4a, 4b, 4c 27
Diversity Appx 1 84
E
Earth electrode 4.8 32
Testing 10.3.5 78
Types 4.9 32
Earthing 4 23
Conductor size Appx 10 161
TN-C-S Fig 4b 28
TN-S Fig 4a 27
TT Fig 4c 29
Earth fault loop impedance
Circuits Appx 2 88
RCD 3.6 20
Supply 1.1(iv) 11
Testing 9.3 65
10.3.6 79
Electrical installation certificates Appx 7 127
Electric shock 3.4 17
8 58
Emergency lighting 7.4.2 57
Emergency switching 5.4 35
Equipotential bonding 4 23
175
F
Fault current
Measurement 10.3.7 80
Protection 3.3 17
7.2.5(I) 49
Table 7.2A 50
Final circuits 7 40
Fire alarms 7.4.1 56
Fireman’s switch 5.4 36
Fixed wiring Table 3A 94
Flexible cords Table 3B 97
Floors 7.3.1 52
Functional
Extra-low voltage 10.3.3(vi) 75
Switching 5.2 35
Testing 10.3.8 80
Fuses 7.2.5 49
Supplier’s 1.1(iii) 11
2.2(I) 14
G
Garages 8.3 60
Garden buildings 8.3 60
Gas pipes 4.1 23
Gas service 4.2 24
Grouping 7.2.1 41
Table 6C 118
H
Hand-held equipment 3.5.2(ii) 19
Hearing aid loop 7.3.4 54
Height of overhead wiring Table 4B 104
Height of switches. Sockets Fig 8A 155
I
Immersion heaters Appx 8 154
Indirect contact 3.4(ii) 18
Information 1.2 13
Inspection and testing 9 62
Inspection certificate Appx 7 127
Inspection schedule 9.1 62
Appx 7 127
Insulation resistance 9.3 65
10.3.3 72
Isolation 5.1 34
176
J
Joists 7.3.1 52
L
Labelling 6 36
Lighting demand Table 1A 85
Diversity Table 1B 86
Lightning protection 4.1 23
Live part 1.1 12
Load characteristics 7.2.5(ii) 51
Load estimation Appx 1 84
Loop impedance Appx 2 88
Testing 10.3.6 79
M
Main earthing
Bar Figs 4a, 4b, 4c 27
Bonding Figs 4a, 4b, 4c 27
Terminal Figs 4a, 4b, 4c 27
Maximum demand Appx 1 84
Mechanical maintenance 5.3 35
Metal pipework 4.5 25
4.6 26
Metal structures 4.1 23
Meter 2.2(ii) 14
Meter tails 2.2(iii) 14
Figs 4a, 4b, 4c 27
Mineral cable Table 3A 94
Minor works certificate Appx 7 127
Motors diversity Table 1B 86
N
Notices 6 36
Number of socket-outlets Table 8B 156
O
Oil service pipe 4.2 24
Overhead wiring Appx 4 100
Overload protection 3.2 17
P
PELV 3.4(iii) 18
9.2.2 62
Table 10.1 73
10.3.3(v) 75
Periodic reports Appx 7 127
Plastic pipes 4.7 26
177
R
Radial circuits Appx 8 150
Testing 10.3.1 67
RCBO 3.6.3 22
RCD 3.6 20
RCD testing 11 81
Reference method 7.1(ii) 40
Reports Appx 7 127
Resistance of conductors Appx 9 157
Ring circuits Appx 8 150
Testing 10.3.2 69
S
Schedules 9.1 62
Appx 7 127
Scope 1.1 11
SELV 3.4(iii) 18
9.2.2 62
Table 10.1 73
10.3.3(v) 75
Sequence of tests 10.2 66
Service position 2 14
Short-circuit protection 3.3 17
Table 7.2A 50
Showers 8 58
Skilled persons 1.1 11
Smoke alarms 7.4.1 56
Socket-outlets 3.6.1 22
Appx 8 150
Special locations 8 58
Spurs Appx 8 150
Standard circuits Appx 8 150
Supplementary bonding 4.5 25
4.6 26
4.7 26
Table 10B 162
Supplier’s cut-out 1.1(iii) 11
2.2(I) 14
178
T
Temporary buildings 8.3 60
Test equipment 10.1 66
Test results schedule 9.1 62
Appx 7 127
Testing 9 62
10 66
Thermal insulation Appx 6 117
Thermoplastic (pvc) cable 7.1 48
Table 6D1 120
Table 6E1 123
Table 6F 126
Thermosetting cable 7.2.2 48
Table 6D1 120
Table 6E1 123
TN-C-S system Fig 4b 28
TN-C Fig 4a 27
Trunking
Capacities Appx 5 109
Supports Table 4D 107
TT system Fig 4c 29
7.2.4 49
Two –way circuits Fig 7.3.4 55
10.3.3(ii) 72
U
Underfloor heating 8.1.2 58
V
Voltage bands 9.22 64
Voltage drop Appx 6 115
Table 6D2 122
Table 6E2 125
Table 6F 126
W
Walls 7.3.2 53
Water heaters Appx 8 154
Water pipes 4.1 22
179