Position Sensor: Type 1
Position Sensor: Type 1
Position Sensor: Type 1
FS1
SK7 SK2 1 +
BATTERY FS3
26 WAY
FS2
+ - SK6 SK3 2 -
FS3 (IF FITTED) 100mA SK3 1 4 3 2 SK13 2 1 SK14 DC/DC
CONVERTER
6 SK9 SK8 1 42
SK5 SK4
5 MONITOR 3 43
RELAY SK20
2 44
SK7
SK10
1 6 _
S1
+
MAKE AT FULLY SHUT SK14
8 7
2 8 SK15
MAKE AT FULLY OPEN S2 7 9
FUSE FS1 - 20A ATO FAST ACTING
3 10 FUSE FS2 - 500mA ANTI-SURGE
BREAK AT FULLY SHUT S3 6 11
4 12 REFER TO SHEET 2 FOR NOTES
BREAK AT FULLY OPEN S4 & OPTION PCB'S IF FITTED
5 13
SK4
CLOSE 9 33
STOP/ MAINTAIN 10 34
50% SK6 OPEN 8 35
COMMON -VE 1 36
18 WAY
ESD 12 25
STOP
CLOSE
LOCAL
OPEN INTERLOCK 13 37
OPEN REMOTE
CLOSE INTERLOCK 14 38
COMMON -VE 5 31
SK1 SK2
SLOT A SLOT B
SLOT A
SK1
SLOT A SK3
-VE +VE
1 23 A
2 22
3
4
5
CPT
SK6
1 0V
SUPPLY FROM SK11 ON MOTOR CONTROL PCB
2 24V
SK8
1
2
NOTES
1.FUSES:
-PS1 is a self-resetting fuse. 3.INDICATION:
-Refer to publication PUB002-065 for approved fuses FS1 and FS2. -For typical position, status and alarm indication see PUB002-041.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -“S” contacts are user configurable and are shown in their default
applies for rated torque performance; duty cycle is not guaranteed. setting.
2.REMOTE CONTROL: -Refer to PUB002-040 for functions and configuration instructions.
-For typical remote control circuits refer to: -Monitor Relay indicates actuator availability for remote control (shown
-RWS indicated or PUB002-041. “unavailable”). It can be configured to exclude local/remote selection.
-For DC and AC control, connect –ve/0V to terminal 36. -Refer to PUB002-040 for monitored functions and configuration
-(For negative switch / positive common, refer to RWS indicated). instructions.
-Control signal threshold voltages: -Voltage applied to indication contacts must not exceed 150Vac
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc. -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-AC: “on” ≥60Vac / “off” ≤40Vac, max 120Vac. and no more than 8A in total for all 4 contacts.
-Control signal duration to be 300ms minimum.
-Maximum current drawn from remote control signals is: 4.BATTERY:
-8mA at 24Vdc or 12mA at 120Vac. -Battery maintains local and remote “S” contact indication only.
-Supply provided on terminals 4 & 5: -Refer to installation manual for approved replacement battery types.
-Intended for remote control. Circuit Diagram Number Issue Sheet
-Max external load 5W at 24Vdc / 5VA at 120Vac No
2
See Sheet 1 for all Revision details/information 301B0000 6 of 2
IQ3