Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Substation Monitoring Device: Instruction Bulletin

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

Substation Monitoring Device

ENGLISH
Instruction Bulletin
This instruction bulletin describes the monitoring, tracking, and measuring functions of the
Substation Monitoring Device.

QGH51397
Release date: 01/2020
Retain for future use.

www.schneider-electric.com
Legal Information
ENGLISH

The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
guide or its content, except for a non-exclusive and personal license to consult it on
an "as is" basis. Schneider Electric products and equipment should be installed,
operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed
by Schneider Electric and its subsidiaries for any errors or omissions in the
informational content of this material or consequences arising out of or resulting
from the use of the information contained herein.
Schneider Electric, Magelis, Modbus, and Square D are trademarks and the
property of Schneider Electric SE, its subsidiaries, and affiliated companies. All
other trademarks are the property of their respective owners.
Table of Contents Substation Monitoring Device

SECTION 1:SAFETY INFORMATION ............................................................................................................ 7


SECTION 2:LIST OF ACRONYMS

ENGLISH
............................................................................................................ 8

SECTION 3:INTRODUCTION ............................................................................................................ 9

SMD General Description ............................................................................... 9


Substation Alarming ......................................................................................... 9
Local and Remote Monitoring .................................................................... 9
Nearby Control ......................................................................................... 10
Thermal Monitoring ........................................................................................ 10
Environmental Monitoring .............................................................................. 10
Dry Transformer Monitoring ........................................................................... 11
Circuit Breaker Monitoring ............................................................................. 11
SECTION 4:SMD ARCHITECTURE .......................................................................................................... 12

SECTION 5:SAFETY PRECAUTIONS ......................................................................................................... 13


SECTION 6:SMD COMMUNICATION (INDICATIONS) .......................................................................... 14
Main Processor Unit TM251......................................................................... 14
TM3DM8R or TM3DI16 Digital Inputs/Outputs ....................................... 14
TM3TI4 Analog Input or TM4ES4 Ethernet Switch ............................... 14
Magelis™ Local HMI ...................................................................................... 14
Disable Buzzer/Configure Backlight ............................................................... 15
SECTION 7:SUBSTATION MONITORING SYSTEM DEVICE USAGE ............................................. 16
Human Machine Interface (HMI) Screen Descriptions ......................... 16
Human Machine Interface (HMI) Screens and Organization.............. 17
Home Screen .................................................................................................... 18
Notifications Screen ....................................................................................... 20
Substation Environment Screen .................................................................... 21
Settings Screen Menu .................................................................................... 21
System Setup Screen Menu .................................................................... 22
Network Screen Menu ....................................................................... 22
ZigBee Concentrator Screen/Sensor Status Screen ......................... 23
Date & Time Configuration Screen .......................................................... 25
Temperature Unit Configuration Screen .................................................. 26
Language Configuration Screen .............................................................. 26
Cubicle Screen Menu ..................................................................................... 27
Environment Screen ................................................................................ 28
Severity Indicator ............................................................................... 29
Degree of Severity History and Reset ............................................... 30
Inspection Date.................................................................................. 30
Busbar Screen ......................................................................................... 31
Circuit Breaker Screen/Load Break Switch Screen ................................. 31

QGH51397 © 2020 Schneider Electric All Rights Reserved 3


Substation Monitoring Device Table of Contents

Circuit Breaker Mechanism Aging Evaluation: Number


of Operations ..................................................................................... 33
ENGLISH

Circuit Breaker Mechanism Aging Evaluation: Operating and


Charging Times ................................................................................. 33
Circuit Breaker Mechanism Aging Evaluation: Breaking Current ...... 34
Circuit Breaker Control ...................................................................... 34
Cable Connections Screen ...................................................................... 35
Transformer Screen Menu ....................................................................... 36
Thermal Monitoring Information of a Dry Transformer Screen Menu 36
Transformer Medium/Low Voltage Screen Menu .............................. 37
Transformer Winding/Tapping Links Screen ..................................... 37
Thermal Monitoring Screens ........................................................................ 38
SECTION 8:TROUBLESHOOTING AND SUPPORT .............................................................................. 40
Main Processor Unit TM251 System Status LEDs ................................ 40
Reference Publications .................................................................................. 41
Maintenance Log ............................................................................................. 42

4 © 2020 Schneider Electric All Rights Reserved QGH51397


List of Figures Substation Monitoring Device

List of Figures

ENGLISH
Figure 1 – Substation Monitoring Device (SMD) Architecture ........................... 12
Figure 2 – Alarm or Pre-alarm Status Indication Icon ........................................ 14
Figure 3 – Magelis Local HMI Configuration Screen ......................................... 15
Figure 4 – HMI Screen Descriptions .................................................................. 16
Figure 5 – HMI Screens and Organization ......................................................... 17
Figure 6 – Home Screen and Navigation Bar .................................................... 18
Figure 7 – Example: Cubicle without a Transformer .......................................... 19
Figure 8 – Example: Cubicle with a Transformer ............................................... 19
Figure 9 – Notifications Screen and Icon ........................................................... 20
Figure 10 – Substation Environment Screen ....................................................... 21
Figure 11 – Settings Screen Menu ...................................................................... 21
Figure 12 – System Setup Screen Menu ............................................................. 22
Figure 13 – Network Screen Menu ...................................................................... 22
Figure 14 – ZigBee Concentrator Screen, Sensor Configurations/Connections,
and Status Icons ............................................................................... 23
Figure 15 – Sensor Status Screen ....................................................................... 23
Figure 16 – Date & Time Configuration Screen ................................................... 25
Figure 17 – Temperature Unit Configuration Screen ........................................... 26
Figure 18 – Language Configuration Screen ....................................................... 26
Figure 19 – Cubicle Screen Menu ....................................................................... 27
Figure 20 – Environment Screen Functions Page 1: Measurements .......................28
Figure 21 – Environment Screen Functions Page 2: Environmental
Severity History ................................................................................. 28
Figure 22 – Environmental Severity: History Reset ............................................. 30
Figure 23 – Environment Inspection Screen ........................................................ 30
Figure 24 – Busbar Thermal Monitoring Screen .................................................. 31
Figure 25 – Circuit Breaker Screen Functions Page 1: Thermal
Monitoring Screen ............................................................................. 32
Figure 26 – Circuit Breaker Screen Functions Page 2: Monitoring and Control .. 32
Figure 27 – Circuit Breaker Screen Navigation Bar ............................................. 33
Figure 28 – Circuit Breaker Maintenance Screen ................................................ 33
Figure 29 – Circuit Breaker Control Procedure .................................................... 34
Figure 30 – Circuit Breaker Control Screens ....................................................... 35
Figure 31 – Cable Connections Thermal Monitoring Screen ............................... 35
Figure 32 – Transformer Screen Menu ................................................................ 36
Figure 33 – Thermal Monitoring Information of a Dry Transformer
Screen Menu .................................................................................... 37
Figure 34 – Transformer Medium/Low Voltage Thermal Monitoring Screen ....... 37
Figure 35 – Transformer Winding/Tapping Links Thermal Monitoring Screen .... 38
Figure 36 – Example 1: Thermal Monitoring Screen: Others Connections .......... 39
Figure 37 – Example 2: Thermal Monitoring Screen: Circuit Breakers ................ 39

QGH51397 © 2020 Schneider Electric All Rights Reserved 5


Substation Monitoring Device List of Tables

List of Tables
ENGLISH

Table 1 – List of Acronyms ................................................................................. 8


Table 2 – Circuit Breaker Positions Indicated from Digital Input Information.... 19
Table 3 – Sensor Status Icon Indications, Troubleshooting, and Solutions...... 24
Table 4 – Cubicle Screen Menu Descriptions................................................... 27
Table 5 – Environmental Monitoring: Degree of Severity ................................. 29
Table 6 – Circuit Breaker Mechanism Number of Operations Value
and Statuses..................................................................................... 33
Table 7 – Circuit Breaker Mechanism Breaking Current Value and Statuses .. 34
Table 8 – Main Processor Unit TM251 System Status LEDs ........................... 40
Table 9 – NEMA Reference Publications ......................................................... 41
Table 10 – Maintenance Log Description ........................................................... 42

6 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 1—Safety Information Substation Monitoring Device

Section 1— Safety Information

ENGLISH
Important Information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service, or maintain it. The following
special messages may appear throughout this bulletin or on the equipment to warn
of hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that
an electrical hazard exists which will result in personal injury if the instructions are
not followed.
This is the safety alert symbol. It is used to alert you to personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol is not used with this signal word.

Please Note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.

QGH51397 © 2020 Schneider Electric All Rights Reserved 7


Substation Monitoring Device Section 2—List of Acronyms

Section 2— List of Acronyms


ENGLISH

Refer to Table 1 for a list of acronyms used within this instruction bulletin.
Table 1 – List of Acronyms

Acronym Stands for:


BMS Building Management System
GSM Global System for Mobile communications
HMI Human Machine Interface
IED Intelligent Electronic Device
I/O Input/Output
LV Low Voltage
MV Medium Voltage
SCADA Supervisory Control and Data Acquisition
SL Serial Line
SLD Single Line Diagram
SMD Substation Monitoring Device
SMS Short Message Service
TCP/IP Transmission Control Protocol/Internet Protocol

8 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 3—Introduction Substation Monitoring Device

Section 3— Introduction

ENGLISH
This document provides monitoring instructions using the Substation Monitoring
Device (SMD) from Schneider Electric.
The signaling information provided by the monitoring system described in this
manual is intended to be informational only. The SMD monitors temperature and
humidity conditions in specific locations within the switchgear and provides
indication signals when thresholds are surpassed. When temperature and humidity
conditions are outside of the pre-established parameters, consider taking action to
assess the equipment condition. Contact your local Schneider Electric
representative or Field Services team to obtain the appropriate information.

SMD General Description


Substation monitoring can be achieved through substation alarming via:
• Local and remote monitoring
• Nearby control
The SMD provides several tracking and measuring functions, as well as monitoring
features, for:
• Thermal monitoring
• Environmental monitoring
• Dry transformer monitoring
• Circuit breaker monitoring

Substation Alarming
The SMD collects all alarming indications available in the substation using digital
input (e.g., blown fuse or Watchdog relay) information. The SMD also collects the
information using Modbus protocol over Ethernet or Serial Line (SL)
communication.The collected alarms are then presented on the Human Machine
Interface (HMI) locally and made available remotely.
Local and Remote Monitoring
The SMD can be used for local and/or remote monitoring.
Local monitoring includes a:
• Single Line Diagram (SLD) representation of the lineup with temperature
values and logs of alarms on a color display:
— If no pre-alarm or alarm, the general status is operating normally (green).
— If at least one pre-alarm is activated, but no alarm, the general status is
pre-alarm (yellow).
— If at least one alarm is activated, the general status is alarm (red).
• Summary of global status of the substation available on digital contact outputs
that can be used for indicating through lights (typically green, yellow, and red) or
any equipment accepting contact output:
— Digital Contact Output 1: Closed when global status is green
— Digital Contact Output 2: Closed when global status is yellow
— Digital Contact Output 3: Closed when global status is red
— Digital Contact Output 4: Always Open

QGH51397 © 2020 Schneider Electric All Rights Reserved 9


Substation Monitoring Device Section 3—Introduction

Remote monitoring can be achieved through:


• Short Message Service (SMS) associated to the alarms.
ENGLISH

• Connection to remote SCADA, Building Management System (BMS), or


Schneider Electric service platform using Modbus TCP/IP link.
Nearby Control

WARNING
LOSS OF SYSTEM CONTROL PATHS
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Example: Emergency Stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of
anticipated transmission delays or failure of the link.
Failure to follow these instructions can result in death or serious injury.

The SMD can be used as remote open or closing means for only circuit breaker or
load break switch operation.
The nearby control is limited to only authorized users and is restricted by password
access. In addition:
• The local HMI allows for the opening and closing of the switchgear through the
SMD only when connected to the protective relay (or other Intelligent Electronic
Device (IED)) through Modbus. The switchgear’s position is available in the SLD.
• The nearby HMI allows switchgear operation through a mobile device (e.g.,
tablet or smart phone) when connected to the SMD.
NOTE: The Magelis™ HMI is required to use the nearby HMI.

Thermal Monitoring
Thermal monitoring of cable, busbar, circuit breaker or withdrawable connections in
cubicle and transformer connections is achieved using TH110 wireless sensors from
Schneider Electric and ZigBee™ concentrators. One of the major causes of medium
voltage equipment damage is aging electrical connections. Thermal monitoring
tracks the temperature of connections and helps determine equipment aging.
Different algorithms apply to temperature measurements that result in indication
alarms. For example, in:
• Standard absolute monitoring: An alarm is indicated when the temperature
exceeds a fixed threshold.
• Advanced absolute monitoring: An alarm is indicated when the temperature
exceeds the threshold and adapts continuously to the load current of the feeder.
• Discrepancy monitoring: An alarm is indicated when the differences between
phase temperatures exceed a fixed threshold.

Environmental Monitoring
Environmental monitoring is achieved using CL110 wireless sensors from
Schneider Electric and ZigBee concentrators that measure humidity and
temperature inside cubicles and determine the severity of condition based on
frequency of condensation and pollution. This severity indicator is used to calculate

10 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 3—Introduction Substation Monitoring Device

when the next inspection should be planned. An alarm can be set on temperature
or humidity conditions.

ENGLISH
Dry Transformer Monitoring
Dry transformers are monitored using PT100 wired sensors from Schneider Electric
that are installed into windings.The transformer’s aging is determined as stated in
Standard IEC60076-12. An alarm also can be set to indicate hotspot temperatures.

Circuit Breaker Monitoring


Circuit breaker monitoring is achieved using TH110 wireless sensors from
Schneider Electric and ZigBee concentrators.The SMD monitors circuit breakers
based on information collected in the protection relays. When the health of the
mechanism and main contacts are monitored, alarms are indicated when
maintenance is needed according to equipment wear thresholds. Abnormal
operating or charging lead times will also indicate alarms.
The HMI shows the monitored and referenced values for the configured circuit
breakers.

QGH51397 © 2020 Schneider Electric All Rights Reserved 11


Substation Monitoring Device Section 4—SMD Architecture

Section 4— SMD Architecture


ENGLISH

The Substation Monitoring Device (SMD) consists of Programmable Logic


Controller (PLC) TM251, which is the main processor unit, and several optional
components (Figure 1). Components include:
• Input/Output (I/O) boards connected to the PLC for binary and analog inputs
acquisition. If configured:
— Digital inputs connect switchgear auxiliary contacts for status monitoring
(e.g., circuit breaker monitoring) and are used for any digital information
collected as an alarm.
— Analog inputs monitor dry transformer internal windings temperature using
an embedded PT100 probe.
• Up to three (3) ZigBee concentrators to interface ZigBee sensors to PLC TM251
unit that include:
— Thermal sensors TH110
— Environmental sensors CL110
• A local Magelis HMI
NOTE: Nearby HMI on a mobile device also is possible when a Wi-Fi access
point is available.
• Protection relays or any other Modbus device for monitoring and controlling
medium voltage switchgears.
• GSM modem for SMS transmission

Figure 1 – Substation Monitoring Device (SMD) Architecture

12 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 5—Safety Precautions Substation Monitoring Device

Section 5— Safety Precautions

ENGLISH
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E
or CSA Z462.
• This equipment must be installed and serviced only by qualified personnel.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric
power. Assume all circuits are live until they are de-energized, tested, and tagged. Pay particular attention to the
design of the power system. Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm power is off.
• Practice lock-out/tag-out procedures according to OSHA requirements.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function properly.
Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as
damage to equipment or other property.
• Operate the equipment, such as the tablet that supports the SMD, within the specified electrical and
environmental limits.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.

WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
• Change default passwords to help prevent unauthorized access to device settings and information.
• Disable unused ports/services and default accounts, where possible, to minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as firewalls, network segmentation, and
network intrusion detection and protection).
• Use cyber security best practices (for example: least privilege, separation of duties) to help prevent unauthorized
exposure, loss, modification of data and logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

WARNING: This product can expose you to chemicals including Nickel


compounds, which are known to the State of California to cause cancer, and
Bisphenol A (BPA), which is known to the State of California to cause birth
defects or other reproductive harm. For more information go to
www.P65Warnings.ca.gov.

QGH51397 © 2020 Schneider Electric All Rights Reserved 13


Substation Monitoring Device Section 6—SMD Communication (Indications)

Section 6— SMD Communication (Indications)


ENGLISH

The main processor unit TM251 and related accessory components are described
in their specific product data sheets or manuals.
Local indicating information includes, but is not limited to the main processor unit,
digital and analog inputs/outputs (I/Os), and Ethernet switch.

Main Processor Unit TM251


When the Substation Monitoring Device (SMD) starts correctly and is fully operational:
— The two (2) green LEDs RUN and PWR are on, and
— All red LEDs are off.
NOTE: Refer to Table 8 on page 40 for additional system status LED
labels, function types, colors, statuses, and descriptions.
NOTE: When the red LED BAT is on, the battery must be replaced to save
the date and time in case of loss of power supply.
Refer to the TM251 instruction bulletin (HRB5960404) that was shipped
with your equipment for battery replacement instructions, or download the
current version at:
https://www.schneider-electric.us/en/download/document/HRB59604/.

All SMD information is stored in the TM251, but the persistent data related to the
thermal monitoring and all applicative functions are stored in non-volatile memory.
They do not rely on the battery.

TM3DM8R or TM3DI16 Digital Inputs/Outputs


Digital inputs/outputs TM3DM8R or TM3DI16 will indicate:
One (1) green LED for each digital input or output for the status.

TM3TI4 Analog Input or TM4ES4 Ethernet Switch


Analog input TM3TI4 or Ethernet switch TM4ES4 will indicate:
One (1) green LED for power.

Magelis™ Local HMI


Any red or yellow status indication ! icon reports an alarm or pre-alarm on the
SMD (Figure 2).
Figure 2 – Alarm or Pre-alarm Status Indication Icon

14 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 6—SMD Communication (Indications) Substation Monitoring Device

Disable Buzzer/Configure Backlight

ENGLISH
The buzzer can be disabled and the backlight can be configured in the Magelis
configuration screen (Figure 3).
1. Press two (2) opposite corners of the screen quickly and successively.
RESULT: The Magelis configuration screen opens.
2. Click the Offline tab.
a. Click the Buzzer box to enable or disable the buzzer.
b. Click the Backlight box to configure the backlight.

Figure 3 – Magelis Local HMI Configuration Screen

QGH51397 © 2020 Schneider Electric All Rights Reserved 15


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Section 7— Substation Monitoring System Device Usage


ENGLISH

Human Machine Interface (HMI) Screen Descriptions

Active areas include buttons Navigation through the SMD HMI screens is achieved by touching active areas on
and status indication icons ! the screen (Figure 4).

• Green or Blue: Indicates The HMI main screen is divided into different sections. The upper green area
normal conditions contains command buttons and general status indications (icons).
• Yellow: Indicates a The white background is the main part of the screen and displays the function
pre-alarm information. This area is organized into different screens that display general
• Red: Indicates an alarm and/or detailed information.
(A temperature or
humidity threshold has
been exceeded.)

Figure 4 – HMI Screen Descriptions

1 Room Temperature Display:


1 2 3 4 5 6
Measured by CL110 sensor and displayed when the
active screen is the Home screen.
Click on the temperature to access the Substation
Environment screen (Figure 10 on page 21).

2 Date & Time Display:


Click to set the date and time (Figure 16 on page 25).

3 Active Page Display:


— In the HMI screen, the name “Substation
Monitoring Device” is displayed.
— For other pages, text is screen-dependent.
The SMD screen menu name appears after
the Home icon.
— Click the HOME screen icon ( not
shown here) to go back to the SMD
Home screen (Figure 6 on page 18).
— Click on the name of the menu to go
back to previous screen.

4 Notifications Icon:
Click to see the list of active and inactive alarms,
and pre-alarms (Figure 9 on page 20).

5 Room Humidity Display:


Measured by CL110 sensor and displayed when
the active screen is the Home screen.
Click on the temperature to access the Substation
Environment screen (Figure 10 on page 21).

6 Settings Icon:
Click the icon to configure the SMD or check the
System Setup (Figure 12 on page 22).

16 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Human Machine Interface (HMI) Screens and Organization

ENGLISH
The HMI screens consist of the following organization levels (Figure 5). Refer to the
table for additional information regarding the screens listed below.
Home Screen Page 18 Inspection Date Page 30
Notifications Screen Page 20 Busbar Screen Page 31
Substation Environment Screen Page 21 Circuit Breaker Screen/Load Break Switch Screen Page 31
Settings Menu Screen Page 21 Circuit Breaker Mechanism Aging Evaluation: Number of Operations Page 33
System Setup Screen Menu Page 22 Circuit Breaker Mechanism Aging Evaluation: Operating and Charging Times Page 33
Network Screen Menu Page 22 Circuit Breaker Mechanism Aging Evaluation: Breaking Current Page 34
ZigBee Concentrator Screen/Sensor Status Screen Page 23 Circuit Breaker Control Page 34
Date & Time Configuration Screen Page 25 Cable Connections Screen Page 35
Temperature Unit Configuration Screen Page 26 Transformer Screen Menu Page 36
Language Configuration Screen Page 26 Thermal Monitoring Information of a Dry Transformer Screen Menu Page 36
Cubicle Screen Menu Page 27 Transformer Medium/Low Voltage Screen Menu Page 37
Environment Screen Page 28 Transformer Winding/Tapping Links Screen Page 37
Severity Indicator Page 29 Thermal Monitoring Screens Page 38
Degree of Severity History and Reset Page 30

Figure 5 – HMI Screens and Organization

QGH51397 © 2020 Schneider Electric All Rights Reserved 17


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Home Screen
ENGLISH

The Home screen is the default screen after start-up of the product.
1. Click the Home icon from any screen.
RESULT: A single line diagram (SLD) with all status information summarized is
displayed within the Home screen (Figure 6).
The SLD is split into four (4) screens with four (4) cubicles each. Refer to the area
at the bottom of the screen to view the number of available screens (Figure 6).
2. Click the Others button (Figure 6).
RESULT: The screen opens to display the temperature at locations “Other”
than cubicles if some are defined in the configuration.
Only two (2) screens, C1–C4 and C5–C8, are available to navigate when six (6)
cubicles are defined in the SMD configuration (Figure 6). If 16 cubicles were
defined, then buttons C9–C12 and C13–C16 would appear, too.
Figure 6 – Home Screen and Navigation Bar

Available screens include:


— Page C1–C4 for cubicle 1 up to cubicle 4.
— Page C5–C8 for cubicle 5 up to cubicle 8.
— Page C9–C12 for cubicle 9 up to cubicle 12.
— Page C13–C16 for cubicle 13 up to cubicle 16.
The Navigation bar provides access to:
— The buttons C1–C4 up to C13–C16 to scroll
between the four (4) screens.
— The Others button to open the screen and display
the temperature at “Other” locations.
— The active screen (shown with a green
background).The inactive screens are shown with
a light gray background.
— Notification alarms and pre-alarms. The status
Home screen navigation bar
indication icon ! appears in yellow or red near the
C1–C4 up to C13–C16 label or near the Others
button to report an alarm or pre-alarm in this part
of the SMD.

The SLD shows up to four (4) cubicles in each Home screen page.
3. Click on the cubicle area (Figure 6).
RESULT: Detail information for each cubicle is displayed (Figure 7 on page 19). In
a transformer cubicle, a second temperature is displayed (Figure 8 on page 19).
NOTE: The SLD does not show sections—only cubicles. Sections with more
than one circuit breaker or switch are represented by showing two (2) cubicles.

18 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Figure 7 – Example: Cubicle without a Transformer Figure 8 – Example: Cubicle with a Transformer

ENGLISH
Displays: Displays:
— The cubicle reference C1, C2, etc., — The highest temperature from different phases
— The status indication icon ! in yellow or red near related to transformer monitoring
the reference if an alarm or pre-alarm exists in — The status indication icon ! in yellow or red in
this cubicle related to the application (thermal, case of problem with a sensor
environmental, or circuit breaker monitoring)
— The current measurement in the cubicle,
if configured
— The switchgear position, if configured
— The connection temperature with:
— Only the highest temperature from different
phases and from all positions (cable, circuit
breaker, busbar, transformer) is displayed
— The status indication icon ! in yellow or red
in case of problem with a sensor

The following rules are applied when digital inputs indicate the circuit breaker
position (Table 2):
Table 2 – Circuit Breaker Positions Indicated from Digital Input Information

NOTE: A dashed line will appear when a circuit breaker position is unknown or
when a protective relay (or other Intelligent Electronic Device (IED)) issue exists.
The circuit breaker can be either open or closed when the status is unknown.

QGH51397 © 2020 Schneider Electric All Rights Reserved 19


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Notifications Screen
ENGLISH

The Notifications screen records and displays status changes related to alarms or
pre-alarms within the Substation Monitoring Device (SMD).
Status indications are shown as notification icons at the beginning of the line where
alarms or pre-alarms are active or inactive. The alarm or pre-alarm time stamp is
shown on the second line of the status change (Figure 9).
1. Click on the status indication icon ! in the header from any Substation
Monitoring Device (SMD) screen.
RESULT: A Notifications screen appears with SMD status information
displayed and time stamped.
The Notifications screen shows five (5) events per page. Up to 10 pages of events
are available to view.
2. Click the up and down arrows at the bottom of the screen to navigate to the
previous and next event pages.

Figure 9 – Notifications Screen and Icon

Pre-alarm or alarm is inactive:


Status: Operating normally (green)

Pre-alarm has been activated, but no alarm:


Status: Pre-alarm (yellow)

Alarm has been activated:


Status: Alarm (red)
A temperature or humidity threshold has
been exceeded.

20 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Substation Environment Screen

ENGLISH
The Environment screen shows lines with temperature and humidity values.
Click on the Temperature or Humidity value in the header screen (Figure 10).
RESULT: The substation room’s Ambient temperature and Humidity
are displayed.
Figure 10 – Substation Environment Screen

Within the Substation Environment function, there are Header screen


two (2) lines:
— Actual Ambient temperature and its alarm trigger
point
— Actual ambient Humidity and its alarm trigger point

Settings Screen Menu


Click the Settings icon from any screen to access the Settings screen menu.
RESULT: The Settings screen opens and allows access to the menu function
lines (Figure 11).
Figure 11 – Settings Screen Menu

Within the Settings menu, there are four (4)


function lines:
— System Setup: Click to check the status of the
communication between PLC, ZigBee
concentrators, and sensors. Displays:
— The version of the SMD and the HMI in the
System Setup label.
— The HMI and PLC versions. If they are
different, then a notification message
appears instead of the HMI version.
— Date & time: Click to set the date and time and to
choose the format.
— Temperature unit: Click to select the temperature
unit (°C or °F).
— Choose language: Click to set the language.

QGH51397 © 2020 Schneider Electric All Rights Reserved 21


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

System Setup Screen Menu


Click on System Setup menu line of the Settings screen.
ENGLISH

RESULT: The System Setup screen opens and allows access to the
communication status between the PLC, ZigBee concentrators, and sensors
(Figure 12).
Figure 12 – System Setup Screen Menu

Within the System Setup menu, there are four (4)


function lines:
— Network: Click to access the network and Modbus
configurations and the ZigBee concentrator
addresses. Icon displayed at the beginning of the line:
— Red icon: Indicates non-communication between
the PLC and one of the ZigBee concentrators.
— Concentrator 1, 2, and 3: Click to check the status
of the communication between the ZigBee
concentrator and the sensors. Icon displayed at the
beginning of the line:
— Red icon: Indicates the PLC cannot communicate
with the ZigBee concentrator. Possible causes
are the ZigBee concentrator is not energized, not
connected to PLC, or has an invalid address.
— Yellow icon: Indicates communication between
the PLC and ZigBee concentrator is
established. One or more sensors are not
connected to the ZigBee concentrator.

Network Screen Menu The Network screen shows the Modbus configuration for the communication
between PLC and ZigBee concentrators.
Click on the Network menu line of the System Setup screen (Figure 12).
RESULT: The Network screen menu opens and displays the communication
settings between the PLC and ZigBee concentrators (Figure 13).
Figure 13 – Network Screen Menu

NOTE: The communication settings between the


PLC and ZigBee concentrators shall not be modified.
The SMD will work only with these settings:
— Baudrate: 38400 bps
— Frame Setting: 8e1
— Number of bits: 8
— Parity: even
— Number of stop bit: 1
— Automatic Detection (of Modbus communication
parameter): No
— Concentrator (ZigBee) 1, 2, and 3 Slave
Addresses: Shown

22 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

ZigBee Concentrator The ZigBee Concentrator screen shows the status of up to 60 sensors that can be
Screen/Sensor Status connected to each ZigBee concentrator.

ENGLISH
Screen
1. Click on one (1) of the three (3) concentrator lines of the System Setup screen
(Figure 12 on page 22).
RESULT: The ZigBee Concentrator screen displays the status icons for the
sensors (Figure 14).
Figure 14 – ZigBee Concentrator Screen, Sensor Configurations/Connections, and Status Icons

Sensor is not configured in the SMD

Sensor is paired to and actively communicating


with the ZigBee concentrator

Sensor is not paired to the ZigBee concentrator,


but is defined in the SMD configuration

Sensor is inoperable:
Sensor is paired with the ZigBee concentrator and
is defined in the SMD configuration, but the sensor
does not communicate with the ZigBee concentrator

Non-communicating sensor or unexpected


sensor type: See Figure 15 and refer to Table 3 on page 24 for
Sensor is paired with the ZigBee concentrator and detailed Sensor Status screen and icon information.
is defined in the SMD configuration, but is inoperable

2. Click on one of the sensors of the ZigBee Concentrator screen (Figure 14).
RESULT: The Sensor Status screen opens and displays the detailed
information and measured values for the sensors (Figure 15).
Figure 15 – Sensor Status Screen

Detailed sensor information is shown in the top half


part of the screen. Displays:
— Cubicle: Reference of the cubicle where the sensor
is used, including the name defined by the user
— Type: Type of sensor: TH110 or CL110
— Id: Unique sensor ID:
— Indicated on the sensor itself, and
— Referenced by the ZigBee concentrator to
identify it.
— RSSI: Received signal strength indicator (power
measurement received by the ZBRN32 concentrator)
— Indicates the quality of the communication
between the sensor and the concentrator
— Should be above -75 dBm (a lower reception Sensor status is indicated as an icon in the middle of
level results in a communication error.) the screen, as well as in the top left part of the screen.
Measured sensor values are shown in the bottom part Refer to Table 3 for sensor status icon indications.
of the screen. Displays: Temperature, Humidity (if
applicable), and Battery voltage (if applicable) Click the left and right arrows in the middle of the
screen to navigate to the previous and next sensors.

QGH51397 © 2020 Schneider Electric All Rights Reserved 23


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Table 3 – Sensor Status Icon Indications, Troubleshooting, and Solutions


ENGLISH

Sensor is paired to and actively communicating with the ZigBee concentrator

Sensor is not paired to the ZigBee Sensor or the ZigBee concentrator is operable, but pairing is
concentrator, but is defined in the not complete:
SMD configuration Possible cause: Commissioning is not finished.

Sensor is inoperable: Yellow indicates that the sensor is not available either
Sensor is paired with the ZigBee because the:
concentrator and is defined in the — Current flowing is null or too low to energize the sensor, or
SMD configuration, but the sensor — Sensor isn’t communicating or sensor type is unexpected.
does not communicate with the
These indications may result in a loss of signal reception or
concentrator
communication.

Non-communicating sensor or Red indicates:


unexpected sensor type: — Unexpected sensor type:
Sensor is paired with the ZigBee Example: Sensor CL110 is paired, but sensor TH110 is
concentrator and is defined in the defined in the configuration.
SMD configuration, but is inoperable Solution: Identify sensor types accurately and check that they
are paired and defined correctly within the SMD configuration.
— Non-communicating sensor CL110:
Example: The battery in sensor CL110 is too low.
Solution: Replace sensor CL110.
— Non-communicating sensor TH110:
Example: A different TH110 sensor communicates
correctly within the same connection, but at another phase.
Solution: Verify the line and sensor TH110 are energized
properly. Check that the value of the current flowing
through each of the three (3) phases is correct.
These indications could lead to finding inoperable sensor(s).

24 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Date & Time Configuration Screen


The Programmable Logic Controller (PLC) stores the Substation Monitoring Device

ENGLISH
(SMD) date and time values in a non-volatile memory using the battery.
NOTE: Refer to Main Processor Unit TM251 on page 14 for battery
replacement information.
1. Click on Date & time menu line of the Settings screen.
RESULT: The Date & time screen opens and allows access to set the date and
time (Figure 16).
NOTE: The Substation Monitoring Device (SMD) is operable, even when the
date and time stamps are inaccurate. However, the date and time should be set
correctly to receive accurate operation and alarming information from the
environmental monitoring function. Refer to Environmental Monitoring on
page 10 and Figure 10 on page 21.
2. Click on the down arrows to modify the date, time, and format values.
3. Check that the values are correct and click the Update button to validate the
Year, Month, Day, Hour, Minute, or AM/PM values.
RESULT: The screen displays a message communicating that the operation is
in progress. The HMI displays the new date and time when the PLC update
is complete.
Figure 16 – Date & Time Configuration Screen

The Date & time screen is split into three (3) parts:
— Date:
New value in black and current date in gray
(second line)
— Time:
New value in black and current time in gray
(second line)
— Update button:
Button used to apply changes

QGH51397 © 2020 Schneider Electric All Rights Reserved 25


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Temperature Unit Configuration Screen


The Temperature Unit Configuration screen allows modification to the language
ENGLISH

used in the HMI.


1. Click on the Temperature Unit menu line of the Settings screen.
RESULT: The current temperature unit is displayed (Figure 17).
2. Click on the current temperature unit (down arrow) to modify it and choose
between Celsius (°C) and Fahrenheit (°F).

Figure 17 – Temperature Unit Configuration Screen

Language Configuration Screen


The Language Configuration screen allows modification to the unit measurement
used to display the temperature.
1. Click on the Choose Language menu line of the Settings screen.
RESULT: The current language is displayed with a label (Figure 18).
2. Click on the current language (down arrow) to modify it and choose the
preferred language from the list. Available languages are: English, French,
Spanish, Italian, and Portuguese.

Figure 18 – Language Configuration Screen

26 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Cubicle Screen Menu

ENGLISH
1. Click on the cubicle in the Home screen to show the Cubicle menu (Figure 6 on
page 18).
RESULT: The Cubicle screen opens and allows access to the function lines
and details information (Figure 19).
Figure 19 – Cubicle Screen Menu

Within the Cubicle screen menu, there are five (5)


function lines:
— Environment
— Busbar
— Circuit Breaker
— Cable Connections
— Transformer
Functions that are not available in the cubicle are
displayed in light gray.
Configured functions are displayed in black.

2. Click on the configured equipment function line.


RESULT: More details about the selected configured function are displayed.
Refer to Table 4 for Cubicle screen menu descriptions.
Table 4 – Cubicle Screen Menu Descriptions

1 Function Description 2 1 4 3

2 Status Indication Icon !:


Appears in yellow or red when an alarm or pre-alarm related to this function in the cubicle exists

3 Connection Temperature Measurement:


— Displays the maximum temperature measured by all sensors
— Status indication icon ! appears in yellow or red near the temperature if an alarm or pre-alarm
threshold is reached

4 Additional information related to the function:


— Circuit breaker status (determined by reading the Modbus address of the protective relay (or other
Intelligent Electronic Device (IED))
— Current flowing in the cubicle
— Humidity
— Transformer internal temperature

QGH51397 © 2020 Schneider Electric All Rights Reserved 27


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Environment Screen
The Environment screen is split into two (2) function screens that show:
ENGLISH

— The temperature and humidity measurements, as well as the estimated


severity indicator (Figure 20).
— The Environment Severity history since the last declared inspection
(Figure 21).
Click on the Environment line of the Cubicle screen.
RESULT: The temperatures, alarms, temperature thresholds, and history of
severity levels are displayed on the screen (Environment Screen Functions
Page 1 and Page 2).

Environment Screen Functions Page 1 measurements Figure 20 – Environment Screen Functions


shown are: Page 1: Measurements
— Ambient temperature of the cubicle: Measured by the
CL110 sensor and the pre-alarm threshold (and
defined by the SMD). The status indication icon !
appears in yellow at the beginning of the line when
the measurement is above the threshold.
— Humidity: Measured by the CL110 sensor and the
related pre-alarm threshold (and defined by the
SMD). The status indication icon ! appears in
yellow at the beginning of the line when the
measurement is above the threshold.
— Pollution level of the substation: Is shown as the same
setting in all cubicle environment screens
(and defined by the SMD). Indicated as Low or High.
— Severity indicator: Calculated by the SMD from the
humidity, temperatures and pollution level defined in
the configuration. Indicated as levels 0, 1, 2, or 3.
Figure 21 – Environment Screen Functions
— Duration without condensation: Measured as the Page 2: Environmental Severity
number of days without condensation. History

Environment Screen Functions Page 2 shows four (4)


severity indicator levels of climatic conditions and the
duration of days in them since the last inspection. The
severity levels are:
— Critical (indicates level 3)
— High (indicates level 2)
— Low (indicates level 1)
— No (indicates level 0)

28 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Severity Indicator Based on standard IEC 62271-304, the SMD indicates four (4) severity levels of
equipment aging that is determined by the cumulative days the equipment spends

ENGLISH
in condensation and pollution conditions.
The indicators are shown in degrees and are as follows (Table 5):
• Degree 0 (indicated in green)
• Degree 1 (indicated in yellow)
• Degree 2 (indicated in orange)
• Degree 3 (indicated in red)
These indicators are used to determine an acceleration factor and when timely
addressed, can lead to a reduction in maintenance time. The degree of severity of
service condition is determined daily based on the measured condensation and
pollution level declared (Figure 20 on page 28 and Table 5).
NOTE: Follow the switchgear maintenance plan that is specific to your
equipment. Contact your local Schneider Electric representative or Field
Services team to obtain the appropriate information.
Table 5 – Environmental Monitoring: Degree of Severity

The SMD measures the condensation level from the


relative humidity and ambient temperatures, as well
as the cold point temperature.
Ambient temperature is the air temperature inside the
cubicle. Cold point temperature is the temperature of the
walls of the cubicle. These two temperatures, along with
humidity are used to calculate the condensation levels.
The possible condensation levels are:
— Co: Normally Nonrecurring condensation:
(not more than twice a year)
— CL: Infrequent condensation:
(not more than twice a month) The severity degree is displayed in green, yellow,
— CH: Frequent condensation: orange, and red depending of its value.
(more than twice a month)
— CH+: Very Frequent condensation: The Environment condition alarm is generated for
(more than twice a week) pollution levels:

The pollution levels defined in the configuration are: — Pollution Level Low

— PL: Low pollution — Degree 1 or 2: Pre-alarm


— PH: High pollution — Degree 3: Alarm
— Pollution Level High
— Degree 2: Pre-alarm
— Degree 3: Alarm

QGH51397 © 2020 Schneider Electric All Rights Reserved 29


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Degree of Severity History The Substation Monitoring Device (SMD) cumulates the days for each severity
and Reset level and represents them in a bar graph (Figure 21 on page 28).
ENGLISH

Click the Reset button at the bottom left of the screen to reset the graph and restart
the calculation (Figure 21 on page 28).
RESULT: A pop-up window appears to confirm the operation (Figure 22).
Figure 22 – Environmental Severity: History Reset

Inspection Date The date of the last inspection can be defined in the configuration during
installation of the SMD. The number of cumulated days of each degree of severity
is used to calculate an aging factor (Figure 23).
Click on the Inspection button in the Environment screen to declare a performed
inspection (Figure 21 on page 28).
RESULT: The Environmental Inspection page opens and the algorithm is reset
to restart the calculation of the next inspection date (Figure 23).
Figure 23 – Environment Inspection Screen

The SMD calculates the next inspection date using:


— The date of the last inspection.
— The period of the inspection defined in the
configuration.
— The aging factor derived from the degree of severity.
NOTE: A pre-alarm occurs two (2) months before the
next inspection date. It is an on-screen notification that
appears when the inspection date is reached or exceeded.

30 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Busbar Screen
The Busbar screen displays the information related to the thermal monitoring

ENGLISH
temperature of the busbar connections.
Click on the Busbar line of the Cubicle screen to view thermal monitoring
information related to the busbar.
RESULT: The Busbar thermal monitoring information is displayed (Figure 24).
Figure 24 – Busbar Thermal Monitoring Screen

For each Busbar connection, there are four (4) lines:


— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature
algorithm result

Refer to Thermal Monitoring Screens on page 38 for


additional pre-alarm and alarm thresholds, status
indication, and bar graph information.

Circuit Breaker Screen/Load Break Switch Screen

WARNING
LOSS OF SYSTEM CONTROL PATHS
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Example: Emergency Stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of
anticipated transmission delays or failure of the link.
Failure to follow these instructions can result in death or serious injury.

The Circuit Breaker screen is split into two (2) function screens that show:
— The information related to the circuit breaker thermal monitoring (Figure 25
on page 32).
— The information related to circuit breaker monitoring and control (Figure 26
on page 32).
Click on the Circuit Breaker line of the Cubicle screen to view the Circuit Breaker
temperature and monitoring.
RESULT: The functions (thermal monitoring, circuit breaker monitoring, and
circuit breaker Control button) are displayed on the screen (Figures 25 and 26
on page 32).

QGH51397 © 2020 Schneider Electric All Rights Reserved 31


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Circuit Breaker Screen Functions Page 1 allows the user Figure 25 – Circuit Breaker Screen Functions
ENGLISH

access to screens that are related to four (4) functions: Page 1: Thermal Monitoring Screen
— Thermal monitoring (Page 1)
— Circuit Breaker monitoring (Page 2)
— Circuit Breaker control (Control button)
— Circuit Breaker maintenance (Maintenance button)
When entering the Circuit Breaker screen, the
Thermal Monitoring screen displays temperature
information for the top and bottom of the circuit breaker
(Figure 25).
For each Circuit Breaker connection, there are four
(4) lines:
— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature
algorithm result
Refer to Thermal Monitoring Screens on page 38 for
additional pre-alarm and alarm thresholds, status
indication, and bar graph information.

Figure 26 – Circuit Breaker Screen Functions


Page 2: Monitoring and Control
Circuit Breaker Screen Functions Page 2 contains Circuit
Breaker monitoring information that is used to perform
circuit breaker health calculations, which determines
equipment aging. The aging evaluation is executed using
the information collected in the protection relay (Figure 26):
— Last operation: Displays the last date of operation
— Number of operations: Displays:
— The number of operations read in the
protection relay.
— The indication status icon ! (Appears in red
or yellow at the beginning of the line when an
alarm or pre-alarm exists)
— Charging time and Operating time: Displays:
— The last value measured
For additional information, refer to:
— The reference value (First value measured by
the SMD) — Circuit Breaker Mechanism Aging Evaluation:
Number of Operations on page 33.
— The indication status icon ! (Appears in red at
the beginning of the line when time is abnormal) — Circuit Breaker Mechanism Aging Evaluation:
Operating and Charging Times on page 33.
— Breaking current: Displays:
— Circuit Breaker Mechanism Aging Evaluation:
— The cumulated breaking current (kA)² read in
Breaking Current on page 34.
protection relay and compares it to the
maximum value specified for the circuit breaker
— The indication status icon ! (Appears in red
or yellow at the beginning of the line when an
alarm or pre-alarm exists

32 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

The bar at the bottom of the Circuit Breaker screen (Figure 27) allows the user to
navigate between Page 1 and Page 2 details, as well as to access Control

ENGLISH
(Figure 27) and Maintenance (Figure 28) functions within the Substation Monitoring
Device (SMD).

Figure 27 – Circuit Breaker Screen Navigation Bar Figure 28 – Circuit Breaker Maintenance Screen
— Click the down arrow to go to Page 2 Circuit Click the Maintenance button to view the date of
Breaker monitoring. the last maintenance and to declare a maintenance
— Click the up arrow to go to Page 1 Thermal has been executed.
monitoring.
— Click on the Control button to operate the Circuit
Breaker from Pages 1 and 2.
— RESULT: The origin page is displayed at the
end of the control operation.

Circuit Breaker Mechanism Mechanism aging is linked directly to the Number of operations realized and
Aging Evaluation: Number correlated to the maximum Number of operations specified for the circuit breaker
of Operations (Figure 26 on page 32).
A % bar graph shows the current value compared to the maximum value specified
for the circuit breaker (Table 6).
Table 6 – Circuit Breaker Mechanism Number of Operations Value and
Statuses

% Bar Graph Color Status


0–25% Blue OK
25%–50% Yellow Pre-alarm 25% mechanical aging
50%–80% Yellow Pre-alarm 50% mechanical aging
80%–100% Red Alarm 80% mechanical aging

Circuit Breaker Mechanism The first operating and charging times that the SMD observes are stored as
Aging Evaluation: Operating reference times (Figure 26 on page 32). The SMD indicates an alarm if the
and Charging Times measured time is too long compared to the reference times based on the following
time increases:
• Operating time is not normal if it increases by 30 ms compared to the
reference time.
• Charging time is not normal if it increases by 3 s compared to the reference time.

QGH51397 © 2020 Schneider Electric All Rights Reserved 33


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Circuit Breaker Mechanism The algorithm is based on the wear of the electrical contact and is measured using the
Aging Evaluation: Breaking cumulated Breaking Current (kA)² stored by protection relay (Figure 26 on page 32).
ENGLISH

Current
A % bar graph shows the electrical aging in % bar graph = current electrical wear /
maximum permissible wear (Table 7).
Table 7 – Circuit Breaker Mechanism Breaking Current Value and Statuses

% Bar Graph Color Status


0–25% Blue OK
25%–50% Yellow Pre-alarm 25% electrical wear
50%–80% Yellow Pre-alarm 50% electrical wear
80%–100%
Red Alarm 80% electrical wear
or >65000 (kA)2

Circuit Breaker Control

WARNING
LOSS OF SYSTEM CONTROL PATHS
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Example: Emergency Stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of
anticipated transmission delays or failure of the link.
Failure to follow these instructions can result in death or serious injury.

1. Click the Control button to operate the circuit breaker (Figure 27 on page 33).
2. Follow the Circuit Breaker procedure (Figure 29).
Figure 29 – Circuit Breaker Control Procedure

3. Enter the password to unlock the control (Figure 30 on page 35).


NOTE: The default password is 123456 if it was not changed during the
Substation Monitoring Device configuration.
NOTE: The HMI returns to the Home page (canceling the password) after one
(1) minute of inactivity within the password or confirmation screens.

34 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Figure 30 – Circuit Breaker Control Screens

ENGLISH
Cable Connections Screen
The Cable Connections screen displays the information related to the thermal
monitoring temperature of the cable connections.
Click on the Cable Connections line of the Cubicle screen to view thermal
monitoring information related to the connections for Cables 1 and 2.
RESULT: The Cable Connections thermal monitoring information is displayed
(Figure 31).
Figure 31 – Cable Connections Thermal Monitoring Screen

For each Cable connection, there are four (4) lines:


— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature
algorithm result
Refer to Thermal Monitoring Screens on page 38 for
additional pre-alarm and alarm thresholds, status
indication, and bar graph information.
NOTE: If the alarm values exceed the threshold values,
contact your local Schneider Electric team for
assistance. Equipment aging can be accelerated under
these conditions.

QGH51397 © 2020 Schneider Electric All Rights Reserved 35


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Transformer Screen Menu


1. Click on the Cubicle in the Home screen to access the Transformer menu screen.
ENGLISH

RESULT: The Cubicle screen opens and allows access to the function lines
and details information (Figure 32).
Figure 32 – Transformer Screen Menu

Within the Transformer menu, there are three (3)


configured function lines:
— Tr. Dry Monitoring: Allows access to dry transformer
monitoring when a PT100 probe is configured
— Medium/Low Voltage: Allows access to the
Thermal monitoring information related to the MV
and LV part of the transformer
— Winding/Tapping Links: Allow access to the
Thermal monitoring information related to the
Winding and the Tapping Links
The status indication icon ! appears in yellow or
red at the beginning of the line where an alarm or
pre-alarm exists.

2. Click on the configured function line.


RESULT: More details about the selected function are displayed.
Thermal Monitoring The Thermal Monitoring Information of a Dry Transformer screen menu shows the
Information of a Dry thermal temperature of the transformer windings and the estimated age of the
Transformer Screen Menu transformer.
Based on standard IEC60076-12, the Substation Monitoring Device (SMD)
monitors the transformer windings temperatures and thermal class information to
determine the life duration (aging) of the transformer.
Click the Tr. Dry Monitoring line of the Transformer screen to view thermal
monitoring information of a dry transformer.
RESULT: A window appears displaying the winding temperatures, aging
information, thermal class, and alarm thresholds (Figure 33 on page 37).
The transformer thermal class within the configuration is used to define the alarm
thresholds for the hotspot temperature:
• Pre-alarm: Is the insulation system temperature
• Alarm: Is defined 10 °C (50 °F) below the maximum hotspot winding temperature

36 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

Figure 33 – Thermal Monitoring Information of a Dry Transformer Screen Menu

ENGLISH
— The hotspot winding temperature is shown in the
top half part of the screen. Displays:
— A numerical value
— A % Bar graph with color status:
(blue by default, yellow if pre-alarm,
or red if alarm)
— The three (3) winding temperature measurements
for three (3) phases are displayed in the bottom
left corner of the screen.
— The transformer thermal class and aging information
is displayed in the bottom right corner
of the screen.

Transformer Medium/Low The Medium/Low Voltage menu screen displays the thermal monitoring information
Voltage Screen Menu related to the temperature of the MV (upper bushing) and LV transformer connections.
Click on the Medium/Low Voltage line of the Transformer screen to view thermal
monitoring information related to the MV and LV connections.
RESULT: The MV and LV Connections thermal monitoring information
is displayed (Figure 34).
Figure 34 – Transformer Medium/Low Voltage Thermal Monitoring Screen

For each Transformer connection, there are four


(4) lines:
— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature
algorithm result
NOTE: The LV transformer has an additional Neutral
connection line.
NOTE: If the alarm values exceed the threshold values,
contact your local Schneider Electric team for
assistance. Aging of the transformer core can be
accelerated under these conditions.

Refer to Thermal Monitoring Screens on page 38 for


additional pre-alarm and alarm thresholds, status
indication, and bar graph information.

Transformer The Winding/Tapping Links screen displays the thermal monitoring information
Winding/Tapping Links related to the temperature of the Winding (lower bushing) and Tapping Links
Screen transformer connections.
Click on the Winding/Tapping Links line of the Transformer screen to view thermal
monitoring information related to the MV and LV connections.
RESULT: The Winding/Tapping Links thermal monitoring information is displayed
(Figure 35 on page 38).

QGH51397 © 2020 Schneider Electric All Rights Reserved 37


Substation Monitoring Device Section 7—Substation Monitoring System Device Usage

Figure 35 – Transformer Winding/Tapping Links Thermal Monitoring Screen


ENGLISH

For each Winding/Tapping Links connection, there are


four (4) lines:
— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature
algorithm result

Refer to Thermal Monitoring Screens on page 38 for


additional pre-alarm and alarm thresholds, status
indication, and bar graph information.

Thermal Monitoring Screens


Thermal Monitoring screens are available within various screens (Figures 36 and 37 on
page 39). For example, it can be accessed by:
• Clicking the Others button from the Home screen.
• Clicking the All functions menu from the Cubicle screen.
RESULT: The temperatures, alarms, and temperature thresholds are displayed
on the screen.
NOTE: The following thermal monitoring screen descriptions are not specific
for all Substation Monitoring Device (SMD) screens.
Example 1 displays the thermal temperatures for “Others” connections
(locations) other than cubicles if some are defined in the configuration.
Example 2 displays the thermal temperatures information for circuit breakers.

38 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 7—Substation Monitoring System Device Usage Substation Monitoring Device

The information related to a set of sensors is displayed Figure 36 – Example 1: Thermal Monitoring

ENGLISH
in half the screen. The monitoring information of two (2) Screen: Others Connections
connections can be displayed in the same screen.
For each connection, there are four (4) lines:
— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature algorithm
result
For each line:
— The measured or calculated value is displayed in
numeric value. When no measurement exists, the
text *** is displayed.
— The pre-alarm and alarm thresholds are displayed:
— If the standard algorithm is used, then the
thresholds are defined in configuration and
are constant.
— If the advanced algorithm is used, then the
thresholds are variable and are changing Figure 37 – Example 2: Thermal Monitoring
depending on the current flowing in the Screen: Circuit Breakers
conductor and the time constant defined in
the configuration.
— The status indication icon ! appears in yellow or
red at the left of the line when an alarm or pre-alarm
is active.
— A bar graph shows the temperature versus the
thresholds. Color changing indicates the status:
— Blue (default): Normal operation
— Yellow: Pre-alarm
— Red: Alarm
— Grey: The SMD does not receive any
measurement (sensor not communicating)

QGH51397 © 2020 Schneider Electric All Rights Reserved 39


Substation Monitoring Device Section 8—Troubleshooting and Support

Section 8— Troubleshooting and Support


ENGLISH

Main Processor Unit TM251 System Status LEDs


Table 8 describes the system status LEDs for the main processor unit TM251:
Table 8 – Main Processor Unit TM251 System Status LEDs

Label Function Type Color Status Description


On Indicates that power is applied
PWR Power Green
Off Indicates that power is removed
On Indicates that the controller is running a valid application
Flashing ,QGLFDWHVWKDWWKHFRQWUROOHUKDVDYDOLGDSSOLFDWLRQWKDWLV VWRSSHG
RUN Machine status Green
1 Flash Indicates that the controller has paused at BREAKPOINT
Off Indicates that the controller is not programmed
On Indicates that an operating system error has been detected
Fast flashing Indicates that the controller has detected an internal error
ERR Internal error Red
,QGLFDWHVHLWKHUWKDWDPLQRUHUURUKDVEHHQGHWHFWHGLI581 LV21RUWKDW
Slow flashing
QRDSSOLFDWLRQKDVEHHQGHWHFWHG
,QGLFDWHVGHYLFHHUURUVRQWKHVHULDOOLQH6'FDUG70EXV 70EXV
I/O I/O error Red On
(WKHUQHWSRUW V RU&$1RSHQSRUW
SD SD card access Green On Indicates that the SD card is being accessed
Indicates that the battery needs to be replaced
On Refer to document number HRB59604:
BAT Battery Red
https://www.schneider-electric.us/en/download/document/HRB59604/
Flashing Indicates that the battery charge is low
On ,QGLFDWHVWKDWWKH (WKHUQHWSRUWLVFRQQHFWHGDQGWKH,3 DGGUHVVLVGHILQHG
3 Flashes Indicates that the Ethernet port is not connected
ETH Ethernet port status Green 4 Flashes Indicates that the IP address is already in used
5 Flashes ,QGLFDWHVWKDWWKHPRGXOHLVZDLWLQJIRU%2273RU'+&3 VHTXHQFH
6 Flashes Indicates that the configured IP address is not valid
On Indicates the status of the serial line
SL Serial line Green
Off Indicates no serial communication
On Indicates that an error has been detected on the TM4 bus
TM4 Error on TM4 bus Red
Off Indicates that no error has been detected on the TM4 bus
On Indicates that the CANopen bus is operational
Off Indicates that the CANopen master is configured
CAN-R CANopen running status Green
Flashing Indicates that the CANopen bus is being initialized
1 Flash per second Indicates that the CANopen bus is stopped
On Indicates that the CANopen bus is stopped (BUS OFF)
Off Indicates no CANopen detected error
Flashing Indicates that the CANopen bus is not valid
CAN-E CANopen error Red ,QGLFDWHVWKDWWKHFRQWUROOHUKDVGHWHFWHGWKDWWKHPD[LPXP QXPEHURI
1 Flash per second
HUURUIUDPHVKDVEHHQUHDFKHGRUH[FHHGHG
,QGLFDWHVWKDWWKHFRQWUROOHUKDVGHWHFWHGHLWKHUD1RGH *XDUGLQJRUD
2 Flashes per second
+HDUWEHDWHYHQW

40 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 8—Troubleshooting and Support Substation Monitoring Device

Reference Publications

ENGLISH
Schneider Electric publications are available through your local representative.
Refer to Schneider Electric support at http://www.schneider-electric.com/CCC to
locate contacts for your region. Also, refer to http://www.schneider-electric.com to
download technical publications and other technical information.
For information about obtaining NEMA documents, write to:
National Electrical Manufacturers Association (NEMA)
Attention: Customer Service
1300 North 17th Street
Suite 1847
Rosslyn, VA 22209
Table 9 – NEMA Reference Publications

Publication Publication Number


General Instructions for Proper Installation, Operation, and
NEMA Publication PB2.1
Maintenance of Switchboards Rated 600 V or Less
Application Guide for Ground-Fault Protective Devices for Equipment NEMA Publication PB2.2
Circuit Breakers NEMA Publication AB-4
Enclosed and Miscellaneous Distribution Switches NEMA Publication KS-1
Electrical Equipment Maintenance NFPA 70B-1999

QGH51397 © 2020 Schneider Electric All Rights Reserved 41


Substation Monitoring Device Section 8—Troubleshooting and Support

Maintenance Log
ENGLISH

Table 10 – Maintenance Log Description

Date Initials Maintenance Performed/Description

42 © 2020 Schneider Electric All Rights Reserved QGH51397


Section 8—Troubleshooting and Support Substation Monitoring Device

Maintenance Log Description

ENGLISH
Date Initials Maintenance Performed/Description

QGH51397 © 2020 Schneider Electric All Rights Reserved 43


ENGLISH

Schneider Electric USA, Inc.


800 Federal Street
Andover, MA 01810 USA
888-778-2733
www.schneider-electric.us

http://www.schneider-electric.com/CCC

Standards, specifications, and designs may change, so please ask for


confirmation that the information in this publication is current.

© 2020 – Schneider Electric. All Rights Reserved.

QGH51397, 01/2020

You might also like