Substation Monitoring Device: Instruction Bulletin
Substation Monitoring Device: Instruction Bulletin
Substation Monitoring Device: Instruction Bulletin
ENGLISH
Instruction Bulletin
This instruction bulletin describes the monitoring, tracking, and measuring functions of the
Substation Monitoring Device.
QGH51397
Release date: 01/2020
Retain for future use.
www.schneider-electric.com
Legal Information
ENGLISH
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
guide or its content, except for a non-exclusive and personal license to consult it on
an "as is" basis. Schneider Electric products and equipment should be installed,
operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed
by Schneider Electric and its subsidiaries for any errors or omissions in the
informational content of this material or consequences arising out of or resulting
from the use of the information contained herein.
Schneider Electric, Magelis, Modbus, and Square D are trademarks and the
property of Schneider Electric SE, its subsidiaries, and affiliated companies. All
other trademarks are the property of their respective owners.
Table of Contents Substation Monitoring Device
ENGLISH
............................................................................................................ 8
List of Figures
ENGLISH
Figure 1 – Substation Monitoring Device (SMD) Architecture ........................... 12
Figure 2 – Alarm or Pre-alarm Status Indication Icon ........................................ 14
Figure 3 – Magelis Local HMI Configuration Screen ......................................... 15
Figure 4 – HMI Screen Descriptions .................................................................. 16
Figure 5 – HMI Screens and Organization ......................................................... 17
Figure 6 – Home Screen and Navigation Bar .................................................... 18
Figure 7 – Example: Cubicle without a Transformer .......................................... 19
Figure 8 – Example: Cubicle with a Transformer ............................................... 19
Figure 9 – Notifications Screen and Icon ........................................................... 20
Figure 10 – Substation Environment Screen ....................................................... 21
Figure 11 – Settings Screen Menu ...................................................................... 21
Figure 12 – System Setup Screen Menu ............................................................. 22
Figure 13 – Network Screen Menu ...................................................................... 22
Figure 14 – ZigBee Concentrator Screen, Sensor Configurations/Connections,
and Status Icons ............................................................................... 23
Figure 15 – Sensor Status Screen ....................................................................... 23
Figure 16 – Date & Time Configuration Screen ................................................... 25
Figure 17 – Temperature Unit Configuration Screen ........................................... 26
Figure 18 – Language Configuration Screen ....................................................... 26
Figure 19 – Cubicle Screen Menu ....................................................................... 27
Figure 20 – Environment Screen Functions Page 1: Measurements .......................28
Figure 21 – Environment Screen Functions Page 2: Environmental
Severity History ................................................................................. 28
Figure 22 – Environmental Severity: History Reset ............................................. 30
Figure 23 – Environment Inspection Screen ........................................................ 30
Figure 24 – Busbar Thermal Monitoring Screen .................................................. 31
Figure 25 – Circuit Breaker Screen Functions Page 1: Thermal
Monitoring Screen ............................................................................. 32
Figure 26 – Circuit Breaker Screen Functions Page 2: Monitoring and Control .. 32
Figure 27 – Circuit Breaker Screen Navigation Bar ............................................. 33
Figure 28 – Circuit Breaker Maintenance Screen ................................................ 33
Figure 29 – Circuit Breaker Control Procedure .................................................... 34
Figure 30 – Circuit Breaker Control Screens ....................................................... 35
Figure 31 – Cable Connections Thermal Monitoring Screen ............................... 35
Figure 32 – Transformer Screen Menu ................................................................ 36
Figure 33 – Thermal Monitoring Information of a Dry Transformer
Screen Menu .................................................................................... 37
Figure 34 – Transformer Medium/Low Voltage Thermal Monitoring Screen ....... 37
Figure 35 – Transformer Winding/Tapping Links Thermal Monitoring Screen .... 38
Figure 36 – Example 1: Thermal Monitoring Screen: Others Connections .......... 39
Figure 37 – Example 2: Thermal Monitoring Screen: Circuit Breakers ................ 39
List of Tables
ENGLISH
ENGLISH
Important Information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service, or maintain it. The following
special messages may appear throughout this bulletin or on the equipment to warn
of hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that
an electrical hazard exists which will result in personal injury if the instructions are
not followed.
This is the safety alert symbol. It is used to alert you to personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol is not used with this signal word.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Refer to Table 1 for a list of acronyms used within this instruction bulletin.
Table 1 – List of Acronyms
Section 3— Introduction
ENGLISH
This document provides monitoring instructions using the Substation Monitoring
Device (SMD) from Schneider Electric.
The signaling information provided by the monitoring system described in this
manual is intended to be informational only. The SMD monitors temperature and
humidity conditions in specific locations within the switchgear and provides
indication signals when thresholds are surpassed. When temperature and humidity
conditions are outside of the pre-established parameters, consider taking action to
assess the equipment condition. Contact your local Schneider Electric
representative or Field Services team to obtain the appropriate information.
Substation Alarming
The SMD collects all alarming indications available in the substation using digital
input (e.g., blown fuse or Watchdog relay) information. The SMD also collects the
information using Modbus protocol over Ethernet or Serial Line (SL)
communication.The collected alarms are then presented on the Human Machine
Interface (HMI) locally and made available remotely.
Local and Remote Monitoring
The SMD can be used for local and/or remote monitoring.
Local monitoring includes a:
• Single Line Diagram (SLD) representation of the lineup with temperature
values and logs of alarms on a color display:
— If no pre-alarm or alarm, the general status is operating normally (green).
— If at least one pre-alarm is activated, but no alarm, the general status is
pre-alarm (yellow).
— If at least one alarm is activated, the general status is alarm (red).
• Summary of global status of the substation available on digital contact outputs
that can be used for indicating through lights (typically green, yellow, and red) or
any equipment accepting contact output:
— Digital Contact Output 1: Closed when global status is green
— Digital Contact Output 2: Closed when global status is yellow
— Digital Contact Output 3: Closed when global status is red
— Digital Contact Output 4: Always Open
WARNING
LOSS OF SYSTEM CONTROL PATHS
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Example: Emergency Stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of
anticipated transmission delays or failure of the link.
Failure to follow these instructions can result in death or serious injury.
The SMD can be used as remote open or closing means for only circuit breaker or
load break switch operation.
The nearby control is limited to only authorized users and is restricted by password
access. In addition:
• The local HMI allows for the opening and closing of the switchgear through the
SMD only when connected to the protective relay (or other Intelligent Electronic
Device (IED)) through Modbus. The switchgear’s position is available in the SLD.
• The nearby HMI allows switchgear operation through a mobile device (e.g.,
tablet or smart phone) when connected to the SMD.
NOTE: The Magelis™ HMI is required to use the nearby HMI.
Thermal Monitoring
Thermal monitoring of cable, busbar, circuit breaker or withdrawable connections in
cubicle and transformer connections is achieved using TH110 wireless sensors from
Schneider Electric and ZigBee™ concentrators. One of the major causes of medium
voltage equipment damage is aging electrical connections. Thermal monitoring
tracks the temperature of connections and helps determine equipment aging.
Different algorithms apply to temperature measurements that result in indication
alarms. For example, in:
• Standard absolute monitoring: An alarm is indicated when the temperature
exceeds a fixed threshold.
• Advanced absolute monitoring: An alarm is indicated when the temperature
exceeds the threshold and adapts continuously to the load current of the feeder.
• Discrepancy monitoring: An alarm is indicated when the differences between
phase temperatures exceed a fixed threshold.
Environmental Monitoring
Environmental monitoring is achieved using CL110 wireless sensors from
Schneider Electric and ZigBee concentrators that measure humidity and
temperature inside cubicles and determine the severity of condition based on
frequency of condensation and pollution. This severity indicator is used to calculate
when the next inspection should be planned. An alarm can be set on temperature
or humidity conditions.
ENGLISH
Dry Transformer Monitoring
Dry transformers are monitored using PT100 wired sensors from Schneider Electric
that are installed into windings.The transformer’s aging is determined as stated in
Standard IEC60076-12. An alarm also can be set to indicate hotspot temperatures.
ENGLISH
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E
or CSA Z462.
• This equipment must be installed and serviced only by qualified personnel.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric
power. Assume all circuits are live until they are de-energized, tested, and tagged. Pay particular attention to the
design of the power system. Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm power is off.
• Practice lock-out/tag-out procedures according to OSHA requirements.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function properly.
Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as
damage to equipment or other property.
• Operate the equipment, such as the tablet that supports the SMD, within the specified electrical and
environmental limits.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
• Change default passwords to help prevent unauthorized access to device settings and information.
• Disable unused ports/services and default accounts, where possible, to minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as firewalls, network segmentation, and
network intrusion detection and protection).
• Use cyber security best practices (for example: least privilege, separation of duties) to help prevent unauthorized
exposure, loss, modification of data and logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The main processor unit TM251 and related accessory components are described
in their specific product data sheets or manuals.
Local indicating information includes, but is not limited to the main processor unit,
digital and analog inputs/outputs (I/Os), and Ethernet switch.
All SMD information is stored in the TM251, but the persistent data related to the
thermal monitoring and all applicative functions are stored in non-volatile memory.
They do not rely on the battery.
ENGLISH
The buzzer can be disabled and the backlight can be configured in the Magelis
configuration screen (Figure 3).
1. Press two (2) opposite corners of the screen quickly and successively.
RESULT: The Magelis configuration screen opens.
2. Click the Offline tab.
a. Click the Buzzer box to enable or disable the buzzer.
b. Click the Backlight box to configure the backlight.
Active areas include buttons Navigation through the SMD HMI screens is achieved by touching active areas on
and status indication icons ! the screen (Figure 4).
• Green or Blue: Indicates The HMI main screen is divided into different sections. The upper green area
normal conditions contains command buttons and general status indications (icons).
• Yellow: Indicates a The white background is the main part of the screen and displays the function
pre-alarm information. This area is organized into different screens that display general
• Red: Indicates an alarm and/or detailed information.
(A temperature or
humidity threshold has
been exceeded.)
4 Notifications Icon:
Click to see the list of active and inactive alarms,
and pre-alarms (Figure 9 on page 20).
6 Settings Icon:
Click the icon to configure the SMD or check the
System Setup (Figure 12 on page 22).
ENGLISH
The HMI screens consist of the following organization levels (Figure 5). Refer to the
table for additional information regarding the screens listed below.
Home Screen Page 18 Inspection Date Page 30
Notifications Screen Page 20 Busbar Screen Page 31
Substation Environment Screen Page 21 Circuit Breaker Screen/Load Break Switch Screen Page 31
Settings Menu Screen Page 21 Circuit Breaker Mechanism Aging Evaluation: Number of Operations Page 33
System Setup Screen Menu Page 22 Circuit Breaker Mechanism Aging Evaluation: Operating and Charging Times Page 33
Network Screen Menu Page 22 Circuit Breaker Mechanism Aging Evaluation: Breaking Current Page 34
ZigBee Concentrator Screen/Sensor Status Screen Page 23 Circuit Breaker Control Page 34
Date & Time Configuration Screen Page 25 Cable Connections Screen Page 35
Temperature Unit Configuration Screen Page 26 Transformer Screen Menu Page 36
Language Configuration Screen Page 26 Thermal Monitoring Information of a Dry Transformer Screen Menu Page 36
Cubicle Screen Menu Page 27 Transformer Medium/Low Voltage Screen Menu Page 37
Environment Screen Page 28 Transformer Winding/Tapping Links Screen Page 37
Severity Indicator Page 29 Thermal Monitoring Screens Page 38
Degree of Severity History and Reset Page 30
Home Screen
ENGLISH
The Home screen is the default screen after start-up of the product.
1. Click the Home icon from any screen.
RESULT: A single line diagram (SLD) with all status information summarized is
displayed within the Home screen (Figure 6).
The SLD is split into four (4) screens with four (4) cubicles each. Refer to the area
at the bottom of the screen to view the number of available screens (Figure 6).
2. Click the Others button (Figure 6).
RESULT: The screen opens to display the temperature at locations “Other”
than cubicles if some are defined in the configuration.
Only two (2) screens, C1–C4 and C5–C8, are available to navigate when six (6)
cubicles are defined in the SMD configuration (Figure 6). If 16 cubicles were
defined, then buttons C9–C12 and C13–C16 would appear, too.
Figure 6 – Home Screen and Navigation Bar
The SLD shows up to four (4) cubicles in each Home screen page.
3. Click on the cubicle area (Figure 6).
RESULT: Detail information for each cubicle is displayed (Figure 7 on page 19). In
a transformer cubicle, a second temperature is displayed (Figure 8 on page 19).
NOTE: The SLD does not show sections—only cubicles. Sections with more
than one circuit breaker or switch are represented by showing two (2) cubicles.
Figure 7 – Example: Cubicle without a Transformer Figure 8 – Example: Cubicle with a Transformer
ENGLISH
Displays: Displays:
— The cubicle reference C1, C2, etc., — The highest temperature from different phases
— The status indication icon ! in yellow or red near related to transformer monitoring
the reference if an alarm or pre-alarm exists in — The status indication icon ! in yellow or red in
this cubicle related to the application (thermal, case of problem with a sensor
environmental, or circuit breaker monitoring)
— The current measurement in the cubicle,
if configured
— The switchgear position, if configured
— The connection temperature with:
— Only the highest temperature from different
phases and from all positions (cable, circuit
breaker, busbar, transformer) is displayed
— The status indication icon ! in yellow or red
in case of problem with a sensor
The following rules are applied when digital inputs indicate the circuit breaker
position (Table 2):
Table 2 – Circuit Breaker Positions Indicated from Digital Input Information
NOTE: A dashed line will appear when a circuit breaker position is unknown or
when a protective relay (or other Intelligent Electronic Device (IED)) issue exists.
The circuit breaker can be either open or closed when the status is unknown.
Notifications Screen
ENGLISH
The Notifications screen records and displays status changes related to alarms or
pre-alarms within the Substation Monitoring Device (SMD).
Status indications are shown as notification icons at the beginning of the line where
alarms or pre-alarms are active or inactive. The alarm or pre-alarm time stamp is
shown on the second line of the status change (Figure 9).
1. Click on the status indication icon ! in the header from any Substation
Monitoring Device (SMD) screen.
RESULT: A Notifications screen appears with SMD status information
displayed and time stamped.
The Notifications screen shows five (5) events per page. Up to 10 pages of events
are available to view.
2. Click the up and down arrows at the bottom of the screen to navigate to the
previous and next event pages.
ENGLISH
The Environment screen shows lines with temperature and humidity values.
Click on the Temperature or Humidity value in the header screen (Figure 10).
RESULT: The substation room’s Ambient temperature and Humidity
are displayed.
Figure 10 – Substation Environment Screen
RESULT: The System Setup screen opens and allows access to the
communication status between the PLC, ZigBee concentrators, and sensors
(Figure 12).
Figure 12 – System Setup Screen Menu
Network Screen Menu The Network screen shows the Modbus configuration for the communication
between PLC and ZigBee concentrators.
Click on the Network menu line of the System Setup screen (Figure 12).
RESULT: The Network screen menu opens and displays the communication
settings between the PLC and ZigBee concentrators (Figure 13).
Figure 13 – Network Screen Menu
ZigBee Concentrator The ZigBee Concentrator screen shows the status of up to 60 sensors that can be
Screen/Sensor Status connected to each ZigBee concentrator.
ENGLISH
Screen
1. Click on one (1) of the three (3) concentrator lines of the System Setup screen
(Figure 12 on page 22).
RESULT: The ZigBee Concentrator screen displays the status icons for the
sensors (Figure 14).
Figure 14 – ZigBee Concentrator Screen, Sensor Configurations/Connections, and Status Icons
Sensor is inoperable:
Sensor is paired with the ZigBee concentrator and
is defined in the SMD configuration, but the sensor
does not communicate with the ZigBee concentrator
2. Click on one of the sensors of the ZigBee Concentrator screen (Figure 14).
RESULT: The Sensor Status screen opens and displays the detailed
information and measured values for the sensors (Figure 15).
Figure 15 – Sensor Status Screen
Sensor is not paired to the ZigBee Sensor or the ZigBee concentrator is operable, but pairing is
concentrator, but is defined in the not complete:
SMD configuration Possible cause: Commissioning is not finished.
Sensor is inoperable: Yellow indicates that the sensor is not available either
Sensor is paired with the ZigBee because the:
concentrator and is defined in the — Current flowing is null or too low to energize the sensor, or
SMD configuration, but the sensor — Sensor isn’t communicating or sensor type is unexpected.
does not communicate with the
These indications may result in a loss of signal reception or
concentrator
communication.
ENGLISH
(SMD) date and time values in a non-volatile memory using the battery.
NOTE: Refer to Main Processor Unit TM251 on page 14 for battery
replacement information.
1. Click on Date & time menu line of the Settings screen.
RESULT: The Date & time screen opens and allows access to set the date and
time (Figure 16).
NOTE: The Substation Monitoring Device (SMD) is operable, even when the
date and time stamps are inaccurate. However, the date and time should be set
correctly to receive accurate operation and alarming information from the
environmental monitoring function. Refer to Environmental Monitoring on
page 10 and Figure 10 on page 21.
2. Click on the down arrows to modify the date, time, and format values.
3. Check that the values are correct and click the Update button to validate the
Year, Month, Day, Hour, Minute, or AM/PM values.
RESULT: The screen displays a message communicating that the operation is
in progress. The HMI displays the new date and time when the PLC update
is complete.
Figure 16 – Date & Time Configuration Screen
The Date & time screen is split into three (3) parts:
— Date:
New value in black and current date in gray
(second line)
— Time:
New value in black and current time in gray
(second line)
— Update button:
Button used to apply changes
ENGLISH
1. Click on the cubicle in the Home screen to show the Cubicle menu (Figure 6 on
page 18).
RESULT: The Cubicle screen opens and allows access to the function lines
and details information (Figure 19).
Figure 19 – Cubicle Screen Menu
1 Function Description 2 1 4 3
Environment Screen
The Environment screen is split into two (2) function screens that show:
ENGLISH
Severity Indicator Based on standard IEC 62271-304, the SMD indicates four (4) severity levels of
equipment aging that is determined by the cumulative days the equipment spends
ENGLISH
in condensation and pollution conditions.
The indicators are shown in degrees and are as follows (Table 5):
• Degree 0 (indicated in green)
• Degree 1 (indicated in yellow)
• Degree 2 (indicated in orange)
• Degree 3 (indicated in red)
These indicators are used to determine an acceleration factor and when timely
addressed, can lead to a reduction in maintenance time. The degree of severity of
service condition is determined daily based on the measured condensation and
pollution level declared (Figure 20 on page 28 and Table 5).
NOTE: Follow the switchgear maintenance plan that is specific to your
equipment. Contact your local Schneider Electric representative or Field
Services team to obtain the appropriate information.
Table 5 – Environmental Monitoring: Degree of Severity
The pollution levels defined in the configuration are: — Pollution Level Low
Degree of Severity History The Substation Monitoring Device (SMD) cumulates the days for each severity
and Reset level and represents them in a bar graph (Figure 21 on page 28).
ENGLISH
Click the Reset button at the bottom left of the screen to reset the graph and restart
the calculation (Figure 21 on page 28).
RESULT: A pop-up window appears to confirm the operation (Figure 22).
Figure 22 – Environmental Severity: History Reset
Inspection Date The date of the last inspection can be defined in the configuration during
installation of the SMD. The number of cumulated days of each degree of severity
is used to calculate an aging factor (Figure 23).
Click on the Inspection button in the Environment screen to declare a performed
inspection (Figure 21 on page 28).
RESULT: The Environmental Inspection page opens and the algorithm is reset
to restart the calculation of the next inspection date (Figure 23).
Figure 23 – Environment Inspection Screen
Busbar Screen
The Busbar screen displays the information related to the thermal monitoring
ENGLISH
temperature of the busbar connections.
Click on the Busbar line of the Cubicle screen to view thermal monitoring
information related to the busbar.
RESULT: The Busbar thermal monitoring information is displayed (Figure 24).
Figure 24 – Busbar Thermal Monitoring Screen
WARNING
LOSS OF SYSTEM CONTROL PATHS
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Example: Emergency Stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of
anticipated transmission delays or failure of the link.
Failure to follow these instructions can result in death or serious injury.
The Circuit Breaker screen is split into two (2) function screens that show:
— The information related to the circuit breaker thermal monitoring (Figure 25
on page 32).
— The information related to circuit breaker monitoring and control (Figure 26
on page 32).
Click on the Circuit Breaker line of the Cubicle screen to view the Circuit Breaker
temperature and monitoring.
RESULT: The functions (thermal monitoring, circuit breaker monitoring, and
circuit breaker Control button) are displayed on the screen (Figures 25 and 26
on page 32).
Circuit Breaker Screen Functions Page 1 allows the user Figure 25 – Circuit Breaker Screen Functions
ENGLISH
access to screens that are related to four (4) functions: Page 1: Thermal Monitoring Screen
— Thermal monitoring (Page 1)
— Circuit Breaker monitoring (Page 2)
— Circuit Breaker control (Control button)
— Circuit Breaker maintenance (Maintenance button)
When entering the Circuit Breaker screen, the
Thermal Monitoring screen displays temperature
information for the top and bottom of the circuit breaker
(Figure 25).
For each Circuit Breaker connection, there are four
(4) lines:
— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature
algorithm result
Refer to Thermal Monitoring Screens on page 38 for
additional pre-alarm and alarm thresholds, status
indication, and bar graph information.
The bar at the bottom of the Circuit Breaker screen (Figure 27) allows the user to
navigate between Page 1 and Page 2 details, as well as to access Control
ENGLISH
(Figure 27) and Maintenance (Figure 28) functions within the Substation Monitoring
Device (SMD).
Figure 27 – Circuit Breaker Screen Navigation Bar Figure 28 – Circuit Breaker Maintenance Screen
— Click the down arrow to go to Page 2 Circuit Click the Maintenance button to view the date of
Breaker monitoring. the last maintenance and to declare a maintenance
— Click the up arrow to go to Page 1 Thermal has been executed.
monitoring.
— Click on the Control button to operate the Circuit
Breaker from Pages 1 and 2.
— RESULT: The origin page is displayed at the
end of the control operation.
Circuit Breaker Mechanism Mechanism aging is linked directly to the Number of operations realized and
Aging Evaluation: Number correlated to the maximum Number of operations specified for the circuit breaker
of Operations (Figure 26 on page 32).
A % bar graph shows the current value compared to the maximum value specified
for the circuit breaker (Table 6).
Table 6 – Circuit Breaker Mechanism Number of Operations Value and
Statuses
Circuit Breaker Mechanism The first operating and charging times that the SMD observes are stored as
Aging Evaluation: Operating reference times (Figure 26 on page 32). The SMD indicates an alarm if the
and Charging Times measured time is too long compared to the reference times based on the following
time increases:
• Operating time is not normal if it increases by 30 ms compared to the
reference time.
• Charging time is not normal if it increases by 3 s compared to the reference time.
Circuit Breaker Mechanism The algorithm is based on the wear of the electrical contact and is measured using the
Aging Evaluation: Breaking cumulated Breaking Current (kA)² stored by protection relay (Figure 26 on page 32).
ENGLISH
Current
A % bar graph shows the electrical aging in % bar graph = current electrical wear /
maximum permissible wear (Table 7).
Table 7 – Circuit Breaker Mechanism Breaking Current Value and Statuses
WARNING
LOSS OF SYSTEM CONTROL PATHS
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Example: Emergency Stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of
anticipated transmission delays or failure of the link.
Failure to follow these instructions can result in death or serious injury.
1. Click the Control button to operate the circuit breaker (Figure 27 on page 33).
2. Follow the Circuit Breaker procedure (Figure 29).
Figure 29 – Circuit Breaker Control Procedure
ENGLISH
Cable Connections Screen
The Cable Connections screen displays the information related to the thermal
monitoring temperature of the cable connections.
Click on the Cable Connections line of the Cubicle screen to view thermal
monitoring information related to the connections for Cables 1 and 2.
RESULT: The Cable Connections thermal monitoring information is displayed
(Figure 31).
Figure 31 – Cable Connections Thermal Monitoring Screen
RESULT: The Cubicle screen opens and allows access to the function lines
and details information (Figure 32).
Figure 32 – Transformer Screen Menu
ENGLISH
— The hotspot winding temperature is shown in the
top half part of the screen. Displays:
— A numerical value
— A % Bar graph with color status:
(blue by default, yellow if pre-alarm,
or red if alarm)
— The three (3) winding temperature measurements
for three (3) phases are displayed in the bottom
left corner of the screen.
— The transformer thermal class and aging information
is displayed in the bottom right corner
of the screen.
Transformer Medium/Low The Medium/Low Voltage menu screen displays the thermal monitoring information
Voltage Screen Menu related to the temperature of the MV (upper bushing) and LV transformer connections.
Click on the Medium/Low Voltage line of the Transformer screen to view thermal
monitoring information related to the MV and LV connections.
RESULT: The MV and LV Connections thermal monitoring information
is displayed (Figure 34).
Figure 34 – Transformer Medium/Low Voltage Thermal Monitoring Screen
Transformer The Winding/Tapping Links screen displays the thermal monitoring information
Winding/Tapping Links related to the temperature of the Winding (lower bushing) and Tapping Links
Screen transformer connections.
Click on the Winding/Tapping Links line of the Transformer screen to view thermal
monitoring information related to the MV and LV connections.
RESULT: The Winding/Tapping Links thermal monitoring information is displayed
(Figure 35 on page 38).
The information related to a set of sensors is displayed Figure 36 – Example 1: Thermal Monitoring
ENGLISH
in half the screen. The monitoring information of two (2) Screen: Others Connections
connections can be displayed in the same screen.
For each connection, there are four (4) lines:
— One (1) for each phase (shown on three (3)
separate lines)
— One (1) for the discrepancy temperature algorithm
result
For each line:
— The measured or calculated value is displayed in
numeric value. When no measurement exists, the
text *** is displayed.
— The pre-alarm and alarm thresholds are displayed:
— If the standard algorithm is used, then the
thresholds are defined in configuration and
are constant.
— If the advanced algorithm is used, then the
thresholds are variable and are changing Figure 37 – Example 2: Thermal Monitoring
depending on the current flowing in the Screen: Circuit Breakers
conductor and the time constant defined in
the configuration.
— The status indication icon ! appears in yellow or
red at the left of the line when an alarm or pre-alarm
is active.
— A bar graph shows the temperature versus the
thresholds. Color changing indicates the status:
— Blue (default): Normal operation
— Yellow: Pre-alarm
— Red: Alarm
— Grey: The SMD does not receive any
measurement (sensor not communicating)
Reference Publications
ENGLISH
Schneider Electric publications are available through your local representative.
Refer to Schneider Electric support at http://www.schneider-electric.com/CCC to
locate contacts for your region. Also, refer to http://www.schneider-electric.com to
download technical publications and other technical information.
For information about obtaining NEMA documents, write to:
National Electrical Manufacturers Association (NEMA)
Attention: Customer Service
1300 North 17th Street
Suite 1847
Rosslyn, VA 22209
Table 9 – NEMA Reference Publications
Maintenance Log
ENGLISH
ENGLISH
Date Initials Maintenance Performed/Description
http://www.schneider-electric.com/CCC
QGH51397, 01/2020