Research On Protection Measure For Very Fast Transient Over-Voltage of GIS
Research On Protection Measure For Very Fast Transient Over-Voltage of GIS
Research On Protection Measure For Very Fast Transient Over-Voltage of GIS
AbstractüBased on Tian huangping GIS Substation, very fast Storage Power Station[4]. Fast operating disconnector
transient over-voltage caused by disconnecting switch switches are usually used to reduce time of the breakdown,
operation of GIS is simulated and calculated in this paper with however, it can not eliminate the harm of the VFTO. Several
ATP-EMTP program. The effect of protection measures on inhibition methods are simulated in this article, which can
equipments is compared and analyzed, such as adding opening provide the new reference for the protection of VFTO.
and closing resistor, MOA, R-C absorber, and Ferrite Rings.
II. THE MODEL BUILDING AND PARAMETERS SELECTION
Also the measures are analyzed with considering the actual
situation, which can provide reference for the implementation This paper selected the Tian Huangping pumped storage
of the practical project. power station to build the model. The equivalent wiring
Key words: ATP-EMTP; VFTO; protection measures diagram is showed in Fig.1. Six pump turbines generating
sets which capacities are 300MW have been erected in Tian
I. INTRODUCTION Huangping pumped storage power station. It takes on the
Gas Insulated Substations have found a broad range of function of peak shaving, off-peak filling, phase modulating,
applications in power systems because of their high frequency modulating, emergency reserving, and so on. Thus
reliability, easy maintenance, small ground space it makes conversion operations much frequently. Since
requirements etc. The study shows that operation of power station ran in September 1998, discharge counters of
disconnector switches and breakers can cause very fast MOA unit 1 and unit 2 in 500kV GIS underground acted
transient overvoltages (VFTO), tip of which is very steep frequently owing to operation, especially opening and
[1]
accompanied with high frequency oscillation .VFTO not closing operation of DS. To early July 2000, they have acted
only influent the operating reliability of GIS, but also causes 189 and 100 phase times each and it also happened
great threat to the insulation of the high-voltage equipment, insulation breakdown of primary transformer unit.
especially to windings of the transformer, its reasons can be
concluded to two aspects[3]:1)the instant of contacts
breakdown can generate VFTO, whose tip is very steep,
which make the voltage distribution on the windings uneven;
2) when the frequency of the oscillating harmonic wave is
matched to the natural frequency of the equipment in the
VFTO, harmonic overvoltage is caused and its amplitude is
very high, which can damage the insulation of the
equipment. The failure accident of transformer has occurred
Figure 1 Equivalent circuit diagram of Tian huang ping GIS Substation
in Bay Nuclear Power Station and Tian Huangping Pumped
1.4
Figure 3 The waveform of VFTO after installed resistor
1.2
8
x 10
1.0
16
0.8
14
12 0.6
Amplitude
10 0.4 *10-6
0 5 10 15 20 25 30
8
6
Figure 5 The waveform of VFTO installed arrester
4
Amplitude
of injury to insulation, the injury accumulated to a certain 10
1.2
inhibiting VFTO. However, this method is not applied in the
actual project. Ferrite ring is modeled as resistor and
1.1
inductance, when the equivalent resistor of the ferrite ring is
1.0
equal to the surge impedance of GIS bus bar and the
0.9 equivalent inductance is 0.02mH, inhibition of the VFTO is
0.8 the largest[7]. This article after adding ferrite ring, VFTO
0.7 *10-6 waveform of the main transformer is showed in Figure 8.
0.0 5.8 11.6 17.4 23.2 29.0 The maximal over-voltage is 1.06pu, which reduce 33.75
Figure 6 The VFTO waveform of transformer B2 installed R-C filter percent than taking no measure and its steepness has also
been reduced.
1.10 to reduce the harmful effects of the VFTO. The equipment
which has windings should consider the ability of bearing
1.01
chopped wave in design, and strengthen the insulation.
0.92
REFERENCE
0.83 [1] QIU Yuchang, GIS Device and Its insulation Technology, Beijing
China: Water and Hydropower Publishiong House, 1994.
0.74 [2] Fujimoto N, “Mechanism and Analysis of Short Raise-time GIS
Transient,” ICGRE Symposium,1987, pp. 5-7.
0.65 *10-6
[3] Popov M, Vander Sluis L, and Paap GC, “Computation of Very Fast
0 5 10 15 20 25 30 Transient Overvoltage in Transformer wingrings,” IEEE
Transactionson Power Delivery, vol. 18, pp.1268-1274. April 2003.
[4] YANG Linghui and ZHANG Jiamin, “Research on transient
over-voltage during operation of 500kV GIS disconnecting switch,”
Figure 8 The waveform of VFTO installed ferrite rings. East China Electric Power, vol.32, pp.38-41. Jan 2004.
[5] P.I.Fergestad and T.H.Henriksen, “Transient Oscillations in
Through the test, we find that the saturation characteristic Multiwinding Transformers,” IEEE Tr., pp. 89-93, vol.2 1974.
of the magnetic ring material have a great impact on VFTO, [6] GAN Xianggen, “Characterstic Parameter Analysis on Suppressing
VFTO in GIS by Ferrite,” High Voltage Engineering, China, vol. 30,
the remanence also has a certain impact[8]. However, this pp. 24-26.sep 2004.
measure would not increase the complexity of the structure [7] GIN Ligun and LIU Weidong, “Research on Suppressing VFTO in
GIS by Ferrite Ring,” High Voltage Engineering, China, vol. 28, pp.
of the GIS and it can play a role in the protection of GIS 1-3. Jul 2002.
equipment inside the bus bar. The protection range is bigger [8] XIANG Zutao and LIU Weidong, “High Voltage Simulation Tests of
Suppressing VFTO in GIS by Magnetic Rings,” Transactions of
than R-C filter. China Electrotechnical Society, China , vol. 19, pp. 1-3. Jul 2004.