Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

QUICK SELECTION GUIDE (SI Units) Final

Download as pdf or txt
Download as pdf or txt
You are on page 1of 74
At a glance
Powered by AI
The document provides an overview of Petra's product range and quality standards.

Petra offers a wide range of HVAC equipment including chillers, air handlers, package units, fan coils, condensing units, computer room units, and mini split units.

Petra adheres to ISO 9001 and ISO 14001 quality standards. Their products are CE marked, UL and ETL listed and certified in compliance with AHRI standards.

2 Introduction

4 Product Range

Products
9 Chillers
10 • Air Cooled Water Chiller with Screw Compressor (APSa)
12 • Air Cooled High Efciency Water Chiller with Screw Compressor (APSaH)
13 • Air Cooled Smart Chiller with Scroll Compressor (PSC4)
14 • Air Cooled Smart Chiller with Scroll Compressor (PSCc)
16 • Air Cooled High Efciency Smart Chiller with Scroll Compressor (PSC4H)
18 • Water Cooled Water Chiller with Screw Compressor (WPSa)
20 • Air Cooled Residential Chiller with Scroll Compressor (RWC4)
22 • Air Cooled Residential Chiller with Scroll Compressor (RWCc)

25 Package Units
26 • Air Cooled Package Unit with Scroll Compressor (PPH4)
28 • Air Cooled Package Unit with Scroll Compressor (PPHc)
30 • Air Cooled Package Unit with Scroll Compressor (PPHa)
31 • Air Cooled High Efciency Package Unit with Scroll Compressor (PPH4H)
32 • Air Cooled Wall Mounted Package Unit (PWM)
32 • Explosion Proof Wall Air Cooled Wall Mounted Package Unit (PWMex)
33 • Water Source Package Unit with Scroll Compressor (PWSP)

35 Air Handlers
36 • Air Handling Units (PAH)
• Comfort Maker (CM)
Contents
38

41 Fan Coils
42 • Fan Coil Unit for Low Static Pressure (RAC)
44 • Fan Coil Unit for Medium Static Pressure (DC)
46 • Chilled Water Decorative Wall Mounted Fan Coil Unit (PWC)
47 • Chilled Water Decorative Cassette Type Fan Coil Unit (PCC)

49 Condensing Units
50 • Air Cooled Condensing Unit with Scroll Compressor (DSP4)
52 • Air Cooled Condensing Unit with Scroll Compressor (DSPc)
53 • Air Cooled Condensing Unit with Scroll Compressor (DSPa)
54 • Air Cooled High Efciency Condensing Unit with Scroll Compressor (DSP4H)
56 • Low Capacity Ducted Split Unit with Scroll Compressor (DSP4 LOW)
58 • Low Capacity Ducted Split Unit with Scroll Compressor (DSPc LOW)
60 • Low Capacity Ducted Split Unit with Scroll Compressor (DSPa LOW)

63 Mini Split Unit


64 • Mini Split Unit - Wall Mounted Inverter Type (PETRA H INV. + HPW INV.)
65 • Mini Split Unit - Cassette Inverter Type (PETRA H INV. + HPC INV.)
65 • Mini Split Unit - Free Standing Inverter Type (PETRA H INV. + HPFS INV.)

67 Computer Room
68 • Air Conditioner Split Computer Room Units (PASC4)
68 • Air Conditioner Split Computer Room Units (PASCc)
70 • Mini Computer Room Units - Ceiling / Wall / Floor Mounted (PASC CM)

72 Dry Cooler
72 • Petra Dry Cooler (PDC)
INTRODUCTION

Petra Engineering Industries Company, with over 30 years of experience in the


eld of design and manufacturing of HVAC equipment is committed to providing
a wide range of sophisticated commercial and industrial products and services
of the highest quality

A continuous improvement process has resulted in a quality level that sets


new standards within the air conditioning industry. To ensure the highest level
of quality, all procedures are carried out according to ISO 9001:2015 Quality
Management Systems and ISO 14001:2015 Environmental Management
System. Also, all Petra major products carry the CE mark, UL and ETL listed and
certied in compliance to AHRI standards

Since Petra started its operations, it understood that unless it could provide
better products at competitive prices, it would not be able to succeed in the
marketplace. Petra rmly believes that %100 continued customer satisfaction is
needed to sustain growth in the marketplace, which has resulted in sustained
sales in more than 50 countries

2 QUICK SELECTION GUIDE - SI Units 2017


Petra offers a wide range of products including chillers, Air Handling
Units, Packages Units, Fan Coil Units, Air Cooled Condensing Units,
Computer Room & Mini Split Units. All of Petra products are designed
with the client`s requirements as the focal point. Products are
available with different ozone-friendly refrigerants including R410-a,
R407-c & R134-a

Petra produces highly efcient and relatively quiet units. Additionally


Petra is taking a lead in producing custom units with advanced new
generation of control solutions including smart chiller technologies
and smart watch keypads. Petra also produce units that t into
restricted spaces with its special compact design.

“These marks apply to different products manufactured by Petra Engineering Industries Co.”
“Not all products shown here have AHRI certification”

QUICK SELECTION GUIDE - SI Units 2017 3


PRODUCT RANGE
Air Cooled Water Chillers
Cooling Capacity (Nominal kW)
Model Picture Frequency
350 700 1,050 1,400 1,750 2,100
50Hz 143-1,800
APSa
60Hz 163-2,072

APSaH 50Hz 183-1,486

50Hz 132-1,342
PSC4
60Hz 153-1,564

50Hz 128-1,319
PSCc
60Hz 149-1,521

50Hz 157-720
PSC4H
60Hz 186-853

Water Cooled Water Chillers


Cooling Capacity (Nominal kW)
Model Type Picture Frequency
700 1,400 2,100 2,800 3,500
50Hz 129-857
WPSa Door Way
60Hz 151-974

Extended 50Hz 129-2,993


WPSa
Chassis 60Hz 151-3,399

Residential Air Cooled Chillers


Cooling Capacity (Nominal kW)
Model Picture Frequency
40 80 120 160 200
50Hz 12-154
RWC4
60Hz 14-179

50Hz 6-157
RWCc
60Hz 7-179

• Data based on standard conditions


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

4 QUICK SELECTION GUIDE - SI Units 2017


Air Cooled Package Unit
Cooling Capacity (Nominal kW)
Model Picture Frequency
133 267 400 533 667 800
50Hz 9-694
PPH4
60Hz 10-776

50Hz 9-707
PPHc
60Hz 10-798

50Hz 11-408
PPHa
60Hz 12-457

50Hz 23-158
PPH4H
60Hz 28-188

50Hz 3-31
PWM4
60Hz 4-35

50Hz 3-31
PWMex
60Hz 4-35

Water Source Package Unit


Cooling Capacity (Nominal kW)
Model Picture Frequency
24 48 72 96 120
50Hz 6-102
PWSP4
60Hz 7-114

Air Handling Units


Air Flow Rate (Nominal L/s)
Model Picture Frequency
5,000 10,000 15,000 20,000 25,000
50Hz
PAH 591-23,071
60Hz
50Hz
CM 736-5,191
60Hz

• Data based on standard conditions


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 5


PRODUCT RANGE
Fan Coil Units
Air Flow Rate (Nominal L/s)
Model Picture Frequency
250 500 750 1,000 1,250 1,500
50Hz
RAC 80-476
60Hz
50Hz
DC 188-1,437
60Hz

Chilled Water Fan Coil Units


Cooling Capacity (Nominal kW)
Model Picture Frequency
3.5 7 10.5 14 17.5
50Hz 4-12
PWC 60Hz 4-12
50Hz 4-16
PCC 60Hz 4-16

Air Cooled Condensing Unit


Cooling Capacity (Nominal kW)
Model Picture Frequency
150 300 450 600 750

50Hz 23-608
DSP4
60Hz 27-722

50Hz 19-396
DSPc
60Hz 22-472

50Hz 19-270
DSPa
60Hz 22-314

50Hz 23-67
DSP4H
60Hz 22-70

Dry Cooler
Cooling Capacity (Nominal kW)
Model Picture Frequency
320 640 960 1,280 1,600
50Hz 12-1,419
PDC
60Hz 14-1,558

• Data based on standard conditions


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

6 QUICK SELECTION GUIDE - SI Units 2017


Ducted Split Unit
Cooling Capacity (Nominal kW)
Model Picture Frequency
3.5 7.5 10.5 14.0 17.5

DSP4 50Hz 5-16


Low 60Hz 5-17

DSPc 50Hz 5-16


Low 60Hz 5-17

50Hz 4-14
DSPa
Low 60Hz 4-16

Mini Split Units


Cooling Capacity (Nominal kW)
Model Picture Frequency
3.5 7.0 10.5 14.0 17.5
50Hz 3.5-7.0
HPW
60Hz 3.5-7.0

50Hz 7.0-17.5
HPC
60Hz 7.0-17.5

50Hz 17.5
HPFS
60Hz 17.5

Computer Room
Cooling Capacity (Nominal kW)
Model Picture Frequency
16 32 48 64 80
50Hz 9-67
PASC4
60Hz 10-78

50Hz 9-58
PASCc
60Hz 10-79

PASC CM 50Hz 6-32


+DSP4 60Hz 6-32

PASC CM 50Hz 6-30


+DSPc 60Hz 6-30

• Data based on standard conditions


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 7


PETRA DESIGN & PRODUCTION FACILITIES (AMMAN - JORDAN)

8 QUICK SELECTION GUIDE - SI Units 2017


CHILLERS

QUICK SELECTION GUIDE - SI Units 2017 9


AIR COOLED CHILLERS

APSa
Air Cooled Water Chiller
»Screw
»

»DX
»Smart
»
compressor
»Microchannel
» condenser coil
» shell and tube coolers
Link microprocessor controller
with Screw Compressor

R
134a

Cooling Capacity (kW) Sound Power


Models Dimensions (mm) Operating weight
@35°C Ambient @46°C Ambient level (dBA)
(APSa) (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
50-1 160 184 143 163 3295 1800 2490 90 93 1,950
60-1 172 200 157 181 3160 2230 2530 92 94 2,398
65-1 191 219 172 199 3160 2230 2530 92 94 2,426
70-1 206 236 187 213 3160 2230 2530 93 95 2,458
70-2 210 241 190 217 3360 2230 2530 93 95 2,752
75-1 234 270 211 243 3160 2230 2530 93 95 2,772
80-1 257 296 232 264 3160 2230 2530 93 96 2,862
95-2 281 323 252 288 3360 2230 2530 94 96 3,182
95-1 282 324 253 289 3160 2230 2530 93 96 2,871
100-2 315 360 282 320 3160 2230 2530 94 97 2,948
100-1 316 361 282 320 3360 2230 2530 94 96 3,345

10 QUICK SELECTION GUIDE - SI Units 2017


R
134a

Cooling Capacity (kW) Sound Power


Models Dimensions (mm) Operating weight
@35°C Ambient @46°C Ambient level (dBA)
(APSa) (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
110-2 335 384 303 346 4740 2230 2530 95 97 4,078
120-2 352 403 318 362 4740 2230 2530 95 97 4,118
125-2 368 420 332 377 4740 2230 2530 95 97 4,037
135-2 407 466 365 416 5140 2230 2530 95 97 4,338
140-2 434 496 389 441 5140 2230 2530 96 98 4,563
145-2 452 519 408 467 6120 2230 2570 96 98 5,420
160-2 478 546 431 491 6120 2230 2570 97 99 5,518
165-2 499 569 449 509 6120 2230 2570 97 99 5,604
175-2 528 598 474 535 6120 2230 2570 97 99 5,536
190-2 544 617 491 556 7300 2230 2570 98 100 6,096
195-2 576 652 515 581 6120 2230 2570 97 99 5,680
200-2 595 677 537 607 7300 2230 2570 98 100 6,304
205-2 647 749 583 672 7500 2230 2570 98 100 6,361
210-2 658 758 588 672 6520 2230 2570 98 100 5,768
220-2 684 790 616 707 7500 2230 2570 99 101 6,334
235-2 739 851 662 758 7700 2230 2570 99 101 6,641
250-2 789 906 706 804 7700 2230 2570 99 101 6,953
275-2 836 962 745 851 7700 2230 2570 99 101 7,622
280-2 830 958 748 857 8780 2230 2570 99 101 8,166
285-2 867 1,013 770 875 7700 2230 2570 99 101 7,731
300-2 906 1,043 812 929 8780 2230 2570 99 101 8,532
315-3 957 1,097 853 974 8980 2230 2570 100 102 8,775
315-2 961 1,101 856 978 8780 2230 2570 99 101 8,607
335-2 1,043 1,197 928 1,062 9180 2230 2570 99 101 8,778
350-3 1,084 1,250 972 1,113 10160 2230 2570 100 102 9,379
350-2 1,074 1,240 964 1,104 10560 2230 2570 100 102 9,262
360-3 1,110 1,281 997 1,147 11540 2230 2570 101 103 10,272
375-3 1,136 1,307 1,016 1,160 10660 2230 2570 100 102 9,893
400-3 1,217 1,397 1,089 1,245 11640 2230 2570 101 103 10,909
415-3 1,308 1,492 1,165 1,324 11640 2230 2570 101 103 11,169
430-3 1,334 1,528 1,194 1,360 13020 2230 2570 101 103 12,137
450-3 1,364 1,570 1,216 1,379 11640 2230 2570 101 103 11,289
465-3 1,397 1,595 1,247 1,418 13020 2230 2570 101 103 12,275
475-3 1,447 1,655 1,292 1,468 13020 2230 2570 101 103 13,401
485-3 1,476 1,689 1,321 1,504 13020 2230 2570 101 103 12,344
500-3 1,498 1,721 1,333 1,505 13030 2230 2570 101 103 12,623
510-3 1,527 1,741 1,364 1,550 14400 2230 2570 101 103 13,382
550-4 1,613 1,853 1,443 1,645 14400 2230 2870 102 104 15,277
580-4 1,733 2,025 1,540 1,749 14400 2230 2870 102 104 15,630
600-4 1,800 2,072 1,598 1,834 14400 2230 2870 102 104 15,862

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 11


AIR COOLED CHILLERS

APSaH
»»EER/COP are up to 12/3.5 at full load
performance
»Screw
» compressor
»Microchannel
» condenser coil
»DX
» shell and tube coolers
Air Cooled High Efciency Water »Smart
» Link microprocessor controller
Chiller with Screw Compressor

R
134a

High Efficiency Series Extra High Efficiency Series


Cooling Capacity Cooling Capacity
Models Dimensions (mm) Models Dimensions (mm)
@ 50 Hz (kW) EER COP @ 50 Hz (kW) EER COP
(APSaH) (APSaH)
@35°C Ambient L W H @35°C Ambient L W H
60-1 183 11.38 3.33 3800 2230 2530 60-1 194 12.04 3.53 3800 2230 2530
65-1 205 11.15 3.27 3800 2230 2530 65-1 222 11.98 3.51 3800 2230 2530
70-1 220 11.07 3.24 3800 2230 2530 70-1 238 11.95 3.50 3800 2230 2530
75-1 237 10.60 3.11 3800 2230 2530 90-1 303 12.04 3.53 4740 2230 2530
90-1 289 11.48 3.37 4740 2230 2530 100-2 332 11.94 3.50 4740 2230 2530
100-2 308 10.87 3.19 4740 2230 2530 110-2 380 11.94 3.50 4740 2230 2530
110-2 351 10.82 3.17 4740 2230 2530 130-2 445 12.06 3.53 6120 2230 2570
120-2 371 10.66 3.12 4740 2230 2530 140-2 475 11.95 3.50 6120 2230 2570
130-2 411 11.17 3.27 6120 2230 2570 160-2 558 11.94 3.50 6120 2230 2570
140-2 440 11.06 3.24 6120 2230 2570 180-2 605 12.02 3.52 7700 2230 2570
145-2 474 10.59 3.10 6120 2230 2570 190-2 645 11.94 3.50 7700 2230 2570
160-2 517 10.69 3.13 6120 2230 2570 220-2 757 11.94 3.50 8000 2230 2570
180-2 560 11.13 3.26 7700 2230 2570 255-2 845 11.98 3.51 9180 2230 2570
190-2 597 10.75 3.15 7700 2230 2570 290-2 965 12.01 3.52 10160 2230 2570
200-2 641 10.66 3.13 7700 2230 2570 305-2 1,000 11.94 3.50 10160 2230 2570
220-2 701 10.84 3.18 8000 2230 2570 330-2 1,100 11.98 3.51 11540 2230 2570
255-2 781 11.04 3.24 9180 2230 2570 355-2 1,165 11.94 3.50 11540 2230 2570
280-2 838 10.72 3.14 9180 2230 2570 385-3 1,290 12.01 3.52 13020 2230 2570
290-2 892 10.96 3.21 10160 2230 2570 400-3 1,352 11.94 3.50 13020 2230 2570
305-2 928 10.82 3.17 10160 2230 2570 435-3 1,450 11.98 3.51 14400 2230 2570
330-2 1,017 10.99 3.22 11540 2230 2570
355-2 1,078 10.79 3.16 11540 2230 2570
360-3 1,106 10.71 3.14 11540 2230 2570
385-3 1,194 10.89 3.19 13020 2230 2570
400-3 1,252 10.70 3.14 13020 2230 2570
435-3 1,342 10.78 3.16 14400 2230 2570
470-3 1,434 10.50 3.08 14400 2230 2570
485-3 1,486 10.27 3.01 14400 2230 2570

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

12 QUICK SELECTION GUIDE - SI Units 2017


PSC4
Air Cooled Smart Chiller
»Scroll
»
»Cu/Al
»
»DX
»Mark
»
compressor
condenser coil
» shell and tube coolers
VII- 2 microprocessor controller
with Scroll Compressor

R
410a

Cooling Capacity (kW) Sound Power


Models Dimensions (mm) Operating weight
@35°C Ambient @46°C Ambient level (dBA)
(PSC4) (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
50 153 179 132 153 3295 1800 2490 93 94 1,615
55 167 195 143 167 3295 1800 2490 93 95 1,645
65 196 230 170 197 3360 2230 2530 94 96 2,457
75 219 254 189 220 3360 2230 2530 94 96 2,691
85 246 285 211 247 3360 2230 2530 94 96 2,872
95 274 319 236 275 3360 2230 2530 94 97 3,102
105 306 357 262 305 3360 2230 2530 96 97 3,177
115 334 389 286 333 3360 2230 2530 96 98 3,231
120 355 413 304 356 4740 2230 2530 96 98 4,204
125 388 451 331 387 4740 2230 2530 96 98 4,264
135 409 476 352 406 4740 2230 2530 96 99 4,324
145 439 511 376 437 4740 2230 2530 97 99 4,376
170 505 587 432 505 4740 2230 2530 98 100 4,752
180 544 633 467 547 6120 2230 2570 98 100 5,995
190 576 672 493 573 6120 2230 2570 98 100 6,050
200 608 705 519 603 6120 2230 2570 99 100 6,110
215 645 751 549 642 6120 2230 2570 99 101 6,230
225 671 782 572 671 6120 2230 2570 99 101 6,280
235 710 827 609 711 8880 2230 2570 99 101 8,460
250 756 873 648 750 8880 2230 2570 99 102 8,580
265 818 951 703 811 8880 2230 2570 99 102 8,700
285 878 1,022 753 873 8880 2230 2570 100 102 8,806
315 952 1,112 819 951 8880 2230 2570 101 103 9,426
335 1,009 1,175 865 1,010 8880 2230 2570 101 103 9,552
355 1,088 1,266 935 1,093 11640 2230 2570 101 103 11,530
380 1,152 1,344 987 1,146 11640 2230 2570 101 103 11,641
400 1,215 1,409 1,038 1,206 11640 2230 2570 102 103 11,753
420 1,290 1,501 1,098 1,285 11640 2230 2570 102 104 11,991
445 1,342 1,564 1,144 1,342 11640 2230 2570 102 104 12,103

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 13


AIR COOLED CHILLERS

PSCc
Air Cooled Smart Chiller
»Scroll
»

»DX
»Mark
»
compressor
»Microchannel
» condenser coil
» shell and tube coolers
VII- 2 microprocessor controller
with Scroll Compressor

R
407c

14 QUICK SELECTION GUIDE - SI Units 2017


R
407c

Cooling Capacity (kW) Sound Power


Models Dimensions (mm) Operating weight
@35°C Ambient @46°C Ambient level (dBA)
(PSCc) (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
45 146 169 128 149 3295 1800 2490 93 94 1,356
50 165 191 146 169 3295 1800 2490 93 95 1,436
60 196 230 175 205 3360 2230 2530 94 96 2,009
65 221 260 197 232 3360 2230 2530 94 96 2,157
70 242 282 215 249 3360 2230 2530 94 96 2,337
80 273 317 240 280 3360 2230 2530 94 97 2,501
85 298 344 263 304 3360 2230 2530 96 97 2,548
95 323 370 285 326 3360 2230 2530 96 98 2,595
100 347 403 308 357 4740 2230 2530 96 98 3,383
105 366 422 324 373 4740 2230 2530 96 98 3,432
115 407 473 358 417 4740 2230 2530 96 99 3,662
125 433 501 381 442 4740 2230 2530 97 99 3,710
130 457 527 403 464 4740 2230 2530 98 99 3,760
145 497 573 439 505 4740 2230 2530 98 100 3,829
155 539 625 474 550 6120 2230 2570 98 100 4,902
165 564 651 497 574 6120 2230 2570 98 100 4,947
175 608 706 537 624 6120 2230 2570 99 100 5,260
180 634 733 560 647 6120 2230 2570 99 101 5,306
190 659 761 582 670 6120 2230 2570 99 101 5,360
200 695 806 616 715 8880 2230 2570 98 101 6,879
215 733 844 647 746 8880 2230 2570 99 101 6,986
235 813 947 717 834 8880 2230 2570 99 102 7,470
250 866 1,001 763 883 8880 2230 2570 100 102 7,568
265 915 1,054 807 928 8880 2230 2570 101 102 7,669
285 993 1,145 877 1,010 8880 2230 2570 101 103 7,794
315 1,078 1,250 949 1,099 11640 2230 2570 101 103 9,405
330 1,129 1,301 994 1,147 11640 2230 2570 101 103 9,478
350 1,217 1,413 1,073 1,247 11640 2230 2570 102 103 10,367
365 1,268 1,467 1,119 1,294 11640 2230 2570 102 104 10,462
380 1,319 1,521 1,164 1,341 11640 2230 2570 102 104 10,563

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 15


AIR COOLED CHILLERS

PSC4H
Air Cooled High Efciency Smart Chiller
»EER
» up to 11.8 at full load with 16.2 IPLV
»Scroll
»
»Cu/Al
»
»DX
»Smart
»
compressor
condenser coil
» shell and tube coolers
Link microprocessor controller
with Scroll Compressor

R
410a

16 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Cooling Capacity (kW) EER Sound


Dimensions (mm) Power Operating
Models @35°C Ambient @46°C Ambient
Full Load IPLV level (dBA) weight
(PSC4H)
(kg)
50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz

60 181 215 157 186 11.78 11.39 16.15 15.62 3360 2230 2530 83 85 2,629

90 270 321 234 276 11.69 11.36 16.03 15.52 4740 2230 2530 84 86 3,846

120 360 427 314 369 11.68 11.32 16.22 15.62 6120 2230 2570 86 88 5,283

150 448 533 390 462 11.62 11.28 16.10 15.57 7500 2230 2570 87 89 6,400

180 540 642 467 553 11.58 11.25 16.03 15.52 8880 2230 2570 87 89 7,460

240 720 853 628 737 11.68 11.32 16.15 15.62 11640 2230 2570 89 91 9,735

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 17


WATER COOLED CHILLERS

WPSa
Water Cooled Water Chiller with
»Door
»
»Screw
»
»DX
»DX
way/extended chassis
compressor
» shell and tube coolers
» shell and tube condensers
Screw Compressor

R
134a

18 QUICK SELECTION GUIDE - SI Units 2017


R
134a

Door Way Series


Models Cooling Capacity (kW) Dimensions (mm) Sound Power level (dBA) Operating weight
(WPSa) 50Hz 60Hz L W H 50Hz 60Hz (kg)
45 129 151 3500 850 1905 80 82 1,800
55 164 191 3500 850 1905 80 82 1,800
65 190 219 3500 850 1905 81 83 1,800
75 224 260 3500 850 2010 82 84 2,300
80 240 279 3500 850 2010 83 85 2,300
90 269 314 3500 850 2010 84 86 2,300
100 302 350 3500 850 2350 86 88 2,500
110 325 375 4500 850 2350 83 85 3,000
130 385 449 5000 850 2350 84 86 3,800
145 435 502 5000 850 2350 85 87 3,800
155 470 543 5000 850 2350 86 88 3,800
175 532 613 5500 850 2400 87 89 4,200
195 592 672 5500 950 2400 89 91 4,600
230 693 797 6500 1000 2500 90 92 6,000
245 746 853 6500 1000 2500 91 93 6,000
260 791 901 6500 1000 2500 91 93 6,000
275 857 974 6500 1000 2500 91 93 6,000

Extended Chassis Series


Models Cooling Capacity (kW) Dimensions (mm) Sound Power level (dBA) Operating weight
(WPSa) 50Hz 60Hz L W H 50Hz 60Hz (kg)
300 919 1,043 5500 1300 2200 92 94 6,300
350 1,072 1,221 5500 1400 2200 92 94 7,600
375 1,156 1,324 5500 1400 2200 92 94 7,600
400 1,225 1,404 5500 1400 2200 93 95 7,600
450 1,361 1,545 6000 2230 2340 95 97 10,000
500 1,497 1,699 6000 2230 2340 95 97 10,000
600 1,838 2,087 12000 2230 2350 95 97 13,600
700 2,143 2,443 12000 2230 2350 95 97 15,800
750 2,312 2,648 12000 2230 2350 95 97 15,800
800 2,449 2,808 12000 2230 2350 96 98 15,800
900 2,722 3,089 12000 2230 2350 98 100 19,000
1000 2,993 3,399 12000 2230 2350 98 100 19,000

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving cooler water temperature & 29.4/ 35.0°C
entering/leaving condenser water temperature
• All door way models are available as extended chassis type
• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 19


RESIDENTIAL CHILLERS

RWC4
Air Cooled Residential Chiller
»Scroll
»
»Cu/Al
»
»DX
»Coil
»
compressor
condenser coil
» shell and tube coolers
guard protection
with Scroll Compressor

R
410a

20 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Cooling Capacity (kW) Sound Power


Models Dimensions (mm) Operating weight
@35°C Ambient @46°C Ambient level (dBA)
(RWC4) (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
55 14 17 12 14 1295 820 1120 80 82 205
76 19 23 17 19 1525 820 1220 83 85 304
105 27 32 23 27 1755 1075 1220 83 85 452
128 34 39 29 34 2210 850 1270 85 87 406
160 40 46 34 40 2210 1000 1350 85 87 425
210 52 61 42 51 2280 1400 1615 86 88 704
260 69 81 59 70 2280 1400 1750 86 88 772
310 81 94 69 80 2280 1400 1825 86 88 827
350 90 106 76 89 2280 1400 1750 86 88 1,015
390 100 118 85 100 2280 1400 1750 86 88 1,015
430 106 124 89 104 2280 1525 1553 86 88 1,109
470 115 134 98 114 2280 1725 1750 86 88 1,015
530 134 157 113 133 2910 1725 1500 86 88 1,394
580 145 169 123 144 2910 1725 1500 86 88 1,394
630 154 179 131 152 2910 1725 1525 86 88 1,547

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 21


RESIDENTIAL CHILLERS

RWCc
Air Cooled Residential Chiller
»Scroll
»
»Cu/Al
»
»DX
»Coil
»
compressor
condenser coil
» shell and tube coolers
guard protection
with Scroll Compressor

R
407a

22 QUICK SELECTION GUIDE - SI Units 2017


R
407a

Cooling Capacity (kW) Sound Power


Models Dimensions (mm) Operating weight
@35°C Ambient @46°C Ambient level (dBA)
(RWCc) (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
30 7 8 6 7 1145 670 1155 79 81 161
55 13 15 12 13 1295 820 1120 80 82 205
76 18 20 16 18 1525 820 1220 83 85 304
105 26 30 23 26 1755 1075 1220 83 85 452
128 31 35 26 31 2210 850 1270 85 87 406
160 39 45 34 40 2210 1000 1350 85 87 425
210 51 58 43 48 2280 1400 1615 86 88 704
260 62 71 56 63 2280 1400 1750 86 88 772
310 82 94 69 80 2280 1400 1825 86 88 827
390 94 106 79 90 2280 1400 1750 86 88 1,015
430 108 121 90 102 2280 1525 1553 86 88 1,109
530 121 137 102 115 2910 1727 1500 86 88 1,394
580 145 166 123 141 2910 1725 1500 86 88 1,394
630 157 179 132 151 2910 1725 1525 86 88 1,547

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 370 and ISO BS 3744 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 23


PETRA COMPANY HEADQUARTER ( JORDAN)

24 QUICK SELECTION GUIDE - SI Units 2017


PACKAGE
UNITS

QUICK SELECTION GUIDE - SI Units 2017 25


AIR COOLED PACKAGE UNIT

PPH4
Air Cooled Package Unit with
»Scroll
»
»Cu/Al
»
»DX
»DWDI
»
compressor
condenser coil
» Cu/Al cooling coils
centrifugal supply fans
Scroll Compressor

R
410a

26 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Air Flow Cooling Capacity (kW)


Models Dimensions (mm) Operating weight
Rate @35°C Ambient @46°C Ambient
(PPH4) (kg)
(L/s) 50Hz 60Hz 50Hz 60Hz L W H
40 661 10 11 9 10 1140 1140 940 296
50 873 14 16 12 14 1140 1140 940 300
60 1,062 18 20 16 18 1140 1140 940 328
85 1,180 23 26 21 23 1140 1140 940 383
95-1 1,534 26 29 23 26 1600 1550 1370 422
95-2 1,534 25 29 22 26 1600 1550 1370 422
105-1 1,746 28 32 25 29 1600 1550 1370 422
105-2 1,746 30 34 26 30 1600 1550 1370 422
115-1 1,888 33 37 30 33 1600 1550 1370 427
115-2 1,888 33 37 30 33 1600 1550 1370 427
135-1 2,124 41 46 36 41 1600 1550 1370 438
135-2 2,124 41 45 36 41 1600 1550 1370 438
160-1 2,124 45 51 41 45 1600 1550 1370 498
160-2 2,124 47 52 42 47 1600 1550 1370 498
175-1 3,067 53 59 47 54 1650 2230 1620 672
175-2 3,067 55 62 49 56 1650 2230 1620 672
195 3,775 60 67 53 60 1650 2230 1620 697
230 4,247 71 80 63 71 1650 2230 1960 737
300 4,719 85 96 76 86 1880 2230 2260 952
360 5,191 96 108 86 97 1880 2230 2460 1,042
450 5,899 128 142 115 129 2440 2230 2460 1,356
530 6,607 150 167 136 151 2440 2230 2460 1,740
640 7,550 190 213 170 191 2440 2230 2460 1,810
700 10,382 204 230 183 207 2700 2230 2460 2,676
800 11,326 231 258 209 233 5360 2230 2460 4,047
900 12,033 291 326 261 294 5360 2230 2460 4,124
1000 13,213 317 354 285 320 5870 2230 2460 5,385
1100 14,157 347 388 311 349 5870 2230 2460 5,439
1200 15,101 375 419 336 377 5870 2230 2460 5,437
1400 16,988 392 436 354 395 8660 2230 2460 7,242
1600 18,876 448 500 402 451 8660 2230 2460 7,512
1800 20,764 505 565 454 508 8660 2230 2460 7,653
2000 22,651 562 628 503 564 8660 2230 2460 7,732
2200 28,314 694 776 623 698 11530 2230 2460 10,130

• Data based on AHRI conditions: 26.7/19.4°C entering dry/wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 27


AIR COOLED PACKAGE UNIT

PPHc
Air Cooled Package Unit with
»Scroll
»
»Cu/Al
»
»DX
»DWDI
»
compressor
condenser coil
» Cu/Al cooling coils
centrifugal supply fans
Scroll Compressor

R
407c

28 QUICK SELECTION GUIDE - SI Units 2017


R
407c

Air Flow Cooling Capacity (kW)


Models Dimensions (mm) Operating weight
Rate @35°C Ambient @46°C Ambient
(PPHc) (kg)
(L/s) 50Hz 60Hz 50Hz 60Hz L W H
40 661 10 11 9 10 1140 1140 940 224
50 873 13 15 12 13 1140 1140 940 242
60 1,062 18 20 16 18 1140 1140 940 248
85 1,180 22 25 20 23 1140 1140 940 280
95-1 1,534 23 27 21 24 1600 1550 1370 419
95-2 1,534 24 27 21 24 1600 1550 1370 419
105-1 1,746 29 33 27 30 1600 1550 1370 421
105-2 1,746 29 33 27 30 1600 1550 1370 421
115-1 1,888 34 37 30 33 1600 1550 1370 425
115-2 1,888 32 35 30 33 1600 1550 1370 425
135-1 2,124 40 44 36 40 1600 1550 1370 436
135-2 2,124 39 43 36 40 1600 1550 1370 436
160-1 2,124 47 52 44 48 1600 1550 1370 498
160-2 2,124 47 51 44 47 1600 1550 1370 498
175-1 3,067 54 61 50 56 1600 2230 1630 640
175-2 3,067 55 59 51 54 1600 2230 1630 640
195 3,775 59 65 54 59 1600 2230 1630 667
230 4,247 70 81 65 73 1600 2230 1630 708
300 4,719 79 90 73 82 1880 2230 1830 952
360 5,191 99 113 92 104 2440 2230 2460 1,041
450 5,899 130 147 120 135 2440 2230 2460 1,356
530 6,607 152 170 141 156 2440 2230 2460 1,740
640 7,550 189 218 175 199 3150 2230 2460 1,810
700 10,382 202 231 187 210 4700 2230 2460 2,676
800 11,326 239 263 218 242 5360 2230 2460 4,047
900 12,033 293 324 268 298 5360 2230 2460 4,124
1000 13,213 328 362 298 331 5870 2230 2460 5,385
1100 14,157 360 399 329 366 7500 2230 2460 5,439
1200 15,101 384 428 352 392 7500 2230 2460 5,437
1400 16,988 407 449 373 413 8660 2230 2460 7,242
1600 18,876 467 517 426 474 8660 2230 2460 7,512
1800 20,764 526 583 481 534 11230 2230 2460 7,631
2000 22,651 576 641 527 587 11230 2230 2460 7,732
2200 28,314 707 798 643 731 11530 2230 2460 10,878

• Data based on AHRI conditions: 26.7/19.4°C entering dry/wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 29


AIR COOLED PACKAGE UNIT

PPHa
Air Cooled Package Unit with
Scroll Compressor

R
134a

Air Flow Cooling Capacity (kW)


Models Dimensions (mm) Operating weight
Rate @35°C Ambient @46°C Ambient
(PPHa) (kg)
(L/s) 50Hz 60Hz 50Hz 60Hz L W H
40 661 11 13 11 12 1140 1140 940 224
50 873 15 17 14 16 1140 1140 940 242
60 1,062 17 18 16 17 1140 1140 940 248
85 1,180 20 22 19 20 1140 1140 940 280
95 1,534 26 30 24 27 1600 1550 1370 419
105 1,746 30 34 28 31 1600 1550 1370 421
135 2,124 35 39 32 36 1600 1550 1370 436
160 2,124 46 50 42 46 1600 1550 1370 498
175 3,067 52 58 47 53 1600 2230 1620 640
195 3,775 60 67 55 62 1600 2230 1620 667
230 4,247 68 77 63 72 1600 2230 1620 708
300 4,719 82 92 76 85 1880 2230 1960 952
360 5,191 99 111 91 102 1880 2230 2260 1,042
450 5,899 130 145 120 135 2440 2230 2460 1,356
530 6,607 152 169 140 158 2440 2230 2460 1,740
640 7,550 177 197 164 182 2440 2230 2460 1,810
700 10,382 199 223 183 207 5360 2230 2460 3,841
800 11,326 236 264 218 245 5360 2230 2460 4,047
900 12,033 256 286 237 265 5360 2230 2460 4,124
1000 13,213 276 309 255 287 6070 2230 2460 5,385
1100 15,101 296 332 274 309 6070 2230 2460 5,397
1200 16,988 337 379 310 351 7500 2230 2460 5,669
1400 18,876 374 421 345 389 8920 2230 2460 7,075
1600 20,764 408 457 376 422 8920 2230 2460 7,211

• Data based on AHRI conditions: 26.7/19.4°C entering dry/wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

30 QUICK SELECTION GUIDE - SI Units 2017


PPH4H
»»EER up to 11.8 at full load
with 13.0 IEER
»Scroll
» compressor
»Cu/Al
» condenser coil
»DX
» Cu/Al cooling coils
Air Cooled High Efciency »DWDI
» centrifugal supply fans
Package Unit with Scroll
Compressor

R
410a

Air Flow Rate Cooling Capacity


Models Dimensions (mm) EER IEER
(L/s) (kW)
(PPH4H)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz 50Hz 60Hz
95 1,298 1,534 23 28 1753 2235 1626 11.7 11.5 13.0 13.0
105 1,486 1,770 27 32 1753 2235 1626 11.7 11.2 12.9 12.9
115 1,722 2,006 31 37 1753 2235 1626 11.8 11.4 13.0 13.0
135 1,840 2,194 34 40 1753 2235 1626 11.7 11.2 12.9 12.8
160 2,006 2,359 37 44 1753 2235 1626 11.6 11.2 12.9 12.9
175 2,359 2,949 44 53 3420 2235 1750 11.5 11.3 12.8 12.8
195 2,831 3,303 52 61 3420 2230 1750 11.4 11.1 12.8 12.8
230 3,303 3,964 59 70 3420 2230 1750 11.3 10.6 12.6 11.6
275 3,657 4,247 67 80 3420 2230 2133 11.3 10.8 12.6 11.6
300 4,011 4,719 74 88 3420 2230 2133 10.8 10.3 12.4 11.6
360 4,719 5,309 89 106 3980 2230 2300 11.2 11.0 12.8 12.0
400 5,073 5,899 98 117 3980 2230 2300 10.9 10.5 12.4 11.6
450 5,663 6,607 111 132 3980 2230 2300 10.8 10.3 12.2 11.6
530 6,607 7,550 127 152 5360 2230 2300 10.9 10.4 12.6 11.6
640 7,786 8,730 158 188 5360 2230 2300 10.7 10.2 12.4 11.6

• Data based on AHRI conditions: 35.0°C ambient temperature and 26.7/19.4°C entering dry/
wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 31


AIR COOLED PACKAGE UNIT

PWM
Air Cooled Wall Mounted Package Unit
»Scroll
» compressor
»Smart
» Control
»Extremely
» quiet operation

PWMex
Explosion Proof Wall Air Cooled Wall
Mounted Package Unit

»Explosion
» proof electrical enclosure
»Liquid
» tight flexible metallic conduits
»Anti-spark
» fans
»Explosion
» proof fan motors

Air Flow Cooling Capacity (kW)


Models Dimensions (mm) Operating weight
Rate @35°C Ambient @46°C Ambient
(PWM4) (kg)
(L/s) 50Hz 60Hz 50Hz 60Hz L W H
12 189 3 4 3 4 830 540 1780 260
24 330 6 7 6 7 830 540 1780 260
33 448 9 10 8 9 830 540 1780 268
42 566 13 14 11 13 1085 540 1980 361
48 590 14 16 12 14 1085 540 1980 363
58 613 15 17 13 15 1085 540 1980 377
95 1,133 25 28 22 26 - - - -
115 1,416 31 35 27 31 - - - -

• Data based on AHRI conditions: 26.7/19.4°C entering dry/wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

32 QUICK SELECTION GUIDE - SI Units 2017


PWSP
Water Source Package Unit with
»Scroll
»
»Brazed
»
compressor
plate heat exchanger
»Centrifugal
» supply fans
Scroll Compressor

R
410a

Dimensions (mm) Discharge


Cooling
Models Sound Power Operating weight (kg)
Capacity (kW) Horizontal Vertical
(PWSP4) (dBA)

50Hz 60Hz L W H L W H 50Hz 60Hz Horizontal Vertical


15 6 7 1050 750 440 750 785 1100 56 56 140 120
20 7 8 1050 750 500 750 785 1100 55 56 150 130
30 9 9 1050 750 500 750 785 1100 58 58 150 130
36 10 12 1250 750 500 750 990 1100 59 59 180 160
48 14 15 1400 750 600 750 1140 1100 62 62 180 160
65 18 19 1400 750 600 750 1140 1100 65 65 200 170
80 25 28 1770 1000 710 900 1290 1500 72 74 230 190
120 36 40 1650 1000 840 900 1290 1500 79 83 230 200
150 42 47 1900 1000 840 1000 1445 1900 80 81 290 290
185 53 63 2500 1100 940 1000 1445 1900 83 88 360 360
250 74 83 3200 1300 1250 1100 2230 1900 84 88 400 400
300 83 94 3200 1300 1250 1100 2230 1900 83 86 450 450
355 102 114 3200 1300 1250 1100 2230 1900 82 85 680 680

• Data based on AHRI conditions: 35.0/29.4°C water in/out temperature & 26.7/ 19.4°C entering dry/wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 33


PETRA FACTORY ( JORDAN - MAFRAQ)

34 QUICK SELECTION GUIDE - SI Units 2017


AIR HANDLERS

QUICK SELECTION GUIDE - SI Units 2017 35


AIR HANDLING UNITS

PAH
Air Handling Units
»Horizontal/vertical
»
»Wide
»
construction
range of optional sections
and parts

Cooling Coil
Models Air Flow Rate (L/s)
(PAH) Total Capacity (kW) Sensible Capacity (kW) Water flow rate (L/s)
@2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s
12 591 651 13 14 9 10 0.5 0.6
16 716 788 16 17 11 12 0.6 0.7
24 1,147 1,262 29 31 19 20 1.1 1.2
32 1,573 1,730 37 40 25 26 1.5 1.6
40 1,966 2,163 46 50 31 33 1.8 1.9
50 2,359 2,595 56 60 37 40 2.2 2.3
62 2,949 3,244 70 75 46 50 2.7 2.9
80 3,893 4,282 100 107 64 69 3.9 4.2
100 4,749 5,223 128 138 81 87 5.0 5.4
120 5,766 6,343 156 168 98 106 6.1 6.6
150 7,123 7,835 193 207 121 131 7.6 8.1
180 8,140 8,954 213 236 135 149 6.7 9.3
200 8,819 9,700 234 251 147 159 9.2 9.8
250 11,375 12,512 280 299 183 196 11.0 11.7
320 15,081 16,589 393 421 250 269 15.4 16.5
400 17,637 19,401 440 516 282 325 17.3 20.2
450 20,973 23,071 547 626 345 391 21.4 24.6

36 QUICK SELECTION GUIDE - SI Units 2017


Arrangement 1 Arrangement 2

Arrangement 3 Arrangement 4

Cabinet Dimensions Arrangment 1 Arrangment 2 Arrangment 3 Arrangment 4


Models
(PAH) Width Height Length Length Length Length
(mm) (mm) (mm) (mm) (mm) (mm)
12 850 800 1450 2150 1900 2600
16 850 800 1450 2150 1900 2600
24 1010 960 1450 2150 1900 2600
32 1420 960 1700 2400 2150 2850
40 1420 960 1700 2400 2150 2850
50 1420 1370 1700 2400 2400 3100
180 2170 2120 2610 2860 3070 3770
200 2170 2280 2610 2860 3070 3770
250 2740 2280 2910 3160 3370 4120
320 3490 2280 2910 3160 3610 4370
400 4060 2280 3150 3400 3860 4610
450 4560 2280 3150 3400 3860 4610

• Above drawings are typical drawings for PAH 200, for other units dimensions, please contact your nearest Petra sales office
• Data based on 4 rows & 472 fins per meter coil
• Data based on AHRI conditions: 6.7/12.2°C entering/leaving water temperature & 26.7/19.4°C entering dry bulb/wet bulb air temperature
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 37


AIR HANDLING UNITS

CM
Comfort Maker

»Chilled
» water/DX coils
»Cu/Al
» cooling coils
»DWDI
» centrifugal supply fans
»25mm
» flat filter

38 QUICK SELECTION GUIDE - SI Units 2017


3rows
Cooling Coil
Models Air Flow Rate (L/s)
Total Capacity (kW) Sensible Capacity (kW) Water flow rate (L/s)
(CM)
@2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s
15 736 811 13 14 9 9 0.5 0.5
20 944 1,038 18 19 12 12 0.7 0.7
24 1,121 1,233 20 24 13 15 0.8 0.9
30 1,444 1,590 30 32 19 20 1.2 1.2
38 1,788 1,968 38 41 24 25 1.5 1.6
48 2,341 2,574 52 34 32 16 2.1 2.2
60 2,831 3,137 61 66 38 41 2.4 2.6
75 3,539 3,893 79 85 48 52 3.1 3.3
96 4,719 5,191 106 113 64 69 4.1 4.4

4rows
Cooling Coil
Models Air Flow Rate (L/s)
Total Capacity (kW) Sensible Capacity (kW) Water flow rate (L/s)
(CM)
@2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s @2.5 m/s @2.8 m/s
15 736 811 17 18 11 12 0.6 0.7
20 944 1,038 22 24 14 15 0.9 0.9
24 1,121 1,233 25 30 16 19 1.0 1.2
30 1,444 1,590 36 39 23 24 1.4 1.5
38 1,788 1,968 46 50 29 31 1.8 2.0
48 2,341 2,574 62 67 38 41 2.4 2.6
60 2,831 3,137 74 80 46 50 2.9 3.1
75 3,539 3,893 94 102 58 62 3.7 4.0
96 4,719 5,191 126 135 77 83 4.9 5.3

Dimensions (mm) Operating


Models Sound Power (dBA)
Horizontal Construction Vertical Construction Weight
(CM)
L W H L W H (kg) Discharge Return
15 986 1059 541 986 650 1161 111 75 73
20 1394 1059 541 1163 650 1161 125 77 76
24 1316 1059 541 1316 650 1161 129 80 79
30 1415 1059 599 1415 752 1300 154 79 77
38 1671 1059 599 1671 752 1300 179 83 81
48 2080 1059 610 1570 749 1529 249 83 82
60 1831 1285 861 1826 950 1740 299 83 82
75 2179 1285 861 1725 950 1999 336 87 86
96 2179 1135 1080 2179 851 1920 399 87 86

• Data based on AHRI conditions: 6.7/12.2°C entering/leaving water temperature & 26.7/19.4°C entering dry bulb/wet bulb air temperature
• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 260 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 39


PETRA FACTORY (KSA)

40 QUICK SELECTION GUIDE - SI Units 2017


FAN COILS

QUICK SELECTION GUIDE - SI Units 2017 41


FAN COIL UNITS

RAC
Fan Coil Unit for Low Static Pressure
»Chilled
»
»Cu/Al
»
»DWDI
»
»25mm
»
water/DX coils
cooling coils
direct drive fans
flat filter

Cooling Coil
Models (RAC)

@ 25 Pa External Static Pressure @ 50 Pa External Static Pressure


3 Rows 4 Rows 3 Rows 4 Rows

Air Flow Total Sensible Air Flow Total Sensible Air Flow Total Sensible Air Flow Total Sensible
Rate Capacity Capacity Rate Capacity Capacity Rate Capacity Capacity Rate Capacity Capacity
(L/s) (kW) (kW) (L/s) (kW) (kW) (L/s) (kW) (kW) (L/s) (kW) (kW)

2 104 3.1 1.9 102 3.5 2.2 80 2.5 1.6 78 2.8 1.7
3 134 3.8 2.4 131 4.3 2.7 103 3.1 1.9 100 3.4 2.1
4 169 4.5 2.9 166 5.3 3.3 129 3.7 2.3 126 4.2 2.6
5 221 6.4 4.0 217 7.2 4.5 169 5.1 3.2 164 5.7 3.5
6 252 7.1 4.4 246 8.1 5.0 193 5.7 3.6 187 6.3 3.9
8 283 8.2 5.0 277 9.2 5.7 218 6.6 4.1 212 7.3 4.5
10 428 12.6 7.7 419 14.1 8.7 328 10.1 6.2 319 11.2 6.9
12 476 13.8 8.4 466 15.5 9.5 369 11.1 6.9 359 12.3 7.6

Models Operating Weight (kg)


(RAC) CBP CB GFC FB GCC PFC PCC
2 11 10 17 13 21 18 18
3 11 10 19 13 21 18 18
4 13 11 19 15 22 20 20
5 15 13 23 15 22 20 20
6 15 13 23 18 26 24 24
8 23 13 26 22 26 24 24
10 24 23 35 32 29 32 32
12 24 23 35 38 40 32 32

42 QUICK SELECTION GUIDE - SI Units 2017


Dimensions (mm)
Models
CBP CB GFC FB
(RAC)
L W H L W H L W H L W H
2 691 500 239 691 488 239 1100 249 655 841 249 655
3 691 500 239 691 488 239 1100 249 655 841 249 655
4 691 500 239 691 488 239 1100 249 655 841 249 655
5 945 500 239 945 488 239 1339 249 655 1087 249 655
6 945 500 239 945 488 239 1339 249 655 1087 249 655
8 1087 500 239 1087 488 239 1501 249 655 1280 249 655
10 1628 500 239 1628 488 239 1885 249 655 1666 249 655
12 1628 500 239 1628 488 239 1885 249 655 1666 249 655

Dimensions (mm)
Models
GCC PFC PCC
(RAC)
L W H L W H L W H
2 1029 640 290 1031 226 635 1031 635 226
3 1029 640 290 1031 226 635 1031 635 226
4 1029 640 290 1031 226 635 1031 635 226
5 1270 640 290 1031 226 635 1031 635 226
6 1270 640 290 1359 226 635 1359 635 226
8 1430 640 290 1359 226 635 1359 635 226
10 1839 640 290 1689 226 635 1689 635 226
12 1839 640 290 1689 226 635 1689 635 226

Sound Power (dBA)


Models
Fan Speed
(RAC)
Low Medium High
2 41 44 48
3 42 46 49
4 43 47 50
5 45 49 52
6 47 50 54
8 49 52 56
10 52 55 59
12 53 56 60

• Data based on AHRI conditions: 6.7/12.2°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 260 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce
• Above data is based on CBP model, for other RAC types data, please contact your nearest Petra sales office

QUICK SELECTION GUIDE - SI Units 2017 43


FAN COIL UNITS

DC
Fan Coil Unit for Medium Static Pressure
»Chilled
»
»Cu/Al
»
»DWDI
»
»25mm
»
water/DX coils
cooling coils
direct drive fans
flat filter

Cooling Coil
@ 25 Pa External Static Pressure @ 50 Pa External Static Pressure @ 75 Pa External Static Pressure
3 Rows 4 Rows 3 Rows 4 Rows 3 Rows 4 Rows
Models (DC)

Total Capacity (kW)

Total Capacity (kW)

Total Capacity (kW)

Total Capacity (kW)

Total Capacity (kW)

Total Capacity (kW)


Air Flow Rate (L/s)

Air Flow Rate (L/s)

Air Flow Rate (L/s)

Air Flow Rate (L/s)

Air Flow Rate (L/s)

Air Flow Rate (L/s)


Sensible Capacity

Sensible Capacity

Sensible Capacity

Sensible Capacity

Sensible Capacity

Sensible Capacity
(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

6 247 7.0 4.4 242 8.0 4.9 218 6.3 3.9 212 7.1 4.4 188 5.6 3.5 183 6.2 3.9
8 310 8.4 5.2 303 9.6 6.0 270 7.5 4.7 264 8.6 5.3 231 6.6 4.1 224 7.4 4.6
10 376 9.7 6.0 367 11.3 7.0 328 8.7 5.4 320 10.0 6.2 281 7.7 4.8 272 8.8 5.4
12 500 13.1 8.3 490 15.3 9.5 429 11.6 7.4 420 13.4 8.4 359 10.1 6.4 349 11.5 7.2
14 591 14.9 9.4 580 17.5 10.9 521 13.5 8.5 510 15.8 9.8 451 12.1 7.6 439 13.9 8.7
16 661 16.2 10.2 648 19.2 11.9 575 14.6 9.2 562 17.1 10.6 488 12.8 8.1 475 14.9 9.3
18 677 17.3 11.0 664 20.3 12.7 590 15.5 9.9 577 18.1 11.3 505 13.7 8.7 491 15.8 9.9
20 803 19.6 12.5 786 23.3 14.6 684 17.4 11.0 667 20.4 12.8 564 15.0 9.5 548 17.3 10.8
24 1,099 28.3 17.6 1,075 31.5 19.8 955 25.5 15.8 931 28.1 17.6 811 22.4 14.0 787 24.5 15.3
30 1,437 38.1 23.4 1,412 42.4 26.3 1,250 34.2 21.0 1,225 37.8 23.4 1,064 30.1 18.5 1,038 33.0 20.5

44 QUICK SELECTION GUIDE - SI Units 2017


Dimensions (mm)
Models
DCP DCB DCC DCV
(DC)
L W H L W H L W H L W H
6 587 719 429 587 699 429 925 800 465 831 455 826
8 587 719 429 587 699 429 925 800 465 831 455 826
10 587 719 429 587 699 429 925 800 465 831 455 826
12 942 719 429 942 699 429 1280 800 465 1184 455 826
14 942 719 429 942 699 429 1280 800 465 1184 455 826
16 942 719 429 942 699 429 1280 800 465 1184 455 826
18 1196 719 429 1196 699 429 1534 800 465 1420 455 826
20 1196 719 429 1196 699 429 1534 800 465 1420 455 826
24 1577 719 429 1196 699 429 1915 800 465 ** ** **
30 1961 719 429 1196 699 429 2296 800 465 ** ** **

Models Operating Weight (kg) Sound Power (dBA)


(DC) DCP DCB DCC DCV Fan Speed
6 42 25 50 40 Low Medium High
8 42 25 50 40 46 50 53
10 42 25 50 40 49 52 56
12 64 49 74 64 50 54 57
14 64 49 74 64 52 56 59
55 59 62
16 64 49 74 64
56 59 63
18 73 63 88 78
58 61 65
20 73 63 88 78 58 62 66
24 92 91 137 ** 58 64 68
30 114 114 152 ** 62 65 69

• Data based on AHRI conditions: 6.7/12.2°C entering/leaving water temperature


• Sound data is calculated based on standard components design
• Sound data shall be as per AHRI 260 standard
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce
• Above data is based on DCP model, for other DC types data, please contact your nearest Petra sales office

QUICK SELECTION GUIDE - SI Units 2017 45


FAN COIL UNITS

PWC
Chilled Water Decorative Wall Mounted
»Chilled
»
»
»Very
»
»Low
»
water coil
»Decorative and attractive look
low power consumption
noise unit (quiet operation)
Fan Coil Unit

Cooling Coil
Operating
Models Air Flow Rate Total Water flow Dimensions (mm)
Weight
(PWC) Capacity rate
(L/s) (kW) (L/s) (kg) L W H
12 130 4 0.2 15 991 215 300
18 203 7 0.3 19 1168 230 360
24 245 8 0.4 19 1168 230 360
30 330 11 0.5 25 1422 230 360
36 354 12 0.5 25 1422 230 360

• Data based on AHRI conditions: 6.7/12.2°C entering/leaving water temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

46 QUICK SELECTION GUIDE - SI Units 2017


PCC
Chilled Water Decorative Cassette Type
»Chilled
»
»
»Very
»
»Low
»
water coil
»Decorative and attractive look
low power consumption
noise unit (quiet operation)
Fan Coil Unit

Cooling Coil
Operating
Models Air Flow Rate Total Water flow Dimensions (mm)
Weight
(PCC) Capacity rate
(L/s) (kW) (L/s) (kg) L W H
12 189 4 0.2 22 940 940 930
18 278 8 0.3 32 940 940 930
24 349 9 0.3 32 940 940 930
30 387 11 0.3 39 940 940 305
36 444 12 0.4 39 940 940 305
42 557 14 0.5 39 940 940 305
48 708 16 0.6 41 940 940 305

• Data based on AHRI conditions: 6.7/12.2°C entering/leaving water temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 47


PETRA SERVICE TEAM

48 QUICK SELECTION GUIDE - SI Units 2017


CONDENSING
UNITS

QUICK SELECTION GUIDE - SI Units 2017 49


CONDENSING UNIT

DSP4
Air Cooled Condensing Unit
»Scroll
»
»Cu/Al
»
compressor
condenser coil
»External
» rotor motor
condenser fan
with Scroll Compressor

R
410a

50 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Cooling Capacity (kW)


Dimensions (mm) Operating
Models
@35°C Ambient @46°C Ambient weight
(DSP4)
(kg)
50Hz 60Hz 50Hz 60Hz L W H
85 25 29 23 27 575 1150 944 184
95 25 30 23 28 825 1560 1370 269
105 28 34 26 32 825 1560 1370 271
115 34 41 32 39 825 1560 1370 276
135 38 45 35 42 825 1560 1370 277
160 49 58 46 55 825 1560 1370 340
175-1 51 62 48 58 850 2230 1625 416
175-2 55 65 52 61 850 2230 1625 420
195 59 71 56 67 850 2230 1625 447
230 68 82 64 76 850 2230 1625 468
300 76 90 71 85 1020 2230 1777 604
360 99 118 92 110 1020 2230 2085 799
450 132 156 123 145 1580 2230 2300 1,151
530 163 193 153 181 1580 2230 2300 1,195
640 203 241 190 225 1580 2230 2300 2,171
700 209 249 197 234 2300 2230 2300 2,285
800 247 291 231 274 2960 2230 2300 2,491
900 309 368 290 345 2960 2230 2300 2,568
1000 326 386 306 361 2960 2230 2300 3,353
1100 367 435 343 407 2960 2230 2300 3,407
1200 406 481 380 450 2960 2230 2300 3,405
1400 424 501 397 469 4340 2230 2340 4,172
1600 454 537 426 503 4340 2230 2340 4,186
1800 531 628 497 588 4340 2230 2340 4,195
2000 608 722 569 675 4340 2230 2340 4,209

• Data based on 7.2°C suction temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 51


CONDENSING UNIT

DSPc
Air Cooled Condensing Unit
»Scroll
»
»Cu/Al
»
compressor
condenser coil
»External
» rotor motor
condenser fan
with Scroll Compressor

R
407c

Cooling Capacity (kW) Sound Power level


Models Dimensions (mm) Operating
@35°C Ambient @46°C Ambient (dBA)
(DSPc) weight (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
85 21 25 19 22 595 1150 1084 83 85 256

95 21 25 19 22 900 1560 1510 83 85 240

105 28 33 25 29 900 1560 1510 83 85 240

115 33 39 29 33 900 1560 1510 83 85 240

135 38 44 32 38 900 1560 1510 84 86 240

160 48 58 42 50 900 1560 1510 84 86 240

175-1 50 60 44 53 950 2230 1765 84 86 465

175-2 49 57 43 51 950 2230 1765 84 86 465

195 54 63 47 55 950 2230 1765 84 86 465

230 66 77 57 66 950 2230 1765 84 86 465

300 74 87 63 74 1020 2230 1916 84 86 680

360 99 119 87 106 1580 2230 2440 84 86 1,098

450 129 152 113 133 1580 2230 2440 87 89 1,290

530 160 188 138 163 1580 2230 2440 90 92 1,415

640 196 234 170 202 2300 2230 2440 92 94 1,564

700 198 236 171 204 2300 2230 2440 92 94 1,569

800 244 286 211 248 2960 2230 2440 92 94 2,406

900 292 344 254 300 2960 2230 2440 94 96 2,646

1000 321 375 276 325 2960 2230 2440 94 96 2,702

1100 363 430 315 373 4600 2230 2480 94 96 2,971

1200 396 472 343 408 4600 2230 2480 94 96 3,016

52 QUICK SELECTION GUIDE - SI Units 2017


DSPa
Air Cooled Condensing Unit
»Scroll
»
»Cu/Al
»
compressor
condenser coil
»External
» rotor motor
condenser fan
with Scroll Compressor

R
134a

Cooling Capacity (kW) Sound Power level


Models Dimensions (mm) Operating
@35°C Ambient @46°C Ambient (dBA)
(DSPa) weight (kg)
50Hz 60Hz 50Hz 60Hz L W H 50Hz 60Hz
85 22 26 19 22 595 1150 1085 83 85 252

95 25 30 22 26 900 1560 1320 83 85 240

105 29 34 25 30 900 1560 1320 83 85 240

115 30 35 26 31 900 1560 1320 83 85 240

135 34 40 30 35 900 1560 1320 84 86 240

160 47 55 41 48 900 1560 1320 84 86 240

175 52 62 46 54 950 2230 1575 84 86 465

195 56 66 49 59 950 2230 1575 84 86 465

230 66 79 58 70 950 2230 1575 84 86 465

300 85 102 76 90 1020 2230 1916 84 86 848

360 95 113 85 101 1020 2230 2225 84 86 932

450 122 144 109 128 1580 2230 2440 87 89 1,350

530 160 190 142 169 1580 2230 2440 90 92 1,608

640 177 208 157 185 2300 2230 2440 92 94 1,740

700 193 229 172 204 2300 2230 2440 92 94 1,880

800 245 288 218 257 2960 2230 2440 92 94 2,652

900 270 314 241 280 2960 2230 2440 94 96 2,694

• Data based on 7.2°C suction temperature


• Sound data is calculated based on standard components design
• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 53


CONDENSING UNIT

DSP4H
»EER
» up to 11.8 at full load
and 13.0 at IPLV
»Scroll
» compressor
»Cu/Al
» condenser coil
»External
» rotor motor
Air Cooled High Efciency condenser fan
Condensing Unit with Scroll
Compressor

R
410a

54 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Models Cooling Capacity (kW) Dimensions (mm) EER IEER


(DSP4H)
50Hz 60Hz L W H 50Hz 60Hz 50Hz 60Hz
75 - 22 800 1560 1370 - 11.5 - 12.9

95 23 28 850 2230 1625 11.7 11.5 13.0 13.0

105 27 32 850 2230 1625 11.7 11.2 12.9 12.9

115 31 37 850 2230 1625 11.8 11.4 13.0 13.0

135 34 40 850 2230 1625 11.7 11.2 12.9 12.8

160 37 44 850 2230 1625 11.6 11.2 12.9 12.9

175 44 53 1020 2230 1776 11.5 11.3 12.8 12.8

195 52 61 1020 2230 1776 11.4 11.1 12.8 12.8

230 59 70 1020 2230 1776 11.3 10.6 12.4 11.6

275 67 - 1020 2230 2085 11.3 - 12.4 -

• Data based on 7.2°C condenser suction temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 55


DUCTED SPLIT UNIT

DSP Low
Low Capacity Ducted Split Unit
»Scroll
»
»Cu/Al
»
compressor
condenser coil
»External
» rotor motor condenser fan
with Scroll Compressor

R
410a

Air Cooling Capacity (kW) Dimensions (mm) Dimensions (mm) Operating Operating
Flow weight weight
Models @35°C Ambient @46°C Ambient Outdoor Unit Indoor Unit (kg) (kg)
Rate
(L/s) 50Hz 60Hz 50Hz 60Hz L W H L W H Outdoor Indoor

178 5.2 5.2 4.7 4.8


DSP 15 + RAC 5 208 5.4 5.4 4.9 5.0 875 390 610 945 856 1245 66 33
252 5.6 5.6 5.1 5.2

161 4.8 4.9 4.5 4.5


DSP 15 + CMD 6 220 5.2 5.3 4.8 4.8 875 390 610 587 498 886 66 42
275 5.5 5.5 5.0 5.1

208 5.8 5.8 5.3 5.3


DSP 18 + RAC 6 252 6.0 6.1 5.5 5.5 875 390 610 945 856 1245 66 33
284 6.2 6.2 5.6 5.7

220 6.0 6.0 5.5 5.5


DSP 18 + CMD 8 275 6.3 6.3 5.7 5.8 875 390 610 587 498 886 66 42
334 6.5 6.5 5.9 5.9

56 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Air Cooling Capacity (kW) Dimensions (mm) Dimensions (mm) Operating Operating
Flow weight weight
Models @35°C Ambient @46°C Ambient Outdoor Unit Indoor Unit (kg) (kg)
Rate
(L/s) 50Hz 60Hz 50Hz 60Hz L W H L W H Outdoor Indoor
237 6.9 7.7 6.3 7.2
DSP 24 + RAC 8 283 7.2 8.0 6.6 7.4 875 390 610 087 998 1387 66 50
327 7.4 8.2 6.8 7.6

275 6.7 7.5 6.2 7.0


DSP 24 + CMD 10 334 7.0 7.8 6.4 7.3 875 390 610 587 498 886 66 42
368 7.1 8.0 6.5 7.4

237 7.5 8.3 7.0 7.7


DSP 30 + RAC 8 283 7.8 8.7 7.2 8.0 875 390 610 1087 998 1387 66 50
327 8.0 8.9 7.4 8.3

346 8.2 9.2 7.6 8.5


DSP 30 + RAC 10 410 8.5 9.6 7.9 8.8 875 390 610 1628 1539 1928 66 54
476 8.7 9.8 8.1 9.1

275 7.7 8.6 7.2 7.9


DSP 30 + CMD 10 334 8.0 8.9 7.4 8.3 875 390 610 587 498 886 66 42
368 8.2 9.1 7.6 8.4

410 9.6 10.7 8.8 9.8


DSP 36 + RAC 12 476 9.9 11.0 9.1 10.1 875 390 762 1628 1539 928 83 54
550 10.1 11.3 9.3 10.3

529 10.2 11.3 9.3 10.3


DSP 36 + CMD 16 586 10.3 11.5 9.4 10.5 875 390 762 942 853 1242 83 64
628 10.5 11.6 9.5 10.6

529 12.5 13.9 11.5 12.9


DSP 48 + CMD 16 586 12.7 14.2 11.8 13.1 875 390 1170 942 853 1242 114 64
628 12.8 14.4 11.9 15.9

663 12.5 14.0 11.6 13.0


DSP 48 + CM 15 736 12.7 14.3 11.8 13.2 875 390 1170 985 1059 540 114 111
810 12.9 14.5 12.0 13.4

639 15.1 17.1 14.0 15.7


DSP 60 + CMD 20 687 15.3 17.4 14.2 15.9 875 390 1170 1196 1107 1496 114 73
741 15.5 17.7 14.4 16.2

849 15.4 17.5 14.2 16.0


DSP 60 + CM 20 944 15.6 17.8 14.4 16.3 875 390 1170 1165 1059 540 114 125
1.038 15.8 18.1 14.6 16.5

• Data based on 7.2°C condenser suction temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 57


DUCTED SPLIT UNIT

DSP Low
Low Capacity Ducted Split Unit
with Scroll Compressor

R
407c

Air Cooling Capacity (kW) Dimensions (mm) Dimensions (mm) Operating Operating
Flow weight weight
Models @35°C Ambient @46°C Ambient Outdoor Unit Indoor Unit (kg) (kg)
Rate
(L/s) 50Hz 60Hz 50Hz 60Hz L W H L W H Outdoor Indoor

178 5.1 5.2 4.7 4.8


DSP 15 + RAC 5 208 5.3 5.4 4.9 5.0 875 390 610 945 856 1245 66 33
252 5.5 5.6 5.0 5.2

161 4.8 4.8 4.4 4.4


DSP 15 + CMD 6 220 5.2 5.2 4.7 4.8 875 390 610 587 498 886 66 42
275 5.5 5.5 5.0 5.0

208 5.7 5.8 5.2 5.3


DSP 18 + RAC 6 252 5.9 6.0 5.5 5.5 875 390 610 945 856 1245 66 33
284 6.1 6.2 5.6 5.6

220 5.9 5.9 5.4 5.5


DSP 18 + CMD 8 275 6.2 6.2 5.7 5.7 875 390 610 587 498 886 66 42
334 6.4 6.5 5.8 5.9

58 QUICK SELECTION GUIDE - SI Units 2017


R
407c

Air Cooling Capacity (kW) Dimensions (mm) Dimensions (mm) Operating Operating
Flow weight weight
Models @35°C Ambient @46°C Ambient Outdoor Unit Indoor Unit (kg) (kg)
Rate
(L/s) 50Hz 60Hz 50Hz 60Hz L W H L W H Outdoor Indoor
237 6.7 7.4 6.3 6.8
DSP 24 + RAC 8 283 7.0 7.7 6.6 7.1 875 390 610 1087 998 1387 66 50
327 7.2 8.0 6.8 7.3

275 6.6 7.3 6.0 6.7


DSP 24 + CMD 10 334 6.8 7.6 6.2 6.9 875 390 610 587 498 886 66 42
368 6.9 7.7 6.3 7.0

237 7.5 8.3 6.9 7.6


DSP 30 + RAC 8 283 7.9 8.7 7.2 7.9 875 390 610 1087 998 1387 66 50
327 8.1 8.9 7.4 8.2

346 8.3 9.9 7.6 8.4


DSP 30 + RAC 10 346 8.6 9.9 7.8 8.7 875 390 610 1628 1539 1928 66 54
346 8.9 9.9 8.0 8.9

275 7.8 8.6 7.1 7.8


DSP 30 + CMD 10 334 8.1 8.9 7.4 8.1 875 390 610 587 498 886 66 42
368 8.2 9.1 7.5 8.3

410 9.6 10.6 8.7 9.7


DSP 36 + RAC 12 476 9.8 10.8 9.0 9.9 875 390 762 1628 1539 1928 83 54
550 10.0 11.1 9.2 10.2

529 10.1 11.2 9.2 10.2


DSP 36 + CMD 16 586 10.2 11.4 9.3 10.4 875 390 762 942 853 1242 83 64
628 10.3 11.5 9.4 10.5

529 12.3 13.6 11.2 12.5


DSP 48 + CMD 16 586 12.5 13.9 11.4 12.7 875 390 1170 942 853 1242 114 64
628 12.7 14.1 11.6 12.9

663 12.4 13.7 11.3 12.6


DSP 48 + CM 15 736 12.6 14.0 11.5 12.8 875 390 1170 985 1059 540 114 111
810 12.7 14.2 11.7 13.0

639 14.9 16.4 13.6 15.0


DSP 60 + CMD 20 687 15.1 16.7 13.7 15.3 875 390 1170 1196 1107 1496 114 73
741 15.3 16.9 13.9 15.5

849 15.2 16.8 13.8 15.3


DSP 60 + CM 20 944 15.4 17.1 14.0 15.6 875 390 1170 1165 1059 540 114 125
1,038 15.6 17.3 14.2 15.8

• Data based on 26.7/19.4°C entering dry/wet bulb air temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 59


DUCTED SPLIT UNIT

DSP Low
Low Capacity Ducted Split Unit
with Scroll Compressor

R
134a

Air Cooling Capacity (kW) Dimensions (mm) Dimensions (mm) Operating Operating
Flow weight weight
Models @35°C Ambient @46°C Ambient Outdoor Unit Indoor Unit (kg) (kg)
Rate
(L/s) 50Hz 60Hz 50Hz 60Hz L W H L W H Outdoor Indoor

178 4.0 4.5 3.7 4.2


DSP 15 + RAC 5 208 4.2 4.7 3.8 4.3 875 390 610 945 856 1245 66 33
252 4.3 4.9 4.0 4.5

161 4.0 4.5 3.7 4.1


DSP 15 + CMD 6 220 4.3 4.9 4.0 4.5 875 390 610 587 498 886 66 42
275 4.5 5.1 4.1 4.7

208 4.8 5.4 4.5 5.0


DSP 18 + RAC 6
252 5.0 5.7 4.7 5.3 875 390 610 945 856 1245 66 33
284 5.2 5.8 4.8 5.4

220 5.0 5.6 4.6 5.2


DSP 18 + CMD 8 275 5.2 5.9 4.9 5.5 875 390 610 587 498 886 66 42
334 5.5 6.2 5.0 5.7

60 QUICK SELECTION GUIDE - SI Units 2017


R
134a

Air Cooling Capacity (kW) Dimensions (mm) Dimensions (mm) Operating Operating
Flow weight weight
Models @35°C Ambient @46°C Ambient Outdoor Unit Indoor Unit (kg) (kg)
Rate
(L/s) 50Hz 60Hz 50Hz 60Hz L W H L W H Outdoor Indoor
237 5.7 6.3 5.2 5.9
DSP 24 + RAC 8 283 5.9 6.6 5.4 6.1 875 390 610 1087 998 1387 66 50
327 6.0 6.8 5.6 6.3

275 5.8 6.5 5.4 6.0


DSP 24 + CMD 10 334 6.0 6.8 5.6 6.3 875 390 610 587 498 886 66 42
368 6.2 6.9 5.7 6.4

237 6.1 6.7 5.6 6.2


DSP 30 + RAC 8 283 6.3 7.0 5.8 6.4 875 390 610 1087 998 1387 66 50
327 6.5 7.2 6.0 6.7

346 7.1 7.9 6.5 7.2


DSP 30 + RAC 10 410 7.3 8.2 6.7 7.5 875 390 610 1628 1539 1928 66 54
476 7.5 8.4 6.9 7.7

275 6.2 6.9 5.8 6.4


DSP 30 + CMD 10 334 6.5 7.2 6.0 6.7 875 390 610 587 498 886 66 42
368 6.6 7.3 6.1 6.8

410 8.4 9.4 7.7 8.6


DSP 36 + RAC 12 476 8.6 9.7 7.9 8.9 875 390 762 1628 1539 1928 83 54
550 8.8 10.0 8.1 9.1

529 8.9 10.0 8.1 9.2


DSP 36 + CMD 16 586 9.0 10.2 8.3 9.3 875 390 762 942 853 1242 83 64
628 9.1 10.3 8.3 9.5

529 10.5 11.8 9.7 11.0


DSP 48 + CMD 16 586 10.7 12.0 9.9 11.2 875 390 1170 942 853 1242 114 64
628 10.8 12.2 10.1 11.3

663 10.6 11.9 9.8 11.1


DSP 48 + CM 15 736 10.8 12.1 10.0 11.3 875 390 1170 985 1059 540 114 111
810 10.9 12.3 10.1 11.4

639 13.4 14.9 12.3 13.7


DSP 60 + CMD 20 687 13.6 15.2 12.4 13.9 875 390 1170 1196 1107 1496 114 73
741 13.8 15.4 12.6 14.1

849 13.6 15.2 12.5 13.9


DSP 60 + CM 20 944 13.9 15.5 12.7 14.2 875 390 1170 1165 1059 540 114 125
1,038 14.0 15.7 12.8 14.4

• - Data based on 26.7/ 19.4°C entering dry/wet bulb air temperature


• - All information contained in this table is subject to change without prior notice
• - For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 61


PETRA RESEARCH & DEVELOPMENT LABORATORY

62 QUICK SELECTION GUIDE - SI Units 2017


MINI SPLIT
UNIT

QUICK SELECTION GUIDE - SI Units 2017 63


MINI SPLIT UNITS

HPW INV.
Wall Mounted Inverter Type

PETRA 12 H INV. + PETRA 20 H INV. + PETRA 25 H INV. +


Models
HPC 12 INV. HPC 20 INV. HPC 25 INV.
Nominal Cooling Capacity kW 3.5 5.3 7.0
Indoor air flow High/Med/Low L/s 175/160/110 235/175/150 320/265/210
Dimension (WxDxH) mm 813x178x305 965x254x330 1092x229x330
Indoor unit Packing (WxDxH) mm 864x279x381 1041x305x406 1143x406x305
Net/Gross weight kg 8/10 10/13 13/17
Dimension (WxDxH) mm 813x305x559 813x305x559 838x330x711
Outdoor unit Packing (WxDxH) mm 940x406x610 940x406x610 965x406x762
Net/Gross weight kg 30/33 36/39 50/54
Thermostat type Remote control
Outdoor Operation temperature (Cooling/Heating) °C 15-50 / 0-30 15-50 / 0-30 15-50 / 0-30

PETRA H INV.
Outdoor unit - Inverter Type

• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

64 QUICK SELECTION GUIDE - SI Units 2017


HPC INV.
Cassette Inverter Type

PETRA 25 H INV. PETRA 36 H INV. + PETRA 60 H INV. +


Models
+ HPC 25 INV. HPC 36 INV. HPC 60 INV.
Nominal Cooling Capacity kW 7.0 10.6 17.6
Indoor air flow High/Med/Low L/s 495/434/378 562/500/415 637/585/500
Dimension (WxDxH) mm 838x838x254 838x838x254 838x838x305
Indoor unit Packing (WxDxH) mm 889x889x279 889x889x279 889x889x330
Net/Gross weight kg 24/28 26/30 26/30
Dimension (WxDxH) mm 813x305x559 940x406x813 940x381x1372
Outdoor unit Packing (WxDxH) mm 940x406x610 1092x483x864 1092x483x1499
Net/Gross weight kg 37/40 69/74 107/120
Thermostat type Remote control
Outdoor Operation temperature (Cooling/Heating) °C 15-50 / 0-30 15-50 / 0-30 15-50 / 0-30

HPFS INV.
Free Standing Inverter Type

Models PETRA 60 H INV. + HPFS 60 INV.


Nominal Cooling Capacity kW 17.6
Dimension (WxDxH) mm 610x381x1930
Indoor unit Packing (WxDxH) mm 686x457x1956
Net/Gross weight kg 70/74
Dimension (WxDxH) mm 940x381x1372
Outdoor unit Packing (WxDxH) mm 1092x483x1499
Net/Gross weight kg 107/120
Thermostat type Remote control
Outdoor Operation temperature (Cooling/Heating) °C 15-50 / 0-30

• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 65


PETRA ACOUSTIC LABORATORY

66 QUICK SELECTION GUIDE - SI Units 2017


COMPUTER
ROOM

QUICK SELECTION GUIDE - SI Units 2017 67


COMPUTER ROOM

PASC
Air Conditioner Split
»Scroll
»
»EC
»Cu/Al
»
»Steam
»
compressor
» technology for supply fan
cooling coil
humidifier & electric heater
Computer Room Units

68 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Cooling Capacity (kW)


Dimensions (mm) Heater umidifier
Models Operating
@35°C Ambient @46°C Ambient Capacity Capacity
(PASC4) weight (kg)
(kW) (kg/hr)
50Hz 60Hz 50Hz 60Hz L W H
35 10 12 9 10 750 860 1975 3 3 250
45 14 16 12 14 750 860 1975 3 3 260
55 16 19 14 17 750 860 1975 3 3 280
85-1 23 26 20 24 750 860 1975 6 5 300
85-2 26 31 23 28 1100 860 1975 6 5 420
115 33 39 29 34 1350 860 1975 7.5 8 500
145 38 45 33 40 1600 860 1975 9 10 600
175 49 58 43 52 1960 860 1975 9 10 750
200 63 73 55 65 1960 860 1975 12 15 780
250 67 78 59 70 1960 860 1975 12 15 800

R
407c

Cooling Capacity (kW)


Dimensions (mm) Heater umidifier
Models Operating
@35°C Ambient @46°C Ambient Capacity Capacity
(PASCc) weight (kg)
(kW) (kg/hr)
50Hz 60Hz 50Hz 60Hz L W H
35 10 11 9 10 750 860 1975 3 3 250
45 13 15 11 13 750 860 1975 3 3 260
55 16 18 15 17 750 860 1975 3 3 280
85-1 25 28 23 26 750 860 1975 6 5 300
85-2 24 29 21 26 1100 860 1975 6 5 420
115 32 37 29 34 1350 860 1975 7.5 8 500
145 40 46 36 42 1600 860 1975 9 10 600
175 52 60 47 55 1960 860 1975 9 10 750
200 52 72 57 65 1960 860 1975 12 15 780
250 58 79 62 71 1960 860 1975 12 15 800

• Data based on 23.9/17.2°C entering/leaving dry bulb temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 69


COMPUTER ROOM

PASC CM
Mini Computer Room Units
»Scroll
»
»DWDI
»
»Cu/Al
»
»Steam
»
compressor
direct drive supply fan
cooling coil
humidifier & electric heater
Ceiling / Wall / Floor Mounted

Wall/Floor type

Ceiling type

70 QUICK SELECTION GUIDE - SI Units 2017


R
410a

Cooling Capacity (kW) PASC CM Dimensions (mm)


Models
Ambient Temperature Ceiling Type Wall Type
Outdoor + Indoor 35°C 46°C L W H L W H
DSP4 18 + PASC CM 15 7.4 6.2
1060 1100 600 1400 380 980
DSP4 24 + PASC CM 15 8.3 7.4
DSP4 36 + PASC CM 20 12.1 10.9
1060 1100 600 1400 380 980
DSP4 48 + PASC CM 20 16.4 16.0
DSP4 60 + PASC CM 24 20.4 18.8
1060 1320 600 1600 380 980
DSP4 95 + PASC CM 24 32.1 29.0

R
407c

Cooling Capacity (kW) PASC CM Dimensions (mm)


Models
Ambient Temperature Ceiling Type Wall Type
Outdoor + Indoor 35°C 46°C L W H L W H
DSPc 18 + PASC CM 15 6.2 5.6
1060 1100 600 1400 380 980
DSPc 24 + PASC CM 15 7.2 6.5
DSPc 36 + PASC CM 20 12.5 11.5
1060 1100 600 1400 380 980
DSPc 48 + PASC CM 20 16.4 14.9
DSPc 60 + PASC CM 24 19.4 17.1
1060 1320 600 1600 380 980
DSPc 95 + PASC CM 24 29.9 27.0

• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce

QUICK SELECTION GUIDE - SI Units 2017 71


DRY COOLER
PDC
Petra Dry Cooler

Cooling Capacity (kW)


Models Dimensions (mm) Operating weight
(PDC) @35°C Ambient @46°C Ambient (kg)
50Hz 60Hz 50Hz 60Hz L W H
30 14 16 12 14 1040 1225 600 100
60 19 21 16 18 1040 1225 600 115
90 25 30 22 26 1020 1520 1450 180
110 55 60 48 52 1020 1520 1790 230
245 71 78 61 67 1020 2230 1780 480
495 142 156 122 134 2230 1580 2300 725
990 284 312 244 268 2960 2230 2300 790
1480 426 467 366 402 4340 2230 2340 2,235
1970 568 623 488 535 5720 2230 2340 3,150
2465 709 779 610 669 7100 2230 2340 3,910
2960 851 935 732 803 8480 2230 2340 4,670
3450 993 1,091 854 937 9860 2230 2340 5,530
3945 1,135 1,246 976 1,071 11240 2230 2340 6,270
4440 1,277 1,402 1,098 1,205 12620 2230 2380 -
4935 1,419 1,558 1,220 1,338 14000 2230 2380 -

• Data based on AHRI conditions: 12.2/6.7°C entering/leaving water temperature


• All information contained in this table is subject to change without prior notice
• For more technical data, please contact your nearest Petra sales ofce