Ametek Manual 049 Power Pro 100
Ametek Manual 049 Power Pro 100
Ametek Manual 049 Power Pro 100
POWER PRO
FERRO 100 SERIES CHARGERS
DO NOT DESTROY
NOTE: Information regarding obtaining additional copies of this manual is located in the Introduction
chapter of this manual.
A battery charger is identified by model number. Incorporated into the model number is the 8-hour
ampere-hour capacity, case size, input power phase, and number of cells in battery for which charger is
intended. The following example explains the basic model numbering arrangement.
Ferroresonant
Number of Cells
INTRODUCTION ........................................................................................................................................ 1
How to use this Manual ......................................................................................................................1-1
Equipment Identification .....................................................................................................................1-1
Receipt of Equipment .........................................................................................................................1-1
INSTALLATION ......................................................................................................................................... 4
Location ..............................................................................................................................................4-1
Environmental Characteristics............................................................................................................4-1
Grounding...........................................................................................................................................4-1
Line Voltage Changeover Instructions ...............................................................................................4-2
Line Connections to Battery Charger .................................................................................................4-2
Charging Cable Connectors ...............................................................................................................4-3
Pre-operation Checks.........................................................................................................................4-3
OPERATION .............................................................................................................................................. 5
Preliminary..........................................................................................................................................5-1
Normal or Daily Charge .....................................................................................................................5-1
Equalize or Weekend Charge ............................................................................................................5-2
Manual Stop .......................................................................................................................................5-2
Refresh Charge ..................................................................................................................................5-2
Backup Timer Shutdown ....................................................................................................................5-2
Battery Disconnect Shutdown ............................................................................................................5-2
AC Power Fail.....................................................................................................................................5-2
MAINTENANCE ......................................................................................................................................... 6
Inspection and Cleaning .....................................................................................................................6-1
Lubrication ..........................................................................................................................................6-1
Fuse Replacement .............................................................................................................................6-1
Silicon Diode Testing..........................................................................................................................6-1
Capacitor Testing ...............................................................................................................................6-2
Troubleshooting..................................................................................................................................6-3
WARRANTY
INTRODUCTION
How To Use This Manual NOTE offers helpful information concerning
certain operating procedures. Notes will be
shown in italics.
INSTALLATION
Location In addition to the usual function of protecting personnel
against the hazard of electrical shock due to fault in the
For best operating characteristics and longest unit life, equipment, grounding serves to discharge the static
take care in selecting an installation site. Avoid electrical charges which tend to build up on the
locations exposed to high humidity, dust, high ambient surfaces of equipment. These static charges can
temperature, or corrosive fumes. Moisture can cause painful shock to personnel, and can lead to the
condense on electrical components, causing corrosion erroneous conclusion that an electrical fault exists in
or shorting of circuits (especially when dirt is also the equipment.
present).
If a charger is to be connected to the AC power supply
Adequate air circulation is needed at all times in order with a flexible jacketed cable, one having a separate
to assure proper operation. Provide a minimum of 6 grounding conductor should be used. When included
inches of free air space at rear and sides of the unit. in cable assembly, grounding conductor will be green,
Make sure that ventilation openings are not obstructed. green with a yellow stripe, or bare. When connecting
Always remove the charger shipping skid from the unit input power to charger (as instructed in Line
before installation. The charger must be installed over Connection to Battery Charger section of this manual),
a noncombustible surface such as concrete or metal. connect grounding conductor to equipment grounding
Keep the charging area clear of all combustible terminal (stud with a green nut and a cup washer and
material such as wood, paper, and cloth. identified by symbol ), taking care to make a
good electrical connection. Connect other end of
WARNING: SPARKS OR MOLTEN METAL falling grounding conductor to the system ground.
through open bottom can cause fire or explosion. If, for any reason, an input cable which does not in-
• Install over noncombustible material such as clude a grounding conductor is used, the equipment
concrete or metal. must be grounded with separate conductor. Minimum
size and color coding requirements must be in accor-
dance with any applicable state or local code, or the
• Keep charging area clear of combustible
National Electrical Code.
material.
If metallic armored cable or conduit is used, the metal
Environmental Characteristics sheathing or conduit must be effectively grounded as
required by state or local code, or the National
Operating Characteristics 0°C to 40°C Electrical Code.
(32°F to 104°F)
If a system ground is not available, the charger frame
Operating Altitude To 2000 Meters must be connected to a driven ground rod (at least 8 ft
(6562 Feet) [2438 mm] long), or to a water pipe that enters the
Operating Humidity 80% up to 31°C, ground not more than 10 ft (3048 mm) from the
decreasing to 50% at charger. A grounding conductor must be connected to
40°C, non-condensing the rod or pipe in a manner that will assure a
permanent and effective ground. The conductor must
80% up to 88°F be sized in accordance with any applicable state or
decreasing to 50% at local code, or by the National Electrical Code. If in
104°F, non-condensing doubt, use the same size conductor as is used for the
conductors supplying power to the charger.
Grounding
The frame of the power source must be grounded for WARNING: ELECTRIC SHOCK Hazard -
personnel safety. Where grounding is mandatory Under no circumstance should you use
under state or local codes, it is the responsibility of the
user to comply with all applicable rules and regulations.
a grounding conductor with a current
Where no state or local codes exist, it is recommended carrying capacity less than the ampere
that the National Electrical Code be followed. rating shown in Table 4-1.
The above table (Table 4-1) is based on 75°C (167°F) rated conductors and 40°C (104°F) ambient temperatures.
Refer to National Electrical Code (2008) Tables 310-16 corrected to 40°C (104°F).
* For 115, 208, and 230-volt lines, use 250-volt disconnect switch.
For 440-480, 575-volt lines, use 600-volt disconnect switch.
** Two conductors and ground conductor required for single phase.
Three conductors and ground conductor required for three phase.
Recommended minimum size of grounding conductors (based on National Electrical Code 2008 – Table 250-95).
3. If charger is reconnected, check input fuse (s) 3. On charger nameplate, note the AC input amperes
ratings with ratings specified on label and replace corresponding to the line voltage to which charger
if necessary. is to be connected. Use that ampere value to select
the proper disconnect switch, fuse, and power cable
sizes from Table 4-1.
OPERATION
A. Preliminary B. Normal or Daily Charge
Make sure the charger is installed and grounded as WARNING: DO NOT connect a battery to
instructed in the INSTALLATION chapter of this this charger if the “Charge in Progress”
manual. LED is lit. Do not disconnect a battery from
this charger while a charge is in progress;
Maintain electrolyte level in the batteries to be otherwise, arcing and burning of connector
charged, as instructed by the battery manufacturer. parts or a battery explosion may result.
Because the volume of electrolyte expands during Batteries produce explosive gases. Keep
the charging process, only add water when the sparks, flame, and cigarettes away.
battery is at least 80% charged. An amber light will Ventilate when charging in an enclosed
be illuminated on the charger control panel when area. Always shield eyes when working
the battery is at or above 80% charge. near batteries.
Battery ampere-hour capacity must be within the 2. Securely engage the battery and charger
ampere-hour range stated on the charger data connectors.
plate.
3. After a five second delay (all LED‘s will be lit),
the charger will turn on. The “Charge in
WARNING: EXPLOSION HAZARD – Do not Progress” LED will indicate charging current.
connect a battery to this charger if the
“Charge in Progress” LED is illuminated on 4. The “80% CHARGED” LED will light when the
the charger. Do not disconnect a battery battery on charge reaches the 80% charged
from this charger if the “Charge in Progress” voltage.
LED is illuminated or ammeter is indicating
charging current; otherwise, arcing and 5. The charger will automatically turn off and the
burning of connector parts can occur or a “Charge Complete” LED will light when the
battery explosion may result. Batteries charge has finished. reaching 80% charge.
produce explosive gases. Keep sparks, The light will remain on until the battery is
flames, and cigarettes away. Ventilate when disconnected from the charger.
charging in an enclosed area. Always
shield eyes using face shield and goggles
when working near batteries. NOTE: To disconnect battery from charger before
charge is complete, first press the “Manual
Stop” key, then disconnect the battery
from the charger.
CAUTION: The charging of a battery with
the incorrect number of cells or an ampere-
hour capacity outside the range stated on
the charger data plate will result in severe
over or under charging of the battery,
resulting in reduced battery performance
and life.
MAINTENANCE
Lubrication
WARNING: ELECTRICAL SHOCK
HAZARD — Before inspecting or None required.
cleaning inside cabinet, turn OFF
and remove fuses of disconnect
switch (supplying AC power to Fuse Replacement
charger), disconnect battery, and
check for voltage on capacitors. The silicon diodes in this charger are protected by a
Discharge through insulated “fast-clearing” type fuse.
screwdriver if there is any reading.
CAUTION: The use of any other type
fuse besides the “fast-clearing” type
may cause damage to silicon diodes.
Inspection And Cleaning
Silicon Diode Testing
For uninterrupted, satisfactory service from this
charger, it's necessary to keep unit clean, dry, and well WARNING: ELECTRICAL SHOCK
ventilated. At least every three months, or more often HAZARD — Before checking electrical
as necessary, wipe and blow out all dirt from unit's components, turn OFF and remove
interior components, with clean, dry air of not over fuses of disconnect switch (supplying
25 psi (172 kPa) pressure. Use a hand bellows if AC power to charger), disconnect
compressed air isn't available. battery, and check for voltage on
capacitors. Discharge through insulated
Check and tighten all electrical connections as screwdriver if there is any reading.
necessary to eliminate unnecessary losses and to
avoid subsequent trouble from overheating or open
circuits. Check for broken wiring or damaged insulation 1. Disconnect one diode lead to isolate diode from
on wiring. electrical circuitry.
Be sure to replace all charger cabinet panels after any 5. Reverse ohmmeter leads on diode and record
servicing, to assure proper flow of cooling air through indicated resistance.
unit and to protect internal components.
6. Consider diode good if one resistance reading is
infinitely (or very) high and the other is extremely
WARNING: ELECTRICAL SHOCK low.
HAZARD — All cabinet panels must
be replaced to protect personnel from NOTE: An acceptable low resistance value
contact with hazardous voltages. or range of values can't be given because of
different readings from different ohmmeters,
and differences in diodes of the same rating.
Capacitor Testing
1. Heed WARNING in Silicon Diode Testing section.
Troubleshooting
CAUTION: HIGH VOLTAGE FROM TEST EQUIPMENT can damage silicon diodes and other
parts. Short silicon diodes with extremely short leads, or disconnect, before applying voltage
from a "megger" or other high voltage test equipment.
The following chart contains information which can be used to diagnose and correct unsatisfactory operation
or failure of various components of the unit. Each malfunction is followed by a suggested checking or inspection
procedure. Refer to Connection/Schematic Diagram in the Diagrams chapter included in this manual.
Troubleshooting Guide
Replace blown fuses. See Table 4-1 for proper fuse sizes.
Connect a jumper from the red-white lead of Control Transformer T1 to the red
lead of Contactor K1 coil. If charger starts and ammeter shows charging current
when a battery is connected, check further for faulty printed circuit card on control
and replace as necessary.
Check output circuit fuses. If fuse has blown, check for problem causing fuse to blow.
Replace capacitor if can is ruptured or fails test. Refer to Capacitor Testing in Maintenance chapter.
Less than rated output on fully discharged battery (approximately 1/2 rated output) (3-phase
chargers only)
Replace as necessary.
1. If charger does not start automatically, check for 24 volts AC between the red-white lead and
the red-black wire of control transformer T1. If 24V AC is present, connect a jumper from the
red-white lead of control transformer T1 to the red lead of contactor K1 coil. If charger
starts, check further for faulty printed circuit card on control and replace as necessary.
2. If charger does not stop automatically when equipped with pt/dv/dt control,
check to be sure charging voltage rises above 2.37 volts/cell during the cycle. If not, see low
charging current or less than rated output above. If battery on-charge voltage rises above
2.37 volts/cell during the cycle, check for defective control printed circuit card.
DANGER: ELECTRICAL SHOCK HAZARD — Before checking electrical components, turn OFF and
remove fuses of disconnect switch (supply AC power to charger), disconnect battery, and check for
voltage on capacitors. Discharge through insulated screwdriver if there is any reading.
DANGER: ELECTRICAL SHOCK HAZARD — Before checking electrical components, turn OFF and
remove fuses of disconnect switch (supply AC power to charger), disconnect battery, and check for
voltage on capacitors. Discharge through insulated screwdriver if there is any reading.
DANGER: ELECTRICAL SHOCK HAZARD — Before checking electrical components, turn OFF and
remove fuses of disconnect switch (supply AC power to charger), disconnect battery, and check for
voltage on capacitors. Discharge through insulated screwdriver if there is any reading.
August 9, 2002
MODEL OUTPUT T2 T3 DIODE CAPS INPUT CONTROL OUTPUT
NUMBER SPEC FUSE TRANS TRANS CONTACTOR (4 Required) /TRANS LABEL TRANS CABLE
12-510FR100T 500522-1 409023-4 195082 195083 406243-1 193143-1 TRY-154-4 191457 406247-2 396143-2
12-600FR100T 500523-1 409023-4 195091 195092 406243-1 193143-1 TRY-154-4 191457 406247-2 396143-2
12-750FR100T 500524-1 409023-5 195100 195101 406243-1 402832-3 TRY-154-6 191457 406247-2 396143-4
12-880FR100T 500525-1 409023-6 195109 195110 406243-1 402832-3 TRY-154-4 191457 406247-2 396143-4
TRY-154-1
12-1050FR100T 500526-1 409023-7 195118 195119 406243-1 402832-3 TRY-154-4 191457 406247-2 396143-5
TRY-154-1
18-510FR100T 500527-1 409023-4 195127 195128 406243-1 193143-1 TRY-154-4 191457 406247-2 396143-2
18-600FR100T 500528-1 409023-4 195136 195137 406243-1 193143-1 TRY-154-4 191457 406247-2 396143-2
TRY-154-2
18-750FR100T 500529-1 409023-5 195145 195146 406243-1 402832-3 TRY-154-4 191457 406247-2 396143-4
TRY-154-2
18-880FR100T 500530-1 409023-6 195154 195155 406243-1 402832-3 TRY-154-6 191457 406247-2 396143-4
18-965FR100T 500531-1 409023-7 195163 195164 406244-1 402832-3 TRY-154-4 191457 406247-2 396143-5
TRY154-2
18-1050FR100T 500532-1 409023-7 195172 195173 406244-1 402832-3 TRY-154-4 191457 406247-2 396143-5
TRY-154-2
18-1100FR100T 500533-1 409023-8 195181 195182 406244-1 402832-3 TRY-154-4 191457 406247-2 396143-5
TRY-154-2
18-1200FR100T 500534-1 409023-8 195190 195191 406244-1 402832-3 TRY-154-4 191457 406247-2 396143-5
TRY-154-3
24-450FR100T 500535-1 409023-4 195199 195200 406243-1 193143-1 TRY-154-6 191457 406247-2 396143-2
24-600FR100T 500536-1 409023-4 195208 195209 406243-1 193143-1 TRY-154-6 191457 406247-2 396143-2
24-750FR100T 500537-1 409023-5 195217 195218 406244-1 402832-3 TRY-154-4 191457 406247-2 396143-4
TRY-154-2
24-880FR100T 500538-1 409023-6 195226 195227 406244-1 402832-3 TRY-154-6 191457 406247-2 396143-4
24-965FR100T 500539-1 409023-7 195235 195236 406244-1 402832-3 TRY-154-6 191457 406247-2 396143-5
7-4
PARTS LIST (3 PHASE)
193111-049
3 PHASE
7-5
480/575 VOLT
UNITS
193111-049
AC
MODEL OUTPUT T2 T3 DIODE CAPS INPUT CONTROL OUTPUT
NUMBER SPEC FUSE TRANS TRANS CONTACTOR (4 Required) /TRANS LABEL TRANS CABLE
12-510FR100T 500522-2 409023-4 195086 195087 406243-1 193143-1 TRY-154-4 191252 406247-4 396143-2
PARTS LIST (3 PHASE)
12-600FR100T 500523-2 409023-4 195095 195096 406243-1 193143-1 TRY-154-4 191252 406247-4 396143-2
12-750FR100T 500524-2 409023-5 195104 195105 406243-1 402832-3 TRY-154-6 191252 406247-4 396143-4
12-880FR100T 500525-2 409023-6 195113 195114 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-4
TRY-154-1
12-1050FR100T 500526-2 409023-7 195122 195123 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-5
TRY-154-1
18-510FR100T 500527-2 409023-4 195131 195132 406243-1 193143-1 TRY-154-4 191252 406247-4 396143-2
18-600FR100T 500528-2 409023-4 195140 195141 406243-1 193143-1 TRY-154-4 191252 406247-4 396143-2
TRY-154-2
18-750FR100T 500529-2 409023-5 195149 195150 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-4
TRY-154-2
18-880FR100T 500530-2 409023-6 195158 195159 406243-1 402832-3 TRY-154-6 191252 406247-4 396143-4
18-965FR100T 500531-2 409023-7 195167 195168 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-5
TRY154-2
18-1050FR100T 500532-2 409023-7 195176 195177 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-5
TRY-154-2
18-1100FR100T 500533-2 409023-8 195185 195186 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-5
TRY-154-2
18-1200FR100T 500534-2 409023-8 195194 195195 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-5
TRY-154-3
24-450FR100T 500535-2 409023-4 195203 195204 406243-1 193143-1 TRY-154-6 191252 406247-4 396143-2
24-600FR100T 500536-1 409023-4 195212 195213 406243-1 193143-1 TRY-154-6 191252 406247-4 396143-2
24-750FR100T 500537-1 409023-5 195221 195222 406243-1 402832-3 TRY-154-4 191252 406247-4 396143-4
TRY-154-2
24-880FR100T 500538-1 409023-6 195230 195231 406243-1 402832-3 TRY-154-6 191252 406247-4 396143-4
24-965FR100T 500539-1 409023-7 195239 195240 406243-1 402832-3 TRY-154-6 191252 406247-4 396143-5
August 9, 2002
193111-049
DIAGRAMS (3 PHASE)
DIAGRAMS - 3 PHASE
DIAGRAM DIAGRAM
MODEL NO. OUTPUT SCHEMATIC OUTPUT SCHEMATIC DIMENSIONAL
INFORMATION 208/240/480 VOLTS 480/575V OUTLINE
3 PHASE
195432 195541 195542
(2 TRANSFORMERS)
August 9, 2002
193111-049
PARTS LIST (1 PHASE)
4 191581 Top
7 191574 Base
8-4
PARTS LIST (1 PHASE)
193111-049
8-5
1 PHASE
480/575 VOLT UNITS
193111-049
AC
MODEL OUTPUT DC T2 CAPS RECTIFIER INPUT CONTROL OUTPUT
NUMBER SPEC FUSE METER TRANS CONTACTOR /TRANS ASSEMBLY LABEL TRANS CABLE
12-510FR100S 500710-2 409023-4 195540-2 197873 406240-1 TRY-154-6 196699-1 191655 406247-4 396143-2
PARTS LIST (1 PHASE)
DIAGRAMS - 1 PHASE
DIAGRAM DIAGRAM
MODEL NO. OUTPUT SCHEMATIC OUTPUT SCHEMATIC DIMENSIONAL
INFORMATION 208/240/480 VOLTS 480/575V OUTLINE
1 PHASE
195433 197871 195859
(1 TRANSFORMER)
AMETEK/Prestolite Power (hereinafter called “Prestolite”) warrants that each new and unused Power Pro Battery Charger manufactured
and supplied by it is of good workmanship and is free from any inherent mechanical defects, provided that (1) the product is installed and
operated in accordance with generally accepted industrial standards and in accordance with the printed instructions of Prestolite, (2) the
product is used under normal conditions for which designed, (3) the product is not subjected to misuse, negligence or accident, and (4) the
product receives proper care, protection and maintenance under supervision of competent personnel. This warranty is subject to the
following provisions:
1.PRODUCTS AND PARTS WARRANTED. Subject to the exceptions listed below each Power Pro Battery Charger is warranted for
a period of one (1) year from the date of its shipment by Prestolite, provided the charger is used in accordance with Prestolite’s published
performance rating for the unit involved. The exceptions to this warranty are as follows:
a) Power transformers and diodes on unit(s) are warranted for ten (10) years after Prestolite’s shipment of the unit(s) of which they
are a part, provided, however, that during the last nine (9) years of this ten (10) year period the warranty covers parts
replacement only-no labor or other services are provided by Prestolite, nor shall Prestolite be obligated to reimburse the owner
or any other person for any work performed.
b) Primary switch contacts, fuses, bulbs, and filters are not warranted unless found to be defective prior to use.
2.COMMENCEMENT OF WARRANTY TIME PERIODS. The warranty periods indicated in the Warranty Schedule shall
commence on the date of shipment by Prestolite.
3.PERSONS COVERED BY WARRANTY. This warranty is extended by Prestolite only to the purchaser of new equipment from
Prestolite or one of its authorized distributors. The products purchased under this agreement shall be used exclusively by the buyer and
its employees and by no other persons, and therefore there shall be no third party beneficiary to this warranty.
4.LIMITATION OF REMEDY. The existence of claimed defects in any product covered by this warranty is subject to Prestolite’s
factory inspection and judgment. Prestolite’s liability is limited to repair of any defects found by Prestolite to exist or, at Prestolite’s
option, the replacement of the defective product. F.O.B. factory after the defective product has been returned by the purchaser at its
expense to Prestolite’s shipping place. Replacement parts will be warranted for the remainder of the original Power Pro Battery Charger
Warranty or for a period of ninety (90) days, whichever is greater.
PRESTOLITE and its authorized distributors or dealers shall not be liable for direct or indirect, special or consequential damages in
excess of such repair or replacement. In no event shall the purchaser be entitled to recover for contingent expenses resulting from, but not
limited to, telephone calls, telegrams, travel expenses, lodging, duties and taxes, labor, rental or replacement equipment, loss of business
or profits or other commercial losses.
5.USE OF DEFECTIVE PRODUCT. Continued use of a Power Pro Battery Charger after discovery of a defect VOIDS ALL
WARRANTIES.
6.ALTERED EQUIPMENT. Except as authorized in writing, the warranty specified does not cover any equipment that has been
altered by any party other that Prestolite.
EXCEPT AS STATED ABOVE, ALL OTHER WARRANTIES AND CONDITIONS, EITHER EXPRESSED OR IMPLIED,
INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE
EXCLUDED AND BUYER ASSUMES ALL RISK AND LIABILITY RESULTING FROM USE OF THE GOODS.
AMETEK/PRESTOLITE POWER NEITHER ASSUMES NOR AUTHORIZES ANY PERSONS TO ASSUME FOR
AMETEK/PRESTOLITE POWER ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OR USE OF THE GOODS
SOLD, AND THERE ARE NO ORAL AGREEMENTS OR WARRANTIES COLLATERAL TO OR AFFECTING THIS WRITTEN
WARRANTY.
WARNING
At all times, safety must be considered an important factor in the installation, servicing, and operation of the product, and skilled,
qualified technical assistance should be utilized.
AMETEK/PRESTOLITE POWER
TROY, OHIO, U.S.A.