Rooftops High Performance, Proven Reliability and Easy Installation
Rooftops High Performance, Proven Reliability and Easy Installation
Rooftops High Performance, Proven Reliability and Easy Installation
High performance,
proven reliability
and easy installation
Airfinity
Airfinity AFD
Airfinity XL
Models IC/IH
Airfinity Rooftops
Comfort and economy
When it comes to installing and maintaining an HVAC system, every cent counts. From your
initial capital investment to utility and maintenance expense, operating HVAC equipment
can have a significant impact on your bottom line. This is why a Trane® Airfinity™ rooftop
unit can be the perfect choice.
Trane delivers a product that is easy to install while providing exceptional reliability, meets
stringent performance requirements and is competitively priced. Trane rooftop solutions
deliver real value for you – and real comfort for your customer.
2 Airfinity
Key features and benefits
of the Trane Airfinity™ solution
30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270
IC 40 - 133
40 - 133
IH* 40 - 133
IC 141-247
140-237
IH 137-273
3
Airfinity™
4 Airfinity
Airfinity™ AFD option
Rooftop units with Adaptive Frequency™ Drive
To run efficiently, buildings need to be capable of adapting to indoor and outdoor conditions.
That’s why Trane Airfinity™ rooftop air sourced heat pumps can be equipped with variable speed technology
and intelligent control that adapt cooling and heating outputs to your building’s demand. It’s that simple.
5
Energy recovery solutions
To enhance energy savings and reduce operating costs, Airfinity rooftops can be equipped
with a heat recovery system. Heat recovery systems are ideal for climates in which there is
a significant difference between outdoor and indoor air temperature , for example during
winter months. Trane design ensures maximum efficiency with minimal impact on unit
footprint and installation time.
Energy Recovery
Module comprising:
• heat exchanger
• G4 filters
• dampers
• a fully integrated exhaust
fan to avoid overpressure
in the building.
Dry efficiency, ε % 81 80 78 77 75 73 71 76 74
Wheel diameter (mm) 1200 1200 1200 1200 1200 1200 1200 1500 1500
Airflow through the wheel* (m3/s) 2340 2740 3310 3820 4400 4850 5700 6560 7600
6 Airfinity
Energy Recovery Circuit (ERC)
The Energy Recovery Circuit features a dedicated high efficiency refrigeration circuit which uses exhaust air
to pre-heat or pre-cool the fresh air introduced into the building. By recovering the heat in the exhaust air,
the overall capacity of the machine can be increased by up to 25% in typical working conditions, without
significantly impacting power consumption*. As a result, the overall efficiency of the rooftop unit increased
considerably, especially at part load conditions.
The ERC is fully integrated into the unit, therefore having zero impact on the installation footprint. Moreover, an
exhaust module is provided as standard and mounted directly under the fresh air damper, avoiding the need of
additional equipment to manage the exhaust air for applications with low to medium static pressure requirements.
Thanks to the additional refrigeration circuit and tighter control of the exhaust air, Trane ERC system
guarantees superior performance when compared to alternative systems which utilize the outdoor coil.
Increases overall
capacity by up to 25%
thanks to thermodynamic
heat recovery on the
+25%
exhaust air.*
EX
AU
ER
OV
H
ST
AIR REC
* Capacity gain with thermodynamic heat recover depends on volume of fresh air intake, outdoor and conditions and building load.
For a detailed selection, please contact your Trane Sales Representative.
7
7
General data
Airfinity™
Models IC (Cooling only) IC038 IC039 IC040 IC048 IC049 IC050 IC058 IC059 IC060
Nominal airflow (m3/h) 7800 8300 8700 9000 10100 10600 11100 11300 12100
Net cooling capacity (1) (kW) 44,8 44,3 46,1 53,8 53,8 55,8 63,6 59,4 63,1
Total power input (1) (kW) 13,3 14,0 14,2 15,9 18,2 18,7 19,6 20,3 19,7
Net EER (1) 3,38 3,16 3,25 3,39 2,95 2,99 3,25 2,93 3,2
Seasonal energy efficiency (ηs,c) (2) (%) 188,6 148,6 184,6 173,4 139,4 177,4 169,4 138,2 161,8
SEER (2) 4,79 3,79 4,69 4,41 3,56 4,51 4,31 3,51 4,12
Outdoor sound power level (3) (dB(A)) 81 85 84 84 85 84 85 85 85
Length (mm) 2830 3020 3020 2830 3020 3020 2830 3020 3020
Width (mm) 2250 2250 2250 2250 2250 2250 2250 2250 2250
Height (mm) 1575 1575 1575 1575 1575 1575 1575 1575 1575
Operating weight (4) (kg) 914 1020 1132 985 1037 1144 985 1048 1148
Models IC (Cooling only) IC063 IC064 IC065 IC074 IC075 IC084 IC085 IC100 IC110 IC130
Nominal airflow (m3/h) 12600 12700 14000 15700 16100 17100 17300 20200 22200 26000
Net cooling capacity (1) (kW) 72,9 66,9 73,8 82,6 84,6 90,2 91,7 110,6 125,1 137,8
Total power input (1) (kW) 23,8 24,5 23,4 26,1 26,6 30,1 29,5 34,8 42,1 49,7
Net EER (1) 3,06 2,73 3,15 3,16 3,18 3 3,11 3,18 2,97 2,77
Seasonal energy efficiency (ηs,c) (2) (%) 172,2 138,2 164,2 143 167,8 143,8 169 169 160,2 152,2
SEER (2) 4,38 3,53 4,18 3,65 4,27 3,67 4,3 4,3 4,08 3,88
Outdoor sound power level (3) (dB(A)) 85 85 85 86 85 86 85 85 85 91
Length (mm) 2830 3020 3020 3900 3900 3900 3900 3900 3900 3900
Width (mm) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
Height (mm) 1575 1575 1575 1595 1595 1595 1595 1900 1900 1900
Operating weight (4) (kg) 985 1048 1185 1333 1374 1347 1380 1598 1602 1602
Models IH (Heat pump) IH038 IH040 IH050 IH060 IH065 IH075 IH085 IH100 IH110 IH130
Nominal airflow (m3/h) 7800 8700 10600 12100 13700 15700 16700 19800 21600 25500
Net cooling capacity (1) (kW) 40,2 44,5 54,3 62,6 69,7 80,9 85,3 106,2 119,3 133,8
Total power input (1) (kW) 13,4 13,0 16,9 19,9 24,5 28,0 30,1 35,1 42,0 49,4
Net EER (1) 3 3,42 3,21 3,15 2,84 2,89 2,83 3,03 2,84 2,71
Seasonal energy efficiency (ηs,c) (2) (%) 157,4 213,4 203,8 186,2 173 172,6 169,8 175,4 165,8 161
SEER (2) 4,01 5,41 5,17 4,73 4,4 4,39 4,32 4,46 4,22 4,1
Net heating capacity (1) (kW) 37,1 42,0 53,3 59,8 68,7 76,2 80,6 102,7 114,8 131,6
Total power input (1) (kW) 10,8 11,4 14,7 17,2 19,8 21,7 23,6 27,3 31,7 37,8
Net COP (1) 3,43 3,69 3,63 3,47 3,47 3,51 3,41 3,76 3,62 3,48
Seasonal energy efficiency (ηs,h) (2) (%) 125,8 125,4 129,4 125,4 129,4 140,6 133 135,4 141 135,8
SCOP (2) 3,22 3,21 3,31 3,21 3,31 3,59 3,4 3,46 3,6 3,47
Outdoor sound power level (3) (dB(A)) 81 84 84 85 85 85 85 85 85 91
Length (mm) 2830 3010 3010 3010 3010 3890 3890 3890 3890 3890
Width (mm) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
Height (mm) 1565 1565 1565 1565 1565 1585 1585 1890 1890 1890
Operating weight (4) (kg) 859 1102 1114 1114 1139 1305 1311 1511 1515 1515
8 Airfinity
Airfinity™ AFD
Model IH (Heat pumps with AFD option) IH021 IH031 IH041 IH051 IH061 IH071
Nominal airflow (m3/h) 3860 5790 7720 9650 11580 11966
Net cooling capacity (1) (kW) 19,8 30,2 39,8 50,2 60,3 64,2
Total power input (1) (kW) 4,6 8,0 10,6 14,7 20,2 23,0
Net EER (1) 4,28 3,76 3,76 3,41 2,99 2,79
Seasonal energy efficiency (ηs,c) (2) (%) 205,8 211,4 190,6 199,4 177 169
SEER (2) 5,22 5,36 4,84 5,06 4,5 4,3
Net heating capacity (1) (kW) 19,9 29,7 40,4 49,6 58,6 58,8
Total power input (1) (kW) 5,3 7,9 11,4 14,6 18,3 18,3
Net COP (1) 3,78 3,75 3,53 3,4 3,21 3,22
Seasonal energy efficiency (ηs,h) (2) (%) 125 131,8 125,4 131 126,2 125,4
SCOP (2) 3,2 3,37 3,21 3,35 3,23 3,21
Outdoor sound power level (3) (dB(A)) 81 82 85 86 88 87
Length (mm) 2830 2830 2830 2830 2830 2830
Width (mm) 2250 2250 2250 2250 2250 2250
Height (mm) 1565 1565 1565 1565 1565 1565
Operating weight (4) (kg) 858 858 926 927 937 937
(1) According to EN14511:2018 nominal conditions (cooling: outdoor 35°C DB, Indoor 27°C DB/19°C WB; heating: 7°C DB.6°C WB, indoor 20°C DB)
(2) Seasonal efficiency according to EN 14825:2018 (average climate)
(3) Sound power level according to ISO 9614
(4) Includes G4 filters, economizer and the full refrigerant charge
9
Airfinity™ XL
Efficient. Flexible. Reliable. Stronger.
Designed for medium to large commercial and industrial buildings, Airfinity™XL rooftop units are easy and
cost-effective to install, operate and maintain.
Airfinity™rooftop units integrate the latest technology available on the market to deliver high efficiency and
reliability all-year around. Every model can be equipped with additional options to deliver free cooling in
summer, free heating in winter and a wider operating map thanks to integrated auxiliary heat sources.
10 Airfinity
Airfinity™ XL
Models IC XL (Cooling only) IC140 IC150 IC170 IC190 IC220 IC250 IC270
Nominal airflow (m3/h) 24000 26000 28000 33000 36000 42000 44000
Net cooling capacity (1) (kW) 141,5 155,5 172,9 196,4 212,9 233,7 247,0
Total power input (1) (kW) 42,6 49,9 57,1 69,7 81,3 87,4 94,0
Net EER (1) 3,32 3,12 3,03 2,82 2,62 2,67 2,63
Seasonal energy efficiency (ηs,c) (2) (%) 191 181,8 175 161,4 147,2 147,2 138,2
SEER (2) 4,85 4,62 4,45 4,11 3,76 3,76 3,53
Outdoor sound power level (3) (dB(A)) 85 85 86 91 91 92 92
Length (mm) 5618 5618 5618 5618 5618 6518 6518
Width (mm) 2250 2250 2250 2250 2250 2250 2250
Height (mm) 2275 2275 2275 2275 2275 2275 2275
Operating weight (4) (kg) 2393 2401 2519 2630 2703 2918 2922
Models IH XL (Heat pump) IH140 IH150 IH170 IH190 IH220 IH250 IH270
Nominal airflow (m3/h) 24000 26000 28000 33000 36000 42000 44000
Net cooling capacity (1) (kW) 139,8 153,6 162,7 187,2 201,8 221,0 236,8
Total power input (1) (kW) 42,7 50,2 57,5 69,6 82,0 90,9 98,3
Net EER (1) 3,27 3,06 2,83 2,69 2,46 2,43 2,41
Seasonal energy efficiency (ηs,c) (2) (%) 183 182,6 171 162,6 145 142,04 138,63
SEER (2) 4,65 4,64 4,35 4,14 3,7 3,626 3,54
Net heating capacity (1) (kW) 136,6 152,9 170,0 195,7 218,4 254,1 272,6
Total power input (1) (kW) 38,4 44,6 49,9 61,0 71,6 92,0 100,5
Net COP (1) 3,56 3,43 3,41 3,21 3,05 2,76 2,713
Seasonal energy efficiency (ηs,h) (2) (%) 131,8 131,8 135,8 128,2 126,2 127,1 125,6
SCOP (2) 3,37 3,37 3,47 3,28 3,18 3,22 2,98
Outdoor sound power level (3) (dB(A)) 85 85 86 91 91 92 92
Length (mm) 5618 5618 5618 5618 5618 6518 6518
Width (mm) 2250 2250 2250 2250 2250 2250 2250
Height (mm) 2275 2275 2275 2275 2275 2275 2275
Operating weight (4) (kg) 2335 2503 2561 2672 2744 2939 2942
(1) According to EN14511:2018 nominal conditions (cooling: outdoor 35°C DB, Indoor 27°C DB/19°C WB; heating: 7°C DB.6°C WB, indoor 20°C DB)
(2) Seasonal efficiency according to EN 14825:2018 (average climate)
(3) Sound power level according to ISO 9614
(4) Includes G4 filters, economizer and the full refrigerant charge
11
Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable,
energy efficient indoor environments through a broad portfolio of heating, ventilating and air
conditioning systems and controls, services, parts and supply. For more information, please
visit trane.eu or tranetechnologies.com.