STORAGE TANK SPECIFICATION Sheet 1 of 1

Montemayor, (English Units)

Rev. No.
Inc. Project No. 1952.000
1 Service : CRUDE OIL Storage Equipment No. : T-400 & T-405
2 Location : Galveston, Texas Unit : Kirwin Design Engineer : Art Montemayor
3 Manufacturer : Model : Mfr Ref. No. : No. Req'd : Two
4 P&ID No. PID115-EPF-01-112A1 Plot Plan No. : Other Ref. Dwg No. :
5
6
7
8 M
9 A P G
10
11
12
13 50.00 Ft
14 H
15 32.00 Ft 48" X 48"
16 FLUSH
E CLEANOUT E
17 K
18
19 L F D
20
21
22 N N J I
23
24 Shell Diameter : 50.00 Feet Shell Height : 32.00
Feet Nominal Volume : 11,191 Barrels
25 Roof Type : Cone Bottom Floor Type: Sloped
26 OPERATING/DESIGN DATA NOZZLES/CONNECTIONS
27 Fluid Stored : CRUDE OIL Sp. Gr. : 0.7900 Mark Service Qty Size Rating Face
28 This Tank Service is considered: Cyclic A Roof Manway 2 24" 150# F. F.
29 Vapor Pressure @ Max. Operating Temperature 5.5 psia E Shell Manway 2 24" 125# R. F.
30 Flash Point (Closed Cup) : ºF Operating Design F Flush Cleanout MW 1 48"x48" 125# R. F.
31 Negative Pressure oz/in.2 0.00 0.50 G Stilling Vent 1 6" 125# F. F.
32 Positive Pressure psig 1.00 2.00 H Temperature Indicator 1 1" 150# L. J.
33 (Hydro)test Pressure expressed in Psig ---- I Outlet Nozzle 1 8" 150# API
34 Minimum Fluid Temperature ºF -25 J Fill Nozzle 1 10" 150# L. J.
35 Maximum Fluid Temperature ºF 200 K Mixer Manway 1 30" 150# F. F.
36 Emergency Vacuum Design ? Yes Set @ 0.0.3 oz/in.2 L Water Draw Nozzle 1 4" 150# R. F.
37 METALLURGY M Top Center Vent 1 8" 150# API
38 Component Material CA, in. Remarks N1 Sample Tap 1 3/4" 150# R. F.
39 Shell & Bottom 57370 0.1250 Normalized N2 Sample Tap 1 3/4" 150# F. F.
40 Roof 516 Grade 55 0.1250 Normalized P Roof Nozzle 1 4" 150# L. J.
41 Lining/Coating D Spare 1 2" 150# API
42 150# API
43 Stress Relieve ? Yes for: 150# API
44 CONSTRUCTION/FABRICATION
45 Code (as appl.): API 650 LATEST EDITION Internals (attach separate sheet, as req'd): Others:
46 Design Specifications: Sump
47 Tank Insulation ? No Thickness : in. Seismic Zone 3 Design Wind Velocity 100 mph
48 Insulation Type: Hot Radiograph 85 % Inspection Req'd ? Yes
49 Fireproofing ? Yes Paint Spec. EmptyTank Weight lb Full of Water lb
50 Remarks
51 1. Items marked with an asterisk (*) to be completed by Vendor/Fabricator.
52 2. Fixed cone roof with internal floating roof.
Approvals
Rev Date Description By Chk. Appr. Rev Date Description By Chk. Appr.
0 For Inquiry