Let-Through Energies 415V-220V
Let-Through Energies 415V-220V
Let-Through Energies 415V-220V
415 V Motor
Rated currrent (A) Let through energy (A2·s) Setting of Im (A)
200 1.80E+06 2000
160 1.70E+06 1600
125 1.60E+06 1250
100 3.80E+05 1000
80 3.80E+05 800 230 F
52 2.20E+05 520 400 F
32 1.90E+05 320 400 M
20 1.70E+05 200
12.5 1.50E+05 163
8.5 7.00E+04 110
6.5 5.00E+04 84
5 3.40E+04
4 3.00E+04
3.2 2.50E+04
2.5 3.10E+03
2 1.40E+03
1.6 9.00E+02
1 2.40E+02
240/220 V Feeder
Cross-section (mm2)
Rated currrent (A) Let through energy (A2·s) Setting of Im (A)
250 1.92E+05 2500 2.5
200 1.82E+05 2000 4
160 1.60E+05 1600 6
125 1.45E+05 1250 10
100 1.30E+05 1000 16
80 1.20E+05 800 25
63 1.20E+05 630 35
50 1.20E+05 500 50
40 7.00E+04 400 70
32 7.00E+04 320 95
25 6.20E+04 250 120
20 6.20E+04 200 150
16 5.10E+04 160 185
10 4.00E+04 100 240
6 1.70E+04 60 300
4 8.50E+03 40
3 4.60E+03 30
2 8.00E+02 20
1.6 5.00E+02 16
1 2.60E+02 10