Semana 09 O - Cold Weather Concreting - PCA Chapter 17
Semana 09 O - Cold Weather Concreting - PCA Chapter 17
Semana 09 O - Cold Weather Concreting - PCA Chapter 17
CHAPTER 17
Cold Weather Concreting
Concrete can be placed safely without damage from fixtures must be free of snow and ice at the time concrete
freezing in cold climates if certain precautions are taken. is placed. Thermometers and proper storage facilities for
Cold weather is defined by ACI Committee 306 as existing test cylinders should be available to verify that precau-
when the air temperature has fallen to, or is expected to tions are adequate.
fall below 4°C (40°F) during the protection period. Under
these circumstances, all materials and equipment needed
for adequate protection and curing must be on hand and
Effect of Freezing on Fresh Concrete
ready for use before concrete placement is started.
Concrete gains very little strength at low temperatures.
During cold weather, the concrete mixture and its temper- Freshly mixed concrete must be protected against the
ature should be adapted to the construction procedure disruptive effects of freezing (Figure 17-2) until the degree
and ambient weather conditions. Preparations should be of saturation of the concrete has been sufficiently reduced
made to protect the concrete from excessively low temper- by the process of hydration. The time at which this reduc-
atures using: enclosures, windbreaks, portable heaters, tion is accomplished corresponds roughly to the time
insulated forms, and blankets to maintain a suitable con- required for the concrete to attain a compressive strength
crete temperature (Figure 17-1). Concrete must be deliv- of 3.5 MPa (500 psi) (Powers 1962). At normal tempera-
ered at the proper temperature and the temperature of tures and water-cement ratios less than 0.60, this occurs
forms, reinforcing steel, the ground, or other concrete on within the first 24 hours after placement. Significant ulti-
which the fresh concrete is cast must also be considered. mate strength reductions, up to about 50%, can occur if
Concrete should not be cast on frozen concrete or on concrete is frozen within a few hours after placement or
frozen ground. Forms, reinforcing steel, and embedded before it attains a compressive strength of 3.5 MPa
Figure 17-1. When suitable preparations to build enclosures and insulate equipment
have been made, cold weather is no obstacle to concrete construction.
327
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 328
\ Casting temperature, °F
32 52 72 92
200
100
50 Mix proportions
held constant.
Cement A Cement B
0
0 10 20 30 40
Casting temperature, °C
Figure 17-2. Closeup view of ice impressions in paste of frozen fresh
concrete. The ice crystal formations occur as unhardened concrete Casting temperature, °F
freezes. They do not occur in adequately hardened concrete. The 32 52 72 92
200
disruption of the paste matrix by freezing can cause reduced strength
Concrete that has been frozen just once at an early age 50 Mix proportions
held constant.
can be restored to nearly normal strength by providing Cement A Cement B
favorable subsequent curing conditions. Such concrete,
however, will not be as resistant to weathering nor as 0
0 10 20 30 40
impermeable. The critical period after which concrete is Casting temperature, °C
not seriously damaged by one or two freezing cycles is
Figure 17-3. Initial set characteristics as a function of casting temper-
dependent upon the concrete ingredients and conditions ature (top), and final set characteristics as a function of casting
of mixing, placing, curing, and subsequent drying. For temperature (bottom) (Burg 1996).
example, air-entrained concrete is less susceptible to dam-
age by early freezing than non-air-entrained concrete. See Casting temperature, °F
32 52 72 92
Chapter 11 for more information on freeze-thaw resistance. 250
Percent slump at 23°C (73°F)
If hardened concrete is frozen and kept frozen above about Mix proportions
50 held constant.
minus 10°C (14°F), it will still be able to gain strength Cement A Cement B
slowly. However, below that temperature, cement hydra-
tion and concrete strength gain cease. Figure 17-3 illus- 0
0 10 20 30 40
trates the effect of cool temperatures on setting time of Casting temperature, °C
concrete. Figure 17-4 illustrates the effects of casting tem- Figure 17-4. Slump characteristics as a function of casting tempera-
perature on slump. Figures 17-5 and 17-6 show the age- ture (Burg 1996).
compressive strength relationship for concrete that has
been cast and cured at various temperatures. Note in
Heat of Hydration
Figure 17-6 that concrete cast and cured at 4°C (40°F) and
13°C (55°F) had relatively low strengths for the first week;
but after 28 days—when all specimens were moist-cured Concrete generates heat during hardening as a result of
at 23°C (73°F)—strengths for the 4°C (40°F) and 13°C the chemical reaction by which cement reacts with water
(55°F) concretes grew faster than the 23°C (73°F) concrete to form a hard, stable paste. The heat generated is called
and at one year they were slightly higher. heat of hydration; it varies in both amount and rate for
328
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 329
)
°F
3°
F)
3
(7
tarpaulin just after the concrete was placed. Tarpaulins and
°C
(7
°C
30
insulated blankets are often necessary to retain the heat of
23 23
4
hydration more efficiently and keep the concrete as warm
RH
as possible. Thermometer readings of the concrete’s tem-
RH
50%
20 perature will indicate whether the covering is adequate.
0%
10
140
Mix data:
Water to cement ratio = 0.43
Air content: 4 to 5%
120 Cement: Type I,
310 kg/m3 (517 lb/yd3)
Compressive strength, percent of
100
28-day 23°C cured concrete
)
°F
80
(40
4°C
)
40
23
329
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 330
50 7
Mix data:
Water to cement ratio = 0.43, Type I cement
= 0.45, Type III cement
Air content: 4 to 5% 6
40 Cement content: 310 kg/m3 (517 lb/yd3)
30
4
20 3
Type III, mixed and cured
at 23°C (73°F)
Type I, mixed and cured
2
at 23°C (73°F)
10 Type III, mixed and cured
at 4°C (40°F) 1
Type I, mixed and cured
at 4°C (40°F)
0
1 3 7 28
Age of test, days Figure 17-9. Finishing this concrete flatwork can proceed because a
windbreak has been provided, there is adequate heat under the slab,
Figure 17-8. Early-age compressive-strength relationships for Type I and the concrete has low slump.
and Type III portland cement concretes mixed and cured at 4°C
(40°F) compared to 23°C (73°F) (Klieger 1958).
Air-Entrained Concrete
Small amounts of a set accelerating admixture can be
used to accelerate the setting and early-age strength Entrained air is particularly desirable in any concrete
development of concrete in cold weather. Set accelerators that will be exposed to freezing weather while in service.
containing chlorides should not be used where there is Concrete that is not air entrained can suffer strength loss
an in-service potential for corrosion, such as in concrete and internal as well as surface damage as a result of
members containing steel reinforcement or where alum- freezing and thawing (Figure 17-10). Air entrainment
inum or galvanized inserts will be used. Chlorides are not provides the capacity to absorb stresses due to ice for-
recommended for concretes exposed to soil or water con- mation within the concrete.
taining sulfates or for concretes susceptible to alkali-aggre-
gate reaction. 400
100
Since the goal of using special concrete mixtures during
cold weather concreting is to reduce the time of setting,
a low water-cement ratio, low-slump concrete is particu-
larly desirable, especially for cold-weather flatwork. In
addition, bleed water is minimized so that finishing can 0
0 10 20 30 40 50 60
be accomplished more quickly (Figure 17-9). Concrete mix- Number of cycles of freezing and thawing
tures with higher slumps provided by water or retarding
water-reducing admixtures usually take longer to set. Figure 17-10. Effect of freezing and thawing on strength of concrete
that does not contain entrained air (cured 7 days before first freeze)
(Powers 1956).
330
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 331
Air entrainment should always be used for construction dissipated less rapidly in heavier sections. Also note that
during the freezing months. The exception is concrete at lower ambient air temperatures more heat is lost from
work done under roof where there is no chance that concrete during transporting and placing. Therefore, the
rain, snow, or water from other sources can saturate the recommended concrete temperatures as mixed are higher
concrete and where there is no chance of freezing. See for colder weather.
Chapters 7 and 11 for more information on air-entraining
admixtures and freeze-thaw resistance of concrete due There is little advantage in using fresh concrete at a tem-
to air-entrainment. perature much above 21°C (70°F). Higher concrete temper-
atures do not afford proportionately longer protection
There is a likelihood of water saturating a concrete floor from freezing because the rate of heat loss is greater. Also,
during construction. Figure 17-11 shows conditions in high concrete temperatures are undesirable since they
the upper story of an apartment building during winter increase thermal shrinkage after hardening, require more
construction. Snow accumulated on the top deck and mixing water for the same slump, and contribute to the
when heaters were used below to warm the deck below, possibility of plastic shrinkage cracking (caused by rapid
then the snow melted. Water ran through floor openings moisture loss through evaporation). Therefore, the temper-
down to a level that was not being heated. The water- ature of the concrete as mixed should not be more than 8°C
saturated concrete froze, which caused a strength loss, (15°F) above the minimum recommended in Table 17-1.
particularly at the floor surface. This could also result
in greater deflection of the floor and a surface that is less Aggregate Temperature. The temperature of aggregates
wear-resistant than originally designed. Steel trowelled varies with weather and type of storage. Aggregates
(burnished) floor finishes should not be used when en- usually contain frozen lumps and ice when the tempera-
trained air content is specified for slabs. Entrained air may ture is below freezing. Frozen aggregates must be thawed
promote blistering and delamination of the slab surface. to avoid aggregate pockets in the concrete after batching,
In addition, the intense energy applied to the slab surface mixing, and placing. If thawing takes place in the mixer,
densifies that surface, removing the entrained air content excessively high water contents in conjunction with the
leaving the surface vulnerable to surface scaling deterior- cooling effect caused by melting ice must be considered.
ation in cold weather conditions.
At air temperatures consistently above -4°C (25°F) it is
seldom necessary to heat aggregates, the desired concrete
temperature can usually be obtained by heating only the
mixing water. At temperatures below freezing, in addition
to heating the mixing water, often only the fine aggregate
needs to be heated to produce concrete of the required
temperature, provided the coarse aggregate is free of
frozen lumps.
331
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 332
Table 17-1. Recommended Concrete Temperature for Cold-Weather Construction – Air-Entrained Concrete*
Thickness of sections, mm (in.)
Less than 300 to 900 900 to 1800 Over
Line Condition 300 (12) (12 to 36) (36 TO 72) 1800 (72)
1 Minimum temperature of Above -1°C (30°F) 16°C (60°F) 13°C (55°F) 10°C (50°F) 7°C (45°F)
fresh concrete as mixed for
2 weather indicated. -18°C to -1°C (0°F to 30°F) 18°C (65°F) 16°C (60°F) 13°C (55°F) 10°C (50°F)
3 Below -18°C (0°F) 21°C (70°F) 18°C (65°F) 16°C (60°F) 13°C (55°F)
4 Minimum temperature of fresh concrete as placed and 13°C (55°F) 10°C (50°F) 7°C (45°F) 5°C (40°F)
maintained.**
332
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 333
To avoid the possibility of a quick or flash set of the con- Table 17-2. Maximum Allowable Temperature Drop During First
crete when either water or aggregates are heated to above 24 Hours After End of Protection Period*
38°C (100°F), they should be combined in the mixer first, Section size, minimum dimensions, mm (in.)
before the cement is added. If this mixer-loading sequence Less than 300 to 900 900 to 1800 Over
is followed, water temperatures up to the boiling point can 300 (12) (12 to 36) (36 to 72) 1800 (72)
be used, provided the aggregates are cold enough to re-
27°C (50°F) 22°C (40°F) 17°C (30°F) 11°C (20°F)
duce the final temperature of the aggregates and water
mixture to appreciably less than 38°C (100°F). *Adapted from Table 5.1 of ACI 306R-10.
drop during the first 24 hours after the end of the protec-
tion is given in Table 17-2. The temperature drops apply Drilled or
preformed
to surface temperatures. Notice that the cooling rates for hole
surfaces of mass concrete (thick sections) are lower than
they are for thinner members.
333
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 334
Concrete test cylinders must be maintained at a tempera- suspended floor, possible high temperatures there will
ture between 16°C (60°F) and 27°C (80°F) at the jobsite not duplicate the average temperature in the slab, or the
for up to 48 hours until they are taken to a laboratory for lowest temperature on top of the slab. Still, field cured
curing (ASTM C31, Standard Practice for Making and cylinders are more indicative of actual concrete strength
Curing Concrete Test Specimens in the Field or AASHTO than laboratory-cured cylinders. Particular care should be
T 23). For concrete mixtures with a specified strength of taken to protect compressive strength test cylinders from
40 MPa (6,000 psi) or greater, the initial curing tempera- freezing; their small mass may not generate enough heat
ture shall be between 20°C and 26°C (68°F and 78°F). of hydration to protect them.
During this period, cylinders should be kept in a curing
box and covered with a nonabsorptive, nonreactive plate Cast-in-place cylinders (ASTM C873, Standard Test Method
or impervious plastic bag. The temperature in the box for Compressive Strength of Concrete Cylinders Cast in Place
should be accurately controlled by a thermostat (Figure in Cylindrical Molds) and nondestructive testing methods
17-15). When stored in an insulated curing box outdoors, (see Chapter 18) as well as maturity techniques (discussed
cylinders are less likely to be disturbed by vibrations than later in this chapter) are helpful in monitoring in place
if left on the floor of a trailer. If kept in a trailer the heat concrete strength.
may be inadvertently turned off at night or over a week-
end or holiday in cold weather conditions. In that case, the Concreting on Ground During Cold Weather
cylinders would not be at the prescribed curing tempera-
tures during this critical period. Concreting on ground during cold weather involves some
Cylinders stripped of molds after the first 24±8 hours must extra preparation. Placing concrete on the ground involves
be wrapped tightly in plastic bags or laboratory curing different procedures than those used at an upper level:
started immediately. When cylinders with strengths less (1) the ground must be thawed before placing concrete;
than 40 MPa (6000 psi) are picked up for delivery to the (2) cement hydration will furnish some of the curing heat;
laboratory, they must be maintained at a temperature of (3) construction of enclosures is much simpler and use of
16°C (60°F) to 27°C (80°F) until they are placed in the lab- insulating blankets may be sufficient; (4) in the case of
oatory curing room. Cylinders with strengths of 40 MPa a floor slab, a vented heater is required if the area is en-
(6000 psi) or greater must be maintained at a temperature closed; and (5) hydronic heaters can be used to thaw sub-
of 20°C (68°F) to 26°C (78°F) (ASTM C31). grades using insulated blankets or to heat enclosures
without concern for carbonation. For more on hydronic
heaters, see Heaters later in this chapter.
334
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 335
Slabs can be cast on ground at ambient temperatures as Table 17-3B. Recommended Duration of Concrete Protection for Fully
low as 2°C (35°F) as long as the minimum concrete tem- Stressed, Exposed, Air-Entrained Concrete
perature as placed is not less than shown on Line 4 of Days at 10°C (50°F) Days at 21°C (70°F)
Table 17-1. Although surface temperatures need not be Required
Type of Type of
higher than a few degrees above freezing, they also should percentage of
hydraulic cement hydraulic cement
preferably not be more than 5°C (10°F) higher than the standard-cured
minimum placement temperature. The duration of curing 28-day I or II or III or I or II or III or
strength GU MH HE GU MH HE
should not be less than that described in Chapter 15 for
the appropriate exposure classification. Because of the risk 50 6 9 3 4 6 3
of surface imperfections that might occur on exterior con- 65 11 14 5 8 10 4
85 21 28 16 16 18 12
crete placed in late fall and winter, many concrete contrac- 95 29 35 26 23 24 20
tors choose to delay concrete placement until spring. By
waiting until spring, temperatures will be more favorable * Adapted from Table 7.1 of ACI 306-10. Cold weather is defined as
for cement hydration; this will help generate adequate when the temperature has, or is expected to, fall below 4°C (40°F).
For recommended concrete temperatures, see Table 17-1. For
strengths along with sufficient drying so the concrete can
concrete that is not air entrained, ACI Committee 306 states that
resist freeze-thaw damage. protection for durability should be at least twice the number of days
listed in Table A.
Part B was adapted from Table 8.2 of ACI 306R-10. The values
Concreting Above Ground During Cold Weather shown are approximations and will vary according to the thickness
of concrete, mix proportions, and so on. They are intended to
Working above ground in cold weather usually involves represent the ages at which supporting forms can be removed.
several different approaches in comparison to work at For recommended concrete temperatures, see Table 17-1.
ground level: ** Made with ASTM C150 Type I, II, or C1157 GU, or MH hydraulic
cement.
1. The concrete mixture may not need to be changed to † Made with ASTM C150Type III or C1157 HE hydraulic cement, an
generate more heat because portable heaters can be accelerator, or an extra 60 kg/m3 (100 lb/yd3) of cement.
used to heat the undersides of floor and roof slabs. ‡ “Exposed” means subject to freezing and thawing.
However, there are advantages to having a mix that
will produce a high strength at an early age; for for surfaces in contact with fresh concrete are the same as
example, artificial heat can be cut off sooner (see those outlined in Concreting on Ground During Cold
Table 17-3), and forms can be recycled faster. Weather. Metallic embedments at temperatures below the
freezing point may result in local freezing that decreases
2. Enclosures must be constructed to retain the heat
the bond between concrete and steel reinforcement. ACI
under floor and roof slabs.
Committee 306 suggests that a reinforcing bar having a
3. Portable heaters used to warm the underside of cross-sectional area of about 650 mm2 (1 in.2) should have
formed concrete can be direct fired heating units a temperature of at least -12°C (10°F) immediately before
(without venting). being surrounded by fresh concrete at a temperature of at
least 13°C (55°F). Caution and additional study are re-
Before placing concrete, the heaters under a formed deck
quired before definitive recommendations can be formu-
should be turned on to preheat the forms and melt any
lated. Good concrete placement practice suggests heating
snow or ice remaining on top. Temperature requirements
surfaces of formwork and large embedments to no more
than 5°C (10°F) above and no less than 8°C (15°F) below
Table 17-3A. Recommended Duration of Concrete Protection in Cold the temperature of the concrete mixture. See ACI 306 for
Weather – Air-Entrained Concrete*
additional information.
High-early-
Conventional strength When slab finishing is completed, insulating blankets
concrete,** concrete,† or other insulation must be placed on top of the slab to
Service category days days ensure that proper curing temperatures are maintained.
The insulation value (R) necessary to maintain the con-
No load, not exposed‡
favorable moist-curing 2 1 crete surface temperature of walls and slabs above ground
at 10°C (50°F) or above for 7 days may be estimated from
No load, exposed, but later Figure 17-16. To maintain a temperature for longer periods,
has favorable moist-curing 3 2 more insulation is required. ACI 306 has additional graphs
Partial load, exposed 6 4 and tables for slabs placed on ground at a temperature of
2°C (35°F). Insulation can be selected based on R values
Fully stressed, exposed See Table B below
provided by insulation manufacturers or by using the
information in Table 17-4.
335
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:50 PM Page 336
R
(4
R
=
)
=
0.
-5
R
0.
70
70
=
20
(4
1.
Minimum ambient temperature, °C
)
-10
=1
(6
)
10
. 06
R
R=
=1
-15
( 6)
.41
1.0
0
R=
6(
( 8)
-20
6)
1.4
-10
1
-25
(8)
R=
1. 4
-20
-30
1 (8
)
-30
-35
-40 -40
Cement content Cement content Cement content
-45 237 kg/m3 296 kg/m3 356 kg/m3
-50
(400 lb/yd3) (500 lb/yd3) (600 lb/yd3)
-50 -60
0 100 200 300 400 500 600 0 100 200 300 400 500 600 0 100 200 300 400 500 600
Wall or slab thickness, mm
Figure 17-16. Thermal resistance (R) of insulation required to maintain the concrete surface temperature of walls and slabs aboveground at 10°C
(50°F) or above for 7 days. Concrete temperature as placed: 10°C (50°F). Maximum wind velocity: 24 km/h (15 mph). Note that in order to main-
tain a certain minimum temperature for a longer period of time, more insulation or a higher R value is required (adapted from ACI 306).
When concrete strength development is not determined, a between the concrete interior and the concrete surface
conservative estimate can be made if adequate protection should be about 20°C (35°F) to minimize cracking. The
at the recommended temperature is provided for the dur- weather forecast should be checked and appropriate
ation of time found in Table 17-3. However, the actual action taken for expected temperature changes.
amount of insulation and length of the protection period
should be determined from the monitored in place con- Columns and walls should not be cast on foundations at
crete temperature and the desired strength. A correlation temperatures below 0°C (32°F) because chilling of con-
between curing temperature, curing time, and compres- crete in the bottom of the column or wall will retard
sive strength can be determined from laboratory testing strength development. Concrete should not be placed
of the particular concrete mixture used in the field (see on any surface that would lower the temperature of the
Maturity Concept). Corners and edges are particularly as-placed concrete below the minimum values shown
vulnerable during cold weather. As a result, the thickness on Line 4 in Table 17-1.
of insulation for these areas, especially on columns,
should be about three times the thickness that is required Enclosures
for walls or slabs. On the other hand, if the ambient tem-
perature rises much above the temperature assumed in
Heated enclosures are very effective for protecting con-
selecting insulation values, the temperature of the con-
crete in cold weather, but are expensive (Figure 17-17).
crete may become excessive. This increases the probability
Enclosures can be of wood, canvas tarpaulins, or poly-
of thermal shock and cracking when forms are removed.
ethylene film (Figure 17-18). Prefabricated, rigid plastic
Temperature readings of insulated concrete should there-
enclosures are also available. Plastic enclosures that admit
fore be taken at regular intervals and should not vary
daylight are the most popular but temporary heat in these
from ambient air temperatures by more than the values
enclosures can prove expensive.
given in ACI 306. The maximum temperature differential
336
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 337
* Values are from ASHRAE Handbook of Fundamentals, American Society of Heating, Refrigerating, and Air-conditioning Enginers, Inc., New York,
1977 and 1981.
R values are the reciprocal of U values (conductivity).
337
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 338
When enclosures are being constructed below a deck, the over the straw or hay to make the insulation more effec-
framework can be extended above the deck to serve as a tive and prevent it from blowing away. The straw or hay
windbreak. Typically, a height of 2 m (6 ft) will protect should be kept dry or its insulation value will drop
concrete and construction personnel against biting winds considerably.
that cause temperature drops and excessive evaporation.
Wind breaks may be taller or shorter depending on antici- Insulating blankets for construction are made of fiberglass,
pated wind velocities, ambient temperatures, relative sponge rubber, open cell polyurethane foam, vinyl foam,
humidity, and concrete placement temperatures. mineral wool, or cellulose fibers. The outer covers are made
of canvas, woven polyethylene, or other tough fabrics that
Enclosures can be quickly transported using flying forms; will withstand rough handling. The R value for a typical
more often, though, they must be removed so that the wind insulating blanket is about 1.2 m2 • °C/W for 50 to 70 mm
will not interfere with maneuvering the forms into position. thickness, (7°F • hr • ft2 )/Btu, but since R values are not
Similarly, enclosures can be built in large panels with the marked on the blankets, their effectiveness should be
windbreak included; much like gang forms (Figure 17-1). checked with a thermometer. If necessary, they can be
used in multiple layers to attain the desired insulation.
Insulating Materials Stay-in-place insulating concrete forms (ICF) became
popular for cold-weather construction in the 1990s (Figure
Heat and moisture can be retained in the concrete by 17-20). Gajda (2002) showed that ICFs can be used to
covering it with commercial insulating blankets or batt successfully place concrete in ambient temperatures as
insulation (Figure 17-19). The effectiveness of insulation low as -29°C (-20°F). Forms built for repeated use often
can be determined by placing a thermometer under it and can be economically insulated with commercial blanket
in contact with the concrete. If the temperature falls below or batt insulation. The insulation should have a tough
the minimum required on Line 4 in Table 17-1, additional moisture proof covering to withstand handling abuse and
insulating material, or material with a higher R value, exposure to the weather. Rigid insulation can also be used
should be applied. Corners and edges of concrete are most (Figure 17-21).
vulnerable to freezing. In view of this, temperatures at
these locations should be checked more often.
Heaters
Figure 17-19. Stack of insulating blankets. These blankets trap heat
and moisture in the concrete, providing beneficial curing.
Three types of heaters are used in cold weather concrete
construction: direct fired, indirect fired, and hydronic
The thermal resistance (R) values for common insulating systems (Figures 17-22 to 17-25). Indirect fired heaters
materials are given in Table 17-4. For maximum efficiency, are vented to remove the products of combustion. Where
insulating materials should be kept dry and in close heat is supplied to the top surface of fresh concrete – for
contact with concrete or formwork. example, a floor slab – vented heaters are required. Carbon
dioxide (CO2) in the exhaust must be vented to the out-
Concrete pavements can be protected from cold weather
side and prevented from reacting with the fresh concrete
by spreading 300 mm (1 ft) or more of dry straw or hay on
(Figure 17-23). Direct fired units can be used to heat the
the surface for insulation. Tarpaulins, polyethylene film,
enclosed space beneath concrete placed for a floor or a
or waterproof paper should be used as a protective cover
roof deck (Figure 17-24).
338
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 339
Air
Air Air,
supply CO,
CO2,
Air
Fan Flame
a) Direct-fired heater
Air,
CO,
CO2,
339
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:54 PM Page 340
therefore, should not be permitted to heat the air over con- nearly eliminated as is the danger of accidentally over-
creting operations – at least until 24 hours have elapsed. In heating the concrete and in potentially damaging long
addition, the use of gasoline-powered construction equip- term strength gain.
ment should be restricted in enclosures during that time.
If unvented heaters are used, immediate wet curing or the Typical applications for hydronic systems include thaw-
use of a curing compound will minimize carbonation. ing and preheating subgrades. They are also used to cure
elevated and on-grade slabs, walls, foundations, and col-
Carbon monoxide (CO), another product of combustion, umns. To heat a concrete element, hydronic heating hoses
is not usually a problem unless the heater is using recircu- are usually laid on or hung adjacent to the structure and
lated air. Four hours of exposure to 200 parts per million of covered with insulated blankets and sometimes plastic
CO will produce headaches and nausea. Three hours of sheets. Usually, construction of temporary enclosures is
exposure to 600 ppm can be fatal. The American National not necessary. Hydronic systems can be used over areas
Standard Safety Requirements for Temporary and Portable much larger than would be practical to enclose. If a
Space Heating Devices and Equipment Used in the Con- heated enclosure is necessary for other work, hydronic
struction Industry (ANSI A10.10) limits concentrations of hoses can be sacrificed (left under a slab on grade) to
CO to 50 ppm at worker breathing levels. The standard make the slab a radiant heater for the structure built
also establishes safety rules for ventilation and the stability, above (Grochoski 2000).
operation, fueling, and maintenance of heaters.
340
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 341
required, depending on the circumstances. Where elec- cracking, especially in massive sections such as bridge
trical resistance wires are used, insulation should be in- piers, abutments, dams, and large structural members;
cluded during the initial setting period. If insulation is thus cooling should be gradual. A safe temperature differ-
removed before the recommended time, the concrete ential between a concrete wall and the ambient air temper-
should be covered with an impervious sheet and the ature can be obtained from ACI 306R-10. The maximum
power continued for the required time. uniform drop in temperature throughout the first 24 hours
after the end of protection should not be greater than the
Steam is another source of heat for winter concreting. amounts given in Table 17-2. Gradual cooling can be ac-
Live steam can be piped into an enclosure or supplied complished by lowering the heat or by simply shutting
through radiant heating units. In choosing a heat source, off the heat and allowing the heat to dissipate.
it must be remembered that the concrete itself supplies
heat through hydration of cement; this is often enough
for curing needs provided the heat can be retained Form Removal and Reshoring
within the concrete using insulation.
It is good practice in cold weather to leave forms in place
as long as possible. Even within heated enclosures, forms
Duration of Heating serve to distribute heat more evenly and help prevent
drying and local overheating.
After concrete is in place, it should be protected and kept
at the recommended temperatures listed on Line 4 of If the curing temperatures listed on Line 4 of Table 17-1
Table 17-1. These curing temperatures should be main- are maintained, Table 17-3A can be used to determine the
tained until sufficient strength is gained to withstand minimum time in days that vertical support for forms
exposure to low temperatures, anticipated environment, should remain in place. Before shores and forms are re-
and construction and service loads. The length of protec- moved, fully stressed structural concrete should be tested
tion required to accomplish this will depend on the cement to determine if in-place strengths are adequate. In-place
type and amount, whether accelerating admixtures were strengths can be monitored using one of the following:
used, and the loads that must be carried. Recommended (1) field-cured cylinders (ASTM C31 or AASHTO T 23);
minimum periods of protection are given in Table 17-3. (2) probe penetration tests (ASTM C803, Standard Test
The duration of heating structural concrete requiring full Method for Penetration Resistance of Hardened Concrete);
service loading before forms and shores are removed (3) cast-in-place cylinders (ASTM C873, Standard Test
should be based on the adequacy of in-place compressive Method for Compressive Strength of Concrete Cylinders Cast
strengths rather than an arbitrary time period. If no data in Place in Cylindrical Molds); (4) pullout testing (ASTM
are available, a conservative estimate of the length of time C900, Standard Test Method for Pullout Strength of Hardened
for heating and protection can be made using Table 17-3. Concrete); or (5) maturity testing (ASTM C1074, Standard
Practice for Estimating Concrete Strength by the Maturity
Moist Curing Method). Many of these tests are indirect methods of mea-
Strength gain stops when moisture required for hydra- suring compressive strength; they require correlation in
tion is no longer available. Concrete retained in forms or advance with standard cylinders before estimates of in-
covered with insulation seldom loses enough moisture at place strengths can be made.
5°C to 13°C (40°F to 55°F) to impair curing. However, a
positive means of providing moist curing is needed to If in-place compressive strengths are not documented,
offset drying from low wintertime humidity and from the Table 17-3B lists conservative time periods in days to
dry air produced by heaters used in enclosures during achieve various percentages of the standard laboratory
cold weather. cured 28-day strength. The engineer issuing project draw-
ings and specifications in cooperation with the formwork
Live steam exhausted into an enclosure around the con- contractor must determine what percentage of the design
crete is an excellent method of curing because it provides strength is required (see ACI Committee 306R-10). Vertical
both heat and moisture. Steam is especially practical in forms can be removed sooner than shoring and temporary
extremely cold weather because the moisture provided falsework (ACI Committee 347).
offsets the rapid drying that occurs when very cold air
is heated. Maturity Concept
Liquid membrane forming compounds can be used for
early curing of concrete surfaces within heated enclosures. The maturity concept is based on the principle that strength
gain in concrete is a function of curing time and tempera-
Terminating the Heating Period ture. The maturity concept, as described in ACI 306R-10
Rapid cooling of concrete at the end of the heating period and ASTM C1074 can be used to evaluate strength devel-
should be avoided. Sudden cooling of the concrete surface opment. Two maturity methods to estimate the in-place
while the interior is still warm may cause thermal
341
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 342
concrete strength are shown in Table 17-5. The first method depths in the concrete. The location giving the lowest
is based on the Nurse-Saul function, also called Time- values provides the series of temperature readings to
Temperature Factor method. This method is simple and be used in the computation (Figure 17-26).
very popular. However, it fails to recognize the fact that
maturity increases disproportionately at elevated temper- See Figure 17-27 for an example using the maturity con-
atures and that this increase depends on the type(s) of cept. Before construction begins, a calibration curve is
cementitious materials used and the water-to-cementi- drawn plotting the relationship between compressive
tious materials ratio. Therefore, the Time-Temperature strength and the maturity factor for a series of test cylin-
Factor method typically underestimates the strength de- ders (of the particular concrete mixture proportions) cured
velopment at elevated temperatures. The “Equivalent in a laboratory and tested for strength at successive ages.
Age” maturity function is based on the Arrhenius equa-
tion; this function presents maturity in terms of equivalent The maturity concept is imprecise and somewhat limited.
age of curing at a specified temperature. However, the concept is useful in checking the curing of
concrete and in estimating strength in relation to time and
Table 17-5. Time-Temperature Factor and Equivalent Age Maturity temperature. It presumes that all other factors affecting
Equations concrete strength have been properly controlled. With
Time-Temperature M = maturity index, °C-hours these limitations in mind, the maturity method has gained
Factor T = average concrete temperature, greater acceptance as a surrogate for measuring the com-
°C, during the time interval t pressive strength of the concrete for removal of shoring
M =∑(T – T0 ) t
T0 = datum temperature (usually or opening a pavement to traffic. It is no substitute for
taken to be 0 °C)
t
quality control and proper concreting practices (Gajda
0 t = elapsed time, hours 2007, Malhotra 1974, and ACI Committee 347).
t= time intervals, hours
Equivalent te = equivalent age at the reference
Age temperature
E = apparent activation energy,
J/mol (see ASTM C1074 for
typical values)
R = universal gas constant, 8.314
1 1
t e =∑e
t –E
–
J/mol-K
R Tr T T = average concrete temperature,
t
0 Kelvin, during the time interval
t
Tr = absolute reference temperature,
Kelvin
t= time intervals, hours
at 23°C ± 2°C (73°F ± 3°F). 2000 4000 6000 8000 10000 12000 14000 16000
°F • hours
2. A time-temperature record of the concrete in place. Maturity, temperature • hours
Temperature readings are obtained by placing ex-
pendable thermistors or thermocouples at varying Figure 17-27. Maturity relation example.
342
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 343
343
Chap. 17 (2010).qxd:EB001 (2010) 1/27/11 3:51 PM Page 344
344