Simulation of Transients With A Modal-Domain
Simulation of Transients With A Modal-Domain
Abstract-- In this paper, a modal-domain based transmission of grounding electrodes [7-11] and on the calculation of
line model available in popular electromagnetic transient switching and lightning transients in power systems [12-19].
programs is adapted to evaluate the effect of frequency-dependent In spite of this trend, the transmission line models available
ground conductivity and permittivity in the calculation of
in popular transient simulators rely on the use of Carson’s
transients on overhead power distribution lines. The calculation
of the line parameters considering ground as a dispersive medium integrals [20] or their approximation through the use of the
is performed in MATLAB making use of practical equations that complex ground return plane [21] for calculating the ground
are based on in situ measurements of ground conductivity and return impedance. Since both approaches are low-frequency
permittivity in a wide frequency range. The propagation function approximations in which σ>>ωε is assumed, the influence of
and characteristic impedance of the line are synthesized in the the ground permittivity in the ground-return impedance is not
frequency domain as the sum of rational functions using the taken into account properly. This feature, combined with the
vector fitting technique. The poles and residues of the synthesized
assumption of a constant value of ground conductivity,
functions are written in a .pch file that is read by the Alternative
Transients Program (ATP) as a JMarti model. Time domain suggests the possibility of errors in the simulation of cases
simulations are performed considering both switching and involving poor ground conductivities, high-frequency
lightning transients on single- and two-phase power distribution transients, or a combination of both.
lines. The results indicate that the consideration of the ground as In this paper, the transmission line model proposed by
a dispersive medium leads to a distortion of the calculated Marti [22] is adapted to include the effect of frequency
transient voltages that can be relevant in the case of very low dependent ground parameters in the time-domain simulation of
ground conductivity. However, such effect can be significantly
electromagnetic transients in power distribution lines. The
reduced in line topologies that include multiple branches and
grounding points. It is also shown that constant values of ground calculation of the line parameters is implemented in
conductivity and permittivity are able to lead to results MATLAB, where the poles and residues necessary to fit the
comparable to those obtained with frequency dependent characteristic impedance and propagation function of each
conductivity and permittivity provided a suitable value of ground mode are determined in the frequency domain via the vector
relative permittivity is selected. fitting technique [23]. The obtained poles and residues are
Keywords: Transmission line modeling, modal domain, then written in a .pch file that can be read by the Alternative
frequency-dependent ground parameters.
Transients Program (ATP) and solved as a JMarti model.
This paper is organized as follows. Section II discusses the
I. INTRODUCTION
calculation of the ground return impedance of transmission
This work was supported by Brazilian agencies CAPES (Coordenação de A. Ground Return Impedance
Aperfeiçoamento de Pessoal de Nível Superior) and CNPq (National Council The self and mutual terms of the ground impedance matrix
for Scientific and Technological Development).
Alberto De Conti and Maique Paulo S. Emídio are with the Lightning
of overhead transmission lines can be calculated with the
Research Center, Federal University of Minas Gerais - UFMG, Belo equations proposed by Sunde [24]. Taking as reference the
Horizonte – MG, Brazil (conti@cpdee.ufmg.br; maiquepaulo@hotmail.com). two-conductor line illustrated in Fig. 1, Sunde’s equations read
In [25] it is shown that (4) and (5) reproduce (1) and (2) for 2 2
0.01 ≥ σ ≥ 0.001 S/m with good accuracy. In Figs. 2 and 3, jωµ 0 (hi + h j + 2 p& ) + rij
Z ′g ij = ln (9)
2π
assuming two conductors with 5 mm radius, one located 10 m (hi + h j ) 2 + rij2
and the other 8.17 m above the ground, with rij=2 m (see Fig.
1), it is confirmed that (4) and (5) are also sufficiently accurate
If σ>>ωε, the complex penetration depth reads [21]
to reproduce (1) and (2) for σ=0.0001 S/m and different values
of εr, at least for heights and distances between conductors that
are typical of power distribution line configurations. 1
p& = (10)
If σ>>ωεrε0 is assumed in (3), then (1) and (2) reduce to jωµσ
jωµ 0 ∞ e −2 hi λ 3
Z g′ ii = ∫ dλ (6) Integral Expression (1)
Ω /m)
σ(ω), εr(ω)
2.5
π 0 2
λ + jωµ 0σ + λ Logarithmic Approx. (4) εr=10
Magnitude (Ω
2
1.5
− ( hi + h j ) λ
jωµ 0 ∞ e 1
Z ′g ij =
π ∫ 0
λ2 + jωµ 0σ + λ
cos(rij λ )dλ (7) 0.5 (a)
εr=40
εr=20
0
1.E+03 1.E+04 1.E+05 1.E+06 1.E+07 1.E+08
which are the equations proposed by Carson to represent the Frequency (Hz)
80
implemented in popular transient simulators and for this reason Integral Expression (1)
60 Logarithmic Approx. (4)
are often used in the simulation of transients in power systems.
εr=10
40
εr=40
σ(ω), εr(ω)
dij 20 εr=20
j (b)
i 0
hi rij hj 1.E+03 1.E+04 1.E+05 1.E+06 1.E+07 1.E+08
Frequency (Hz)
Ground (σ, ε) Fig. 2 – Comparison between Sunde’s integral expression (1) and its
logarithmic approximation (4) for constant σ=0.0001 S/m and different
Fig. 1. Problem geometry. values of εr. Also included are curves obtained for frequency-dependent
values of ground resistivity and permittivity according to (12) and (13),
For a relatively high ground conductivity of σ=0.01 S/m, it obtained for ρ0=10000 Ω.m.
3 simplified equations proposed by Deri et al. [21] to calculate
Integral Expression (2) σ(ω), εr(ω)
Ω /m)
2.5 Logarithmic Approx. (5) εr=10 the ground-return impedance. This procedure can be readily
Magnitude (Ω
80
Integral Expression (2) assuming εr=1 (if a lossless propagation constant is considered
60 Logarithmic Approx. (5) in the derivation of the aforementioned equations) [26-28]. For
40 εr=10 example, it is known that Sunde’s equations (1) and (2) were
εr=40
σ(ω), εr(ω) derived neglecting propagation effects, which could be viewed
20
(b) εr=20 as a shortcoming. However, for including propagation effects
0 in (1) and (2) as well as in their approximate representations
1.E+03 1.E+04 1.E+05 1.E+06 1.E+07 1.E+08
(4) and (5), it suffices to use the product (εr – 1)ε0 instead of
Frequency (Hz) εrε0 in (3) and (11), as suggested in [26, 28]. Given that the
Fig. 3 – Same as Fig. 2, but for Sunde’s integral expression (2) and its differences observed in the calculated ground return
logarithmic approximation (5).
impedance with assuming either (εr – 1)ε0 or εrε0 in (3) are not
significant for the transient studies performed in this paper, all
250
Percentage Error (%)
(a) Magnitude εr=20 calculations presented here consider Sunde’s equations in their
200
εr=40 original form, which means to assume εrε0 in (3) and (11).
150
100 B. Ground Admittance
σ(ω), εr(ω) εr=10
50 Several expressions have been proposed to include the
0 ground admittance in the calculation of transmission line
1.E+03 1.E+04 1.E+05 1.E+06 1.E+07 parameters [26]. It can be shown that at high frequencies the
Frequency (Hz) ground admittance can be used to explain the transition from a
250 pure TEM propagation to a mixed TEM/TM/TE propagation
Percentage Error (%)
2.5
2
section were assumed for the calculation of the ground-return
1.5 impedance, namely frequency-dependent ground parameters
1
0.5
according to (12) and (13) for σ0=0.0001 S/m, or constant
(a)
0 ground parameters with σ0=0.0001 S/m assuming either
0 5 10 15 20 25 30
Carson’s expressions or Sunde’s expressions with εr=40. The
µs)
Time (µ
.pch file obtained for the frequency dependent case
3
(determined considering a maximum frequency of 107 Hz) is
Voltage (MV)
2.5
2 listed in Appendix B.
1.5
1
0.5 300
(b)
0
0 5 10 15 20 25 30 250
µs)
Time (µ µs)
Phase velocity (m/µ
3 200
Voltage (MV)
2.5
2 150
1.5 σ(ω), εr(ω)
1 σ0, εr=40, Sunde
0.5 σ0, Carson 100
(c)
0 σ(ω), εr(ω)
0 5 10 15 20 25 30 50 σ0, εr=40, Sunde
µs)
Time (µ σ0, Carson
Fig. 5 – Voltages at the receiving end of a single-phase line with length of 0
1 10 100 1000 10000
(a) 600 m, (b) 1800 m or (c) 3600 m assuming the injection of a lightning
Frequency (kHz)
current at the sending end and considering σ0=0.0001 S/m. Both line ends
were connected to a matching resistance of 497.6 Ω. Fig. 6 – Phase velocity associated with a single-phase overhead line with
height of 10 m and radius of 5 mm for σ0=0.0001 S/m and different ground
models.
Taking as reference the voltages calculated assuming
frequency-dependent ground parameters, the results shown in 1.6
Fig. 5 indicate peak values up to 15% higher if a constant
Voltage (V)
1.2
conductivity is assumed in Carson’s expressions. A noticeable 0.8 σ(ω), εr(ω)
difference is also observed in the propagation speed, which 0.4 σ0, εr=40, Sunde
seems to be slower if Carson’s expressions are considered. σ0, Carson (a)
0
This observation is consistent with Fig. 6, which shows that 0 10 20 30 40 50
the phase velocity associated with the use of Carson’s formula µs)
Time (µ
approaches the speed of light slower than the remaining curves 0.8
Voltage (V)
PCH
V R2 V R2
σ0=0.0001 S/m and εr=40 leads again to voltage waveforms in A C
PCH
PCH
PCH
very good agreement with those calculated assuming
frequency-dependent ground parameters. Although not shown, R1 V
additional tests made for lateral distances up to 4 m between PCH PCH PCH PCH PCH PCH PCH D
both conductors (parameter rij in Fig. 1), which could be R2 R2 R2 R2 R2
considered representative of power distribution lines, were
seen to lead to similar conclusions. Again, as expected, the
differences between the calculated waveforms reduced Fig. 8 – Circuit implemented in ATPDraw to simulate a branched distribution
significantly with increasing ground conductivity. line. Each transmission line block is 150-m long, R1=150 Ω and R2=80 Ω.
Voltage (V)
1.2
Most of the literature dealing with the influence of 0.8 σ(ω), εr(ω)
frequency-dependent ground parameters on switching and 0.4 σ0, εr=40, Sunde
σ0, Carson (a)
lightning transients on overhead lines disregards the presence 0
of line branches and multiple grounding points. Since this 0 10 20 30 40 50
µs)
Time (µ
condition is typical of power distribution lines, a final case is
presented here in which the branched distribution line 2
1.6
Voltage (V)
parameters according to (12) and (13) for σ0=0.0001 S/m, or Fig. 9 – Voltages at points (a) A, (b) B, (c) C, and (d) D of the power
constant ground parameters with σ0=0.0001 S/m assuming distribution line of Fig. 8.
either Carson’s expressions or Sunde’s expressions with εr=40.
V. CONCLUSIONS
The .pch file obtained for the frequency dependent case
(determined considering a maximum frequency of 108 Hz) is In this paper, a modal-domain based transmission line
listed in Appendix C. model was used to calculate lightning and switching transients
Fig. 9 shows the voltages calculated at points A, B, C, and considering frequency-dependent ground parameters. Tests
D for the case illustrated in Fig. 8. It is seen that the presence performed in single- and two-phase power distribution lines
of multiple branches and grounding points makes the results indicate that the consideration of ground as a dispersive
nearly independent on the ground-return impedance model, medium can be of some importance in the study of high-
which is an interesting result that might suggest the suitability frequency phenomena on overhead lines located above a
of simplified models for representing the ground parameters in poorly conducting ground (e.g., σ < 0.001 S/m).
certain types of analysis. Once again the results obtained By taking as reference a specific soil model that includes
assuming constant ground conductivity and εr=40 leads to the variation of the ground conductivity and permittivity with
voltage waveforms nearly coincident with the ones calculated frequency, it is shown that assuming a constant value for σ
assuming frequency-dependent ground parameters. together with a suitable value for ε is able to lead to voltage
waveforms in good agreement with those obtained with the C. PCH file of the 150-m long two-phase line of
frequency-dependent ground model. On the basis of the Section IV-C considering frequency-dependent ground
analysis presented in this paper, the use of εr=40 together with parameters
the low-frequency value of the ground conductivity is -1IN___AOUT__A 2. 0.00 -2 2
5 3.5562312867613576000E+02
recommended. In any case, it must be noted that additional 1.40366924312754850E+05
5.79144374266837620E+03
1.20280579296726370E+04
3.97251078211775480E+03
1.01033996388505820E+04
5 5.0010361896812359000E-07
holds for different soil models. If that is the case, a simple 6.58093722985256200E+09
3.74773839204539220E+03
2.11127069118262040E+06
4.27736359182266880E+01
1.27876661948336260E+05
-2IN___BOUT__B 2. 0.00 -2 2
transient simulators to accommodate the possibility of 10 6.2523360219713925000E+02
2.54382062355948330E+08 1.09120891224525930E+08 1.09851497441550920E+07
adjusting a suitable value for εr in the calculation of the 1.42639674133274950E+07
3.07688682057636800E+04
2.94692618246592670E+06
7.15373162912701990E+03
3.00291081286946840E+05
8.89594132964325040E+03
6.71087897067659650E+03
ground-return impedance of transmission lines. 9.06949432833862120E+06 1.78709259622575830E+06 5.87765236367034840E+05
2.70236454624685170E+05 5.00521462255167930E+04 5.95591089011073930E+03
Finally, the obtained results suggest that the presence of 6.12149900566291420E+02
4.21975457926969360E+00
4.74398752824588290E+01 1.20395534102758270E+01
5 4.9964038993728571000E-07
multiple branches and multiple grounding points is likely to -9.87211106052957920E+07 7.67339900090667960E+08 1.13095461526605150E+07
1.70281252045315550E+06 2.06398618397906680E+05
reduce the relative importance of the assumed ground- 3.20416100549760630E+09
1.08002289264442010E+07
1.23780467419306330E+09
1.55435466974295470E+06
9.55644856004598740E+07
0.74278792 0.62609170
impedance model in the simulation of transients in power 0.00000000 0.00000000
-0.66952476 0.77974458
distribution lines. In any case, a more definitive conclusion in -0.00000000 0.00000000