Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Deep Sea PLC Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 65

COMPLEX SOLUTIONS

MADE SIMPLE.

DEEP SEA ELECTRONICS PLC

DSE5310
AUTOSTART CONTROL MODULE

OPERATING MANUAL
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Deep Sea Electronics Plc


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099


Sales Fax: +44 (0) 1723 893303

E-mail: sales@Deepseaplc.com
Website: www.deepseaplc.com

DSE Model 5310 Control and Instrumentation System Operators Manual

© Deep Sea Electronics Plc


All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any
medium by electronic means or other) without the written permission of the copyright holder except in accordance with the
provisions of the Copyright, Designs and Patents Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep
Sea Electronics Plc at the address above.

Any reference to trademarked product names used within this publication is owned by their respective companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

2 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

TABLE OF CONTENTS

Section Page
1  INTRODUCTION .............................................................................................. 5 
2  CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION. ........ 5 
3  OPERATION .................................................................................................... 6 
3.1  AUTOMATIC MODE OF OPERATION ............................................................................... 7 
3.2  MANUAL OPERATION ....................................................................................................... 9 
4  PROTECTIONS .............................................................................................. 10 
4.1  WARNINGS ....................................................................................................................... 11 
4.2  ANALOGUE PRE-ALARMS ............................................................................................. 13 
4.3  HIGH CURRENT WARNING ALARM ............................................................................... 14 
4.4  SHUTDOWNS .................................................................................................................... 15 
4.5  HIGH CURRENT SHUTDOWN ALARM ........................................................................... 19 
4.6  ELECTRICAL TRIPS ......................................................................................................... 19 
5  DESCRIPTION OF CONTROLS .................................................................... 20 
5.1  TYPICAL LCD DISPLAY SCREENS ................................................................................ 22 
5.1.1  TYPICAL STATUS DISPLAY...................................................................................... 22 
5.1.2  TYPICAL INSTRUMENT DISPLAY ............................................................................ 22 
5.1.3  TYPICAL ALARM DISPLAY ....................................................................................... 22 
5.1.4  TYPICAL EVENT DISPLAY ........................................................................................ 23 
5.2  VIEWING THE INSTRUMENTS ........................................................................................ 23 
5.2.1  INSTRUMENT PAGE CONTENT ............................................................................... 24 
5.2.2  MANUALLY SELECTING AN INSTRUMENT ............................................................ 24 
5.2.3  MODEM STATUS ....................................................................................................... 25 
5.2.4  CAN ERROR MESSAGES ......................................................................................... 26 
5.3  VIEWING THE EVENT LOG.............................................................................................. 26 
5.4  USER CONFIGURABLE INDICATORS ........................................................................... 27 
5.5  CONTROLS ....................................................................................................................... 27 
6  FRONT PANEL CONFIGURATION ............................................................... 28 
6.1.1  ENTERING THE CONFIGURATION EDITOR PIN NUMBER ................................... 28 
6.2  EDITING A VALUE ............................................................................................................ 30 
6.2.1  LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’ ...... 31 
6.2.2  LIST OF ADJUSTABLE PARAMETERS IN ‘APPLICATION EDITOR’ ...................... 32 
6.2.3  EDITING THE CURRENT DATE AND TIME ............................................................. 33 
7  INSTALLATION INSTRUCTIONS .................................................................. 35 
7.1  PANEL CUT-OUT .............................................................................................................. 35 
7.2  COOLING........................................................................................................................... 35 
7.3  UNIT DIMENSIONS ........................................................................................................... 35 
7.4  FRONT PANEL LAYOUT .................................................................................................. 36 
7.5  REAR PANEL LAYOUT .................................................................................................... 36 
8  ELECTRICAL CONNECTIONS ...................................................................... 37 
8.1  CONNECTION DETAILS................................................................................................... 37 
8.1.1  PLUG “A” 8 WAY ........................................................................................................ 37 
8.1.2  PLUG “B” 11 WAY ...................................................................................................... 38 
8.1.3  PLUG “C” 3 WAY ........................................................................................................ 38 
8.1.4  PLUG “D” 4 WAY (OPTIONAL) .................................................................................. 39 
8.1.5  PLUG “F” 4 WAY ........................................................................................................ 39 
8.1.6  PLUG “G” 5 WAY ........................................................................................................ 39 
8.1.7  PLUG “H” 4 WAY ........................................................................................................ 40 
8.1.8  PC CONFIGURATION INTERFACE CONNECTOR .................................................. 40 
8.1.9  EXPANSION OUTPUT CONNECTOR ....................................................................... 40 
8.2  CONNECTOR FUNCTION DETAILS ................................................................................ 41 
8.2.1  PLUG “A” 8 WAY ........................................................................................................ 41 
8.2.2  PLUG “B” 11 WAY ...................................................................................................... 41 

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 3
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8.2.3  PLUG “C” 3 WAY ........................................................................................................ 42 


8.2.4  PLUG “D” 4 WAY (OPTIONAL) .................................................................................. 42 
8.2.5  PLUG “F” 4 WAY ......................................................................................................... 42 
8.2.6  PLUG “G” 5 WAY ........................................................................................................ 43 
8.2.7  PLUG “H” 4 WAY ........................................................................................................ 43 
8.2.8  PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ............................ 43 
9  SPECIFICATION.............................................................................................44 
10  COMMISSIONING .......................................................................................46 
10.1.1  PRE-COMMISSIONING.............................................................................................. 46 
11  FAULT FINDING ..........................................................................................47 
12  FACTORY DEFAULT CONFIGURATION ...................................................48 
13  TYPICAL WIRING DIAGRAM......................................................................52 
14  APPENDIX ...................................................................................................53 
14.1  ALTERNATIVE WIRING TOPOLOGIES ....................................................................... 53 
14.1.1  3 PHASE, 3 WIRE ....................................................................................................... 53 
14.1.2  1 PHASE, 2 WIRE ....................................................................................................... 54 
14.1.3  2 PHASE, 3 WIRE ( 2 PHASE CENTRE TAP NEUTRAL) ......................................... 54 
14.2  ICONS AND LCD IDENTIFICATION ............................................................................. 55 
14.2.1  PUSH BUTTONS ........................................................................................................ 55 
14.2.2  STATUS / MEASUREMENT UNITS ........................................................................... 55 
14.2.3  LED INDICATION ....................................................................................................... 55 
14.3  5310 IDMT TRIPPING CURVES (TYPICAL) ................................................................. 56 
14.4  SENDER WIRING RECOMMENDATIONS.................................................................... 57 
14.4.1  EARTH RETURN SENDERS ..................................................................................... 57 
14.4.2  INSULATED RETURN SENDERS ............................................................................. 57 
14.4.3  FUEL LEVEL SENDERS ............................................................................................ 57 
14.5  CAN INTERFACE ......................................................................................................... 59 
14.6  OUTPUT EXPANSION ................................................................................................... 59 
14.6.1  RELAY OUTPUT EXPANSION (157) ......................................................................... 59 
14.6.2  LED OUTPUT EXPANSION (548) .............................................................................. 59 
14.7  INPUT EXPANSION ....................................................................................................... 59 
14.8  COMMUNICATIONS OPTION CONNECTIONS ........................................................... 60 
14.8.1  DESCRIPTION ............................................................................................................ 60 
14.8.2  PC TO CONTROLLER (DIRECT) CONNECTION ..................................................... 60 
14.8.3  MODEM TO CONTROLLER CONNECTION ............................................................. 60 
14.8.4  RS485 LINK TO CONTROLLER ................................................................................ 61 
14.8.5  MODBUS™ ................................................................................................................. 62 
14.9  ENCLOSURE CLASSIFICATIONS ............................................................................... 63 

4 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

1 INTRODUCTION
The DSE 5310 autostart module has been designed to allow the user to start and stop the generator, and if
required, transfer the load to the generator either manually (via external push-buttons) or automatically. The user
also has facility to view all the system operating parameters via the LCD display.

The DSE 5310 module monitors the engine, indicating the operational status and fault conditions; automatically
shutting down the engine and giving a true first up fault condition of an engine failure by a COMMON AUDIBLE
ALARM. The exact failure mode is indicated by text messages on the LCD display on the front panel.

The powerful microprocessor contained within the module allows for a range of complex features to be
incorporated as standard:

• Text based LCD display (supporting multiple languages).


• Voltage, Current and Power monitoring.
• Engine parameter monitoring.
• Fully configurable inputs for use as alarms or a range of different functions.
• Extensive range of output functions using built in relay outputs or relay expansion modules available.

Selective operational sequences, timers and alarm trips can be altered by the customer via a PC using the 52/53xx
series configuration software and P810 interface. Additionally, a subset of this information can be adjusted from the
module’s front panel configuration editor.

The module is housed in a robust plastic case for front panel mounting. Connections to the module are via locking
plug and sockets.

2 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.

Highlights an essential element of a procedure to ensure


NOTE: correctness.

Indicates a procedure or practice which, if not strictly observed,


CAUTION! could result in damage or destruction of equipment.

Indicates a procedure or practice, which could result in injury to


WARNING! personnel or loss of life if not followed correctly.

Compliant with BS EN 60950 Low Voltage Directive


Compliant with BS EN 50081-2 EMC Directive
Compliant with BS EN 50082-2 EMC Directive
Indicates a function only applicable when the controller is
configured for connection to a CAN engine controller

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 5
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

3 OPERATION
The following description details the sequences followed by a module containing the standard ‘factory
configuration’. Always refer to your configuration source for the exact sequences and timers observed by any
particular module in the field.

FIG 1

6 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

3.1 AUTOMATIC MODE OF OPERATION

NOTE:- If a digital input configured to panel lock is active, changing module modes will not be

possible. Viewing the instruments and i


is NOT affected by panel lock. If panel lock is active the
Panel lock indicator (if configured) illuminates.

This mode is activated by pressing the pushbutton. An LED indicator beside the button confirms this
action.

If the Remote Start input (if configured) is activated the relevant indicator (if configured) illuminates.

To allow for false remote start signals, the Start Delay timer is initiated. After this delay, if the pre-heat output option
is selected then the pre-heat timer is initiated, and the corresponding auxiliary output (if configured) will energise.

NOTE:- If the Remote Start signal is removed during the Start Delay timer, the unit will return to a
stand-by state.

After the above delays the Fuel Solenoid (or enable ECU output if configured) is energised, then one second
later, the Starter Motor is engaged.

NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command
via CAN.

The engine is cranked for a pre-set time. If the engine fails to fire during this cranking attempt then the starter
motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts,
the start sequence will be terminated and Fail to Start fault will be displayed.

Alarm
Shutdown
Failed to start

When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator
output. Alternatively, a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is
selected by PC using the 5xxx series configuration software). Rising oil pressure can also be used to disconnect
the starter motor; however, it cannot be used for underspeed or overspeed detection.

NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 7
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.

Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before
accepting the load.

If an auxiliary output has been selected to give a load transfer signal, this then activates.

NOTE:-A load transfer will not be initiated until the Oil Pressure has risen. Thus preventing
excessive wear on the engine.

On removal of the Remote Start signal, the Stop delay timer is initiated, once it has timed out, the load Transfer
signal is de-energised, removing the load. The Cooling timer is then initiated, allowing the engine a cooling down
period off load before shutting down. Once the Cooling timer expires the Fuel Solenoid is de-energised, bringing
the generator to a stop.

Should the Remote Start signal be re-activated during the cooling down period, the set will return on load.

8 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

3.2 MANUAL OPERATION

NOTE:- If a digital input configured to panel lock is active, changing module modes will not be

possible. Viewing the instruments and event logs i


is NOT affected by panel lock. If panel lock is
active the Panel lock indicator (if configured) illuminates.

To initiate a start sequence in MANUAL, press the pushbutton. When the controller is in the manual mode
(indicated by an LED indicator beside the button), pressing the START (I) button will initiate the start sequence.

NOTE:- There is no Start Delay in this mode of operation.

If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised.

After the above delay, the Fuel Solenoid (or ECU output if configured) is energised, then one second later, the
Starter Motor is engaged.

NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command
via CAN.

The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the
starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of
attempts, the start sequence will be terminated and Fail to Start will be displayed.

When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator
output. Alternatively, a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is
selected by PC using the 52/53xx series configuration software). Rising oil pressure can also be used to
disconnect the starter motor; however, it cannot be used for underspeed or overspeed detection.

NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.

After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.

Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before it
can be loaded.

The generator will run off load, unless the Remote Start on load signal is applied or, if Close generator has been
selected as a control source, the appropriate auxiliary output will then activate.

The generator will continue to run On load, until the Auto mode is selected.

If Auto mode is selected, and the remote start on load signal is not active, then the Stop Delay Timer begins,
after which, the load is disconnected. The generator will then run off load allowing the engine a cooling down
period.

Selecting STOP (O) de-energises the FUEL SOLENOID, bringing the generator to a stop.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 9
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

4 PROTECTIONS
When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configured will illuminate.

The audible alarm can be silenced by pressing the ‘Mute’ button

The LCD display will jump from the ‘Information page’ to display the Alarm Page

Alarm
Warning The type of alarm. E.g. Shutdown or warning
Low oil pressure
The nature of alarm, eg Low oil pressure.

The LCD will display multiple alarms E.g. “High Engine Temperature shutdown”, “Emergency Stop” and “Low
Coolant Warning” alarms have been triggered. These will automatically scroll round in the order that they occurred;

Running in auto If no alarms are present the


LCD will display this default
Generator on load page.
L-N 230V 240A 50Hz
L-L 400V 133kW
In the event of a warning alarm, the LCD will display the appropriate text. If a shutdown then occurs, the module
will again display the appropriate text.
Example:-

Alarm
Shutdown
High engine temperature

Followed by….

Alarm
Shutdown
Emergency stop

Followed by….

Alarm
Warning
Low coolant level

The unit will scroll through all


active alarms in a continuous
loop.
Alarm
Shutdown
High engine temperature

10 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

4.1 WARNINGS

Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operators attention to an undesirable condition.

In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and
shutdowns.

BATTERY CHARGE FAILURE, will be displayed if the module does not detect a voltage from the warning light
terminal on the auxiliary charge alternator.

Alarm
Warning
Charge fail

BATTERY LOW VOLTAGE, will be displayed if the module detects that the plant DC supply has fallen below the
low volts setting level. The Battery Low Voltage alarm is delayed by the Low DC Volts Delay timer.

Alarm
Warning
Low battery volts

BATTERY HIGH VOLTAGE, will be displayed if the module detects that the plant DC supply has risen above the
high volts setting level. The Battery High Voltage alarm is delayed by the High DC Volts Delay timer.

Alarm
Warning
High battery volts

MAINTENANCE ALARM, will be displayed if the maintenance period is exceeded (engine running hours or date
interval whichever is configured).

Alarm
Warning
Maintenance alarm

FAIL TO STOP, will be displayed if the module detects the engine is still running when the ‘Fail to stop timer’
expires.

Alarm
Fail to stop

NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sender - If engine is at rest check oil sender
wiring and configuration.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 11
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

AUXILIARY INPUTS, auxiliary inputs can be user configured and will display the message as written by the user.

Example
Alarm
Warning
Bearing temp high

LOW FUEL LEVEL will be displayed if the fuel level detected by the fuel level sender falls below the low fuel level
setting.

Alarm
Warning
Low fuel level

CAN ECU ERROR If the module is configured for CAN instruments and receives an “error” message from
the engine control unit, ‘Can ECU error” is shown on the module’s display and a warning alarm is
generated.

Example
Alarm The display will alternate Alarm
between the text display and the
Can ECU error manufacturers error codes Can ECU error
Exhaust high SPNnnnnnnn
temperature FMInnnnnnn

12 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

4.2 ANALOGUE PRE-ALARMS


The following alarms are termed ‘pre-alarms’ as they pre warn the operator of a potentially more serious alarm
condition. For instance, if the engine temperature rises past the pre alarm level, a warning condition will occur to
notify the operator. If the temperature falls below this level, then the alarm ceases, and the set will continue to run
as normal. However if the temperature continues to rise until the coolant temperature trip point is reached, the
warning is escalated and a high coolant temperature shutdown is initiated.

LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure pre-
alarm setting level after the Safety On timer has expired, a warning will occur. Alarm Warning Low Oil Pressure will
be displayed.

Alarm
Warning
Low oil pressure

HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high
engine temperature pre-alarm setting level after the Safety On timer has expired, a warning will occur. Alarm
Warning High Coolant Temperature will be displayed.

Alarm
Warning
High temperature

LOW ENGINE TEMPERATURE if the module detects that the engine coolant temperature has fallen below the low
engine temperature pre-alarm setting level after the Safety On timer has expired, a warning will occur. Alarm
Warning Low Coolant Temp will be displayed.

Alarm
Warning
Low Coolant Temp

OVERSPEED, if the engine speed exceeds the pre-alarm trip a warning is initiated. Alarm Warning Overspeed will
be displayed. It is an immediate warning.

Alarm
Warning
Overspeed

UNDERSPEED, if the engine speed falls below the pre-set pre-alarm after the Safety On timer has expired, a
warning is initiated. Alarm Warning Underspeed will be displayed.

Alarm
Warning
Underspeed

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 13
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of the pre-set
pre-alarm, a warning is initiated. Alarm Warning High frequency will be displayed, it is an immediate warning.

Alarm
Warning
Over frequency

GENERATOR LOW FREQUENCY if the module detects a generator output frequency below the pre-set pre-alarm
after the Safety On timer has expired, a warning is initiated. Alarm Warning Low Frequency will be displayed

Alarm
Warning
Under frequency

GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre-set pre-
alarm, a warning is initiated. Alarm Warning High voltage will be displayed, it is an immediate warning.

Alarm
Warning
AC Overvolts

GENERATOR LOW VOLTAGE if the module detects a generator output voltage below the pre-set pre-alarm after
the Safety On timer has expired, a warning is initiated. Alarm Warning Low Voltage will be displayed.

Alarm
Warning
AC Undervolts

CAN ECU ERROR If the module is configured for CAN instruments and receives an “error” message from
the engine control unit, ‘Can ECU error” is shown on the module’s display and a warning alarm is
generated.

Example
Alarm The display will alternate Alarm
between the text display and the
Can ECU error manufacturers error codes Can ECU error
Exhaust high SPNnnnnnnn
temperature FMInnnnnnn

4.3 HIGH CURRENT WARNING ALARM

GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning is initiated. Alarm Warning High Current will be displayed. If this high current condition continues for an
excess period of time, then the alarm is escalated to a shutdown condition. For further details of the high current
alarm, please see High Current Shutdown Alarm.

Alarm
Warning
High current

14 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

4.4 SHUTDOWNS
Shutdowns are latching and stop the Generator. The alarm must be cleared, and the fault removed to reset the
module.

NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition
remains it will not be possible to reset the unit (The exception to this is the Low Oil Pressure alarm and
similar ‘delayed alarms’, as the oil pressure will be low with the engine at rest).

FAIL TO START, if the engine does not fire after the pre-set number of attempts has been made a shutdown will
be initiated. Alarm Shutdown Fail To Start will be displayed.

Alarm
Shutdown
Failed to start

EMERGENCY STOP, removal of the Positive DC Supply from the Emergency Stop input initiates the following
sequence. Firstly it will initiate a controlled shutdown of the Generator and prevent any attempt to restart the
Generator until the Emergency Stop push-button has been reset. Secondly it removes the Positive DC supply from
both the Fuel Solenoid and Starter Solenoid.

Alarm Shutdown Emergency Stop will be displayed.

Alarm
Shutdown
Emergency stop

NOTE:- The Emergency Stop Positive signal must be present otherwise the unit will shutdown.

LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure trip
setting level after the Safety On timer has expired, a shutdown will occur. Alarm Shutdown Low Oil Pressure will
be displayed.

Alarm
Shutdown
Low oil pressure

HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high
engine temperature trip setting level after the Safety On timer has expired, a shutdown will occur. Alarm Shutdown
High Engine Temperature will be displayed.

Alarm
Shutdown
High temperature

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 15
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

OVERSPEED, if the engine speed exceeds the pre-set trip a shutdown is initiated. Alarm Shutdown Overspeed will
be displayed. Overspeed is not delayed, it is an immediate shutdown.

Alarm
Shutdown
Overspeed

NOTE:-During the start-up sequence the overspeed trip logic can be configured to allow an extra
trip level margin. This is used to prevent nuisance tripping on start-up - Refer to the 53xx series
configuration software manual under heading ‘Overspeed Overshoot’ for details.

UNDERSPEED, if the engine speed falls below the pre-set trip after the Safety On timer has expired, a shutdown is
initiated. Alarm Shutdown Underspeed will be displayed.

Alarm
Shutdown
Underspeed

GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of the pre-set trip
a shutdown is initiated. Alarm Shutdown High Frequency will be displayed, it is an immediate shutdown.

Alarm
Shutdown
Over frequency

GENERATOR LOW FREQUENCY, if the module detects a generator output frequency below the pre-set trip after
the Safety On timer has expired, a shutdown is initiated. Alarm Shutdown Low Frequency will be displayed.

Alarm
Shutdown
Under frequency

GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre-set trip a
shutdown is initiated. Alarm Shutdown High Volts will be displayed, it is an immediate shutdown.

Alarm
Shutdown
AC Overvolts

GENERATOR LOW VOLTAGE if the module detects a generator output voltage below the below the pre-set trip
after the Safety On timer has expired, a shutdown is initiated. Alarm Shutdown Low Volts will be displayed.

Alarm
Shutdown
AC Undervolts

16 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

OIL PRESSURE SENDER OPEN CIRCUIT, if the module detects a loss of signal from the oil pressure sender
(open circuit) a shutdown is initiated. Alarm Shutdown Sender Fault will be displayed. Sender failure is not delayed,
it is an immediate shutdown.

Alarm
Shutdown
Oil pressure
sender fault

AUXILIARY INPUTS, if an auxiliary input has been configured as a shutdown the appropriate message will be
displayed as configured by the user.

Alarm
Shutdown
Bearing temp high

MAINTENANCE ALARM, will be displayed if the maintenance period is exceeded (engine running hours or date
interval whichever is configured). The engine is shutdown (if configured to do so)

Alarm
Shutdown
Maintenance alarm

LOSS OF SPEED SIGNAL, if the speed sensing signal is lost during cranking, a shutdown is initiated. Alarm
Shutdown Loss Of Speed Signal will be displayed.

Alarm
Shutdown
Loss of speed
signal

NOTE:- This will only occur if the speed sensing signal is lost during cranking or during the safety
on timer. If the signal is lost during normal operation the Generator will shutdown with an Under-speed
alarm.

CAN DATA FAIL If the module is configured for CAN operation and does not detect data on the engine Can
datalink, a shutdown will occur and ‘Can data fail’ is shown on the module’s display.

Alarm
Shutdown
Can data fail

CAN ECU FAIL If the module is configured for CAN instruments and receives a “fail” message from the
engine control unit, the engine is shutdown and ‘Can ECU fail” is shown on the module’s display.

Example
Alarm The display will alternate Alarm
between the text display and the
Can ECU fail manufacturers error codes Can ECU fail
Fuel pressure low SPNnnnnnnn
FMInnnnnnn

NOTE:- If the CAN message is a manufacturers specific code, it may not be displayed as text.
If this is the case the display will show the generic manufacturers code, which must be cross-
referenced with the engine manufacturers literature. . Please contact the engine manufacturer for
further assistance.
Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 17
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Example
Alarm
Can ECU fail
SPNnnnnn
FMInnnn

18 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

4.5 HIGH CURRENT SHUTDOWN ALARM


GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning is initiated. This warning will continue for a period of time depending upon the level of overload that the
generator is subjected to, and the configuration setting for Generator High Current in the 5xxx series configuration
software.

Alarm
Shutdown
High current trip

For instance the factory default settings for Generator High Current allow for a loading of the generator to 110% for
one hour. That is to say if the generator load level exceeds the trip point by 10%, a warning alarm will occur while
the overload condition exists. If the load level does not drop to normal levels within one hour, the set is stopped,
the 5310 module displaying either shutdown alarm or electrical trip alarm depending upon module configuration.

NOTE:- Higher overload levels will result in a faster acting shutdown condition. For instance with
the factory default configuration, an overload level twice that of the trip level ( typically 200%) will result
in a Generator High Current shutdown condition after 36 seconds.
For details of the relationship between the overload and the shutdown time, please see the Appendix
section of this manual.

4.6 ELECTRICAL TRIPS

Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip
condition the module will de-energise the ‘Close Generator’ Output to remove the load from the generator. Once
this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down
the engine. The alarm must be accepted and cleared, and the fault removed to reset the module.

AUXILIARY INPUTS, if an auxiliary input has been configured as an electrical trip the appropriate message will be
displayed as configured by the user.

Example
Alarm
Electrical trip
Phase rotation

GENERATOR HIGH CURRENT. If the module detects a generator output current in excess of the pre-set trip a
warning is initiated. If this high current condition continues for an excess period of time, then the alarm is escalated
to either a shutdown or electrical trip condition (depending upon module configuration). For further details of the
high current alarm, please see High Current Shutdown Alarm.

Alarm
Electrical trip
High current

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 19
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5 DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.

Scroll Down Next page Configurable LEDs

Stop Manual Auto Mute/Lamp Start


Test

20 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Close Generator Generator available


Output LED. On When LED. On When The
The Generator Is Generator Is Available
Required To Be On For Loading.
Load

NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of
the controllers digital inputs.
1) Digital input configured for “Generator closed auxiliary” – The LED will be lit when the generator
closed auxiliary input is active – The LED shows the state of the auxiliary contact.
2) There is NO input configured for “Generator closed auxiliary” (factory default setting) – The LED will
be lit when the 5310 gives the loading signal to the generator – The LED shows the state of the
5310’s loading request.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 21
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5.1 TYPICAL LCD DISPLAY SCREENS

5.1.1 TYPICAL STATUS DISPLAY

Waiting in auto Indicates that the module is in Automatic. The unit will respond to
an active remote start.

Starting remote Indicates that the module is in automatic and that a start sequence
Cranking attempt 1 has been initiated, with an active remote start. The module is
attempting to crank the generator.

Running in auto Indicates that the module is in Automatic, and that the generator is
Generator on load running on load. This default screen also indicates the average line
to neutral voltage, highest of the 3 phase currents, generator
L-N 230V 240A 50Hz frequency, average line to line voltage and total kilowatts.
L-L 400V 133kW
5.1.2 TYPICAL INSTRUMENT DISPLAY

Coolant temperature The display of coolant temperature in both degrees centigrade and
Fahrenheit.
60 ºC 140 ºF

Oil pressure The display of engine oil pressure in Bar, Pounds Per Square Inch
and kilo Pascal.
6 Bar 87 PSI
600 kPa

Generator Amps The display of all three generator line currents.


L1 L2 L3
238 241 241

5.1.3 TYPICAL ALARM DISPLAY

Alarm The module is warning that the engine oil pressure has fallen
Warning below a pre-set level. The generator is not shut down.
Low oil pressure

Alarm The oil pressure has fallen below a second pre-set value and has
Shutdown shut down the generator.
Low oil pressure

Alarm The module is warning that the battery volts is below a pre-set
Warning value.
Low battery Volts

22 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5.1.4 TYPICAL EVENT DISPLAY

Event log 21:15:00 On the 10th September 2005 at 21:15 the unit detected that the oil
10th September 2005 pressure was below the pre-set trip level, and has shut down the
Low oil pressure generator.
Shutdown

Event log 20:10:00 On the 8th September 2005 at 20:10. The emergency stop button
8th September 2005 was pressed and the generator was shut down.
Emergency stop
Shutdown

Event log 08:46:00 On the 7th September 2005 at 08:46 the unit detected that the
7th September 2005 generator out put volts exceeded pre-set trip level, and has shut
Over Volts down the generator.
Shutdown

5.2 VIEWING THE INSTRUMENTS


It is possible to manually scroll to display the different pages of information by repeatedly operating the next page
i button.

Page order:-
• Status display
• Instrument display
• Alarms display
• Event log

It is possible to manually scroll to display the different instruments by repeatedly operating the next page
button . Once selected the instrument will remain on the LCD display until the user selects a different
instrument or after a period of inactivity for the duration of the configurable Page Timer, the module will revert to the
default display.
Alternatively, to autoscroll through all instruments on the currently selected page, press and hold the scroll
button.

To disable autoscroll, press and hold the scroll button, or select another page with the page select i button.
When autoscroll is disabled, the display will automatically return to the Status/Alarms page if no buttons are
pressed for the duration of the configurable Page Timer.
If an alarm becomes active while viewing instruments, the Status/Alarms page will be automatically displayed to
draw the operator’s attention to the alarm condition.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 23
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5.2.1 INSTRUMENT PAGE CONTENT


• Engine speed
• Oil Pressure
• Coolant temperature
• Fuel level (%)
• Engine Hours Run
• DC Battery Voltage
• Charge alternator volts
• Modem Status (GSM only)
• Generator AC RMS Voltage Line-Neutral
• Generator AC RMS Voltage Line-Line
• AC RMS Line Current
• Generator Output
• Number of starts
If enhanced instrumentation is selected, the following instrumentation will become
available, if supported by the engine manufacturer.
• Engine oil temperature
• Inlet manifold temperature
• Coolant pressure
• Fuel pressure
• Fuel consumption
• Total fuel used
• Turbo pressure

5.2.2 MANUALLY SELECTING AN INSTRUMENT


Default display Running in auto
Generator on load
L-N 230V 240A 50Hz
L-L 400V 133kW
Pressing the DOWN button the LCD will Engine speed
then show Engine speed.
1500 RPM
50 Hz
Pressing the DOWN button the LCD will Oil pressure
then show Oil pressure.
6 Bar 87 PSI
600 Kpa

Pressing the button again will scroll through each individual instrument eventually returning to the original
instrument displayed.

NOTE:-Once selected the instrument will remain on the LCD display until the user selects a different
instrument or after a period of inactivity for the duration of the configurable Page Timer, the module will
revert to the initial display.

24 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5.2.3 MODEM STATUS

When configured and connected to a GSM Modem for cellular network communications, the GSM MODEM
STATUS screen shows the following information.

Modem Status The modem is reset by the 5300 series controller.


Resetting modem

Modem Status Modem initialising strings are sent to the modem (as set in the Edit Config | Comms
Initialising modem… tab of the configuration software.

Modem Status The modem has been initialised and is ready to answer.
Ready to answer

If the module does not detect that the modem is operating correctly, this procedure begins again from Resetting
modem and will continue to repeat until the modem operation is detected correctly.

GSM STATUS

If the DSE controller detects that the modem connected is a GSM modem, the following additional status is shown:

Modem Status The modem has been initialised and is ready to answer. OK shows the SIM card is
Ready to answer inserted but there is no signal
OK

Modem Status The modem has been initialised and is ready to answer.
Ready to answer The SIM card is inserted, the signal is received full strength and the operator name is
OK shown.

ORANGE UK NOTE:- Operator name is not available in all GSM areas.

Modem Status The modem has been initialised and is ready to answer.
Ready to answer The SIM card is inserted, the signal is received but is low and the operator name is
OK shown.

ORANGE UK NOTE:- Operator name is not available in all GSM areas.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 25
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5.2.4 CAN ERROR MESSAGES

Where 53xx controllers are connected to a suitable Can ECU, alarm status messages are transmitted to the
53xx controller and displayed on the alarms page.

Alarm Here the ECU code is interpreted by the module, which Alarm
CAN ECU error displays the warning as text. An error is like a warning, and CAN ECU error
Exhaust hi temp does not shutdown the generator. SPNnnnnn
The display will alternate between the text display and the FMInnnnn
manufacturers error codes

Alarm A CAN ECU fail is a shutdown and the module stops the Alarm
CAN ECU fail generator. CAN ECU fail
Fuel pressure low The display will alternate between the text display and the SPNnnnnn
manufacturers error codes FMInnnnn

Alarm Where the module does not recognise the ECU error / fail
CAN ECU error code the SPN and FMI codes are displayed. These codes
SPNnnnnn then have to be cross referenced with engine manufactures
FMInnnnn literature to determine the exact problem.

NOTE:- For details on these code meanings, refer to the ECU instructions provided by the engine
manufacturer, or contact the engine manufacturer for further assistance.

NOTE:- For further details on connection to electronic engines please refer to the CAN and DSE
wiring manual.

5.3 VIEWING THE EVENT LOG


The 53xx modules maintains a log of the last 30
Event log 21:15:00
shutdown alarms to enable the operator or
engineer to view the past alarms history. Only 10th September 2005
shutdown and electrical trip alarms are logged; Low oil pressure
warning alarms are not logged. Once the log is Shutdown
full (30 events, any subsequent shutdown
alarms will overwrite the oldest entry in the log.
Hence the log will always contain the 30 most
recent shutdown alarms.
The alarm is logged, along with the date and
time of the event in the format shown in this
example.

To view the event log, repeatedly press the next page button i the LCD screen displays Event log.

Press down to view the next most recent shutdown alarm:

Continuing to press down will cycle through the past alarms until all 30 logged alarms have been viewed,
after which the most recent alarm will again be showed and the cycle will begin again.

To exit the event log and return to viewing the instruments, press the next page i button.

26 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

5.4 USER CONFIGURABLE INDICATORS


These LEDs can be configured by the user to indicate any one of 100+ different functions
based around the following:-
• Indications - Monitoring of a digital input and indicating associated functioning user’s
equipment - Such as Battery Charger On or Louver’s Open, etc.
• WARNINGS And SHUTDOWNS - Specific indication of a particular warning or
shutdown condition, backed up by LCD indication - Such as Low Oil Pressure
Shutdown, Low Coolant level, etc.
• Status Indications - Indication of specific functions or sequences derived from the
modules operating state - Such as Safety On, Pre-heating, Panel Locked, Generator
Available, etc.
5.5 CONTROLS
Stop / Reset
This button places the module into its Stop/reset mode. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine is running and this position is selected,
the module will automatically instruct the changeover device to unload the generator (‘Close
Generator’ becomes inactive (if used)). The fuel supply will be removed and engine will be brought
to a standstill. Should a remote start signal be present while operating in this mode, a remote start
will not occur.
If configured, the 5310 controller will enter sleep mode after 60 seconds of inactivity as a power
saving feature.
Manual
This mode is used to allow manual control of the generator functions. Once in Manual mode the
module will respond to the start (I) button and start the engine and run off load. If the engine is
running off-load in the Manual mode and a remote start signal becomes present, the module will
automatically instruct the changeover device to place the generator on load (‘Close Generator’
becomes active (if used)). Should the remote start signal then be removed the generator will
remain on load until either the ‘STOP/RESET’ or ‘AUTO’ positions is selected.
Auto
This button places the module into its ‘Automatic’ mode. This mode allows the module to control the
function of the generator automatically. The module will monitor the remote start input and once a
start condition is signalled the set will be automatically started and placed on load (‘Close
Generator’ becomes active (if used)). If the starting signal is removed the module will automatically
transfer the load from the generator and shut the set down observing the stop delay timer and
cooling timer as necessary. The module will then await the next start event. For further details
please see the more detailed description of ‘Auto Operation’ earlier in this manual.
Test
This button places the module into its ‘Test’ mode. This mode allows the operator to perform an ‘on
load’ test of the system. Once in Test mode the module will respond to the start I button and start
the engine, and run on load (‘Close Generator’ becomes active (if used)). The generator will
continue to run on load until Auto mode is selected. Then, If the starting signal is removed, the
module will automatically transfer the load from the generator and shut the set down observing the
stop delay timer and cooling timer as necessary. The module will then await the next start event.
For further details please see the more detailed description of ‘Test Operation’ earlier in this manual.
Start
This button is only active in STOP/RESET , MANUAL or TEST mode.
Pressing this button in manual or test mode will start the engine and run off load (manual) or on load
(test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly
I
configured and fitted to a compatible engine ECU)
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs. If there is no
audible alarm this button will only illuminate all the LEDs.
When correctly configured and fitted to a compatible engine ECU, pressing this button in
STOP/RESET mode after pressing the START I button (to power the ECU) will cancel any
“passive” alarms on the engine ECU.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 27
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

6 FRONT PANEL CONFIGURATION


This configuration mode allows the operator limited customising of the way the module operates.

Operation Detail
To enter the ‘configuration mode’ press both the INFO
and STOP buttons together.
+
6.1.1 ENTERING THE CONFIGURATION EDITOR PIN NUMBER
The configuration editor contains two sections.
• Main configuration editor (for ‘site adjustable’ or ‘commissioning’ parameters)
• Application editor (to allow installation engineers to make application changes).
The ‘Application Editor’ is designed to allow the module to be configured for different applications without
needing to re-configure the module settings. This makes it particularly suitable for applications where the
generator would be used in a number of different roles, specifically in Rental or mobile type applications.

If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be
viewed or changed until the PIN number is correctly entered.

Enter either the ‘main’ PIN or the application PIN.

If no PIN has been set, then skip to the next section.

NOTE:- The ‘Application Editor’ must be enabled first in order to make it accessible from the
module’s fascia. This is done by setting a PIN (number) for the module’s main front panel editor, using the
5xxx for Windows™ PC configuration software.

- button + button 9 button

The configuration editor contains two sections.


• Main configuration editor (for ‘site adjustable’ or ‘commissioning’ parameters)
• Application editor (to allow installation engineers to make application changes).
The ‘Application Editor’ is designed to allow the module to be configured for different applications without
needing to re-configure the module settings. This makes it particularly suitable for applications where the
generator would be used in a number of different roles, specifically in Rental or mobile type applications.

28 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be
viewed or changed until the PIN number is correctly entered.

Enter either the ‘main’ PIN or the application PIN.

If no PIN has been set, then skip to the next section.

NOTE:- The ‘Application Editor’ must be enabled first in order to make it accessible from the
module’s fascia. This is done by setting a PIN (number) for the module’s main front panel editor, using the
5xxx for Windows™ PC configuration software.

Enter pin The first * is flashing. Press + or – buttons to adjust it to the correct value for the first digit
of the PIN number.
**** Press 9 when the first digit is correctly entered.
The entered digit will turn back to a * to maintain security.

Enter pin The second * is now flashing. Press + or – buttons to adjust it to the correct value for the
second digit of the PIN number.
**** Press 9 when the second digit is correctly entered.
The entered digit will turn back to a * to maintain security.

Enter pin The third * is now flashing. Press + or – buttons to adjust it to the correct value for the third
digit of the PIN number.
**** Press 9 when the third digit is correctly entered.
The entered digit will turn back to a * to maintain security.

Enter pin The fourth * is now flashing. Press + or – buttons to adjust it to the correct value for the
fourth digit of the PIN number.
**** Press 9 when the fourth digit is correctly entered.

NOTE:- When 9 is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, the editor is automatically exited. To retry you must re-enter the editor as
described above.

Oil pressure pre-alarm If the Configuration PIN has been entered successfully (or the PIN
number has not been set in the module) the first configurable parameter is
2 Bar 30 PSI displayed :
200 kPa

NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes you have made by pressing the 9 button first.

NOTE:- When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.

NOTE:- If the Application Menu PIN is entered, then only the Application Menu is displayed. If the
Full Configuration PIN is entered, the entire configuration menu is displayed including the Application
Menu.

NOTE:- The PIN number is automatically reset when the editor is exited (manually or automatically)
to ensure security.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 29
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

6.2 EDITING A VALUE

Oil pressure pre-alarm i


Press the Stop/Reset and Info buttons
2 Bar 30 PSI simultaneously.

200 kPa If the module PIN number has been set, the PIN number
request is then shown. The configuration cannot be viewed
or changed until the PIN number is correctly entered. (see
the section ACCESSING THE FRONT PANEL
CONFIGURATION EDITOR)

Press the + button until the desired page is shown. EG oil


pressure pre-alarm.

Oil pressure pre-alarm To edit the oil pressure pre-alarm, press the 9 button, the
will start to flash. Pressing the + or – buttons will
2 Bar 30 PSI pressure
200 kPa adjust the parameter to the desired value. In this example,
the 30 PSI will be adjusted, and the bar/kPA units will
automatically show their respective values.

Oil pressure pre-alarm Press the 9 button to ‘save’ the value. The value will stop
3 Bar 45 PSI flashing to confirm that it has been saved.
300 kPa

Oil pressure shutdown To select another value to edit, press the + button.
1 Bar 15 PSI
100 kPa

NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes you have made by pressing the 9 button first.

Continuing to press the + or – buttons will cycle through the adjustable parameters in the order shown overleaf:

30 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

6.2.1 LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’

Section Parameter Display shows Values


Input settings Low Oil Pressure warning Oil pressure pre-alarm 0-4bar (1.17bar)
Low Oil Pressure shutdown Oil pressure shutdown 0-4bar (1.03bar)
High Temperature warning Coolant temp pre-alarm 80-140°C (110°C)
High Temperature shutdown Coolant temp shutdown 80-140°C (120°C)
Low Coolant Temperature Low Coolant Temperature 65-136°C (65°C)
Timers Generator transient delay Gen transient delay 0 -10s (0s)
Start delay Start delay 0 -60m (5s)
Return delay Return delay 0 -60m (30s)
Preheat Preheat 0 -60m (5s)
Crank attempt Cranking time 0 -60s (10s)
Crank rest Crank rest 0-60s (10s)
Safety delay Safety on delay 0-30s (10s)
Overspeed overshoot Overspeed overshoot 0-10s (0s)
Warming up Warm up 0-60m (0s)
Cooling run Cooling 0-60m (60s)
Fail to stop delay Fail to stop 0-30s (30s)
Low battery volts delay Battery low delay 0-10m (1m)
High battery volts delay Battery high delay 0-10m (1m)
Generator Generator Under voltage shutdown Gen low voltage shutdown 50-360V ph-N (184V)
Generator Under voltage prealarm Gen low voltage pre-alarm 50-360V ph-N (196V)
Generator Over voltage prealarm Gen high voltage pre-alarm 50-360V ph-N (253V)
Generator Over voltage shutdown Gen high voltage shutdown 50-360V ph-N (265V)
Generator Under frequency shutdown Gen low frequency shutdown 0 -75Hz (40Hz)
Generator Under frequency prealarm Gen low frequency pre-alarm 0 -75Hz (42Hz)
Generator Over frequency prealarm Gen high frequency pre-alarm 0 -75Hz (55Hz)
Generator Over frequency shutdown Gen high frequency shutdown 0 -75Hz (57Hz)
Generator delayed overcurrent Delayed high current 100-200% (100%)
Engine Underspeed (RPM) shutdown Underspeed shutdown 0-6000RPM (1270)
Underspeed (RPM) warning Underspeed pre-alarm 0-6000RPM (1350)
Overspeed (RPM) warning Overspeed pre-alarm 0-6000RPM (1650)
Overspeed (RPM) shutdown Overspeed shutdown 0-6000RPM (1710)
Overspeed overshoot % Overspeed overshoot percent 0-10 (0%)
Low DC Voltage Battery low warning 0-24V (8V)
High DC Voltage Battery high warning 0-24V (33V)
Charge Alternator Failure Charge fail warning 0-24V (6V)
Display Language Language ENGLISH, OTHER
(see note below)

Application Engine speed selection Alternative Frequency Disable, Enable


Volts selection Alternative Voltage Disable, Enable
Wiring topography AC System 3 phase 4 wire
Single phase, 2 wire
3 phase, 3 wire
2 phase 3 wire (L1 & L2)
2 phase 3 wire (L1 & L3)

Full load current rating Generator Full Load 5A - 6000A (500A)


Droop Disable, Enable
Droop % 0% - 5%
LCD Contrast Contrast † „
Date/Time Date and Time dd mmm yyyy hh:mm

NOTE:- Display language selection via the modules front panel configuration editor is between
English and a PC configurable language. This ‘other’ language is configurable using the 5xxx PC
configuration software in conjunction with the P810 interface.

NOTE:- Droop percent is only applicable to CAN controlled engines when CAN is enabled in the
5300 series controller.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 31
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

6.2.2 LIST OF ADJUSTABLE PARAMETERS IN ‘APPLICATION EDITOR’

Section Parameter Display shows Values


Application Engine speed selection Alternative Frequency Disable, Enable
Volts selection Alternative Voltage Disable, Enable
Wiring topography AC System 3 phase 4 wire
Single phase, 2 wire
3 phase, 3 wire
2 phase 3 wire (L1 & L2)
2 phase 3 wire (L1 & L3)

Full load current rating Generator Full Load 5A - 6000A (500A)


Droop Disable, Enable
Droop % 0% - 5%
LCD Contrast Contrast † „
Date/Time Date and Time dd mmm yyyy hh:mm

32 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

6.2.3 EDITING THE CURRENT DATE AND TIME

The date and time can be set either using the 5xxx series configuration software or the front panel configuration
editer.

NOTE:- The 5320 controller maintains the current date and time so long as it is connected to a DC
supply within the operating range. Disconnection of the supply will result in the date and time being
frozen until the module’s power is reapplied. When this occurs, the date and time will resume operation
from the time the power was disconnected. If this occurs you can use the front panel configuration
editor to correct the date and time or reset it using the 5xxx series configuration software.

NOTE:- The calendar is used by the 5310’s run scheduler and the event log.

Date and time i


Press the Stop/Reset and Info buttons simultaneously.
19 Sep 2005 10:00
If the module PIN number has been set, the PIN number request
is then shown. The configuration cannot be viewed or changed
until the PIN number is correctly entered. (see the section
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR)

Press the + button until the desired page is shown. Date and
time

Date and time To edit the Date and time, press the 9 button, the minutes will
19 Sep 2005 10:00 start to flash. Pressing the + or – buttons will adjust the
minutes to the desired value.

Date and time


Press the button to ‘save’ the value, and select the hours
19 Sep 2005 10:00 for adjustment. The hours will start to flash.

Pressing the + or – buttons will adjust the hours to the desired


value.

Date and time


Press the button to ‘save’ the value, and select the day for
19 Sep 2005 10:00 adjustment. The day will start to flash.

Pressing the + or – buttons will adjust the day to the desired


value.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 33
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Date and time


Press the button to ‘save’ the value, and select the month
19 Sep 2005 10:00 for adjustment. The month will start to flash.

Pressing the + or – buttons will adjust the month to the desired


value.

Date and time


Press the button to ‘save’ the value, and select the year
19 Sep 2005 10:00 for adjustment. The year will start to flash.

Pressing the + or – buttons will adjust the year to the desired


value.

Date and time Press the 9 button to ‘save’ the values.


19 Sep 2005 10:00

NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes you have made by pressing the 9 button first.

Continuing to press the + or – buttons will cycle through the adjustable parameters in the order shown overleaf:

34 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

7 INSTALLATION INSTRUCTIONS
The model DSE 5310 Module has been designed for front panel mounting. Fixing is by 4 clips for easy assembly.

7.1 PANEL CUT-OUT

160.00mm
(6.3”)

220.00mm
(8.7”)

FIG 3
Maximum panel thickness – 8mm (0.3”)
In conditions of excessive vibration the module should be mounted on suitable anti-vibration mountings.

7.2 COOLING
The module has been designed to operate over a wide temperature range -30 to +70º C. Allowances should be
made for the temperature rise within the control panel enclosure. Care should be taken NOT to mount possible
heat sources near the module unless adequate ventilation is provided. The relative humidity inside the control
panel enclosure should not exceed 95%.

7.3 UNIT DIMENSIONS

Panel cutout 220mm x 160mm ( 8.7” x 6.3”)


FIG 4

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 35
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

7.4 FRONT PANEL LAYOUT

FIG 5
7.5 REAR PANEL LAYOUT

FIG 6

36 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8 ELECTRICAL CONNECTIONS
Connections to the Module are via plug and sockets.

8.1 CONNECTION DETAILS


The following describes the connections and recommended cable sizes to the 7 plugs and sockets on the rear of
the Module. See rear panel layout FIG 6.

8.1.1 PLUG “A” 8 WAY


PIN DESCRIPTION CABLE NOTES
No SIZE
1 DC Plant Supply Input 2.5mm²
(Negative) AWG 13
2 DC Plant Supply Input 2.5 mm² (Recommended Maximum Fuse 21A)
(Positive) AWG 13
3 Emergency Stop Input 2.5mm² Plant Supply Positive. Also supplies fuel &
AWG 13 start outputs.
(Recommended Maximum Fuse 32A)
4 Fuel relay Output 2.5mm² Plant Supply Positive from pin 3. 16 Amp
AWG 13 rated.
5 Start relay Output 2.5mm² Plant Supply Positive from pin 3. 16 Amp
AWG 13 rated.
6 Auxiliary Output relay 1 1.0mm² Plant Supply Positive. 5 Amp rated.
AWG 18
7 Auxiliary Output relay 2 1.0mm² Plant Supply Positive. 5 Amp rated.
AWG 18
8 Auxiliary Output relay 3 1.0mm² Plant Supply Positive. 5 Amp rated.
AWG 18

NOTE:- When the module is configured for CAN operation, FUEL, START and AUXILIARY output
requirements may be different. Refer to CAN and DSE Wiring for further information.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 37
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8.1.2 PLUG “B” 11 WAY


PIN DESCRIPTION CABLE NOTES
No SIZE
9 Charge fail / excite 2.5mm² Do not connect to ground (battery Negative)
AWG 13
10 Auxiliary input 1 0.5mm² Switch to Negative
AWG 20
11 Auxiliary input 2 0.5mm² Switch to Negative
AWG 20
12 Auxiliary input 3 0.5mm² Switch to Negative
AWG 20
13 Auxiliary input 4 0.5mm² Switch to Negative
AWG 20
14 Auxiliary input 5 0.5mm² Switch to Negative
AWG 20
15 Auxiliary input 6 0.5mm² Switch to Negative
AWG 20
16 Functional Earth 2.5mm² Connect to a good clean earth point
AWG 13
17 Magnetic pickup Positive 0.5mm² Connect to Magnetic Pickup device
AWG 20
18 Magnetic pickup Negative 0.5mm² Connect to Magnetic Pickup device
AWG 20
19 Not connected -

NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.

NOTE:- When the module is configured for CAN operation, terminals 17 & 18 should be left
unconnected. Engine speed is transmitted to the 53xx controller on the CAN link.
Refer to CAN and DSE Wiring for further information.

8.1.3 PLUG “C” 3 WAY


PIN DESCRIPTION CABLE NOTES
No SIZE
20 CAN port Common 0.5mm² Use only 120Ω CAN approved cable
AWG 20
21 CAN port H 0.5mm² Use only 120Ω CAN approved cable
AWG 20
22 CAN port L 0.5mm² Use only 120Ω CAN approved cable
AWG 20

NOTE:- Screened 120Ω impedance cable specified for use with CANBUS must be used.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for
CANbus use (DSE part number 016-030)
Refer to CAN and DSE Wiring for further information.

38 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8.1.4 PLUG “D” 4 WAY (OPTIONAL)

PIN DESCRIPTION CABLE NOTES


No SIZE
23 RS485 port Common 0.5mm² Use only 120Ω RS485 approved cable
AWG 20
24 RS485 port B 0.5mm² Use only 120Ω RS485 approved cable
AWG 20
25 RS485 port A 0.5mm² Use only 120Ω RS485 approved cable
AWG 20
26 Not connected -

NOTE: - Screened 120Ω impedance cable specified for use with RS485 must be used.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for
RS485 use (DSE part number 016-030)

NOTE: - Connector E is not fitted to the 5310 remote start module.

8.1.5 PLUG “F” 4 WAY

PIN DESCRIPTION CABLE SIZE NOTES


No
35 Generator L1 voltage 1.0mm² Connect to generator L1 output (AC)
monitoring input AWG 18 (Recommend 2A fuse)
36 Generator L2 voltage 1.0mm² Connect to generator L2 output (AC)
monitoring input AWG 18 (Recommend 2A fuse)
37 Generator L3 voltage 1.0mm² Connect to generator L3 output (AC)
monitoring input AWG 18 (Recommend 2A fuse)
38 Generator Neutral input 1.0mm² Connect to generator Neutral terminal
AWG 18 (AC)

8.1.6 PLUG “G” 5 WAY

PIN DESCRIPTION CABLE NOTES


No SIZE
39 CT Secondary for L1 2.5mm² Connect to secondary of L1 monitoring CT
AWG 13
40 CT Secondary for L2 2.5mm² Connect to secondary of L2 monitoring CT
AWG 13
41 CT Secondary for L3 2.5mm² Connect to secondary of L3 monitoring CT
AWG 13
42 CT secondary common 2.5mm² Connect to secondary of all monitoring CT’s
AWG 13
43 Not connected -

WARNING! - Do not disconnect this plug when the generator set is running. Disconnection will open
circuit the secondary of the CT’s and dangerous voltages may then develop. Always ensure the
generating set is at rest before making or breaking connections to the module.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 39
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8.1.7 PLUG “H” 4 WAY

PIN DESCRIPTION CABLE NOTES


No SIZE
44 Oil Pressure Input 0.5mm² Connect to Oil pressure sender
AWG 20
45 Coolant Temperature 0.5mm² Connect to Coolant Temperature sender
Input AWG 20
46 Fuel Level input 0.5mm² Connect to Fuel Level sender
AWG 20
47 Sender Common Return 0.5mm² Return feed for senders*.
AWG 20

NOTE*:- If using single terminal senders refer to connection diagram. If using earth return type
senders connect return terminals to pin 47 and also connect pin 47 to earth. This is detailed in the
Appendix section entitled “Sender wiring recommendations” elsewhere in this manual.

NOTE:- When the module is configured for CAN operation, terminals 44 & 45 should be left
unconnected. Engine oil pressure and coolant temperature is transmitted to the 53xx controller on the
CAN link.

8.1.8 PC CONFIGURATION INTERFACE CONNECTOR

8-way connector allows connection to PC via the 810 configuration interface.


Module can then be re-configured utilising the 5xxx series configuration
software.

8.1.9 EXPANSION OUTPUT CONNECTOR

The expansion connector allows connection to the 157 relay expansion module
or to the 548 LED Remote annunciator module.

40 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8.2 CONNECTOR FUNCTION DETAILS

The following describes the functions of the 7 connectors on the rear of the module. See rear panel layout FIG 5.

8.2.1 PLUG “A” 8 WAY

PIN DESCRIPTION
No
1 DC Supply Negative input. (Battery Negative).
2 DC Supply Positive input. (Battery Positive).
3 Emergency Stop input. Internally linked to Starter and Fuel outputs. If this input is
not connected to positive the module will be locked out, and if the engine is
running it will shutdown immediately. The Positive Supply is also removed from
Starter and Fuel outputs, therefore only a single pole Emergency Shutdown button
is required.
4 Fuel Relay output. Plant Supply Positive from pin 3. Used to control the fuel
solenoid or engine fuel control system.
5 Starter Relay output. Plant Supply Positive from pin 3. Used to control the Starter
Motor.
6 Auxiliary Relay output 1. Plant Supply Positive. Configurable output, see
Calibration Manual for options available.
7 Auxiliary Relay output 2. Plant Supply Positive. Configurable output, see
Calibration Manual for options available.
8 Auxiliary Relay output 3. Plant Supply Positive. Configurable output, see
Calibration Manual for options available.

8.2.2 PLUG “B” 11 WAY

PIN DESCRIPTION
No
9 Charge Fail input / Excitation output. Supplies excitation to the Plant Battery
Charging Alternator, also an input for the Charge Fail detection circuitry.
10 Auxiliary input 1. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
11 Auxiliary input 2. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
12 Auxiliary input 3. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
13 Auxiliary input 4. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
14 Auxiliary input 5. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
15 Auxiliary input 6. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
16 Functional Earth - Ensure connection to a good clean earth point.
17 Magnetic Input Positive. An AC signal from the magnetic pickup Positive for speed
sensing.
18 Magnetic Input Negative. An AC signal from the magnetic pickup Negative for
speed sensing.
19 Not connected

NOTE: - Ensure magnetic pickup screen is connected to ground at one end only.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 41
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

NOTE: - When the module is configured for CAN operation, terminals 17 & 18 should be left
unconnected. Engine speed is transmitted to the 53xx controller on the CAN link.

8.2.3 PLUG “C” 3 WAY

PIN DESCRIPTION
No
20 CAN port Common. Do not connect this terminal to earth. Use only screened 120Ω cable approved
specifically for use in CAN applications.
21 CAN port H. Use only screened 120Ω cable approved specifically for use in CAN applications.
22 CAN port L. Use only screened 120Ω cable approved specifically for use in CAN applications.

NOTE:- Screened 120Ω impedance cable specified for use with CANBUS must be used.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for
CANbus use (DSE part number 016-030)

8.2.4 PLUG “D” 4 WAY (OPTIONAL)

PIN DESCRIPTION
No
23 RS485 port Common
24 RS485 port B. Use only screened 120Ω cable approved specifically for use in RS485 applications.
25 RS485 port A. Use only screened 120Ω cable approved specifically for use in RS485 applications.
26 Not used. Do not connect to this terminal.

NOTE:- Screened 120Ω impedance cable specified for use with RS485 must be used.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for
RS485 use (DSE part number 016-030)

NOTE: - Connector E is not fitted to the 5310 remote start module.

8.2.5 PLUG “F” 4 WAY

PIN DESCRIPTION
No
35 Generator L1 sensing input. Connect to alternator L1 output.
36 Generator L2 sensing input. Connect to alternator L2 output. If using single phase only do not
connect this terminal.
37 Generator L3 sensing input. Connect to alternator L3 output. If using single phase only do not
connect this terminal.
38 Generator N sensing input. Connect to alternator N output.

42 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

8.2.6 PLUG “G” 5 WAY

PIN No DESCRIPTION
39 Generator L1 current transformer connection.
40 Generator L2 current transformer connection. If single phase is used do not connect this pin.
41 Generator L3 current transformer connection. If single phase is used do not connect this pin.
42 Generator current transformer common connection and CT earth connection.
43 Not used. Do not connect to this terminal.

WARNING! - Do not disconnect this plug when the generator set is running. Disconnection will open
circuit the secondary of the CT’s and dangerous voltages may then develop. Always ensure the
generating set is at rest before making or breaking connections to the module.

8.2.7 PLUG “H” 4 WAY

PIN DESCRIPTION
No
44 Oil Pressure sensing input. Connect to resistive type oil pressure sender. Refer to connection
diagram for details.
45 Coolant Temperature sensing input. Connect to resistive type coolant temperature sender. Refer
to connection diagram for details.
46 Fuel Level sensing input. Connect to resistive type fuel level sender. Refer to connection diagram
for details.
47 Sender Common connection. Return feed from sender units - refer to connection diagram for
details.

NOTE:- When the module is configured for CAN operation, terminals 44 & 45 should be left
unconnected. Engine oil pressure and coolant temperature is transmitted to the 53xx controller on the
CAN link.

8.2.8 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE

If you require additional plugs from DSE, please contact our Sales department using the part numbers below.

5310 Terminal Connector Plug description DSE Part number


1-8 A BL08 8way 5.08mm spacing connector plug 007-125
9-19 B BL11 11way 5.08mm spacing connector plug 007-135
20-22 C BL03 3way 3.81mm spacing connector plug 007-409
23-26 D BL04 4way 3.81mm spacing connector plug 007-408
35-38 F BL04 4way 10.16mm spacing connector plug 007-003
39-43 G BL05 5way 5.08mm spacing connector plug 007-329
44-47 H BL04 4way 5.08mm spacing connector plug 007-100

NOTE:- Plug E is not fitted to this module.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 43
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

9 SPECIFICATION
DC Supply Continuous voltage rating :
8V to 35V
Cranking dip protection :
Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply
recovers to 5V. This is achieved without the need for internal batteries
Charge Fail/ Excitation:
0V to 35V fixed power source 25W
Max. Standby Current:
250mA at 12V. 125mA at 24V.
Max. Sleep Mode Current:
75mA at 12V. 45mA at 24V
Max. Operating Current:
425mA at 12V. 215mA at 24V
Alternator Input Range:
15V - 277(ph-N) (+20%) 50Hz - 60Hz (Minimum 15V AC Ph-N)
Accuracy:
1% of full scale Average sensing
Supported topologies:
3 Phase 4 wire
3 phase 3 wire
Single phase 2 wire
2 Phase 3 wire L1 & L2
2 Phase 3 wire L1 & L3
Bus Input Range:
15V - 277(ph-N) (+20%) 50Hz - 60 Hz
Accuracy:
1% of full scale Average sensing
Supported topologies:
3 Phase 4 wire
3 phase 3 wire
Single phase 2 wire
2 Phase 3 wire L1 & L2
2 Phase 3 wire L1 & L3
CT’s Burden:
0.5VA
Primary rating:
1A - 6000A (user selectable)
Secondary rating:
1A or 5A secondary (user selectable)
Accuracy of measurement:
1% of full load rating (when using 0.5% or better CTs with 5A secondary winding) Lower class CTs
will reduce the overall accuracy of the reading.
Recommendations:
Class 1 required for instrumentation
Protection class required if using for protection.
Magnetic Pickup Voltage range :
+/- 0.5V minimum (during cranking) to 70V Peak
Frequency range:
10,000 Hz (max)
Relay outputs Fuel:
16 Amp DC at supply voltage
Start:
16 Amp DC at supply voltage
Auxiliary outputs 1,2,3:
5 Amp DC at supply voltage
Output 4 (Generator loading relay)
Voltage free, normally open, 8 Amp 250V AC RMS rated
Output 5 (spare)
Voltage free, normally closed, 8 Amp 250V AC RMS rated

44 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Dimensions Overall:
240mm x 172 mm x 57mm
(9 ½“ x 6 ¾” x 2 ¼”)
Panel cut-out:
220mm x 160mm
( 8.7” x 6.3”)
Max panel thickness 8mm ( 0.3”)
Electrical Safety BS EN 60950 Safety of information technology equipment, including electrical business equipment
/Electromagnetic BS EN 61000-6-2 EMC Generic Emission Standard (Industrial)
Compatibility BS EN 61000-6-4 EMC Generic Emission Standard (Industrial)
Environmental BS EN 60068-2-1 Cold Temperature
-30°C
BS EN 60068-2-2 Hot Temperature
+70°C
BS2011-2-1 Humidity
93% RH@40°C for 48 Hours
BS EN 60068-2-6 Vibration
10 sweeps at 1 octave/minute in each of 3 major axes
5Hz to 8Hz @ +/-7.5mm constant displacement
8Hz to 500Hz @ 2gn constant acceleration
BS EN 60068-2-27 Shock
3 Half sine shocks in each of 3 major axes
15gn amplitude, 11mS duration
BS EN 60529 Degrees of protection provided by enclosures:
IP55 (Front of module when module is installed into the control panel with the optional sealing
gasket).
IP42 (front of module when module is installed into the control panel WITHOUT being sealed to
the panel)
NEMA Rating (Approximate)
12 (Front of module when module is installed into the control panel with the optional sealing
gasket).
2 (front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
Product Certification

C US
UL approved Russia and other CIS
European CE approved.
C-UL / CSA approved. countries approved

BS EN 2002/95/EC BS EN 2002/96/EC CAN interface certified by


Restriction of Hazardous Waste Electrical and MTU for use with MDEC
Substances Electronic Equipment (WEEE) engines
(RoHS)
Relevant Company
Certification

BS EN ISO 9001:2000
Applicable to Design,
marketing, assembly, service
and repair of electronic control
modules

In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 45
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

10 COMMISSIONING
10.1.1 PRE-COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-

10.1. The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the
system.

10.2. The unit DC supply is fused and connected to the battery and that it is of the correct polarity.

10.3. The Emergency Stop input is wired to an external normally closed switch connected to DC positive.

NOTE:- If Emergency Stop feature is not required, link this input to the DC Positive. The module will
not operate unless either the Emergency Stop is fitted correctly OR Pin 3 is connected to DC positive.

10.4. To check the start cycle operation take appropriate measures to prevent the engine from starting (disable the
operation of the fuel solenoid). After a visual inspection to ensure it is safe to proceed, connect the battery
supply. Select “MANUAL”, the unit start sequence will commence.

10.5. The starter will engage and operate for the pre-set crank period. After the starter motor has attempted to
start the engine for the pre-set number of attempts the LCD will display ‘Failed to start. Select the
STOP/RESET position to reset the unit.

10.6. Restore the engine to operational status (reconnect the fuel solenoid), again select “MANUAL”, this time the
engine should start and the starter motor should disengage automatically. If not then check that the engine is
fully operational (fuel available, etc.) and that the fuel solenoid is operating. The engine should now run up to
operating speed. If not, and an alarm is present, check the alarm condition for validity, then check input
wiring. The engine should continue to run for an indefinite period. It will be possible at this time to view the
engine and alternator parameters - refer to the ‘Description of Controls’ section of this manual.

10.7. Select “AUTO” on the front panel, the engine will run for the pre-set cooling down period, then stop. The
generator should stay in the standby mode. If not check that there is not a signal present on the Remote
start input.

10.8. Initiate an automatic start by supplying the remote start signal. The start sequence will commence and the
engine will run up to operational speed. Once the generator is available a load transfer will take place, the
Generator will accept the load. If not, check the wiring to the Generator Contactor Coil (if used). Check the
Warming timer has timed out.

10.9. Remove the remote start signal, the return sequence will start. After the pre-set time period, the load will be
removed from the generator. The generator will then run for the pre-set cooling down period, then shutdown
into it’s standby mode.

10.10. Set the modules internal clock/calendar to ensure correct operation of the scheduler and event logging
functions. For details of this procedure see section entitled Front Panel Configuration – Editing the date and
time.

10.11. If, despite repeated checking of the connections between the 5310 and the customer’s system, satisfactory
operation cannot be achieved, then the customer is requested to contact the factory for further advice on:-

INTERNATIONAL TEL: +44 (0) 1723 890099


INTERNATIONAL FAX: +44 (0) 1723 893303
E-mail: Support@Deepseaplc.com
Website : www.deepseaplc.com

46 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

11 FAULT FINDING

SYMPTOM POSSIBLE REMEDY


Unit is inoperative Check the battery and wiring to the unit. Check the DC supply. Check the DC
fuse.
Unit shuts down Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70 °C. Check the DC fuse.
Unit locks out on Emergency Stop If an Emergency Stop Switch is not fitted, ensure that a positive is connected
to the Emergency Stop input. Check emergency stop switch is functioning
correctly. Check Wiring is not open circuit.
Intermittent Magnetic Pick-up Ensure that Magnetic pick-up screen is only connected at one end, if
sensor fault connected at both ends, this enables the screen to act as an aerial and will
pick up random voltages.
Low oil Pressure fault operates Check engine oil pressure. Check oil pressure switch/sender and wiring.
after engine has fired Check configured polarity (if applicable) is correct (i.e. Normally Open or
Normally Closed) or that sender is compatible with the 5310 Module and is
correctly configured.
High engine temperature fault Check engine temperature. Check switch/sender and wiring. Check
operates after engine has fired. configured polarity (if applicable) is correct (i.e. Normally Open or Normally
Closed) or that sender is compatible with the 5310 Module.
Shutdown fault operates Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input.
Warning fault operates Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input.
Fail to Start is activated after pre- Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery
set number of attempts to start supply is present on the Fuel output of the module. Check the speed sensing
signal is present on the 5310 inputs. Refer to engine manual.
Continuous starting of generator Check that there is no signal present on the “Remote Start” input. Check
when in AUTO configured polarity is correct.
Generator fails to start on receipt Check Start Delay timer has timed out.
of Remote Start signal. If remote start fault, check signal is on “Remote Start” input. Confirm input is
configured to be used as “Remote Start”.
Pre-heat inoperative Check wiring to engine heater plugs. Check battery supply. Check battery
supply is present on the Pre-heat output of module. Check pre-heat has been
selected in your configuration.
Starter motor inoperative Check wiring to starter solenoid. Check battery supply. Check battery supply
is present on the Starter output of module. Ensure that the Emergency Stop
input is at Positive.
Engine runs but generator will not Check Warm up timer has timed out. Ensure generator load inhibit signal is
take load not present on the module inputs. Check connections to the switching device.
Incorrect reading on Engine Check engine is operating correctly. Check sender and wiring paying
gauges particular attention to the wiring to terminal 47 (refer to appendix). Check that
sender is compatible with the 5310 Module and is correctly configured.

NOTE:- The above fault finding is provided as a guide check-list only. As it is possible for the
module to be configured to provide a wide range of different features always refer to the source of your
module configuration if in doubt.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 47
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

12 FACTORY DEFAULT CONFIGURATION


In the tables below, the icon # indicates an item that can be adjusted from the module’s front panel editor.
Absence of the # icon beside an item means that adjustment of this parameter is only possible using the 5300
series configuration software in conjunction with the P810 interface.
For further details on adjustment from the front panel editor, see the section entitled “Front panel configuration”
elsewhere within this manual.

5300 series configuration software. Configuration for 5310 module.


Filename – 5310a.XCF
Printed on 25/10/05

Module settings Value


Base module 5310 Remote start module

Miscellaneous settings Value


Two lines of text (Configuration
Blank
description)
Alternator fitted Yes
Poles 4
Magnetic pickup fitted No
CAN enabled No
AC System 3 phase, 4 wire
VT Ratio Disabled
Number of start attempts 3
Enable fast loading feature No
Audible alarm prior to starting No
Sleep when in stop mode No
All warnings are latched No

Input settings – Analogue | Oil pressure Value


Low oil pressure input type VDO 10 bar

Trip Return
Low oil pressure pre-alarm # 1.17 Bar 17.0 PSI 1.24 Bar 18.0 PSI
Low oil pressure shutdown # 1.03 Bar 14.9 PSI N/A

Input settings – Analogue | Coolant Value


temp
High coolant temp input type VDO 120 degrees C
Trip Return
High coolant temp pre-alarm # 115°C 239°F 110°C 230°F
High coolant temp shutdown # 120°C 248°F N/A
Low coolant temp pre-alarm # Disabled Disabled

Input settings – Analogue | Fuel level Value


Fuel level input type Disabled

48 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Input settings - Digital Value


1 Remote start on load Close to activate
2 Lamp test Close to activate
3 User configured Close to activate, Warning Active from safety on
4 User configured Close to activate, Shutdown Always active
5 User configured Close to activate, Shutdown Active from safety on
6 User configured Close to activate, Electrical trip Always active

NOTE:- Inputs set to ‘User configured’ have an extra text box to allow the user to type in a
description.

Output settings – Relay Value


1 Energise Preheat (during pre-heat timer)
2 Energise Common alarm
3 Energise Close generator

Output settings – Expansion Value


A
1 Energise System in auto mode
2 Energise Fail to start
3 Energise Generator available
4 Energise Delayed alarms armed
5 Energise Combined under / over freq. shutdown
6 Energise Combined under / over voltage shutdown
7 Energise Cooling timer in progress
8 Energise Mains failure

Output settings – Expansion Value


B
1 Energise Output not used
2 Energise Output not used
3 Energise Output not used
4 Energise Output not used
5 Energise Output not used
6 Energise Output not used
7 Energise Output not used
8 Energise Output not used

LED indicator settings Value


1 Lit Digital input 1 active
2 Lit Digital input 2 active
3 Lit System in auto mode
4 Lit Common alarm

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 49
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Timer settings Value


Start delay # 5s
Pre-heat # 0s
Cranking time # 10s
Crank rest time # 10s
Smoke limit 0s
Smoke limit off 0s
Safety on delay # 10s
Overspeed overshoot # 2s
Warming up time # 0s
Breaker close pulse 0.5s
Breaker trip pulse 0.5s
Return delay # 30s
Cooling time # 1m
ETS solenoid hold 0s
Fail to stop delay # 30s
Generator transient delay # 0s
Battery low volts delay # 1m
Battery high volts delay # 1m
LCD page timer 5m

Generator settings – Voltage/frequency Trip Return


Under volts trip # 184V AC N/A
Under volts pre-alarm # 196V AC 207V AC
Over volts pre-alarm # 265V AC 253V AC
Over volts trip # 276V AC N/A
Under frequency trip # 40.0Hz N/A
Under frequency pre-alarm # 42.0Hz 45.0Hz
Over frequency pre-alarm # 55.0Hz 52.0Hz
Over frequency trip # 57.0Hz N/A
Droop # Disabled N/A
Droop % # 0.0% N/A

Loading Voltage 207V Ph-N


Loading Frequency 45.0 Hz
Alternative voltage # 230v norm / 115v alt Disabled on module
Alternative Frequency # 50Hz norm / 60Hz alt Disabled on module

Generator settings – Current/power Value


Generator CT primary 600A
Generator CT secondary 5A
CT location Generator only
Generator full load rating # 500 A
Delayed overcurrent # 100% ( 500A )
Trip Curve 36

Engine settings – Crank disconnect Value


Crank disconnect on generator frequency 21.0Hz
Crank disconnect oil pressure <Disabled>
Check oil pressure prior to starting Yes

Engine settings – speed Value


Underspeed trip # 1250 RPM Disabled
Underspeed prealarm # 1350 RPM Disabled
Overspeed prealarm # 1650 RPM Disabled
Overspeed trip # 1750 RPM Disabled
Overspeed overshoot # 0% Disabled

50 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

Plant battery settings Trip Return


Under volts warning # 8.0V DC 9.0V DC
Over volts warning # 33.0 V DC 32.0V DC
Charge alternator warning # 6.0V DC N/A

Exercise scheduler settings Value


Enable exercise scheduler No

Comms Value
Site identity
Genset ID
Modem mode No modem
Modem init (not auto answer) E0S7=60S0=0&S0&C1&D3
Modem init (auto answer) E0S7=60S0=2&S0&C1&D3
Modem Hang H0
Master inactivity timeout 0
Slave ID 10 (Default)
Baud Rate 19200 (Default)

Languages Value
Fixed Languages # English (UK)
User configured languages Not used

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 51
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

13 TYPICAL WIRING DIAGRAM

52 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14 APPENDIX
14.1 ALTERNATIVE WIRING TOPOLOGIES
The 53xx series controllers can support many different wiring topologies (AC systems) to suit the many systems in
use worldwide. The ‘Typical connection diagram’ details how to connect the module when used in a 3 phase, 4
wire system (3 phase star connected alternators). Changes to this typical wiring diagram for other AC systems are
detailed below.

NOTE:- The factory default configuration for the 5310 module is for use with the 3 phase, 4 wire AC
system. If another system is to be used, the controller must be reconfigured using the 5xxx series
configuration software.

14.1.1 3 PHASE, 3 WIRE

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 53
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.1.2 1 PHASE, 2 WIRE


Single phase alternator with neutral conductor.

14.1.3 2 PHASE, 3 WIRE ( 2 PHASE CENTRE TAP NEUTRAL)


The alternator is 2 phase star connected. The live phases are separated by 180°

54 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.2 ICONS AND LCD IDENTIFICATION

14.2.1 PUSH BUTTONS

Display Description Display Description Display Description

Stop/Reset i Page scroll Auto mode

Scroll Manual mode


Start (when in

Mute
I Manual or Test
mode)

14.2.2 STATUS / MEASUREMENT UNITS

Display Description Display Description Display Description

L1 Phase L2 Phase L3 Phase

L1- N Phase - Neutral L2- N Phase - Neutral L3- N Phase -Neutral

L1- L2 Phase - Phase L2- L3 Phase - Phase L3- L1 Phase - Phase


KPa Oil Pressure
BAR Pressure KPa Units PSI Pressure

V Voltage o Temperature Hz Frequency


F
A Amperes o Temperature RPM Speed
C
KW divided by
kW KiloWatts kVA Apparent power
kVA

14.2.3 LED INDICATION

Display Description
Generator
available

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 55
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.3 5310 IDMT TRIPPING CURVES (TYPICAL)

5310 Delayed over-current protection

1000000

100000
Tripping time in seconds

10000

1000

100

10

1
1 2 3
Current as a multiple of the trip-point setting (tripping curve = 36)

56 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.4 SENDER WIRING RECOMMENDATIONS

14.4.1 EARTH RETURN SENDERS

Connection Name Terminal Number

Oil pressure Sender 44

Coolant temperature
45
sender

Fuel level sender 46

Sender common 47
53xx

NOTE:- . It is important that terminal 47 ( sender common ) is soundly connected to an earth point
on the ENGINE BLOCK, not within the control panel, and must be a sound electrical connection to the
sender bodies.

NOTE:- . If you use PTFE insulating tape on the sender thread when using earth return senders,
ensure you do not insulate the entire thread as this will prevent the sender body from being earthed via
the engine block.

14.4.2 INSULATED RETURN SENDERS

Connection Name Terminal Number

Oil pressure Sender 44

Coolant temperature
45
sender

Fuel level sender 46

Sender common 47
53xx

NOTE:- . It is important that terminal 47 ( sender common ) is soundly connected to an earth point
on the ENGINE BLOCK, not within the control panel .

14.4.3 FUEL LEVEL SENDERS


Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 57
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

The resistive fuel level senders supported by the 5300 series controllers are devices that translate fuel level into
resistance. A change in fuel level translates directly to a change in the resistance of the sender. In the case of a
parallel sided fuel tank, an accurate measure of the fuel level can easily be made, however as shown in the
example below, this is not the case with non-parallel sided fuel tanks. Therefore it is recommended that only
parallel sided fuel tanks are used to ensure correct fuel level detection.

The fuel sender measures


the distance between the top
of the tank and the fuel level.
Typically, they use a ball
float.
In this example, the distance
between the top of the tank
and the level of the fuel is
50% of the height of the
tank. The fuel level sender
will report the tank correctly
as being 50% full.

For a parallel-sided tank like


this one, 50% distance
between the top of the tank
and the level of the fuel will
occur when the tank is 50%
full of fuel.
In this example, the distance
between the top of the tank
and the level of the fuel is
again 50% of the height of
the tank, the fuel level
sender will report the tank as
being 50% full.

However, as the bottom of


the tank is curved, the actual
amount of fuel in the tank is
only about 40%. The fuel
sender is incorrectly
reporting the amount of
remaining fuel.

58 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.5 CAN INTERFACE


Modules are fitted with the CAN interface as standard and are capable of receiving engine data from
engine CAN controllers compliant with the CAN standard.
CAN enabled engine controllers monitor the engines operating parameters such as engine speed, oil
pressure, engine temperature (among others) in order to closely monitor and control the engine. The data that is
gathered by the engine controller is then transmitted on an industry standard communications interface (CAN). This
allows generator controllers such as the DSE 53xx range to access these engine parameters with no physical
connection to the sensor device.

NOTE:- For further details for connections to CAN enabled engines refer to the manual CAN and
DSE Wiring Part No. 057-004

14.6 OUTPUT EXPANSION


There are several methods of output expansion available for the 5xxx module:-

14.6.1 RELAY OUTPUT EXPANSION (157)


An expansion module is available, which connects to the configuration socket and enables the 53xx to use eight
additional relays on the 157 relay module, providing Volt-free contacts for customer connection. A maximum of 2
off 157 relay modules can be connected, there are identified as ‘A’ and ‘B’ and give a total of 16 extra relay
outputs.

Refer to technical data sheet on the 157 relay module for further details.

14.6.2 LED OUTPUT EXPANSION (548)


An expansion module is available, which connects to the configuration socket, and enables the 53xx to use eight
additional LED’s on the 548 module, providing remote LED’s indication up to 50 metres away. A maximum of 2 off
548 LED modules can be connected, there are identified as ‘A’ and ‘B’ and give a total of 16 extra LED outputs.

It is possible to use a mix of 157 and 548 modules to give both relay and LED expansion if required (Please refer to
our Technical Support department for details.).

14.7 INPUT EXPANSION


It is possible to increase the number of monitored inputs available by utilising either :

¾ DSE P130 input expansion


¾ 54x Protection Expansion/Annunciator.

Please refer to the relevant product documentation for further details.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 59
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.8 COMMUNICATIONS OPTION CONNECTIONS


14.8.1 DESCRIPTION
The 5xxx series configuration software allows the 5310 controller to communicate with a PC. The computer can be
connected to the module either directly (P810 shown to the right), via a modem (RS232)* or via an RS485 link**.

The operator is then able to remotely control the module, starting or stopping the generator, selecting operating
modes, etc. The various operating parameters (such as output volts, oil pressure, etc.) on the remote generator
can also be viewed.

The information contained in this manual should be read in conjunction with the appropriate module
documentation. This manual only details the operation of the communications software and how it should be used.
The operation of the module is detailed in its own relevant manual.

NOTE: - *If modem communications is a requirement, then it is important to order the correct 5310
module with the RS232 communications board fitted. This provides a 9-way D-type connector suitable
for connection to the modem. Please refer to the comms section of this manual for details of how the
system should be configured.

**If RS485 communications is required, then it is important to order the correct 5310 module with the
RS485 communications board fitted. This provides a 3-way terminal block for connection of the RS485
link.

14.8.2 PC TO CONTROLLER (DIRECT) CONNECTION

To connect a 5310 to a modem the following items are required: -


• Any 5310 Module (RS232 or RS485)
• 5xxx series configuration software (Supplied on DSE software
CD).
• P810 interface (USB or RS232 as required)

14.8.3 MODEM TO CONTROLLER CONNECTION

To connect a 5310 to a modem the following items are required: -

• 5310 Module with RS232 Communications Interface


• Compatible RS232 Modem (PSTN or GSM)
• Suitable connection leads
• Power supply for the modem
• 5xxx series configuration software (Supplied on DSE software CD).
• Access to a PSTN Line or GSM network.

CAUTION! - The modem must be powered from a suitably stabilised supply, preferably supplied with
the modem (see below). Failure to ensure continuity of supply will result in communication difficulties at
such times as Mains failure or during cranking. An uninterruptible power supply arrangement is
recommended (AC or DC depending on modem power requirement).

60 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.8.4 RS485 LINK TO CONTROLLER

The RS485 enabled 5310 modules are able to communicate with a PC or other RS485 enabled device over a
standard RS485 connection. Typical uses of RS485 are:

• Direct connection to a remote PC running the 5xxx series configuration software. RS485 is capable of
communication over a distance of 1.2km where suitable 120Ω RS485 cable is installed.
• Connection to a building management to allow mains, generator and engine parameters/alarm conditions to be
displayed along with information from other devices (air conditioning, fire alarm system etc).

Typical connections of
RS485 PC system
(master) to RS485 DSE
controller (slave)

NOTE: - The RS485 system will comprise of one MODBUS master (typically a PC) and up to 31
MODBUS slaves. The 5310 modules are always MODBUS slave devices. To ensure correct operation a
suitable 120Ω terminal resistor must be fitted to each end of the RS485 connection bus.

Caution! - The A and B lines of the 485 network should be terminated at each end with a 120Ω
resistor.

Some RS485 devices (PC cards in particular) are already fitted with a terminating resistor. However if
they are not installed as an ‘end of line’ device then such terminating resistors must be removed. Other
RS485 devices may be fitted with a ‘switchable’ resistor, again this must be switched out if the device is
not installed as an ‘end of line’ device.

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 61
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

TYPICAL BUILDING MANAGEMENT SCHEME USING RS485 MONITORING

CAUTION! -. RS485 cabling must be 120Ω impedance cable, specified for use with RS485. 120Ω
terminating resistors must be fitted to the first and last devices on the bus. Some PC RS485 cards are
already fitted with this resistor, and in this case should not be fitted externally. If in doubt, consult the
supplier of your PC RS485 card.
If the 5310 controller is the ‘last’ device on the bus, then it’s RS485 connection must be suitably
terminated with a 120Ω resistor as detailed in the specification laid out in the RS485 standard.

Recommended cable BELDEN 9841 120Ω RS485 cable.


DSE part number 016-030.

NOTE: - The RS485 output uses ‘MODBUS’ protocol. It is possible to use third party software to
monitor and control the 5310 module via this protocol.
Please refer to Deep Sea Electronics Plc for details.

14.8.5 MODBUS™

The RS485 output uses Modbus™ communications protocol. This uses a master-slave technique to communicate.
Only the Master can initiate a packet transaction, called a ‘query’. When appropriate the slave (5310 Module)
responds to the query and provides the information requested by the master.

All supported data can be read and written as specified in the register table (documentation is available from Deep
Sea Electronics Plc.).

When the 5310 Module receives a query it will respond by either supplying the requested register data or
performing the requested action. A slave device (the 5310 module) will never initiate communications on the
Modbus™ link. The 5310 can only be configured as a slave device. The Master can only query individual slaves.
Refer to the Modbus™ protocol document for more details.

62 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

14.9 ENCLOSURE CLASSIFICATIONS

IP CLASSIFICATIONS

BS EN 60529 Degrees of protection provided by enclosures

First Digit Second digit


Protection against contact and ingress of solid objects Protection against ingress of water

0 No protection 0 No protection

1 Protected against ingress solid objects with a 1 Protection against dripping water falling vertically. No
diameter of more than 50 mm. No protection against harmful effect must be produced (vertically falling
deliberate access, e.g. with a hand, but large drops).
surfaces of the body are prevented from approach.

2 Protected against penetration by solid objects with a 2 Protection against dripping water falling vertically.
diameter of more than 12 mm. Fingers or similar There must be no harmful effect when the equipment
objects prevented from approach. (enclosure) is tilted at an angle up to 15° from its
normal position (drops falling at an angle).

3 Protected against ingress of solid objects with a 3 Protection against water falling at any angle up to 60°
diameter of more than 2.5 mm. Tools, wires etc. with from the vertical. There must be no harmful effect
a thickness of more than 2.5 mm are prevented from (spray water).
approach.

4 Protected against ingress of solid objects with a 4 Protection against water splashed against the
diameter of more than 1 mm. Tools, wires etc. with a equipment (enclosure) from any direction. There must
thickness of more than 1 mm are prevented from be no harmful effect (splashing water).
approach.

5 Protected against harmful dust deposits. Ingress of 5 Protection against water projected from a nozzle
dust is not totally prevented but the dust must not against the equipment (enclosure) from any direction.
enter in sufficient quantity to interface with There must be no harmful effect (water jet).
satisfactory operation of the equipment. Complete
protection against contact.

6 Protection against ingress of dust (dust tight). 6 Protection against heavy seas or powerful water jets.
Complete protection against contact. Water must not enter the equipment (enclosure) in
harmful quantities (splashing over).

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 63
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

NEMA CLASSIFICATIONS

NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.

1 Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.

IP30

2 Provides a degree of protection against limited amounts of falling water and dirt.

IP31

3 Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure.

IP64

3R Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.

IP32

4 (X) Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the
formation of ice on the enclosure. (Resist corrosion).
IP66

12/12K Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.

IP65

13 Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.

IP65

64 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual

<<< THIS PAGE INTENTIONALLY BLANK >>>

Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM 65

You might also like