Ekor - Rpa Series 200: Advanced Protection, Metering and Control Multifunction Unit
Ekor - Rpa Series 200: Advanced Protection, Metering and Control Multifunction Unit
Ekor - Rpa Series 200: Advanced Protection, Metering and Control Multifunction Unit
Preface I II
As a result of new demands in supply Depending on the model, the ekor.rpa
quality, there is an increasing need for series 200 units can incorporate current,
automation in distribution networks and voltage and frequency protection functions, 7
for equipment to carry out metering and as well as automation, local/remote control, 1
control supervision functions for the switch metering of electrical parameters, presence 6
in distribution cubicles. and absence of voltage, phase imbalance,
etc.
The ekor.rpa series 200 protection, 2
metering and control units have There are also variants depending on the 8
been designed to cover these needs, characteristics of the voltage metering 5
9
complying with the requirements of the channels (capacitive, resistive and
national and international standards and transformers).
4
recommendations.
3
Technical characteristics
ekor.rpa series 200 ekor.rpa-210 ekor.rpa-220
General characteristics
24/48/125 Vcc - 230 Vca (Dual power)
Current analogue inputs 5 + Io(1) 5 + Io(1)
Voltage analogue inputs 5 + Vo(1) 5 + Vo(1)
Configurable digital inputs/outputs (extendable with additional expansion modules) 10/4 10/4
Settings groups 2 2
Timing curve types: IEC and ANSI
Protection functions
50-51[1]-51[2] 50N-51N[1]-51N[2] 51G
50Ns-51Ns
PWH
46 46BC
67 67N
67Ns
49
49T
27 59 59N -
81m/81M/81R -
Cold load
Metering
Current
Voltage Active/reactive/apparent power
Energy P+, P-, Q1,…,Q4 Phi angle (φ)
Thermal image accumulation
Frequency
Temperature
Voltage and current THD
Control and supervision
Automatic switch operation and control Blocking (86)
Tripping coil supervision (TCS) Presence/absence of voltage
Events log 4000 4000
Fault report 10 10
Oscillograph report 10 10
Configurable LED/LED 8/2 8/2
Tripping blocked by 2nd harmonic
Recloser (79)
Other automations
Web configuration
1 x micro-USB 1 x micro-USB
Front communication ports
1 x RJ-45: web server (local access) 1 x RJ-45: web server (local access)
2 x RS-485: Modbus-RTU or PROCOME 2 x RS-485: Modbus-RTU or PROCOME
1 x RS-485: Temperature bus 1 x RS-485: Temperature bus
Rear communication ports
1 x Ethernet: Modbus-TCP and remote 1 x Ethernet: Modbus-TCP and remote
web server web server
Communications: serial(2)
MODBUS-RTU PROCOME
Communications: IP(2)
MODBUS-TCP
Notes: Configuration:
(1)
Calculated Standard
(2)
Ask Ormazabal about other protocols (DNP3, IEC 60870-5-104, etc.) Optional
ANSI functions
27 - Minimum voltage protection
46 - Reverse sequence
46BC - Broken conductor detection
49 - Thermal overload
49T - Temperature trip
50 - Overcurrent instantaneous protection
50N - Earthing overcurrent instantaneous protection
50NS - Sensitive neutral overcurrent instantaneous protection
51 - Inverse time overcurrent protection
51N - Earthing overcurrent instantaneous protection
51NS - Inverse time sensitive neutral overcurrent protection
51G - Earthing timed overcurrent protection
59 - Overvoltage protection
59N - Residual overvoltage protection
67 - Overcurrent directional protection
67N - Neutral overcurrent directional protection
67NS - Sensitive neutral overcurrent directional protection
79 - Recloser (automatic recloser)
81m - Minimum frequency protection
81M - Maximum frequency protection
81R - Frequency drift protection
86 - Blocking protection
PWH - Zero-sequence wattmeter
www.ormazabal.com