P33 1 (4PP) GB (0213)
P33 1 (4PP) GB (0213)
P33 1 (4PP) GB (0213)
com
P33-1
Image for illustration purposes only.
Generating Set Model Prime Standby Engine Make & Model: Perkins 1103A-33G1
380-415V,50Hz 30.0 kVA / 24.0 kW 33.0 kVA / 26.4 kW Alternator manufactured for
Leroy Somer
FG Wilson by:
480V, 60 Hz 33.8 kVA / 27.0 kW 37.5 kVA / 30.0 kW
Alternator Model: LL1514F
Ratings at 0.8 power factor. Control Panel: DCP-10
Base Frame: Heavy Duty Fabricated Steel
Circuit Breaker Type: 3 Pole MCB / 3 Pole MCCB
Frequency: 50 Hz 60 Hz
Prime Rating
These ratings are applicable for supplying continuous electrical power Engine Speed: RPM 1500 1800
(at variable load) in lieu of commercially purchased power. There is no
limitation to the annual hours of operation and this model can supply 10% Fuel Tank Capacity: 161 (42.5)
litres (US gal)
overload power for 1 hour in 12 hours.
Fuel Consumption: l/hr (US gal/hr)
Standby Rating
These ratings are applicable for supplying continuous electrical power (at (100% Load) - Prime 7.0 (1.8) 8.1 (2.1)
variable load) in the event of a utility power failure. No overload is
- Standby 7.7 (2.0) 9.0 (2.4)
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
1540 (60.6) 970 (38.2) 1361 (53.6) 830 (1830) 843 (1858)
Dry = With Lube Oil Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.
Generating set pictured may include optional accessories.
Engine Technical Data Air Systems 50 Hz 60 Hz
Bore / Stroke: mm (in) 105.0 (4.1)/127.0 (5.0) - Prime 2.2 (76) 2.6 (92)
Naturally Aspirated - Standby 2.2 (76) 2.6 (91)
Induction:
Max. Combustion Air Intake
Restriction: kPa (in H2O) 6.5 (26.1) 6.5 (26.1)
Cooling Method: Water
Governing Type: Mechanical
Governing Class: ISO 8528 G2
Compression Ratio: 19.25:1
Cooling System 50 Hz 60 Hz
Displacement: l (cu. in) 3.3 (201.4)
Cooling System Capacity: l (US gal) 10.2 (2.7) 10.2 (2.7)
Moment of Inertia: kg m² (lb/in²) 1.14 (3896)
Water Pump Type: Centrifugal
Engine Electrical System:
Heat Rejected to Water & Lube Oil:
- Voltage / Ground 12/Negative
kW (Btu/min) - Prime 16.0 (910) 18.0 (1024)
- Battery Charger Amps 65
- Standby 18.0 (1024) 22.0 (1251)
Weight: kg (lb) - Dry 412 (908)
Heat Radiation to Room: Heat radiated from engine and alternator
- Wet 430 (948) kW (Btu/min) - Prime 7.9 (449) 8.2 (466)
- Standby 9.3 (529) 9.7 (552)
Performance 50 Hz 60 Hz Radiator Cooling Airflow: m³/min (cfm) 62.6 (2211) 84.8 (2995)
External Restriction to
Engine Speed: rpm 1500 1800 125 (0.5) 125 (0.5)
Cooling Airflow: Pa (in H2O)
Gross Engine Power: kW (hp)
Designed to operate in ambient conditions up to 50°C (122°F).
- Prime 28.2 (38.0) 33.1 (44.0) Contact your local FG Wilson Dealer for power ratings at specific site conditions.
- Standby 752.0 (109.0) 738.0 (107.0) Oil Filter Type: Spin-On, Full Flow
Total Oil Capacity: l (US gal) 8.3 (2.2)
Oil Pan: l (US gal) 7.8 (2.1)
Oil Type: API CG4 / CH4 15W-40
(Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Exhaust Gas Temperature: °C (°F)
Class A2, EN590)
- Prime 500 (932) 520 (968)
- Standby 520 (968) 530 (986)
Alternator Physical Data Alternator Operating Data
Alternator
50 Hz 60 Hz
Performance Data:
Data Item 415/240V 400/230V 380/220V 220/127V 480/277V 380/220V 240/120V 230/115V 440/254V
200/115V
Motor Starting
72 68 63 78 78 55 63 59 69
Capability* kVA
Short Circuit
- - - - - - - - -
Capacity %
400/230V 30.0 24.0 33.0 26.4 220/127V 33.8 27.0 37.5 30.0
380/220V 30.0 24.0 33.0 26.4 380/220V 33.8 27.0 37.4 29.9
230/115V 30.0 24.0 33.0 26.4 240/120V 33.8 27.0 37.5 30.0
220/127V 30.0 24.0 33.0 26.4 230/115V 33.8 27.0 37.5 30.0
220/110V 30.0 24.0 33.0 26.4 440/254V 33.8 27.0 37.5 30.0
200/115V 30.0 24.0 33.0 26.4 220/110V 33.8 27.0 37.4 29.9
Documentation
A full set of operation and maintenance manuals and circuit wiring diagrams.
The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.
Warranty
All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's
warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com.