Üç Yollu Vana
Üç Yollu Vana
Üç Yollu Vana
PRODUCT DATA
FEATURES
• Chrome-plated plug for long life.
• Optimized characteristic for supply water temperature
control
• Protected against corrosion and blocking
• Reliable mounting for electrical actuators
• Clear position indicator
• Wide range of flow rates with suitable actuators
SPECIFICATIONS
Nominal static
6 bar, 600kPa
pressure
depending on type (see section
Maximum pressure
"Specification and Order Number" on
drop
page 2)
Leakage rate 1% of kvs
Internal threads / flange in
accordance with DIN EN 1092-2
Ports depending on type (see section
"Specification and Order Number" on
page 2)
Angle of rotation 90 °
Internal threads 8 windings long
APPLICATION Packing Double o-ring sealing
Material body Cast iron
The DRxxGMLA / DRxxxGFLA rotary valves provide water
temperature control in heating and air conditioning Material inner parts Chrome-plated cast iron
applications. Heating water according to VDI 2035
These valves are designed for accurate mixing control of (oxygen concentration less than 0.2
Medium
supply water temperature in heating and air conditioning g/m3, pH 8...9.5), glycol-water
systems. mixtures (max. 50% glycol)
Its sturdy construction ensures a long and reliable operating Water temperatures
2 to 130 °C, non-condensing
life when used in combination with M6061/VMM and in the valve
M7061/VRM actuators. depend on type (see sections
"Dimensions with DRxxGMLA (mm)"
Weight
and "Dimensions with DRxxxGFLA
(mm)" on page 3)
Flow characteristic equal percentage
SUITABLE ACTUATORS
M6061A (24V; floating); M6061L (230V/240V; floating); M7061E (0/2 to 10V modulating)
OS no. OS no. OS no.
torque [Nm]
24 Vac floating 230 Vac floating 0/2...10 V
10 M6061A1013 M6061L1019 M7061E1012
20 M6061A1021 / VMM20-24 M6061L1027 / VMM20 M7061E1020 / VRM20
30 M6061A1039 / VMM30-24 M6061L1035 / VMM30 –
40 M6061A1047 / VMM40-24 M6061L1043 / VMM40 –
40 VMM40-24F VMM40F –
OPERATION MOUNTING
The valve controls a mixing water temperature with a rotating
plug. The plug adjusts with two control curves the water flow
of two inputs. The required flow water temperature is reached C°
by adding a proportion of return water to the boiler hot water.
For optimum control performance, the DR has special control
characteristics. C°
0
0
R L
L R
EN0B-0607GE51 R0208 2
DRxxGMLA / DRxxxGFLA – PRODUCT DATA
a i
h
b
d
a e f
g c
3 EN0B-0607GE51 R0208
DRxxGMLA / DRxxxGFLA – PRODUCT DATA
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: