Flare Stack Calculation Sheet: Brzustowski and Sommer's Approach

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6
At a glance
Powered by AI
This document contains information about flare stack calculations including gas properties, operating conditions, and composition.

The mass flow rate is 453600 kg/hr and the molecular weight is 46.1 kg/kmol.

The flowing temperature is 149°C, atmospheric pressure is 101.325 kPa, and the flare tip diameter is 0.91 m.

Flare Stack Calculation Sheet

Brzustowski and Sommer's Approach


Client: TGS Date: 44489
Project: TRATAYEN 2022/3 Tag Nº: FL-XXX
Case: INVIERNO ALTA PRESION By: MJD
FLUID PROPIERTIES, OPERATING CONDITIONS AND FLARE CHARACTERISTICS

Variable Symbol Value Units Observations


Mass Flow qm 453600 kg/hr For Match no. = 0,5
126 kg/s
Mol Weigth M 46.1 kg/kmol From Simulation
108 kPa_a
Flowing Temperature Tj 149 °C From Simulation
Altitude ovear sea level 0 m From design basis
Atmospheric pressure 101.325 kPa
422.15 °K
Air Temperature T∞ 15 °C
288.15 °K
Compressibility factor Z 1 From Simulation
Flare tip diameter dj 0.91 m
Pressure at Flare Tip p2 14.201536657029 kPa_g
Density gas ρ 1.5174202154131 kg/m3
Flare height h 123 m
Ma number Ma2 0.496
Isothermal sonic velocity 275.98010302703 m/s
Tip velocity μj 136.81374614706 m/s
Heat of combustion LHV 50000 kJ/kg From Simulation
Heat liberated Q 6300000 kJ/s
Wind velocity μj 8.9 m/s
LEL CL 2.1 %v/v Calculated as suggested by API 521
LEL Conc Factor CL 0.513170816137
Jet & Wind thrust parameter dj.R 78.470694831985
xc 18 m
Horizontal distance, from stack to flame centre From Api 521 graphs
yc 30 m
Vertical distance, from stack to flame centre From Api 521 graphs
Fraction Radiated Heat F 0.3 Chamberlain, 1987 + 15%

τ 1

Allowable Radiation 9.5

6.3

K kW/m2
4.7

3.2

1.6

0.244991583713855
Fraction Radiated Heat F 0.3 Chamberlain, 1987
Solar Radiation 0 kW/m2
D K=9,5 kW/m2 125.8
D K=6,3 kW/m2 154.5
Values calculated with
Safe Distance to Flame Centre D K=4,7 kW/m2 178.9 m
transmissivity = 1
D K=3,2 kW/m2 216.8
D K=1,6 kW/m2 306.6
ΔX K=9,5 kW/m2 #NUM!
ΔX K=6,3 kW/m2 39.5
Values calculated with
Distance from flare base (at ground level) ΔX K=4,7 kW/m2 110.7 m
transmissivity = 1
ΔX K=3,2 kW/m2 171.6
ΔX K=1,6 kW/m2 283.7

Thermal radiation at ground level


7
Thermal radiation [kW/m2]

HR% 10
6
HR% 50
5 HR% 100
4 Transmissivity = 1

3
2
1
0
0 50 100 150 200 250 300
Distance from stack base [m]
Compound Molar fraction Cli % v/v
Nitrogen 3.49E-03 0
CO2 2.81E-03 0
Methane 0.843947737638145 4.4
Ethane 9.13E-02 2.9
Propane 3.74E-02 2
i-Butane 6.56E-03 1.8
n-Butane 9.77E-03 1.5
i-Pentane 2.37E-03 1.3
n-Pentane 1.55E-03 1.3
n-Hexane 6.74E-04 1.05
n-Heptane 6.79E-05 1
n-Octane 7.41E-06 0.8
n-Nonane 0.00E+00 0.7
n-Decane 0 0.7
n-C11 0 0.65
n-C12 0 0.6
H2O 5.98E-05 0
CL Mixture 3.90816986089401 % v/v