National Electrical Code Allowable Conductor Ampacity: TABLE 310-16 TABLE 310-17
National Electrical Code Allowable Conductor Ampacity: TABLE 310-16 TABLE 310-17
National Electrical Code Allowable Conductor Ampacity: TABLE 310-16 TABLE 310-17
† Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (†) shall not exceed 15
amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper, after any correction factors for ambient temperature and number of conductors
have been applied.
For Example:
LAPP USA P/N 221007, 10 AWG, 6 Cond. + 1 ground, 90OC THHN At 40OC = 40 AMPS X .91 (Temp. Correction Factor) = 36 AMPS
at 30OC = 40 AMPS x .80 (Adjustment Factor) = 32 AMPS = 36 AMPS X .80 (Adjustment Factor) = 28 AMPS
Adjustment Factors for More than Three Current-Carrying Conductors in a TEMPERATURE CORRECTION FACTORS
Raceway or Cable. Where the number of current-carrying conductors in a For ambient temperatures other than 30°C (86°F),
raceway or cable exceeds three, the allowable ampacities shall be reduced as
multiply the allowable ampacities shown above by the
shown in the following table:
appropriate factor shown below.
Percent of Values in
Number of Ambient Temp.
Tables as Adjusted for
Current-Carrying Ambient Temperature °C 60°C 75°C 90°C
Conductors * if Necessary
4 through 6 80 30 1.00 1.00 1.00
7 through 9 70 40 .82 .88 .91
10 through 20 50
50 .58 .75 .82
21 through 30 45
31 through 40 40 60 .... .58 .71
41 and above 35 70 .... .33 .58
80 .... .... .41
* Does not include ground